WP-CAN 3200
Microprocessor Based
Serial Communication
Lift Controller
User Manual
H_Ver1.0
&
Preface
WP-CAN Microprocessor-based Control System is applied for VVVF Elevators supported by full
collective operation with a rise of up to 64 floors and speed lower than 6m/s, which is functionally
featured as following:
3200 applied dual-CPU architecture with 32-digit high capability PHILIPS ARM chip. Flash Rom
with high capacity of 256K applied for PC controller acts together with Intel CPU for upgrading
programs conveniently according to the specific requirement. 128-digit memorizer interface and
unique accelerating configuration make the 32-digit code work under the maximum clock
velocity(44M).
Can-Bus LAN Serial Communication with speed up to 125Kbit/s and instruction time delay up to
9m/s. Real-time control and quick response.
Two independent CAN communication circuits used in car and hall call separately, highly
improved communication frequency of the CAN-BUS.
Multiple communication interface: 8 CAN with advanced checking filter, 3 RS232 and 1 RS485,
to improve the function expansion.
LCD display with large screen is applied for interface operation. Easy & simple working with
Chinese menu, Safe & reliable to set parameters with classified codes, and the function of
checking faults & running records (running time, runs) etc. is also available.
Automatically function recording the type and the time of faults leads to the powerful maintenance
and treatment on faults by use of Real-Time Clock and Fault Diagnostics, which is built-in.
Module structure is applied for this system so that car I/O board can deal with internal signals and
accomplish the motion of door operator. The full serial communication structure makes installation
quicker and economical.
Remote monitoring can be provided, as well as Duplex and Group Controlling.
Integrating floor display to landing call board, the system applies Dot Matrix Module displaying
rolling running direction to feedback dynamically current traveling speed of elevators.
SMT technology delivers reliable quality and small & delicate appearance to PCBs with low
power-consumption, which requires the cable diameter of 1mm2 in maximum powering the board
up to 1W.
The unique anti-interference can powerfully realize the automatic identification of faults when
single I/O board is malfunctioned and keep normal operation. The strictly selected components and
EMC-tested PCBs, e.g. output relays 3,000,000 times-tested in service life, ensure system
reliability.
Two input ports of high-speed counting, provide high-speed lift the speed compare and monitor
function to improve the reliability and security.
To realize the DCP function and park directly.
The control system, which is structured in building block module, mainly provides following parts
WIPO Electronic VVVF main controller WP-CAN-3200 user manual
Contents
WP-CAN 3200..........................................................................................................................................
1.11 COMMUNICATION BETWEEN MAIN CONTROLLER AND CAR & LANDING FLOOR
DISPLAY CONTROLLER ....................................................................................................................
WIPO Electronic VVVF main controller WP-CAN-3200 user manual
WIPO Electronic VVVF main controller WP-CAN-3200 user manual
5.1 LCD DISPLAY AND C-CALL CONTROLLER WP-CAN06BNORMALLY USE FOR LOP ............
5.1.1 WP-CAN06B In PictureDisplay Side ..............................................................................
5.1.2 WP-CAN06B In PictureElemental Side...........................................................................
WIPO Electronic VVVF main controller WP-CAN-3200 user manual
WIPO Electronic VVVF main controller WP-CAN-3200 user manual
7.15 PUSH-TO-OPEN.............................................................................................................................
WIPO Electronic VVVF main controller WP-CAN-3200 user manual
8.3 WIRING.............................................................................................................................................
WIPO Electronic VVVF main controller WP-CAN-3200 user manual
WIPO Electronic VVVF main controller WP-CAN-3200 user manual
WIPO Electronic VVVF mian controller WP-CAN3200 user manual
1.1 In picture
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
UP Lift up T7
DOWN Lift down T8
Common port 4 COM4
Inverter control 1 T9
Inverter control 2 T10 J25
Inverter control 3 T11
Inverter control 4 T12
Inverter control 5 T13
Common port 5 COM5
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
But applied digital multi-segment control, the inverter output will display as follows: the
number with the black background stands for output.
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Two groups of DC regulated constant voltage required for operation, which are individually 5V
and 24V, must be isolated.
