APPLICATION:
For indoor or outdoor installation in open
air in tray, trough and conduit or for direct
burial in free draining soil or inside duct
where no mechanical damage is to be
expected. Power cable for utilities low voltage
distribution systems and in commercial
buildings, industrial plants, power stations
and substations. For systems operating at
not more than 0.6 kV between a conductor
to earth or 1 kV between conductors at
maximum conductor temperatures of 90 C
for continuous normal operation and 250 C 2. Conforms to Israeli Standard IS 1516: CONSTRUCTION:
for short circuit. Extruded solid dielectric insulated A copper compacted circular conductor
power cables for rated voltages from has an extruded cross-linked polyethylene
STANDARDS: 1 kV to 30 kV for the type N2XY FR1. (XLPE) insulation applied around the
1. Conforms to IEC 60502-1 Standard: 3. Conforms to the Council of the European conductor. A green PVC outer sheath with
Power cables with extruded insulation Communities Directives 73/23/EEC printed marking is extruded over all.
and their accessories for rated voltages (Low Voltage Directive), 92/59/EEC and
from 1 kV (Um = 1,2 kV) up to 30 kV (Um 93/68/EEC for black and yellow/green PACKAGING:
= 36 kV) Part 1: Cables for rated coloured insulation.CE 1000 m bobbins up to 120 mm2. 500 m
voltages of 1 kV (Um = 1,2 kV) and 3 kV bobbins above 120 mm2. Other bobbin
(Um = 3,6 kV). lengths are available upon request.
No. and Nominal Nominal Approximate Approximate Minimum Max. Short Current rating (2) Voltage Drop (5)
Catalog Nominal cross insulation sheath outer cable bending conductor circuit
Number sectional area thickness thickness diameter weight radius resistance rating (1 sec) In Air Buried Single Three
of conductors at 20 oC (3) (4) Phase Phase
(1) AC AC
No. x mm2 mm mm mm kg/km mm /km kA A A mV/A/m mV/A/m
181001 1 x 10 0.7 1.4 9 150 135 1.83 1.4 77 90 4.7 4.0
1810027 1 x 16 0.7 1.4 10 215 150 1.15 2.3 102 115 2.9 2.5
1810037 1 x 25 0.9 1.4 12 315 180 0.727 3.6 139 149 1.85 1.60
1810047 1 x 35 0.9 1.4 13 410 195 0.524 5.0 170 178 1.35 1.15
1810057 1 x 50 1.0 1.4 15 530 225 0.387 7.2 208 211 1.00 0.87
1810067 1 x 70 1.1 1.4 18 750 270 0.268 10.0 265 259 0.71 0.61
1810087 1 x 95 1.1 1.5 19 1000 285 0.193 13.6 326 310 0.52 0.45
181009 1 x 120 1.2 1.5 21 1270 315 0.153 17.2 381 352 0.43 0.37
181010 1 x 150 1.4 1.6 23 1530 345 0.124 21.5 438 396 0.36 0.31
1810111 1 x 185 1.6 1.6 25 1950 375 0.0991 26.5 507 449 0.30 0.26
1810121N 1 x 240 1.7 1.7 27 2500 420 0.0754 34.3 606 521 0.25 0.22
181014 1 x 300 1.8 1.8 30 3050 450 0.0601 42.9 697 587 0.22 0.195
1810151 1 x 400 2.0 1.9 33.5 3950 505 0.0470 57.2 816 669 0.20 0.175
(1) Short circuit rating is based on an initial conductor temperature of 90 C and a final temperature of 250 C.
(2) Current rating based upon operation at 90 C conductor, three-phase a.c. load. According to VDE 0298.
(3) Cable laid in trefoil touching in freely circulating air at 30 C, protected against direct thermal radiation due to sun, etc.
(4) Cable directly buried in trefoil touching at 0.7 m deep in soil at 20 C, with 1 K . m/W thermal resistivity. Load factor 0.7.
(5) Voltage drop according to BS 7671:1992.3 assuming that the conductor temperature is 90 C, the load is balanced and the phase angle of the cable
equals that of the load. Single-phase (two cables) touching or three-phase in trefoil touching.
PCD 45-6 , October 2007
Composite
Power Cables
XLPE Insulated, PVC Sheathed
Single Core Cables for Fixed
Installations, 0.6/1 kV
Specification