RAJASTHAN RAJYA VIDYUT UTPADAN LIMITED

UTPADAN NIGAM LIMITED

DESIGN CRITERIA FOR HRSG FOUNDATION PROJECT NAME: 1x160 MW CCPP , RRVUNL . RAMGARH RAJASTHAN\ PACKAGE/ SYSTEM , CIVIL

DESIGN OF FOOTING MARK F1L and F1R

DEPTH OF FOOTING BELOW N.G.L. , h= 4.000 M


HEIGHT OF PEDESTAL ABOVE N.G.L. , h1'= 0.877 M
UNIT WT. OF RCC = g rcc 2.500 (T/M3)
UNIT WT. OF SOIL = g soil 1.800 (T/M3)
HT. OF SOIL ABOVE THE FOOTING = h1 =165.7-161-t 4.000 M
NET SAFE BEARING CAPACITY = 50.000 (T/M2)
LENGTH OF FOOTING = Lf 3.500 (M)
WIDTH OF FOOTING = wf 2.500 (M)
AREA OF FOOTING = A 8.750 (M2)
ASSUME THICKNESS OF FOOTING = t 0.700 M
ASSUME WIDTH OF PEDESTAL wp 0.900 M
ASSUME LENGTH OF PEDESTAL Lp 1.500 M
WEIGHT OF PEDESTAL Wped =Lpxwpx(h+h1')xg rcc 14.097 ton
WEIGHT OF SOIL OVER FOOTING Wsoil =((Lfxwf)-(Lpxwp))xh1xg soil 53.280 ton
SELF WEIGHT OF FOOTING Wf =Lfxwfxtxg rcc 15.313 ton
Wself 82.690 ton

CHECKING OF SOIL PRESSURE FOR GROSS LOAD

REFER DRAWING NUMBER NO 1-00-281-53214

BASE PALTE SIZE 32X700X1200 , Assume pedestal size 0.9x1.5 m

Load Data
Vertical Load Horizontal Load
Dead Load Max V DL = 122.7 ton , Max Fx = 0.3 ton
Min V DL = 93.3 ton , Min Fx = 0.3 ton

Live Load LL(V) = 28.8 ton

Wind Load (longitudna wl(V) = 31.0 ton wl(Fx) = 6.2 ton

wind Load (transverse wt(V) = 32.8 ton wt(Fy) = 0.2 ton

seismic Load (longtidu sl(V) = 31.3 ton sl(Fx) = 2.9 ton

Seismic Load (transver st(V) = 18.7 ton st(Fy) = 0.5 ton

Friction Load fl(Fy) = 22.8 ton


fl(Fx) = 22.8 ton
For C3 coefficient value please refer Handbook of concrete engineering by MARK FINTEL , refer page number 147

NET GROSS
FX Force-V FY MX MY BEARING BEARING
CASES (Mton) (Mton) (Mton) (Mton-M) (Mton-M) CAPACITY CAPACITY GROSS FY Qp = P/A ex=MX/FY eY=MY/FY e/Lf e/wf c3 qmax= c3xQp F.O.S.
(T) (T/M2) (T/M2) Overturning sliding
DL+LL 0.30 151.50 0.00 1.46 0.00 50 57.2 234.190 26.76 0.01 0.00 0.00 0.00 1 26.765 < 57.2 280.1 312.3 >1.5 OK
DL+LL+FR 0.30 151.50 22.80 1.46 111.20 50 57.2 234.190 26.76 0.01 0.47 0.00 0.19 2.1 56.206 < 57.2 280.1 312.3 >1.5 OK
DL+LL+WL(T)+FR 29.30 182.50 0.00 142.90 0.00 62.5 69.7 265.190 30.31 0.54 0.00 0.15 0.00 2.1 63.646 < 69.7 3.2 3.6 >1.5 OK
DL+LL+WL(T)-FR 0.30 182.50 22.80 1.46 111.20 62.5 69.7 265.190 30.31 0.01 0.42 0.00 0.17 2.1 63.646 < 69.7 317.2 353.6 >1.5 OK
DL+LL+WL(L)+FR 23.30 184.30 0.00 113.63 0.00 62.5 69.7 266.990 30.51 0.43 0.00 0.12 0.00 1.8 54.924 < 69.7 4.1 4.6 >1.5 OK
DL+LL+WL(L)-FR 0.50 184.30 22.80 2.44 111.20 62.5 69.7 266.990 30.51 0.01 0.42 0.00 0.17 2.1 64.078 < 69.7 191.6 213.6 >1.5 OK
DL+LL-WL(T)+FR -16.30 120.50 0.00 79.50 0.00 62.5 69.7 203.190 23.22 0.39 0.00 0.11 0.00 1.8 41.799 < 69.7 4.5 5.0 >1.5 OK
DL+LL-WL(T)-FR 0.30 120.50 22.80 1.46 111.20 62.5 69.7 203.190 23.22 0.01 0.55 0.00 0.22 2.4 55.732 < 69.7 243.0 270.9 >1.5 OK
DL+LL-WL(L)+FR -22.30 118.70 0.00 108.76 0.00 62.5 69.7 201.390 23.02 0.54 0.00 0.15 0.00 2.1 48.334 < 69.7 3.2 3.6 >1.5 OK
DL+LL-WL(L)-FR 0.50 118.70 22.80 2.44 111.20 62.5 69.7 201.390 23.02 0.01 0.55 0.00 0.22 2.4 55.238 < 69.7 144.5 161.1 >1.5 OK
DL+LL+SL(T)+FR 26.00 141.40 0.00 126.80 0.00 62.5 69.7 224.090 25.61 0.57 0.00 0.16 0.00 2.1 53.782 < 69.7 3.1 3.4 >1.5 OK
DL+LL+SL(T)-FR 0.30 141.40 23.30 1.46 113.63 62.5 69.7 224.090 25.61 0.01 0.51 0.00 0.20 2.2 56.343 < 69.7 268.0 298.8 >1.5 OK
DL+LL+SL(L)+FR 0.30 151.50 25.70 1.46 125.34 62.5 69.7 234.190 26.76 0.01 0.54 0.00 0.21 2.3 61.558 < 69.7 280.1 312.3 >1.5 OK
DL+LL+SL(L)-FR 23.10 151.50 2.90 112.66 14.14 62.5 69.7 234.190 26.76 0.48 0.06 0.14 0.02 1.8 48.176 < 69.7 3.6 4.1 >1.5 OK
DL+WL(L) 6.50 62.30 0.00 31.70 0.00 62.5 69.7 144.990 16.57 0.22 0.00 0.06 0.00 1.4 23.198 < 69.7 8.0 8.9 >1.5 OK
DL-WL(T) 0.30 62.30 6.20 1.46 30.24 62.5 69.7 144.990 16.57 0.01 0.21 0.00 0.08 1.5 24.855 < 69.7 173.4 193.3 >1.5 OK