Symbol Description
5V supply 5V+current1000mA
0V supply 5V-
FG grounding
24V+ supply 24V+current1000mA
24V- supply 24V-
552 Supply 24V+, current1 A
551 Supply 24V-, current1 A
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Surrounding -20 ~ 60
temperature
Relative 35~85% RH
temperature
Anti-librate 0~100 Hz 0.5mm 100 times
Anti-impact Acceleration in peak value 100 gn 100 times
Anti-electric Static Impulse of speediness Electromagnetism field
noise group
6 kv discharge by Peak value 4kv Intensity 10 V/m
contacting directly 5k hz frequency 80k ~ 1000M hz testing
6 kv discharge by 5/50 ns(Tr/Td) for scanning frequency
contacting indirectly 1 min interfere time
15kv discharge by air
directly
Grounded The third way of groundeddont grounded with the strong electricity
Work Non-causticity gas non-combustibility gaslittle dust
surroundings
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Differential Level Input, four terminals A1+A1- B1+ and B1- are defined for application and
others are in suspension. Additionally, the connection between S12 and S13 is off.
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Port type 4
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Note: the array of above form isnt set logicly. If you want to revise the logic setting
of the inputs, please see the part systemcontrolsIV logic setting for your
reference.
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
When the lift need front/back door control, it need to be installed a piece of WP-CAN-01C. At the
same time, it also need short connect J1 using short-connect board, which set as the back door
control board.
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Port type4
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WP-CAN-03,WP-CAN-03C
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Port typeVH-4
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
4.5.1 P6 in drawing:
4.5.2 P6 in definition:
Symbol Description
Normal display state by short-connection between the two
Setting state accessed by short-connection of terminals hold in 2sec.
Multi-function output supply 0V
Multi-function output supply 5V
Multiple function output assembly
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
K: Display Address
Run parameter symbols in
F: Function Selection
circle, e.g.,
G: Group Number
KFGVD
V: Version Number
D: Special Function
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Symbol Description
Display Address, range: 0~64
Function selection:
Lift Lock Enabled, Fire Protection Enabled, Arrowhead Type
Group Number
Version Number
D Special Function
Value
(value in random 0 or 1)
Definition
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Note: As a part of the whole lift system, the hall call controller could only have one LIFT
LOCK ENABLED and FIRE PROTECTION ENABLED into practice, which could be
separately configured into different hall call controller.
Functions
Value in Binary
Value in
Decimal Fire
Arrowhead Lift Lock
Protection
Mode Enabled
Enabled
0 0 0 0 0 0 0 0 0 Type A No No
0 0 0 0 0 0 0 1 1 Type A No Yes
0 0 0 0 0 0 1 0 2 Type A Yes No
0 0 0 0 0 0 1 1 3 Type A Yes Yes
0 0 0 0 0 1 0 0 4 Type B No No
0 0 0 0 0 1 0 1 5 Type B No Yes
0 0 0 0 0 1 1 0 6 Type B Yes No
0 0 0 0 0 1 1 1 7 Type B Yes Yes
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Hex Value 1 2 4 12
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
for LOP
Single Color
Display Area LCD Display
Module
Picture2.2
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Picture2.3
1. Definition
S2 Function 1. SET
2. Shift the Menu
Press the S1S2 together to confirm and save the setting
J5 is reserved setting port.
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
c Set floor NoThe setting value corresponds to the floors number. The lowest is 1.
Then gradually increase till the highest floor. The maximum is 64.
d Set group IDSet it into 0 when in single elevator mode. In case of duplex situation,
set elevator A to 1 and elevator B into 2.
e Lift lock enabledThe lift lock signal take effect after this setting is enabled. in case
the lift is under automatic running and the lift lock signal is connected, . After
having automatically returned to parking floor, the lift closes and locks the door.
f Fire protection enabledThe fire protection signal take effect after this setting is
enabledwhen the lift runs automatically and the fire protection signal is connected,
the function is enabled.
g Code setting1 self coding2 binary code3 BCD code4 seven phases code
5 gray code.
Note: As a part of the whole lift system, the hall call controller could only have one LIFT
LOCK ENABLED and FIRE PROTECTION ENABLED into practice, which could be
separately configured into different hall call controller.
