Quick Start Guide

600-R-D-0-0-x Programmable PID Controller Heat & Alarm


GETTING STARTED 2 Program Your Gefran Controller 3 Connect Your Controller
Unpack Contents
Verify model numberand application Press and hold F until PAS appears ENTER 99 -
Input Sensor 19 Additional wiring
Power Controller
Press F once, Pro appears ENTER 128 Sensor Type Sensor Type configurations
Program for yourapplication 0 TC J C 30 PT100 C are available
Press F once, PAS appears ENTER 99 1 TC J F 31 PT100 F
+ 20 in the Users
2 TC K C 32 JPT100 C
Note Press and hold F until Hrd appears HEATER Manual and
3 TC K F 33 JPT100 F
Change all menu parameters by
POWER CONTROL General Setup
Press F repeatedly until but appears ENTER 1 4 TC R C 34 PTC C
Guide
using the front panel buttons
5 TC R F 35 PTC F 21
Press and hold F until1 nP appears 6 TC S C 36 NTC C
7 TC S F 37 NTC F
Press F twice, tYP appears ENTER the Input Sensor number 8 TC T C 44 4...20 mA
22
from the list 9 TC T F 46 0...10 V

ALARM
Press F repeatedly until Lo.S* appears ENTER the minimum Input Scale limit
1 Whats Included
Press F once, H i.S* appears ENTER the maximum Input Scale limit
23 2 -
Press F repeatedly until Lo.L* appears ENTER the minimum Alarm Scale limit
Press F once, H i.L* appears ENTER the maximum Alarm Scale limit 24 1 +
Press and hold F until you return to the main process display. This is the display after PAS POWER THERMOCOUPLE
and will be indicated by the Process Variable if an input sensor is connected, or Lo, H i, Sbr,
Err if no input is connected. If needed, automatic tuning (Self-Tune) can be enabled
with the following steps
Use the and buttons to adjust the control setpoint (SV) from the main display. With the machine at ambient temperature and
the control setpoint (SV) set...
Press F once from the main display, AL.1 appears to adjust the Alarm 1 setpoint.

Press the button to switch between automatic and manual control modes from the Press and hold F until CFG appears
Press F once, S.Tu appears ENTER 2
main display. LED 1( L1 ) will light while in manual mode.
Press F once
Cycle power to the controller
LED 3 ( L3 ) will flash during the tuning process

Self-Tune will automatically save new PID


48x48 DIN 600-R-D-0-0-x values once complete
Gefran Controller This Quick Start Guide provides basic information on setting
Mounting Bracket up the Gefran 600 controller for the application referenced
Panel Sealing Gasket above. Additional software and hardware configuration
Screw Terminal Cover information can be found in the Users Manual included
Multi-Language Manual * Parameter may be left at default value for input types 0...37 with this controller or online at www.gefran.com

GEFRAN SpA
Via Sebina, 74 - 25050 PROVAGLIO DISEO (BS) ITALY
Quick Start Guide
600-R-D-0-0-x Programmable PID Controller Heat - Cool
GETTING STARTED 2 Program Your Gefran Controller 3 Connect Your Controller
Unpack Contents
Verify model numberand application Press and hold F until PAS appears ENTER 99 -
Input Sensor 19 Additional wiring
Power Controller
Press F once, Pro appears ENTER 128 Sensor Type Sensor Type configurations
Program for yourapplication 0 TC J C 30 PT100 C are available
Press F once, PAS appears ENTER 99 1 TC J F 31 PT100 F
+ 20 in the Users
2 TC K C 32 JPT100 C
Note Press and hold F until Hrd appears HEATER Manual and
3 TC K F 33 JPT100 F
Change all menu parameters by
POWER CONTROL General Setup
Press F twice, Ctr appears ENTER14 4 TC R C 34 PTC C
Guide
using the front panel buttons
5 TC R F 35 PTC F 21
Press F once, AL.n appears ENTER 0 6 TC S C 36 NTC C
7 TC S F 37 NTC F
Press and hold F until CFG appears 8 TC T C 44 4...20 mA
22
Press and hold F until C.Me appears 9 TC T F 46 0...10 V

