SECTION 16621
AUTOMATIC TRANSFER SWITCH
1.01
A. General: It is the intent of this specification to secure an automatic transfer switch that
has been prototype tested, factory built, production tested, and site tested, together with
all accessories necessary for a complete installation as shown on the plans and drawings
and specified herein. An automatic transfer switch with number of poles, voltage and
current ratings as shown on the plans shall be provided. Each ATS shall consist of an
inherently double-throw power transfer switch unit and a control module interconnected
to provide complete automatic operation. All equipment shall be new and of current
production by an international firm which manufactures the generator, controls, and
transfer switch. The company selected will assemble the standby generator set and
system as a matched unit so that there is one source responsibility for factory-backed and
approved warranty, parts and service through a local representative with factory-trained
personnel, with 24-hour response time.
B. Mechanical Requirements
3. All main contacts shall be of silver composition. The main contacts shall be
protected by arcing contacts in sizes 400 amperes and over. The main contacts
shall be of the blow-on configuration and of segmented construction in ratings
600 amperes and over.
5. All contacts, coils, springs, and control elements shall be conveniently removable
from the front of the transfer switch without major disassembly or disconnection
of power conductors.
C. Electrical Requirements
1. Automatic transfer switches not intended for continuous duty or repetitive load
transfer switching are not acceptable.
2. The automatic transfer switch shall be rated in amperes for total system transfer
16621.1
Rev 1.04
3. The automatic transfer switch shall be rated to withstand the rms symmetrical
short circuit current available at the automatic transfer switch terminals, with the
type of overcurrent protection shown on the plans.
1. The control module shall direct the operation of the transfer switch. The
modules sensing and logic shall be a built-in microprocessor-based system for
maximum reliability, minimum maintenance, and inherent digital
communications capability. The control settings shall be stored in nonvolatile
EEPROM. The module shall contain an integral programmable clock and
calendar. The control module shall have a keyed disconnect plug to enable the
control module to be disconnected from the transfer mechanism for routine
maintenance.
The control module shall be mounted separately from the transfer mechanism unit
for safety and ease of maintenance. Interfacing relays shall be industrial control
grade plug-in type with dust cover.
2. The control module shall include programming keypad, alpha-numeric display for
monitoring settings and diagnostic values, key-lockable program selector switch,
light emitting diode status indication, and user instructions. These features shall
be user accessible when the enclosure door is closed.
3. The control module shall be capable of storing the following records in memory
for access either locally (at the control module) or remotely (at a computer):
E. Operation
16621.2
Rev 1.04
1. Source Voltages
a. The voltage of each phase of the normal source and a single phase of the
emergency source shall be monitored with pickup adjustable from 75% to
100% and dropout adjustable from 70% to 95% of nominal. Adjustment
must be digital.
2. Time Delays
a. The control module shall include four time delays that are fully field-
adjustable or keypad or keyboard in increments of 1 second over the entire
range.
c. Light emitting diodes shall indicate when the timing feature is running and
when the time delay has ended.
(1) Time delay for engine start to delay initiation of transfer for
momentary source outages: Range 0-6 seconds. Factory set at 5
seconds.
(2) Time delay for transfer to emergency: Range 0-5 minutes. Set
time shall be 1 minute.
16621.3
Rev 1.04
(3) Time delay for transfer back to normal: Range 0-30 minutes. Set
time shall be 2 minutes.
(4) Time delay for engine cool down: Range 0-30 minutes. Set time
shall be 5 minutes.
(5) Time delay for neutral load: Range 0-60 seconds.
e. Input values outside the allowable parameters shall cause a range error
message to be displayed.