5
RAJASTHAN RAJYA VIDYUT UTPADAN LIMITED
UTPADAN NIGAM LIMITED

DESIGN CRITERIA FOR HRSG FOUNDATION PROJECT NAME: 1x160 MW CCPP , RRVUNL . RAMGARH RAJASTHAN\ PACKAGE/ SYSTEM , CIVIL

DESIGN OF FOOTING MARK F9L and F9R

DEPTH OF FOOTING BELOW N.G.L. , h= 165.0-160.0-3.0 2.700 M


HEIGHT OF PEDESTAL ABOVE N.G.L. , h1'= 0.877 M
UNIT WT. OF RCC = g rcc 2.500 (T/M3)
UNIT WT. OF SOIL = g soil 1.800 (T/M3)
HT. OF SOIL ABOVE THE FOOTING = h1 =2.7-1.0 1.700 M
NET SAFE BEARING CAPACITY = 50.000 (T/M2)
LENGTH OF FOOTING = Lf 3.500 (M)
WIDTH OF FOOTING = wf 2.500 (M)
AREA OF FOOTING = A 8.750 (M2)
ASSUME THICKNESS OF FOOTING = t 0.700 M
ASSUME WIDTH OF PEDESTAL wp 0.900 M
ASSUME LENGTH OF PEDESTAL Lp 1.500 M
WEIGHT OF PEDESTAL Wped =Lpxwpx(h+h1')xg rcc 9.710 ton
WEIGHT OF SOIL OVER FOOTING Wsoil =((Lfxwf)-(Lpxwp))xh1xg soil 22.644 ton
SELF WEIGHT OF FOOTING Wf =Lfxwfxtxg rcc 15.313 ton
Wself 47.666 ton

CHECKING OF SOIL PRESSURE FOR GROSS LOAD

REFER DRAWING NUMBER NO 1-00-281-53214

BASE PALTE SIZE 32X700X1200 , Assume pedestal size 0.9x1.5 m

Load Data
Vertical Load Horizontal Load
Dead Load Max V DL = 122.7 ton , Max Fx = 0.3 ton
Min V DL = 93.3 ton , Min Fx = 0.3 ton

Live Load LL(V) = 28.8 ton

Wind Load (longitudna wl(V) = 31.0 ton wl(Fx) = 6.2 ton

wind Load (transverse wt(V) = 32.8 ton wt(Fy) = 0.2 ton

seismic Load (longtidu sl(V) = 31.3 ton sl(Fx) = 2.9 ton

Seismic Load (transver st(V) = 18.7 ton st(Fy) = 0.5 ton

Friction Load fl(Fy) = 22.8 ton


fl(Fx) = 22.8 ton
For C3 coefficient value please refer Handbook of concrete engineering by MARK FINTEL , refer page number 147