COOLING
ENTER 0 cooling with Air
1 Whats Included
ENTER 1 cooling with Oil
23 2 -
ENTER 0 cooling with Water
Press and hold F until1 nP appears 24 1 +
Press F twice, tYP appears ENTER the Input Sensor number POWER THERMOCOUPLE
Press F repeatedly until Lo.S* appears ENTER the minimum Input Scale limit
Press F once, H i.S* appears ENTER the maximum Input Scale limit If needed, automatic tuning (Self-Tune) can be enabled
with the following steps
Press F repeatedly until Lo.L* appears ENTER the minimum Alarm Scale limit
With the machine at ambient temperature and
Press F once, H i.L* appears ENTER the maximum Alarm Scale limit the control setpoint (SV) set...
Press and hold F until Out appears
Press and hold F until CFG appears
Press F once, rl.1 appears ENTER1
Press F once, S.Tu appears ENTER 2
Press and hold F until you return to the main process display. This is the display after PAS
Press F once
and will be indicated by the Process Variable if an input sensor is connected, or Lo, H i, Sbr, Cycle power to the controller
Err if no input is connected. LED 3 ( L3 ) will flash during the tuning process
Use the and buttons to adjust the control setpoint (SV) from the main display. Self-Tune will automatically save new PID
48x48 DIN 600-R-D-0-0-x values once complete
Press the button to switch between automatic and manual control modes from the
Gefran Controller This Quick Start Guide provides basic information on setting
main display. LED 1( L1 ) will light while in manual mode.
Mounting Bracket up the Gefran 600 controller for the application referenced
Panel Sealing Gasket above. Additional software and hardware configuration
Screw Terminal Cover information can be found in the Users Manual included
Multi-Language Manual * Parameter may be left at default value for input types 0...37 with this controller or online at www.gefran.com

GEFRAN SpA
Via Sebina, 74 - 25050 PROVAGLIO DISEO (BS) ITALY
Quick Start Guide
600-R-R-R-0-x Programmable PID Controller Heat - Cool - Alarm
GETTING STARTED 2 Program Your Gefran Controller 3 Connect Your Controller
Unpack Contents
Verify model numberand application Press and hold F until PAS appears ENTER 99 Additional wiring
Input Sensor 19
Power Controller configurations are
Press F once, Pro appears ENTER 128 Sensor Type Sensor Type
Program for yourapplication 0 TC J C 30 PT100 C available in the Users
Press F once, PAS appears ENTER 99 1 TC J F 31 PT100 F Manual and General
20
Note Press and hold F until Hrd appears 2 TC K C 32 JPT100 C
HEATER Setup Guide
3 TC K F 33 JPT100 F
Change all menu parameters by Press F twice, Ctr appears ENTER14 4 TC R C 34 PTC C

using the front panel buttons Press F twice, but appears ENTER1 5 TC R F 35 PTC F 21 6
6 TC S C 36 NTC C
Press and hold F until CFG appears 7 TC S F 37 NTC F

Press and hold F until C.Me appears 8 TC T C 44 4...20 mA


22 5
9 TC T F 46 0...10 V
ENTER 0 cooling with Air COOLING ALARM
1 Whats Included ENTER 1 cooling with Oil
ENTER 0 cooling with Water 23 2 -
Press and hold F until1 nP appears
24 1 +
Press F twice, tYP appears ENTER the Input Sensor number from the list
Press F repeatedly until Lo.S* appears ENTER the minimum Input Scale limit POWER THERMOCOUPLE
Press F once, H i.S* appears ENTER the maximum Input Scale limit
Press F repeatedly until Lo.L* appears ENTER the minimum Alarm Scale limit If needed, automatic tuning (Self-Tune) can be enabled
Press F once, H i.L* appears ENTER the maximum Alarm Scale limit
with the following steps
Press and hold F until Out appears With the machine at ambient temperature and
the control setpoint (SV) set...
Press F three times, rl.1 appears ENTER1
Press F twice, rl.3 appears ENTER 2 Press and hold F until CFG appears
Press and hold F until you return to the main process display. This is the display after PAS Press F once, S.Tu appears ENTER 2
and will be indicated by the Process Variable if an input sensor is connected, or Lo, H i, Sbr, Press F once
Err if no input is connected. Cycle power to the controller
LED 3 ( L3 ) will flash during the tuning process
Use the and buttons to adjust the control setpoint (SV) from the main display.
Self-Tune will automatically save new PID
Press F once from the main display, AL.1 appears to adjust the Alarm 1 setpoint.
48x48 DIN 600-R-R-R-0-x values once complete
Gefran Controller Press the button to switch between automatic and manual control modes from the This Quick Start Guide provides basic information on setting
Mounting Bracket main display. LED 1( L1 ) will light while in manual mode. up the Gefran 600 controller for the application referenced
Panel Sealing Gasket above. Additional software and hardware configuration
Screw Terminal Cover information can be found in the Users Manual included
Multi-Language Manual * Parameter may be left at default value for input types 0...37 with this controller or online at www.gefran.com

