Sei sulla pagina 1di 6

Centrifugal Chiller

Job Information

Job01
TIG

Tag 7/12-0004 Model Number CVHE0420


Quantity 1

Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump
Water-Heating Packages Certification Program, which is based on AHRI Standard
550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the
AHRI Directory at www.ahridirectory.org.

Sound pressure measured in accordance with AHRI Standard 575-94.

ASHRAE 90.1 - 2007 Add. M Complies

ASHRAE 90.1-2010 Complies

Unit Information

Model CVHE Compressor size 420


Impeller size 273 Orifice size 500
Motor size 300 Refrigerant R-123
Motor frequency 50 Hz Motor voltage 380
Incoming line frequency 50.0 Hz Incoming line voltage 380
Evap shell size 050S Cond shell size 050L
Evap bundle size 580 Cond bundle size 500
Evap tube type IMC1 Cond tube type IECU
Evap tube thickness 0.025" Cond tube thickness 0.025"
Evap passes Two pass evap water box Cond passes Two pass cond water box

Design Information
Refrigeration capacity 1500.0 kW Refrigerant charge 318 kg
Total power 254.5 kW Shipping weight 7989 kg
Cooling Efficiency 0.5966 kW/ton Operating weight 8998 kg
NPLV 0.1535 kW/kW Free cooling option No
Wye-delta starter type Unit Mounted WyeD Green Seal certification No
Unit heat rejected to ambient 1.273 kW Application type Standard cooling

Evaporator Information
Leaving fluid evap 7.00 C Fluid pressure drop evap 58.8 kPa
Flow evap 71.44 L/s Evap fluid type water
Entering fluid evap 12.00 C Evap fluid concentration N/A
Flow evap/refrigeration capacity 0.0476 L/s/kW Evap water box type non-marine
Evap fouling factor 0.017610 m2-deg C/kW Evap water box pressure 150 psig

Condenser Information
Entering fluid cond 32.00 C Fluid pressure drop cond 58.4 kPa
Flow cond 85.01 L/s Cond fluid type water
Leaving fluid cond 37.00 C Cond fluid concentration N/A
Flow cond/refrigeration capacity 0.0567 L/s/kW Cond water box type non-marine
Cond fouling factor 0.044025 m2-deg C/kW Cond water box pressure 150 psig

Product Version 31.8.0.0

Selection code revision level 55186 M0C0E000C000S00 Page 1 of 6

Report Date 8/9/2017 Data generation date 8/9/2017


Centrifugal Chiller
Job Information

Job01
TIG

Tag 7/12-0004 Model Number CVHE0420


Quantity 1

Electrical Information
Motor LRA 2123 A Compressor motor RLA 454.30 A
Primary RLA (Incoming line) 464.8 A Min circuit ampacity 579 A
Un-corrected power factor 0.89 Max overcurrent protection 1000 A

Information for LEED Projects


Refrigeration capacity 1500 kW Total power 254.5 kW

Refrigerant charge 317.51 kg NPLV 0.1535 kW/kW

Note: Trane recognizes and respects the U.S. Green Building Council mandate that a default 2% Refrigerant Leakage Rate (Lr) be used by

all manufacturers of centrifugal chillers when calculating the Enhanced Refrigerant Management Credit because there is no industry

standard. Trane has exhaustively documented a leak rate of less than 0.5% for R-123 CenTraVac chillers (models CVHE, CVHF,

CVHG, CVHL, CVHS, CDHF and CDHG) and utilizes an average design refrigerant charge of less than 2 lb./ton. The overall

environmental performance of the CenTraVac chiller is verified in its product-specific Type III Environmental Product Declaration (EPD)

in accordance with ISO 14025, further demonstrating Tranes commitment to safeguarding the environment.

The U.S. Green Building Councils LEED green building program is the preeminent program for the design, construction, maintenance and operations of
high-performance green buildings. It provides independent, third-party verification that a building project meets the highest green building and performance measures.