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
LCD protect
shell and fixing
frame
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Setting push
button K1-K4 Terminal
bridge port J8
CAN communication
Salutatory
port J10
modifying
port J11
Lift lock and fire
protection portJ4,J5
Inverter J12
UP DOWN C-Call
port J2,J3
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
5.2.5 Functions
1. It also can be used in LOPsame functions and interfaces with WP-CAN 06B
2. More informations(maintanance,overload,full load,manual,nonstop etc)can be showed in
Chinese, English or Japanese
3. It is able to set up the salutatory in Chinese or English by the edit software.
4. Date displayYY,MM,DDSample: 2004/05/05 18:25
5. Temperature of the car
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Connect the J11 and the serial interface COM1 of the PC. The communication cable should
less than 30m by the 232, less than 1200m by the 485. The default communication type is 232.
The long distance communication could be ordered if there is a need.
The LCD will stop perform the floor indicate when modifying the salutatory till edit
successfully.
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Parameters information
1. LanguageSet the menu into different languages. Including Chinese English and Japanese.
After setting the language, the information display change according to the chosen language.
2. Set floor number00 means this board is used in COP and the up/down/lock/fire signals are
invalid. 1-64 indicates this board is used in LOP and corresponding floor.
3. Lift lock enabledThe lift lock signal take effect after this setting is enabled. in case the lift
is under automatic running and the lift lock signal is connected, . After having automatically
returned to parking floor, the lift closes and locks the door.
4. Fire protection enabledThe fire protection signal take effect after this setting is enabled
when the lift runs automatically and the fire protection signal is connected, the function is enabled.
5.TemperatureWith the reason of the different temperatures between COP and CAR, so it
need to adjust the temperature to reduce this difference.
6.Time setupSet the century, year, month, day, hour, minute(It is not necessary to set the week
and the second).
Note: Lift lock enabled and the fire protection enable function can only be set in one hall call
control board(Normally, the board of the main floor). Other hall call control board should be set
to disable.
5.2.11 Description
1LCDSingle colorwhite character and blue grounding, high lumcurrent 350mA
2Display area :118.18mm89.38mm
3Matrix 320240
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Voice announcement
signal input JTAG1,
connect Audio,volume
WE-CAN01 adjuster RW1
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Please pay attention to following information, which are easily be ignored during application.
6.1 Dont touch the circuit board with hands directly, avoiding human body discharge to the
components by static, and destroy them. If you must do it, please touch the grounded metal
firstly.
6.2 Never pull out plug connector of CANBUS (24V+, 24V-, CANH, CANL) when power supply
is switched on. Improper using may cause damage to the device.
6.3 Please refer to chapter 4.8.6 for the setting of terminal resistor. Ignoring this part may cause
malfunction in communication. In case of correct setting, the resistance between CANH and
CANL is approximately 70.
6.4 High requirement of wiring & installation of CANBUS communication cables to be supplied
by special lines, which shall be isolated from 24V supply of the controller and is not
allowed for other purposes. Communication wires must be the twisted-pair wires, the
distance between the twist should be 2~3 cm.
6.5 Lift Lock Enable and Fire Protection Enable could be separately set at any hall call controller.
Be sure that, within an entire lift hall call controller, either Lift Lock Enable or Fire
Protection Enable is available to function. In the case of unusual lift motion under lift lock
or fire protection condition, please emphasize the check on parameter F of WP-CAN-03
where the setup may be in confliction.
6.6 The stopping mode of inverter must be set as free deceleration (Inertial stop), Normal
Deceleration to stop is not allowed for it may cause door lock broken during operation
resulting main contactor to be released when the current for inverter is not switched off thus
injury may occur to inverter.
6.7 Applying the wiring of A+, A-, B+ and B- when high-speed counting input by 422 differential
level signals (YASKAWA 676GL5-IP synchronous inverters and KEB F4 inverters etc.) to
ensure that the jump-connection between S12 and S13 of main controller is off.
6.8 The sensible load such as relay, contactor, arrival chirm must be installed the absorbing circuit
in the side of loop.
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
An up-button and down-button are separately mounted at bottom and top floor, both of which are
mounted at middle floors. The command button corresponding to landing floors are mounted on
car operation box. When any call button is pressed, the signal is registered and the lift runs in the
direction to be determined by first registration. The lift has no response to all calls but car
commands and the landing call(s) in same direction. Automatically, following the sequence, slow
down the speed, leveling at door zone, then open the door. The door is closed automatically or by
pressing close-button and then the lift restarts for next floor until last call in the direction. The
running direction could be re-determined by next call to be registered. In case no more command
followed, the car is parking at last landing floor (in case of Auto homing function, the lift is back
to home station after certain delay).