NET GROSS
FX Force-V FY MX MY BEARING BEARING
CASES (Mton) (Mton) (Mton) (Mton-M) (Mton-M) CAPACITY CAPACITY GROSS FY Qp = P/A ex=MX/FY eY=MY/FY e/Lf e/wf c3 qmax= c3xQp F.O.S.
(T) (T/M2) (T/M2) Overturning sliding
DL+LL 0.30 151.50 0.00 1.07 0.00 50 54.86 199.166 22.76 0.01 0.00 0.00 0.00 1 22.762 < 54.86 324.8 265.6 >1.5 OK
DL+LL+FR 0.30 151.50 22.80 1.07 81.56 50 54.86 199.166 22.76 0.01 0.41 0.00 0.16 2 45.524 < 54.86 324.8 265.6 >1.5 OK
DL+LL+WL(T)+FR 29.30 182.50 0.00 104.81 0.00 62.5 67.36 230.166 26.30 0.46 0.00 0.13 0.00 1.8 47.349 < 67.36 3.8 3.1 >1.5 OK
DL+LL+WL(T)-FR 0.30 182.50 22.80 1.07 81.56 62.5 67.36 230.166 26.30 0.00 0.35 0.00 0.14 1.8 47.349 < 67.36 375.4 306.9 >1.5 OK
DL+LL+WL(L)+FR 23.30 184.30 0.00 83.34 0.00 62.5 67.36 231.966 26.51 0.36 0.00 0.10 0.00 1.6 42.417 < 67.36 4.9 4.0 >1.5 OK
DL+LL+WL(L)-FR 0.50 184.30 22.80 1.79 81.56 62.5 67.36 231.966 26.51 0.01 0.35 0.00 0.14 1.8 47.719 < 67.36 227.0 185.6 >1.5 OK
DL+LL-WL(T)+FR -16.30 120.50 0.00 58.31 0.00 62.5 67.36 168.166 19.22 0.35 0.00 0.10 0.00 1.8 34.594 < 67.36 5.0 4.1 >1.5 OK
DL+LL-WL(T)-FR 0.30 120.50 22.80 1.07 81.56 62.5 67.36 168.166 19.22 0.01 0.48 0.00 0.19 2.1 40.36 < 67.36 274.2 224.2 >1.5 OK
DL+LL-WL(L)+FR -22.30 118.70 0.00 79.77 0.00 62.5 67.36 166.366 19.01 0.48 0.00 0.14 0.00 1.8 34.224 < 67.36 3.6 3.0 >1.5 OK
DL+LL-WL(L)-FR 0.50 118.70 22.80 1.79 81.56 62.5 67.36 166.366 19.01 0.01 0.49 0.00 0.20 2.2 41.829 < 67.36 162.8 133.1 >1.5 OK
DL+LL+SL(T)+FR 26.00 141.40 0.00 93.00 0.00 62.5 67.36 189.066 21.61 0.49 0.00 0.14 0.00 1.8 38.894 < 67.36 3.6 2.9 >1.5 OK
DL+LL+SL(T)-FR 0.30 141.40 23.30 1.07 83.34 62.5 67.36 189.066 21.61 0.01 0.44 0.00 0.18 2.1 45.376 < 67.36 308.3 252.1 >1.5 OK
DL+LL+SL(L)+FR 0.30 151.50 25.70 1.07 91.93 62.5 67.36 199.166 22.76 0.01 0.46 0.00 0.18 2.1 47.8 < 67.36 324.8 265.6 >1.5 OK
DL+LL+SL(L)-FR 23.10 151.50 2.90 82.63 10.37 62.5 67.36 199.166 22.76 0.41 0.05 0.12 0.02 1.8 40.971 < 67.36 4.2 3.4 >1.5 OK
DL+WL(L) 6.50 62.30 0.00 23.25 0.00 62.5 67.36 109.966 12.57 0.21 0.00 0.06 0.00 1.4 17.595 < 67.36 8.3 6.8 >1.5 OK
DL-WL(T) 0.30 62.30 6.20 1.07 22.18 62.5 67.36 109.966 12.57 0.01 0.20 0.00 0.08 1.5 18.851 < 67.36 179.3 146.6 >1.5 OK

5
RAJASTHAN RAJYA VIDYUT UTPADAN LIMITED
UTPADAN NIGAM LIMITED

DESIGN CRITERIA FOR HRSG FOUNDATION PROJECT NAME: 1x160 MW CCPP , RRVUNL . RAMGARH RAJASTHAN\ PACKAGE/ SYSTEM , CIVIL

DESIGN OF FOOTING MARK F2L AND F2R

DEPTH OF FOOTING BELOW N.G.L. , h= 4.000 M


HEIGHT OF PEDESTAL ABOVE N.G.L. , h1'= 0.877 M
UNIT WT. OF RCC = g rcc 2.500 (T/M3)
UNIT WT. OF SOIL = g soil 1.800 (T/M3)
HT. OF SOIL ABOVE THE FOOTING h1 =165.7-161-t 3.500 M
NET SAFE BEARING CAPACITY = 50.000 (T/M2)
LENGTH OF FOOTING = Lf 6.000 (M)
WIDTH OF FOOTING = wf 2.800 (M)
AREA OF FOOTING = A 16.800 (M2)
ASSUME THICKNESS OF FOOTING = t 1.200 M
ASSUME WIDTH OF PEDESTAL wp 0.900 M
ASSUME LENGTH OF PEDESTAL Lp 1.500 M
WEIGHT OF PEDESTAL Wped =Lpxwpx(h+h1')xg rcc 12.410 ton
WEIGHT OF SOIL OVER FOOTING Wsoil =((Lfxwf)-(Lpxwp))xh1xg soil 97.335 ton
SELF WEIGHT OF FOOTING Wf =Lfxwfxtxg rcc 50.400 ton
Wself 160.145 ton

CHECKING OF SOIL PRESSURE FOR GROSS LOAD

REFER DRAWING NUMBER NO 1-00-281-53214

BASE PALTE SIZE 32X700X1200 , Assume pedestal size 0.9x1.5 m

Load Data
Vertical Load Horizontal Load
Dead Load Max V DL = 247.7 ton , Max Fx = 23 ton
Min V DL = 198.4 ton , Min Fx = 20.8 ton

Live Load LL(V) = 27.7 ton

Wind Load (longitudnal wl(V) = 5.0 ton wl(Fx) = 7.9 ton

wind Load (transverse) wt(V) = 50.5 ton wt(Fy) = 0.4 ton

seismic Load (longtidu sl(V) = 5.3 ton sl(Fx) = 6 ton

Seismic Load (transver st(V) = 29.3 ton st(Fy) = 1.1 ton

Friction Load fl(Fy) = 41.300 ton


fl(Fx) = 41.300 ton
For C3 coefficient value please refer Handbook of concrete engineering by MARK FINTEL , refer page number 147