Product Version 31.8.0.0

Selection code revision level 55186 M0C0E000C000S00 Page 2 of 6

Report Date 8/9/2017 Data generation date 8/9/2017


Centrifugal Chiller
Job Information

Job01
TIG

Tag 5/12-0012 Model Number CVHE0420


Quantity 1

Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump
Water-Heating Packages Certification Program, which is based on AHRI Standard
550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the
AHRI Directory at www.ahridirectory.org.

Sound pressure measured in accordance with AHRI Standard 575-94.

ASHRAE 90.1 - 2007 Add. M Complies

ASHRAE 90.1-2010 Complies

ASHRAE 90.1-2013 Complies

Unit Information

Model CVHE Compressor size 420


Impeller size 277 Orifice size 560
Motor size 300 Refrigerant R-123
Motor frequency 50 Hz Motor voltage 380
Incoming line frequency 50.0 Hz Incoming line voltage 380
Evap shell size 050S Cond shell size 080S
Evap bundle size 580 Cond bundle size 800
Evap tube type TECU Cond tube type TECU
Evap tube thickness 0.025" Cond tube thickness 0.025"
Evap passes Two pass evap water box Cond passes Two pass cond water box

Design Information
Refrigeration capacity 1500.0 kW Refrigerant charge 340 kg
Total power 264.2 kW Shipping weight 8757 kg
Cooling Efficiency 0.6192 kW/ton Operating weight 9900 kg
NPLV 0.1628 kW/kW Free cooling option No
Wye-delta starter type Unit Mounted WyeD Green Seal certification No
Unit heat rejected to ambient 1.321 kW Application type Standard cooling

Evaporator Information
Leaving fluid evap 5.00 C Fluid pressure drop evap 34.0 kPa
Flow evap 51.01 L/s Evap fluid type water
Entering fluid evap 12.00 C Evap fluid concentration N/A
Flow evap/refrigeration capacity 0.0340 L/s/kW Evap water box type non-marine
Evap fouling factor 0.017610 m2-deg C/kW Evap water box pressure 150 psig

Condenser Information
Entering fluid cond 32.00 C Fluid pressure drop cond 34.6 kPa
Flow cond 85.39 L/s Cond fluid type water
Leaving fluid cond 37.00 C Cond fluid concentration N/A
Flow cond/refrigeration capacity 0.0569 L/s/kW Cond water box type non-marine
Cond fouling factor 0.044025 m2-deg C/kW Cond water box pressure 150 psig

Product Version 31.8.0.0

Selection code revision level 55186 M0C0E000C000S00 Page 3 of 6

Report Date 8/9/2017 Data generation date 8/9/2017


Centrifugal Chiller
Job Information

Job01
TIG

Tag 5/12-0012 Model Number CVHE0420


Quantity 1

Electrical Information
Motor LRA 2123 A Compressor motor RLA 467.90 A
Primary RLA (Incoming line) 478.4 A Min circuit ampacity 596 A
Un-corrected power factor 0.89 Max overcurrent protection 1000 A

Information for LEED Projects


Refrigeration capacity 1500 kW Total power 264.2 kW

Refrigerant charge 340.19 kg NPLV 0.1628 kW/kW

Note: Trane recognizes and respects the U.S. Green Building Council mandate that a default 2% Refrigerant Leakage Rate (Lr) be used by

all manufacturers of centrifugal chillers when calculating the Enhanced Refrigerant Management Credit because there is no industry

standard. Trane has exhaustively documented a leak rate of less than 0.5% for R-123 CenTraVac chillers (models CVHE, CVHF,

CVHG, CVHL, CVHS, CDHF and CDHG) and utilizes an average design refrigerant charge of less than 2 lb./ton. The overall

environmental performance of the CenTraVac chiller is verified in its product-specific Type III Environmental Product Declaration (EPD)

in accordance with ISO 14025, further demonstrating Tranes commitment to safeguarding the environment.

The U.S. Green Building Councils LEED green building program is the preeminent program for the design, construction, maintenance and operations of
high-performance green buildings. It provides independent, third-party verification that a building project meets the highest green building and performance measures.