Under driver operation, the lift has its direction but doesnt run with door close. When driver
close the door, he can change the direction by selecting AS/AX to make lift run along the direction
driver selected.
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Within 15 seconds, the door cannot open completely, the lift will stop opening the door until there
is new hall call or car call. Then lift will close the door automaticly and run according to the call.
7.15 Push-to-open
The door can be reopened by pressing Open-button in car/hall when the car is parking within door
zone.
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
By setting the time parameter of the analogue curve, to shape the running curve and achieve
to stop directly.
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
When power off, the system will switch to the UPS to level and let the passenger out.
After the lift was locked, under the energy-saving status, the door opening button in the car was
lightened to indicate open the door.
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Please perform the installation with the mechanical specification of circuit boards, setting holes
and necessarily make sure that electrical parts do not in contact with others.
One YMQ leveling switch is mounted on the car-top and an isolation (magnet or light) plate
(length 100 ~ 300mm) at landings. When the cars leveling, the plate functions at the middle level
between two contacts of leveling switch.
The quantity of pre-limit switches is defined corresponding to various lift speed for deceleration
purpose. For lifts with speed up to 1.0m/s (including 0.63m/s and 0.5m/s), the 1KW and 2KW are
required; in the case of lift with speed up to 1.75m/s (including 1.6m/s), the 3KW and 4KW shall
be additionally equipped; besides, the 9KW and 10KW shall be additionally equipped in
complementary; for lifts with speed up to2.5m/s (including 2.0m/s, in order to avoid the impact at
high-speed running, flip-flop magnetic switches is generally applied). the installation position
illustrated in the drawing is the distance of car to leveling line when the switches activate
efficiently (That is the distance between leveling switch and the center line of isolation plate); for
the lifts integrating door pre-opening function, additionally YMQS (upper leveling switch) and
YMQX (lower leveling switch) are necessarily to be mounted on the car-top. Three switches are
mounted in vertical direction separately in lower, middle and upper position where TMQ needs to
be placed in middle position. When the car levels accurately in the door zone, the isolation plate is
simultaneously plugged into three leveling switches.
Top landing: terminal limit switch of 6KW (1piece), final limit switch of 8KW (1piece)
Bottom landing: terminal limit switch of 5KW (1piece), final limit switch of 7KW (1piece)
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Note: The following table lists recommended position of pre-limit switches common
speed. The actual activation position should be same to the deceleration distance defined by main
controller (Basic menu B. Parameters 1 Lift data 7 Decel. distance). Therefore, the
installation position of pre-limit switches should be adjusted according to actual condition.
Speed
0.5 0.63 1.0 1.6 1.75 2.0 2.5
Decel.distance
0.8
L1 1.0D0 1.4D0 1.4D1 1.4D1 1.4D2 1.4D2
D0
L3 4.0D0 6.0D0
Please refer to following drawing, the noted installation position is the distance of car to leveling
line when the switches activate efficiently (That is the distance between leveling switch and the
center line of isolation plate.)
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Note:
1. When magnetic switch is applied as YMQ, if the inserted depth of isolation plate reaches
the standard line of switches.
2. The input form of leveling switches could be changed via the parameter setting of main
controller: (Basic menu B. Parameters 3 Controls 4 Logic P2)
Current value = 63 Level switching inputs as NO contacts
Current value = 62 Level switching inputs as NC contacts
8.3 Wiring
For detailed wiring information, please refer to the electric diagrams.
Can-bus applies 4-core pair-twisted shield cables for communication. Supply cables (24V, 24V-)
are of pair-twisted with section area of 0.75mm2 generally. For the floors from 25th stage or in
other occasions where higher drop of voltage may occur to the circuit, the treatment should be
taken to reduce the higher drop and ensure the supply voltage of WP-CAN-03 that has the farthest
location from control cabinet is 20V in minimum. The communication cables (CANH, CANL) are
of pair-twisted with section area of 0.75mm2.
Serial mains (24V, 0C) support nothing but floor indication and communication board.
Serial communication circuit is not allowed to connect with other circuit or grounding. Its supply
shall not be provided for other electric devices.