GEFRAN SpA
Via Sebina, 74 - 25050 PROVAGLIO DISEO (BS) ITALY
Quick Start Guide
600-R-R-0-0-x Programmable PID Controller Heat - Cool
GETTING STARTED 2 Program Your Gefran Controller 3 Connect Your Controller
Unpack Contents
Verify model numberand application Press and hold F until PAS appears ENTER 99 Input Sensor 19 Additional wiring
Power Controller
Press F once, Pro appears ENTER 128 Sensor Type Sensor Type configurations
Program for yourapplication 0 TC J C 30 PT100 C are available
Press F once, PAS appears ENTER 99 1 TC J F 31 PT100 F
20 in the Users
2 TC K C 32 JPT100 C
Note Press and hold F until Hrd appears HEATER Manual and
3 TC K F 33 JPT100 F
Change all menu parameters by General Setup
Press F twice, Ctr appears ENTER14 4 TC R C 34 PTC C
Guide
using the front panel buttons
5 TC R F 35 PTC F 21
Press F once, AL.n appears ENTER 0 6 TC S C 36 NTC C
7 TC S F 37 NTC F
Press and hold F until CFG appears 8 TC T C 44 4...20 mA
22
Press and hold F until C.Me appears 9 TC T F 46 0...10 V

COOLING
ENTER 0 cooling with Air
1 Whats Included
ENTER 1 cooling with Oil
23 2 -
ENTER 0 cooling with Water
Press and hold F until1 nP appears 24 1 +
Press F twice, tYP appears ENTER the Input Sensor number POWER THERMOCOUPLE
Press F repeatedly until Lo.S* appears ENTER the minimum Input Scale limit
Press F once, H i.S* appears ENTER the maximum Input Scale limit If needed, automatic tuning (Self-Tune) can be enabled
with the following steps
Press F repeatedly until Lo.L* appears ENTER the minimum Alarm Scale limit
With the machine at ambient temperature and
Press F once, H i.L* appears ENTER the maximum Alarm Scale limit the control setpoint (SV) set...
Press and hold F until Out appears
Press and hold F until CFG appears
Press F once, rl.1 appears ENTER1
Press F once, S.Tu appears ENTER 2
Press and hold F until you return to the main process display. This is the display after PAS
Press F once
and will be indicated by the Process Variable if an input sensor is connected, or Lo, H i, Sbr, Cycle power to the controller
Err if no input is connected. LED 3 ( L3 ) will flash during the tuning process
Use the and buttons to adjust the control setpoint (SV) from the main display. Self-Tune will automatically save new PID
48x48 DIN 600-R-R-0-0-x values once complete
Press the button to switch between automatic and manual control modes from the
Gefran Controller This Quick Start Guide provides basic information on setting
main display. LED 1( L1 ) will light while in manual mode.
Mounting Bracket up the Gefran 600 controller for the application referenced
Panel Sealing Gasket above. Additional software and hardware configuration
Screw Terminal Cover information can be found in the Users Manual included
Multi-Language Manual * Parameter may be left at default value for input types 0...37 with this controller or online at www.gefran.com

GEFRAN SpA
Via Sebina, 74 - 25050 PROVAGLIO DISEO (BS) ITALY
Quick Start Guide
600-R-R-0-0-x Programmable PID Controller Heat & Alarm
GETTING STARTED 2 Program Your Gefran Controller 3 Connect Your Controller
Unpack Contents
Verify model numberand application Press and hold F until PAS appears ENTER 99 Input Sensor 19 Additional wiring
Power Controller
Press F once, Pro appears ENTER 128 Sensor Type Sensor Type configurations
Program for yourapplication 0 TC J C 30 PT100 C are available
Press F once, PAS appears ENTER 99 1 TC J F 31 PT100 F
20 in the Users
2 TC K C 32 JPT100 C
Note Press and hold F until Hrd appears HEATER Manual and
3 TC K F 33 JPT100 F
Change all menu parameters by General Setup
Press F repeatedly until but appears ENTER 1 4 TC R C 34 PTC C
Guide
using the front panel buttons
5 TC R F 35 PTC F 21
Press and hold F until1 nP appears 6 TC S C 36 NTC C
7 TC S F 37 NTC F
Press F twice, tYP appears ENTER the Input Sensor number 8 TC T C 44 4...20 mA
22
from the list 9 TC T F 46 0...10 V

ALARM
Press F repeatedly until Lo.S* appears ENTER the minimum Input Scale limit
1 Whats Included
Press F once, H i.S* appears ENTER the maximum Input Scale limit
23 2 -
Press F repeatedly until Lo.L* appears ENTER the minimum Alarm Scale limit
Press F once, H i.L* appears ENTER the maximum Alarm Scale limit 24 1 +
Press and hold F until you return to the main process display. This is the display after PAS POWER THERMOCOUPLE
and will be indicated by the Process Variable if an input sensor is connected, or Lo, H i, Sbr,
Err if no input is connected. If needed, automatic tuning (Self-Tune) can be enabled
with the following steps
Use the and buttons to adjust the control setpoint (SV) from the main display. With the machine at ambient temperature and
the control setpoint (SV) set...
Press F once from the main display, AL.1 appears to adjust the Alarm 1 setpoint.