NET GROSS
FX Force-V FY MX MY BEARING BEARING
CASES (Mton) (Mton) (Mton) (Mton-M) (Mton-M) CAPACITY CAPACITY GROSS FY Qp = P/A ex=MX/FY eY=MY/FY e/Lf e/wf c3 qmax= c3xQp F.O.S.
(T) (T/M2) (T/M2) Overturning sliding
DL+LL 23.00 275.40 0.00 112.17 0.00 50 57.2 435.545 25.93 0.26 0.00 0.04 0.00 1.3 33.703 < 57.2 11.6 7.6 >1.5 OK
DL+LL+FR 23.00 275.40 41.30 112.17 201.42 50 57.2 435.545 25.93 0.26 0.46 0.04 0.17 2.15 55.739 < 57.2 11.6 7.6 >1.5 OK
DL+LL+WL(T)+FR 72.20 280.40 0.00 352.12 0.00 62.5 69.7 440.545 26.22 0.80 0.00 0.13 0.00 1.8 47.201 < 69.7 3.8 2.4 >1.5 OK
DL+LL+WL(T)-FR 23.00 280.40 41.30 112.17 201.42 62.5 69.7 440.545 26.22 0.25 0.46 0.04 0.16 2.15 56.379 < 69.7 11.8 7.7 >1.5 OK
DL+LL+WL(L)+FR 64.70 325.90 0.00 315.54 0.00 62.5 69.7 486.045 28.93 0.65 0.00 0.11 0.00 1.6 46.29 < 69.7 4.6 3.0 >1.5 OK
DL+LL+WL(L)-FR 23.40 325.90 41.30 114.12 201.42 62.5 69.7 486.045 28.93 0.23 0.41 0.04 0.15 2.1 60.756 < 69.7 12.8 8.3 >1.5 OK
DL+LL-WL(T)+FR -10.40 270.40 0.00 50.72 0.00 62.5 69.7 430.545 25.63 0.12 0.00 0.02 0.00 1.1 28.19 < 69.7 25.5 16.6 >1.5 OK
DL+LL-WL(T)-FR 23.00 270.40 41.30 112.17 201.42 62.5 69.7 430.545 25.63 0.26 0.47 0.04 0.17 2.2 56.381 < 69.7 11.5 7.5 >1.5 OK
DL+LL-WL(L)+FR -17.90 224.90 0.00 87.30 0.00 62.5 69.7 385.045 22.92 0.23 0.00 0.04 0.00 1.3 29.795 < 69.7 13.2 8.6 >1.5 OK
DL+LL-WL(L)-FR 23.40 224.90 41.30 114.12 201.42 62.5 69.7 385.045 22.92 0.30 0.52 0.05 0.19 2.4 55.006 < 69.7 10.1 6.6 >1.5 OK
DL+LL+SL(T)+FR 70.30 277.00 0.00 342.85 0.00 62.5 69.7 437.145 26.02 0.78 0.00 0.13 0.00 1.8 46.837 < 69.7 3.8 2.5 >1.5 OK
DL+LL+SL(T)-FR 23.00 277.00 42.40 112.17 206.78 62.5 69.7 437.145 26.02 0.26 0.47 0.04 0.17 2.4 62.449 < 69.7 11.7 7.6 >1.5 OK
DL+LL+SL(L)+FR 23.00 275.40 47.30 112.17 230.68 62.5 69.7 435.545 25.93 0.26 0.53 0.04 0.19 2.4 62.221 < 69.7 11.6 7.6 >1.5 OK
DL+LL+SL(L)-FR 64.30 275.40 6.00 313.59 29.26 62.5 69.7 435.545 25.93 0.72 0.07 0.12 0.02 1.7 44.073 < 69.7 4.2 2.7 >1.5 OK
DL+WL(L) 28.70 193.40 0.00 139.97 0.00 62.5 69.7 353.545 21.04 0.40 0.00 0.07 0.00 1.5 31.567 < 69.7 7.6 4.9 >1.5 OK
DL-WL(T) 20.80 193.40 7.90 101.44 38.53 62.5 69.7 353.545 21.04 0.29 0.11 0.05 0.04 1.5 31.567 < 69.7 10.5 6.8 >1.5 OK

6
RAJASTHAN RAJYA VIDYUT UTPADAN LIMITED
UTPADAN NIGAM LIMITED

DESIGN CRITERIA FOR HRSG FOUNDATION PROJECT NAME: 1x160 MW CCPP , RRVUNL . RAMGARH RAJASTHAN\ PACKAGE/ SYSTEM , CIVIL

DESIGN OF FOOTING MARK F3L AND F3R

DEPTH OF FOOTING BELOW N.G.L. , h= 4.000 M


HEIGHT OF PEDESTAL ABOVE N.G.L. , h1'= 0.877 M
UNIT WT. OF RCC = g rcc 2.500 (T/M3)
UNIT WT. OF SOIL = g soil 1.800 (T/M3)
HT. OF SOIL ABOVE THE FOOTING h1 =165.7-161-t 3.600 M
NET SAFE BEARING CAPACITY = 50.000 (T/M2)
LENGTH OF FOOTING = Lf 5.000 (M)
WIDTH OF FOOTING = wf 2.800 (M)
AREA OF FOOTING = A 14.000 (M2)
ASSUME THICKNESS OF FOOTING = t 1.100 M
ASSUME WIDTH OF PEDESTAL wp 0.900 M
ASSUME LENGTH OF PEDESTAL Lp 1.500 M
WEIGHT OF PEDESTAL Wped =Lpxwpx(h+h1')xg rcc 12.747 ton
WEIGHT OF SOIL OVER FOOTING Wsoil =((Lfxwf)-(Lpxwp))xh1xg soil 81.972 ton
SELF WEIGHT OF FOOTING Wf =Lfxwfxtxg rcc 38.500 ton
Wself 133.219 ton