H-call boards and c-call board (open collector output), which are applicable for LED-type loading,
do not applicable for bulb-type loading. In the event of lift modernizations, bulb-type button lamp
must be changed
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
each floor for its operation status, i.e. calls, running direction, current floor position.
Real time monitor, to monitor the current running speed of the lift, the inpulse of
high-speed counting(the current floor height) and leveling distance after decelerating the speed of
the controller.
System information, to inquiry the version number of the software and the lift number.
After all, other information of controllers e.g. mains condition, door open/close,
communication and faults etc., could be monitored via LED indicators mounted on LCD
operation panel.
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
3 RST CPU Reset Twinkling: Supply input too low or CPU fault reset
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Main Menu
System Monitor
System Parameters
Other Function
Move the cursor by -key or -key. Press Enter for sub-menu or confirm current operation. Press
Esc -key for back to upper menu. With Menu-key, directly switch back to main menu from any
sub-menu.
In sub-menu Parameters, to adjust the value, press and hold Ctrl-key, then press -key or -key
to increase or decrease the value. Press simply -key or - key can move the cursor to
individually modify each digital number of parameter value (that is ones place, tens place and
hundreds place etc.). If there is more than one line in the screen, hold Ctrl-key, then press -key
or -key to change the line.
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
2 PC system Clock
RS232 comm.
Multifunctional input
Multifunctional output
Preset the maintain time
5 Operation language
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
The menu of Call signals Input manually, press Ctrl and to switch to the menu
System controlReal time monitor.
The submenu of Call signalsRandom automaticly is same with the one of Call signals
Input manually. The difference is in this menu, the call signals were produced by the controller
random or the call button in the spot instead of by the manual. When the lift run without direction,
it will used through the call signals provided by random.
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Show as follows
Count: 203 mm
Crawl: 0 mm
Bak1: 0
Bak1: 0
Bak1: 0
S p e e d is the current run speed of the lift C o u n t is impulse value under high-speed
The menu of r Call signals Input manually, press Ctrl and to switch to the menu
System controlReal time monito.
No. 1 Sum 10
Code 20 Flo 1
As showed in the menu, the first line displays Fault No/Total No. That is here, 10 faults are
occurred in total among which this is the first fault occurred in recent days. The second line shows
the fault code 20. The 3rd and 4th line separately display other information of this record, i.e. Fault
occurred time detailed in hour, minute, second and date. Press -key or -key to increase or
decrease current fault number. Ctrl + sc -key to cancel all existed records.
o u n d
Scan/us 2342
TIME is showed in Hour & Minute. ROUND is the total run. SCAN /US is the average time of
scanning.
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
8.00A-1
InCallVer: 1.0
OutCallVer: 1.0
In the menu, the first line shows the version number of controller softwarethe second line is the
version number of car call software, the third line is the version number of hall call software, the
last line is the serial number of control cabinet.
C 1 2 3 4 5 6 7 8 9 0
C 1 2 3 4 5 6 7 8 9 0
The input signals of main controller show as P+No., from P1 to P39, total 39 pcs. Among them,
P1P11P21P31 are the start signs of each line, for example, in the line of P1, 128
90 stand for the signals from P1 to P10, and in the line of P11, 12890 stand for the
signals from P11 to P20, the valid signals are in the reverse video.
From C1 to C16 are the 16 inputs signals in the car call board.
NoteThe signal status is related with the signal logic setting. Please check the part of logic
setting.
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
05/ 06/ 10
The system clock shows the real time clock of system and 24 hours format: hour : minute :second
YY/MM/DD.
Upon pressing Ctrl Enter to enter into the clock setting status, the curve will flash on the
screen, the setting method is to press Ctrl Ctrl to remove the curve UP,
DOWN, LEFT, RIGHT. And press to increase/decrease the value. Pressing Ctrl Esc
to rewrite the value of clock and back to the clock setting status. If the setting is uniform with
the time/date setting standard, it is right. Otherwise, its fault, and it will display the last setting
results.
Note: After replacing the battery of the main control board, you should click into the
levelling system clock menu of system clock setting status.
Function settings: 1
Up-door zone
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Multifunctional input and output include some preserved input/putput backup ports to extend the
increment function.