Press the button to switch between automatic and manual control modes from the Press and hold F until CFG appears
Press F once, S.Tu appears ENTER 2
main display. LED 1( L1 ) will light while in manual mode.
Press F once
Cycle power to the controller
LED 3 ( L3 ) will flash during the tuning process

Self-Tune will automatically save new PID


48x48 DIN 600-R-R-0-0-x values once complete
Gefran Controller This Quick Start Guide provides basic information on setting
Mounting Bracket up the Gefran 600 controller for the application referenced
Panel Sealing Gasket above. Additional software and hardware configuration
Screw Terminal Cover information can be found in the Users Manual included
Multi-Language Manual * Parameter may be left at default value for input types 0...37 with this controller or online at www.gefran.com

GEFRAN SpA
Via Sebina, 74 - 25050 PROVAGLIO DISEO (BS) ITALY
Quick Start Guide
600-R-D-R-0-x Programmable PID Controller Heat - Cool - Alarm
GETTING STARTED 2 Program Your Gefran Controller 3 Connect Your Controller
Unpack Contents
Verify model numberand application Press and hold F until PAS appears ENTER 99 Additional wiring
Input Sensor - 19
Power Controller configurations are
Press F once, Pro appears ENTER 128 Sensor Type Sensor Type
Program for yourapplication 0 TC J C 30 PT100 C available in the Users
Press F once, PAS appears ENTER 99 1 TC J F 31 PT100 F Manual and General
+ 20
Note Press and hold F until Hrd appears 2 TC K C 32 JPT100 C
HEATER Setup Guide
3 TC K F 33 JPT100 F
Press F twice, Ctr appears ENTER14 POWER CONTROL
Change all menu parameters by 4 TC R C 34 PTC C

using the front panel buttons Press F twice, but appears ENTER1 5 TC R F 35 PTC F 21 6
6 TC S C 36 NTC C
Press and hold F until CFG appears 7 TC S F 37 NTC F

Press and hold F until C.Me appears 8 TC T C 44 4...20 mA


22 5
9 TC T F 46 0...10 V
ENTER 0 cooling with Air COOLING ALARM
1 Whats Included ENTER 1 cooling with Oil
ENTER 0 cooling with Water 23 2 -
Press and hold F until1 nP appears
24 1 +
Press F twice, tYP appears ENTER the Input Sensor number from the list
Press F repeatedly until Lo.S* appears ENTER the minimum Input Scale limit POWER THERMOCOUPLE
Press F once, H i.S* appears ENTER the maximum Input Scale limit
Press F repeatedly until Lo.L* appears ENTER the minimum Alarm Scale limit If needed, automatic tuning (Self-Tune) can be enabled
Press F once, H i.L* appears ENTER the maximum Alarm Scale limit
with the following steps
Press and hold F until Out appears With the machine at ambient temperature and
the control setpoint (SV) set...
Press F three times, rl.1 appears ENTER1
Press F twice, rl.3 appears ENTER 2 Press and hold F until CFG appears
Press and hold F until you return to the main process display. This is the display after PAS Press F once, S.Tu appears ENTER 2
and will be indicated by the Process Variable if an input sensor is connected, or Lo, H i, Sbr, Press F once
Err if no input is connected. Cycle power to the controller
LED 3 ( L3 ) will flash during the tuning process
Use the and buttons to adjust the control setpoint (SV) from the main display.
Self-Tune will automatically save new PID
Press F once from the main display, AL.1 appears to adjust the Alarm 1 setpoint.
48x48 DIN 600-R-D-R-0-x values once complete
Gefran Controller Press the button to switch between automatic and manual control modes from the This Quick Start Guide provides basic information on setting
Mounting Bracket main display. LED 1( L1 ) will light while in manual mode. up the Gefran 600 controller for the application referenced
Panel Sealing Gasket above. Additional software and hardware configuration
Screw Terminal Cover information can be found in the Users Manual included
Multi-Language Manual * Parameter may be left at default value for input types 0...37 with this controller or online at www.gefran.com

GEFRAN SpA
Via Sebina, 74 - 25050 PROVAGLIO DISEO (BS) ITALY
Gefran 600: Temperature
Controller - Quick Start Guide