CHECKING OF SOIL PRESSURE FOR GROSS LOAD

REFER DRAWING NUMBER NO 1-00-281-53214

BASE PALTE SIZE 32X700X1200 , Assume pedestal size 0.9x1.5 m

Load Data
Vertical Load Horizontal Load
Dead Load Max V DL = 210.7 ton , Max Fx = 16.6 ton
Min V DL = 161.7 ton , Min Fx = 15.1 ton

Live Load LL(V) = 29.2 ton

Wind Load (longitudnal wl(V) = 0.2 ton wl(Fx) = 0.7 ton

wind Load (transverse) wt(V) = 40.7 ton wt(Fy) = 0.4 ton

seismic Load (longtidu sl(V) = 1.4 ton sl(Fx) = 5.3 ton

Seismic Load (transver st(V) = 23.4 ton st(Fy) = 0.9 ton

Friction Load fl(Fy) = 36.000 ton


fl(Fx) = 36.000 ton
For C3 coefficient value please refer Handbook of concrete engineering by MARK FINTEL , refer page number 147

NET GROSS
FX Force-V FY MX MY BEARING BEARING
CASES (Mton) (Mton) (Mton) (Mton-M) (Mton-M) CAPACITY CAPACITY GROSS FY Qp = P/A ex=MX/FY eY=MY/FY e/Lf e/wf c3 qmax= c3xQp F.O.S.
(T) (T/M2) (T/M2) Overturning sliding
DL+LL 16.60 239.90 0.00 80.96 0.00 50 57.2 373.119 26.65 0.22 0.00 0.04 0.00 1.4 37.312 < 57.2 11.5 9.0 >1.5 OK
DL+LL+FR 16.60 239.90 36.00 80.96 175.57 50 57.2 373.119 26.65 0.22 0.47 0.04 0.17 2.1 55.968 < 57.2 11.5 9.0 >1.5 OK
DL+LL+WL(T)+FR 53.30 240.10 0.00 259.94 0.00 62.5 69.7 373.319 26.67 0.70 0.00 0.14 0.00 1.8 47.998 < 69.7 3.6 2.8 >1.5 OK
DL+LL+WL(T)-FR 16.60 240.10 36.00 80.96 175.57 62.5 69.7 373.319 26.67 0.22 0.47 0.04 0.17 2.1 55.998 < 69.7 11.5 9.0 >1.5 OK
DL+LL+WL(L)+FR 53.00 280.60 0.00 258.48 0.00 62.5 69.7 413.819 29.56 0.62 0.00 0.12 0.00 1.4 41.382 < 69.7 4.0 3.1 >1.5 OK
DL+LL+WL(L)-FR 17.00 280.60 36.00 82.91 175.57 62.5 69.7 413.819 29.56 0.20 0.42 0.04 0.15 2.15 63.551 < 69.7 12.5 9.7 >1.5 OK
DL+LL-WL(T)+FR -18.70 239.70 0.00 91.20 0.00 62.5 69.7 372.919 26.64 0.24 0.00 0.05 0.00 2.1 55.938 < 69.7 10.2 8.0 >1.5 OK
DL+LL-WL(T)-FR 16.60 239.70 36.00 80.96 175.57 62.5 69.7 372.919 26.64 0.22 0.47 0.04 0.17 2.1 55.938 < 69.7 11.5 9.0 >1.5 OK
DL+LL-WL(L)+FR -19.00 199.20 0.00 92.66 0.00 62.5 69.7 332.419 23.74 0.28 0.00 0.06 0.00 1.4 33.242 < 69.7 9.0 7.0 >1.5 OK
DL+LL-WL(L)-FR 17.00 199.20 36.00 82.91 175.57 62.5 69.7 332.419 23.74 0.25 0.53 0.05 0.19 2.6 61.735 < 69.7 10.0 7.8 >1.5 OK
DL+LL+SL(T)+FR 57.90 234.10 0.00 282.38 0.00 62.5 69.7 367.319 26.24 0.77 0.00 0.15 0.00 1.4 36.732 < 69.7 3.3 2.5 >1.5 OK
DL+LL+SL(T)-FR 16.60 234.10 36.90 80.96 179.96 62.5 69.7 367.319 26.24 0.22 0.49 0.04 0.17 2.3 60.345 < 69.7 11.3 8.9 >1.5 OK
DL+LL+SL(L)+FR 16.60 239.90 41.30 80.96 201.42 62.5 69.7 373.119 26.65 0.22 0.54 0.04 0.19 2.4 63.963 < 69.7 11.5 9.0 >1.5 OK
DL+LL+SL(L)-FR 52.60 239.90 5.30 256.53 25.85 62.5 69.7 373.119 26.65 0.69 0.07 0.14 0.02 2 53.303 < 69.7 3.6 2.8 >1.5 OK
DL+WL(L) 15.80 161.50 0.00 77.06 0.00 62.5 69.7 294.719 21.05 0.26 0.00 0.05 0.00 1.4 29.472 < 69.7 9.6 7.5 >1.5 OK
DL-WL(T) 15.10 161.50 0.70 73.64 3.41 62.5 69.7 294.719 21.05 0.25 0.01 0.05 0.00 1.4 29.472 < 69.7 10.0 7.8 >1.5 OK 7
RAJASTHAN RAJYA VIDYUT UTPADAN LIMITED
UTPADAN NIGAM LIMITED