3. The user shall have the ability to manually program an engine start and run for a
period of up to 72 hours in the loaded or unloaded mode of operation. The time
delay transfer to emergency and/or normal may be bypassed during the run
period. A numeric indication shall be displayed of the run time remaining in
hours and minutes. The run period may be stopped at any time with a single key
stroke. After the run period has stopped, the engine shall run unloaded for the
cool-down time.
a. Connect a normally closed contact that, when opened, signals the control
module to start and transfer load to the engine-generator. Closing this
contact shall initiate a retransfer and engine cool down sequence.
b. Monitor an external normally open contact that, when closed, signals the
control module via the ATS to start and transfer load to the engine
generator. Opening this contact shall initiate a retransfer and engine cool-
down sequence. This feature would be used to monitor an external peak
shaving controller, for example.
The load shall transfer to an available utility source immediately upon failure of
the generator source.
5. The following features shall be built into the control module logic. These features
shall be enabled at the factory or in the field by installing an insulated program
jumper provided by the vendor as standard.
16621.4
Rev 1.04
g. Provide red flashing light on top of ATS for indication of normal power
failure and emergency power operation.
6. Status Indicators: Light-emitting diodes shall indicate the status of the following:
a. Contactor Position
b. System Status:
(1) Transfer Switch Position Sensing Fault
(2) Transfer Switch Fail to Transfer
(3) Internal Control Module Fault
(4) Manual Transfer Operation
(5) External Fault Condition (two inputs)
(6) Not In Automatic
(7) Programming Switch Not In Off
The system status messages shall also be shown on the alpha-numeric
display.
c. Accessory Active:
16621.5
Rev 1.04
9. The transfer switch shall have load-shed and sequencing capability to allow up to
nine selected loads to be disconnected prior to transfer in either direction. It shall
be possible to vary the time sequence for reenergizing of the nine loads.
10. A set of gold-flashed contacts rated 10 amps, 28 VDC shall be provided for a low-
voltage engine start signal when the normal source fails.
F. Time-Delay Sequence for Loads: The following loads shall be time delayed as follows:
Pre-load: 3KW
G. Compliance with Codes and Standards: The ATS shall conform to the requirements of:
16621.6
Rev 1.04
H. Withstand Ratings:
1. The ATS shall be rated to withstand 35,000 available rms symmetrical short-
circuit current at the ATS terminals with the type of over current protection
shown on the plans.
2. The control panel shall meet or exceed the voltage surge withstand capability in
accordance with IEEE Standard 472-1974 (ANSI C37.90a-1974) and the impulse
withstand voltage test in accordance with the proposed NEMA Standard ICS 1-
109. The control panel shall conform to the test requirements of UL 991 for
transient over voltage, electromagnetic susceptibility, and electrostatic discharge.
I. Test and Certification: All production units shall be subjected to the following factory
tests:
1. The complete ATS shall be tested to ensure proper operation of the individual
components and correct overall sequence of operation and to ensure that the
operating transfer time, voltage, frequency and time delay settings are in
compliance with the specification requirements.
2. The switch shall be subjected to a dielectric strength test per NEMA Standard ICS
1-109.21.
J. Manufacturers Responsibility:
1. The supplier shall be able to provide the services of a field technician to test and
adjust the system for satisfactory operation. The supplier shall be factory
warranted and trained to work the complete system.
2. The consultant shall have the option of witnessing the testing of the system.
Notification shall be provided one week prior to the test.
3. Submittal shall include specification sheets showing all standard and optional
accessories to be supplied: schematic, wiring diagrams, dimension drawings, and
interconnection diagrams identifying by terminal number each required
interconnection between the generator set and the transfer switch.
4. Each transfer switch shall be provided with two operator manuals providing
installation and operating instructions.
5. Each automatic transfer switch and generator set shall be warranted by the
generator set manufacturer for one year from the date placed in service. Where
manufacturers standard guarantees or warranties are written for a period of more
than one year, at no additional cost to the Owner, such longer terms shall apply.
2.01 Payment
Payment: No separate payment will be made for Section 16621, Automatic Transfer
Switch 30-4000 Ampere - Microprocessor-Controlled Logic. All costs incurred by the
contractor for this work should be included in the unit price or lump sum for the item of
work to which it pertains.
16621.7