Product Version 31.8.0.0

Selection code revision level 55186 M0C0E000C000S00 Page 4 of 6

Report Date 8/9/2017 Data generation date 8/9/2017


Centrifugal Chiller
Job Information

Job01
TIG

Tag 5/10-0010 Model Number CVHE0420


Quantity 1

Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump
Water-Heating Packages Certification Program, which is based on AHRI Standard
550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the
AHRI Directory at www.ahridirectory.org.

Sound pressure measured in accordance with AHRI Standard 575-94.

ASHRAE 90.1 - 2007 Add. M Complies

ASHRAE 90.1-2010 Complies

ASHRAE 90.1-2013 Complies

Unit Information

Model CVHE Compressor size 420


Impeller size 277 Orifice size 560
Motor size 300 Refrigerant R-123
Motor frequency 50 Hz Motor voltage 380
Incoming line frequency 50.0 Hz Incoming line voltage 380
Evap shell size 050S Cond shell size 080S
Evap bundle size 580 Cond bundle size 630
Evap tube type TECU Cond tube type TECU
Evap tube thickness 0.025" Cond tube thickness 0.025"
Evap passes Two pass evap water box Cond passes Two pass cond water box

Design Information
Refrigeration capacity 1500.0 kW Refrigerant charge 340 kg
Total power 263.7 kW Shipping weight 8548 kg
Cooling Efficiency 0.6182 kW/ton Operating weight 9615 kg
NPLV 0.1611 kW/kW Free cooling option No
Wye-delta starter type Unit Mounted WyeD Green Seal certification No
Unit heat rejected to ambient 1.319 kW Application type Standard cooling

Evaporator Information
Leaving fluid evap 5.00 C Fluid pressure drop evap 61.9 kPa
Flow evap 71.38 L/s Evap fluid type water
Entering fluid evap 10.00 C Evap fluid concentration N/A
Flow evap/refrigeration capacity 0.0476 L/s/kW Evap water box type non-marine
Evap fouling factor 0.017610 m2-deg C/kW Evap water box pressure 150 psig

Condenser Information
Entering fluid cond 32.00 C Fluid pressure drop cond 51.4 kPa
Flow cond 85.47 L/s Cond fluid type water
Leaving fluid cond 37.00 C Cond fluid concentration N/A
Flow cond/refrigeration capacity 0.0570 L/s/kW Cond water box type non-marine
Cond fouling factor 0.044025 m2-deg C/kW Cond water box pressure 150 psig

Product Version 31.8.0.0

Selection code revision level 55186 M0C0E000C000S00 Page 5 of 6

Report Date 8/9/2017 Data generation date 8/9/2017


Centrifugal Chiller
Job Information

Job01
TIG

Tag 5/10-0010 Model Number CVHE0420


Quantity 1

Electrical Information
Motor LRA 2123 A Compressor motor RLA 471.10 A
Primary RLA (Incoming line) 481.6 A Min circuit ampacity 600 A
Un-corrected power factor 0.89 Max overcurrent protection 1000 A

Information for LEED Projects


Refrigeration capacity 1500 kW Total power 263.7 kW

Refrigerant charge 340.19 kg NPLV 0.1611 kW/kW

Note: Trane recognizes and respects the U.S. Green Building Council mandate that a default 2% Refrigerant Leakage Rate (Lr) be used by

all manufacturers of centrifugal chillers when calculating the Enhanced Refrigerant Management Credit because there is no industry

standard. Trane has exhaustively documented a leak rate of less than 0.5% for R-123 CenTraVac chillers (models CVHE, CVHF,

CVHG, CVHL, CVHS, CDHF and CDHG) and utilizes an average design refrigerant charge of less than 2 lb./ton. The overall

environmental performance of the CenTraVac chiller is verified in its product-specific Type III Environmental Product Declaration (EPD)

in accordance with ISO 14025, further demonstrating Tranes commitment to safeguarding the environment.

The U.S. Green Building Councils LEED green building program is the preeminent program for the design, construction, maintenance and operations of
high-performance green buildings. It provides independent, third-party verification that a building project meets the highest green building and performance measures.

Product Version 31.8.0.0

Selection code revision level 55186 M0C0E000C000S00 Page 6 of 6

Report Date 8/9/2017 Data generation date 8/9/2017

Potrebbero piacerti anche