DESIGN CRITERIA FOR HRSG FOUNDATION PROJECT NAME: 1x160 MW CCPP , RRVUNL . RAMGARH RAJASTHAN\ PACKAGE/ SYSTEM , CIVIL

DESIGN OF FOOTING MARK S8L , S8R , S6L ,S6R , S4L AND S4R

DEPTH OF FOOTING BELOW N.G.L. , h= 4.000 M


HEIGHT OF PEDESTAL ABOVE N.G.L. , h1'= 0.877 M
UNIT WT. OF RCC = g rcc 2.500 (T/M3)
UNIT WT. OF SOIL = g soil 1.800 (T/M3)
HT. OF SOIL ABOVE THE FOOTING = h1 =165.7-161-t 3.800 M
NET SAFE BEARING CAPACITY = 50.000 (T/M2)
LENGTH OF FOOTING = Lf 4.200 (M)
WIDTH OF FOOTING = wf 2.800 (M)
AREA OF FOOTING = A 11.760 (M2)
ASSUME THICKNESS OF FOOTING = t 0.900 M
ASSUME WIDTH OF PEDESTAL wp 0.900 M
ASSUME LENGTH OF PEDESTAL Lp 1.500 M
WEIGHT OF PEDESTAL Wped =Lpxwpx(h+h1')xg rcc 13.422 ton
WEIGHT OF SOIL OVER FOOTING Wsoil =((Lfxwf)-(Lpxwp))xh1xg soil 71.204 ton
SELF WEIGHT OF FOOTING Wf =Lfxwfxtxg rcc 26.460 ton
Wself 111.087 ton

CHECKING OF SOIL PRESSURE FOR GROSS LOAD

REFER DRAWING NUMBER NO 1-00-281-53214

BASE PALTE SIZE 32X700X1200 , Assume pedestal size 0.9x1.5 m

Load Data
Vertical Load Horizontal Load
Dead Load Max V DL = 157.300 ton , Max Fx = 15.5 ton
Min V DL = 122.800 ton , Min Fx = 14.2 ton

Live Load LL(V) = 29.100 ton

Wind Load (longitudnal) wl(V) = 0.100 ton wl(Fx) = 7.1 ton

wind Load (transverse) wt(V) = 41.700 ton wt(Fy) = 0.4 ton

seismic Load (longtidunal) sl(V) = 0.200 ton sl(Fx) = 5.4 ton

Seismic Load (transverse) st(V) = 20.600 ton st(Fy) = 0.9 ton

Friction Load fl(Fy) = 10.000 ton


fl(Fx) = 28.000 ton
NET GROSS
FX Force-V FY MX MY BEARING BEARING
CASES (Mton) (Mton) (Mton) (Mton-M) (Mton-M) CAPACITY CAPACITY GROSS FY Qp = P/A ex=MX/FY eY=MY/FY e/Lf e/wf c3 qmax= c3xQp F.O.S.
(T) (T/M2) (T/M2) Overturning sliding
DL+LL 15.50 186.40 0.00 75.59 0.00 50 57.2 297.487 25.30 0.25 0.00 0.06 0.00 1.5 37.945 < 57.2 8.3 7.7 >1.5 OK
DL+LL+FR 15.50 186.40 28.00 75.59 136.56 50 57.2 297.487 25.30 0.25 0.46 0.06 0.16 2.25 56.917 < 57.2 8.3 7.7 >1.5 OK
DL+LL+WL(T)+FR 50.60 186.50 0.00 246.78 0.00 62.5 69.7 297.587 25.30 0.83 0.00 0.20 0.00 1.1 27.835 < 69.7 2.5 2.4 >1.5 OK
DL+LL+WL(T)-FR 15.50 186.50 28.00 75.59 136.56 62.5 69.7 297.587 25.30 0.25 0.46 0.06 0.16 2.3 58.201 < 69.7 8.3 7.7 >1.5 OK
DL+LL+WL(L)+FR 25.90 228.10 0.00 126.31 0.00 62.5 69.7 339.187 28.84 0.37 0.00 0.09 0.00 1.5 43.264 < 69.7 5.6 5.2 >1.5 OK
DL+LL+WL(L)-FR 15.90 228.10 10.00 77.54 48.77 62.5 69.7 339.187 28.84 0.23 0.14 0.05 0.05 1.4 40.379 < 69.7 9.2 8.5 >1.5 OK
DL+LL-WL(T)+FR -5.40 186.30 0.00 26.34 0.00 62.5 69.7 297.387 25.29 0.09 0.00 0.02 0.00 1.1 27.817 < 69.7 23.7 22.0 >1.5 OK
DL+LL-WL(T)-FR 15.50 186.30 28.00 75.59 136.56 62.5 69.7 297.387 25.29 0.25 0.46 0.06 0.16 2.3 58.162 < 69.7 8.3 7.7 >1.5 OK
DL+LL-WL(L)+FR 5.90 144.70 0.00 28.77 0.00 62.5 69.7 255.787 21.75 0.11 0.00 0.03 0.00 2.2 47.851 < 69.7 18.7 17.3 >1.5 OK
DL+LL-WL(L)-FR 15.90 144.70 10.00 77.54 48.77 62.5 69.7 255.787 21.75 0.30 0.19 0.07 0.07 1.8 39.151 < 69.7 6.9 6.4 >1.5 OK
DL+LL+SL(T)+FR 48.90 177.90 0.00 238.49 0.00 62.5 69.7 288.987 24.57 0.83 0.00 0.20 0.00 2.2 54.062 < 69.7 2.5 2.4 >1.5 OK
DL+LL+SL(T)-FR 15.50 177.90 10.90 75.59 53.16 62.5 69.7 288.987 24.57 0.26 0.18 0.06 0.07 2.3 56.52 < 69.7 8.0 7.5 >1.5 OK
DL+LL+SL(L)+FR 15.50 186.40 15.40 75.59 75.11 62.5 69.7 297.487 25.30 0.25 0.25 0.06 0.09 2.3 58.182 < 69.7 8.3 7.7 >1.5 OK
DL+LL+SL(L)-FR 25.50 186.40 5.40 124.36 26.34 62.5 69.7 297.487 25.30 0.42 0.09 0.10 0.03 2.2 55.652 < 69.7 5.0 4.7 >1.5 OK
DL+WL(L) 21.30 122.70 0.00 103.88 0.00 62.5 69.7 233.787 19.88 0.44 0.00 0.11 0.00 1.6 31.808 < 69.7 4.7 4.4 >1.5 OK
DL-WL(T) 14.20 122.70 7.10 69.25 34.63 62.5 69.7 233.787 19.88 0.30 0.15 0.07 0.05 2.3 45.724 < 69.7 7.1 6.6 >1.5 OK 8
RAJASTHAN RAJYA VIDYUT UTPADAN LIMITED
UTPADAN NIGAM LIMITED