Setting method: press to select the port No. Pxx . The cursor flashed in the line of port
you selected. After that, press Ctrl to select the function we want to set, then the cursor
will flash in the line of selected function. Press to select the number of the function, on
the last line you can see the Chinese description of the relative function.
NoteDont set the same function on the more than two ports, if it sets wrong,the last set port
is valid.
Pre-open the door Equiped the pre-open door Ports need to be set
monitor
Backup operation Using the UPS made in Santak Ports need to be set
( Weak earthquake )
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
dup home, offset. Press to remove the digit, press to plus/minus the value.
The menu displays 7 setting items:
Total
Fir e r etur n
Park
Ho me
VI Up- offset
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Brake start
Brake stop
Opera. Pr otect
Homing dela y
Start anti-vibration
Direction cancel
Heat pr otect da la y
Backup time da la y
Brake start After the brake is released, the time delayed before traction
machine runs at given speed.
Setting range: 0 ~ 5000mS.
Brake stop When the car stops, the time delayed for braking after zero speed
is given.
Setting range: 0 ~ 5000mS.
Open door completely Setting the holding time from the open door completely to close
door automaticly.
Setting range: 0~5000 S.
Opera Protect Time setting for operation protection.
Setting range: 0 ~ 5000S
Homing delay Time delayed before auto-return to home station
Setting range: 0 ~ 5000S
Leisure energy-saving delay Time setting for from leisure status to energy-saving status
Setting range: 0~5000S.
Start anti-vibration Delaying time setting for providing start signals to avoid some
negative influences because of the vibration of the door lock.
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Setting range:0~5000 mS
Direction cancel delay Time setting for from lift brake to cut the power to cancel inverter
running direction
Setting range:0~5000 mS
Inspection parking Time setting for inspection parking when lift is under inspection
running after releasing the button.
Setting range: 0~5000 mS
Fireman delay Time setting for how long enter into the fireman status after lift
back to fireman floor.
Setting range: 0~5000 mS
If it is set 0, driver+fireman switch should work at the same time when entering into the
fireman status.
Arrival Chime Delay Time setting for how long the arrival chime ends after lift arrived
the door zone.
Setting range: 0~5000 mS ; Default: 500 mS
Heat Protection Delay Time setting for lift back to the normal condition after heat
protection switch get right.
Backup Time Delay Preserve the backup time.
Setting range: 0~5000 mS
Logic N/C and N/O of controller inputs could be set in the menu, including 4 groups settings, each
group can set all the properties of the 32 inputs.
Logic setting:
Max. value FFFFFFFF
Min. valne 00000000
Current value 0 1 0 1 B 8 F F|
Press to remove the cursor press to revise the value and press Enter to
save and back, press Esc to back the menu without any amending.
Suppose the sequence of inputs P8- P1 is N/ON/ON/CN/ON/CN/CN/CN/C,others
are N/O.
Relative binary system:
0000 0000 0000 0000 0000 0000 0010 1111
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Logic setting 1 default value: 0101B8FF The relative input P1P32 show as below
Location Item Component Default Setting
code property digital value
P1 Forced to decelerate 0.51.0M/S S1W N/C 1
under low speed
P2 Forced to decelerate 0.51.0M/S S2W N/C 1
above low speed
P3 Forced to decelerate1.21.75M/S S3W N/C 1
under middle speed
P4 Forced to decelerate1.21.75M/S S4W N/C 1
above middle speed
1111 relative setting value: F
P5 Forced to decelerate2.03.5M/S S9W N/C 1
under high speed
P6 Forced to decelerate2.03.5M/S S10W N/C 1
above high speed
P7 Lower limit of low-speed lift S5W N/C 1
P8 Upper limit of low-speed lift S6W N/C 1
1111 relative setting value: F
P9 Inverter working status FC1 N/O 0
P10 Low speed signals<0.2M/S ZERO N/O 0
P11 Inverter running data exchange signal R2 N/O 0
P12 Brake travelling switch BZK N/C 1
1000 relative setting value: 8
P13 Running contactor conglutination N/C 1
monitorKM1
P14 Brake contactor conglutination N/C 1
monitor 1KZD
P15 Levelling switch in the middle door MQ N/O 0
zone
P16 Inspection 1 JX1 N/C 1
1011 relative setting value: B
P17 Inspection 2 JX2 N/C 1
P18 Inspection / going up AS N/O 0
P19 Inspection / going down AX N/O 0
P20 Hall lock signals KMBT N/O 0
0001 relative setting value: 1
P21 Hall lock signals KMBJ N/O 0
P22 Safety circuit 1 JY1 N/O 0
P23 Levelling switch in the up door zone PS N/O 0
P24 Levelling switch in the down door PX N/O 0
zone
0000 relative setting value: 0
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
From the example above, if there is some N/C input, the relative value of the input is 1.