DESIGN CRITERIA FOR HRSG FOUNDATION PROJECT NAME: 1x160 MW CCPP , RRVUNL . RAMGARH RAJASTHAN\ PACKAGE/ SYSTEM , CIVIL

DESIGN OF FOOTING MARK F7L , F7R, F5L AND F5R

DEPTH OF FOOTING BELOW N.G.L. , h= 4.000 M


HEIGHT OF PEDESTAL ABOVE N.G.L. , h1'= 0.877 M
UNIT WT. OF RCC = g rcc 2.500 (T/M3)
UNIT WT. OF SOIL = g soil 1.800 (T/M3)
HT. OF SOIL ABOVE THE FOOTING = h1 =165.7-161-t 3.700 M
NET SAFE BEARING CAPACITY = 50.000 (T/M2)
LENGTH OF FOOTING = Lf 4.700 (M)
WIDTH OF FOOTING = wf 2.800 (M)
AREA OF FOOTING = A 13.160 (M2)
ASSUME THICKNESS OF FOOTING = t 1.000 M
ASSUME WIDTH OF PEDESTAL wp 0.900 M
ASSUME LENGTH OF PEDESTAL Lp 1.500 M
WEIGHT OF PEDESTAL Wped =Lpxwpx(h+h1')xg rcc 13.085 ton
WEIGHT OF SOIL OVER FOOTING Wsoil =((Lfxwf)-(Lpxwp))xh1xg soil 78.655 ton
SELF WEIGHT OF FOOTING Wf =Lfxwfxtxg rcc 32.900 ton
Wself 124.639 ton

CHECKING OF SOIL PRESSURE FOR GROSS LOAD

REFER DRAWING NUMBER NO 1-00-281-53214

BASE PALTE SIZE 32X700X1200 , Assume pedestal size 0.9x1.5 m

Load Data
Vertical Load Horizontal Load
Dead Load Max V DL = 180.4 ton , Max Fx = 17.8 ton
Min V DL = 137.6 ton , Min Fx = 16.3 ton

Live Load LL(V) = 29.4 ton

Wind Load (longitudna wl(V) = 0.8 ton wl(Fx) = 6.9 ton

wind Load (transverse wt(V) = 53.1 ton wt(Fy) = 0.4 ton

seismic Load (longtidu sl(V) = 1.9 ton sl(Fx) = 5.3 ton

Seismic Load (transver st(V) = 25.3 ton st(Fy) = 0.9 ton

Friction Load fl(Fy) = 31.500 ton


fl(Fx) = 31.500 ton

For C3 coefficient value please refer Handbook of concrete engineering by MARK FINTEL , refer page number 147