Logic setting 1 is to set the inputs P1-P32 of the main controller WP-CAN3200.
Logic setting 2 is to set the inputs P33-P35 of the main controller WP-CAN3200.
Logic setting 3 is to set the inputs C1-C16 of the car call controller WP-CAN01C.
Details show as follows:
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Binary system and hex can be transformed each other. Please check the annex table 1.
VS 616 G5/G7
VS 676GL5-JJ/IP
FUJI 5000G11UD
MICO 2000
KEB F4
KEF F4-E
SIEI AVY-L
SIEMENS MM440
indicates the current setting, remove cursor to choose the one you need and press
Door layout setting includes 3 setting items: front door layout setting, back door layout
setting, two doors layout setting.
It can be set the following function separately:
If it is set the front door only, show that the lift will open the front door, wherever
the front/back door option switch is, the lift will open the front door when it arrives one
floor.
If it is set the back door only, show that the lift will open the back door, wherever
the front/back door option switch is, the lift will open the back door when it arrives one floor.
If it isnt set the double doors, but the front door and back door, it shows that when
the lift arrive at a floor, lift will choose to open the front door or back door by the front/back
door option switchQHK.
When you set the double doors, it means when lift arrive at a floor, front and
backdoor will open/close at the same time (run-through door). Once the double doors were
set, the front/back door setting of the relative floor will be selected automaticly.
If the front/back/double door has not been set, lift will pass the floor without
parking.
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Setting sequence: when you enter the menu, press to remove the cursor, and ,
to modify the number, and press Enter to save the modification and exit. If you press
Esc, you will exit the menu without any modification.
A group of setting can set the door layout of 32 floors at most, using 8 hex digits. Each
digit should be set 1, to make sure the front/door/double door setting of the floor which the
digit represented is valid.
For instance: total 13 floors, first floor is run-through door, 2nd,3rd,4th floor select the
front/back door by the door open switch(QHK), 5th , 6th ,7th floor open the front door only,
8th, 9th, 10th floor open the back door only, 11th, 12th floor are passed directly, and 12th floor is
also a run-through door.
Layout setting of the front door:
0 0 0 1 0 0 0 0 0 1 1 1 1 1 1 1
0 0 0 1 0 0 1 1 1 0 0 0 1 1 1 1
0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 1
Binary system and hex can be transformed each other. Please check the annex table 1.
By pressing to make the data between Fxx, Uxx and Dxx to switch to display.
And using to change the floor number.
Floor indication is set separately in left-hand and right-hand digit. Setting range from 0 to 90, 0
for spacebar and others indicate corresponding character.
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Given value 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Given value 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47
Display @ A B C D E F G H I J K L M N O
Given value 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
Display P Q R S T U V W X Y Z [ \ ] ^ _
Given value 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79
Display ` a b c d e f g h i j k l m n o
Given value 80 81 82 83 84 85 86 87 88 89 90
Display p q r s t u v w x y z
During the setting, dot matrix graphics corresponding to defined characters can be seen in LCD
screen, e.g. value defined as 3417, the screen displays B1; in the case of 16xx, the display is
at middle level of right-hand digit position.
Note: It is necessary to save the parameters after the setting or self-learning achieved.
Otherwise, in case of next time when the controller is powered on and reset, the previously
stored parameters setting is unvalued.
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
The function of this menu is to use the default setting to cover the current setting
parameters. When you enter the submenu, system will ask if you need to set default, press
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Notice: if these parameters do not in hand before the operation, it is possible to obtain data via
motor self-learning (Caution: Not with shaft self-learning.). So the inverter can get the parameters
by self-learning. For the detailed operation in inverter programming, refer to the operational
description of inverter in the chapter.
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
After solved the problem, input the parameters again and re-operate.
Fault displayed Causes Troubleshooting
Motor speed Motor speed Check the setting and motor wiring whether motor
(8) After self-learning is done, remove short-connection wire (Brake A50-A63), release KM1,
recovery steel wire ropes and car.
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
The following table, for lifts with speed up to 1.75m/s, which applies inverter YASKAW616G5,
provides parameters as below.
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
l Make sure Lift A and Lift B connect parallelly well. The two relative controller CANH4,
CANL4 also connect well.
1. Set Lift A as Group 1 and Lift B as Group 2. In the case one lift is set with underground
operation and another hasnt, should the group number of the former be set as 1 (Lift A)
and the latter be set as 2 (Lift B).
2. Through the menu B Parameters 3 Controls 7 Calls ctrl., if previous two steps
has been accomplished, the duplex control symbol(appears next to floor display
meaning the success of duplex connection. In the case of absence of the symbol, check
previous operations and the wiring of duplex connection and the connection at J4 on
main board (in normal condition, the resistance between CAN2H and CAN2L is around
60.).
3. The total floors of two lifts should be the same.
4. In case of one set of push buttons for two lifts, take care of followings:
i. Provide a group of DC24V supply separately for driving push-buttons and
push-button lamps. Normally may output two groups of AC20V
individually from the transformer of Lift A and Lift B, which are in
parallel at positive and negative pole after being bridge-rectified.(Attention:
The phase position of the transformer must be in accordance between Lift
A and Lift B to avoid the high voltage after the supply being
interconnected.)
Correspondently interconnect the push-button plug-ins of two hall call controller;
connect V+ to the supply group at positive end and V- at negative end.
ii. Cut off D10 and D11 on the controller.
iii. Parameter F: To enable cancellation of Inspection/Lift lock indication,
set ON at 5th position of binary value or to set 2 at tens place of decimal
value; to set fire protection as NC, set 3 at tens place of decimal value.
Normally, set parameter F as 20 at ordinary floors and as 23 at home station.
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
BRAKE
BRAKE cont
*DO 1 src CONT Brake contactor control
mon
MON
*DO 2 src Drive ready Drive OK Drive OK
Speed is
*DO 3 src Door open mon Door pre-open speed monite
zero
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
Asynchronism reference:1350
*LF.33 Speed adjustment para. Ki 1000 Adjustment on the spot.
Synchronization reference:26100
*LF.34 Current adjuster Kp 1500 1~65535 Adjustment on the spot.
WIPO Electronic VVVF main controller WP-CAN 3200 user manual
adjustable.
0:Universal Rota.Encoder:
HeidenhainERN1387,Resolver,Hi
perface
EC.03 Encoder pole 0OFF 0~1 1: Poles Encoder,HUBNER
Hogs15dn2048a12,UVW Encoder
Synchronous motorLF.04=1can
be adjusted.
EC.04 System position learning 0 0~7
EC.05 Spring frequency 8
0: low precision, increment
encoder, Resolver Encoder
1: high precision, such as
EC.06 Encoder type 0 0/1
sine/cosine encoder, Heidenhain
ERN1387 encoder, Hiperface
Encoder, UVW Encoder
Store system is the result of the
EC.07 19017 0~65535 self-learning.
EC.17 Frequency coefficient 0 1 Normally, it is not used.
Depend on the nameplate of the
dr.00 Motor power motor on the spot.
Depend on the nameplate of the
dr.01 Rate rotation speed motor on the spot.
Depend on the nameplate of the
dr.02 Rated current motor on the spot.
Depend on the nameplate of the
dr.03 Rated frequency motor on the spot.
Depend on the nameplate of the
dr.04 Power factor motor on the spot.
Depend on the nameplate of the
dr.07 Static current 1.1*dr.02 motor on the spot.
Depend on the nameplate of the
dr.09 Rated torque motor on the spot.
Depend on the nameplate of the
dr.10 Max. torque motor on the spot.
Depend on the nameplate of the
dr.12 Rated voltage motor on the spot.
Synchronization Depend on the nameplate of the
dr.17 kilo-rotation voltage motor on the spot.
Depend on the nameplate of the
dr.41 Coil resistance motor on the spot.
Depend on the nameplate of the
dr.42 Coil inductance motor on the spot.
WIPO Electronic VVVF main controller WP-CAN 3200 user manual