NET GROSS
FX Force-V FY MX MY BEARING BEARING
CASES (Mton) (Mton) (Mton) (Mton-M) (Mton-M) CAPACITY CAPACITY GROSS FY Qp = P/A ex=MX/FY eY=MY/FY e/Lf e/wf c3 qmax= c3xQp F.O.S.
(T) (T/M2) (T/M2) Overturning sliding
DL+LL 17.80 209.80 0.00 86.81 0.00 50 57.2 334.439 25.41 0.26 0.00 0.06 0.00 1.1 27.955 < 57.2 9.1 7.5 >1.5 OK
DL+LL+FR 17.80 209.80 31.50 86.81 153.63 50 57.2 334.439 25.41 0.26 0.46 0.06 0.16 2.25 57.18 < 57.2 9.1 7.5 >1.5 OK
DL+LL+WL(T)+FR 56.20 210.60 0.00 274.09 0.00 62.5 69.7 335.239 25.47 0.82 0.00 0.17 0.00 1.7 43.306 < 69.7 2.9 2.4 >1.5 OK
DL+LL+WL(T)-FR 17.80 210.60 31.50 86.81 153.63 62.5 69.7 335.239 25.47 0.26 0.46 0.06 0.16 2.25 57.317 < 69.7 9.1 7.5 >1.5 OK
DL+LL+WL(L)+FR 49.70 262.90 0.00 242.39 0.00 62.5 69.7 387.539 29.45 0.63 0.00 0.13 0.00 1.75 51.535 < 69.7 3.8 3.1 >1.5 OK
DL+LL+WL(L)-FR 18.20 262.90 31.50 88.76 153.63 62.5 69.7 387.539 29.45 0.23 0.40 0.05 0.14 2.1 61.841 < 69.7 10.3 8.5 >1.5 OK
DL+LL-WL(T)+FR -6.80 209.00 0.00 33.16 0.00 62.5 69.7 333.639 25.35 0.10 0.00 0.02 0.00 1.1 27.888 < 69.7 23.6 19.6 >1.5 OK
DL+LL-WL(T)-FR 17.80 209.00 31.50 86.81 153.63 62.5 69.7 333.639 25.35 0.26 0.46 0.06 0.16 2.5 63.381 < 69.7 9.0 7.5 >1.5 OK
DL+LL-WL(L)+FR -13.30 156.70 0.00 64.86 0.00 62.5 69.7 281.339 21.38 0.23 0.00 0.05 0.00 1.4 29.93 < 69.7 10.2 8.5 >1.5 OK
DL+LL-WL(L)-FR 18.20 156.70 31.50 88.76 153.63 62.5 69.7 281.339 21.38 0.32 0.55 0.07 0.20 2.8 59.859 < 69.7 7.4 6.2 >1.5 OK
DL+LL+SL(T)+FR 54.60 205.70 0.00 266.28 0.00 62.5 69.7 330.339 25.10 0.81 0.00 0.17 0.00 2.1 52.714 < 69.7 2.9 2.4 >1.5 OK
DL+LL+SL(T)-FR 17.80 205.70 32.40 86.81 158.01 62.5 69.7 330.339 25.10 0.26 0.48 0.06 0.17 2.3 57.734 < 69.7 8.9 7.4 >1.5 OK
DL+LL+SL(L)+FR 17.80 209.80 36.80 86.81 179.47 62.5 69.7 334.439 25.41 0.26 0.54 0.06 0.19 2.6 66.075 < 69.7 9.1 7.5 >1.5 OK
DL+LL+SL(L)-FR 49.30 209.80 5.30 240.44 25.85 62.5 69.7 334.439 25.41 0.72 0.08 0.15 0.03 2.1 53.368 < 69.7 3.3 2.7 >1.5 OK
DL+WL(L) 23.20 136.80 0.00 113.15 0.00 62.5 69.7 261.439 19.87 0.43 0.00 0.09 0.00 1.6 31.786 < 69.7 5.4 4.5 >1.5 OK
DL-WL(T) 16.30 136.80 6.90 79.50 33.65 62.5 69.7 261.439 19.87 0.30 0.13 0.06 0.05 1.7 33.773 < 69.7 7.7 6.4 >1.5 OK 9
RAJASTHAN RAJYA VIDYUT UTPADAN LIMITED
UTPADAN NIGAM LIMITED

DESIGN CRITERIA FOR HRSG FOUNDATION PROJECT NAME: 1x160 MW CCPP , RRVUNL . RAMGARH RAJASTHAN\ PACKAGE/ SYSTEM , CIVIL

DESIGN OF FOOTING MARK F'4L AND F'4R

DEPTH OF FOOTING BELOW N.G.L. , h= 4.000 M


HEIGHT OF PEDESTAL ABOVE N.G.L. , h1'= 0.877 M
UNIT WT. OF RCC = g rcc 2.500 (T/M3)
UNIT WT. OF SOIL = g soil 1.800 (T/M3)
HT. OF SOIL ABOVE THE FOOTING h1 =165.7-161-t 4.100 M
NET SAFE BEARING CAPACITY = 50.000 (T/M2)
LENGTH OF FOOTING = Lf 3.000 (M)
WIDTH OF FOOTING = wf 2.500 (M)
AREA OF FOOTING = A 7.500 (M2)
ASSUME THICKNESS OF FOOTING = t 0.600 M
ASSUME WIDTH OF PEDESTAL wp 0.900 M
ASSUME LENGTH OF PEDESTAL Lp 1.500 M
WEIGHT OF PEDESTAL Wped =Lpxwpx(h+h1')xg rcc 14.435 ton
WEIGHT OF SOIL OVER FOOTING Wsoil =((Lfxwf)-(Lpxwp))xh1xg soil 45.387 ton
SELF WEIGHT OF FOOTING Wf =Lfxwfxtxg rcc 11.250 ton
Wself 71.072 ton

CHECKING OF SOIL PRESSURE FOR GROSS LOAD

REFER DRAWING NUMBER NO 1-00-281-53214

BASE PALTE SIZE 32X700X1200 , Assume pedestal size 0.9x1.5 m

Load Data
Vertical Load Horizontal Load
Dead Load Max V DL = 34.4 ton , Max Fx = 0.6 ton
Min V DL = 31.3 ton , Min Fx = 0.5 ton

Live Load LL(V) = 4.6 ton

Wind Load (longitudnal wl(V) = 0.0 ton wl(Fx) = 0 ton

wind Load (transverse) wt(V) = 11.3 ton wt(Fy) = 4.2 ton

seismic Load (longtidu sl(V) = 0.0 ton sl(Fx) = 0 ton

Seismic Load (transver st(V) = 8.6 ton st(Fy) = 3.3 ton

Friction Load fl(Fy) = 5.900 ton


fl(Fx) = 5.900 ton

For C3 coefficient value please refer Handbook of concrete engineering by MARK FINTEL , refer page number 147

NET GROSS
FX Force-V FY MX MY BEARING BEARING
Node CASES (Mton) (Mton) (Mton) (Mton-M) (Mton-M) CAPACITY CAPACITY GROSS FY Qp = P/A ex=MX/FY eY=MY/FY e/Lf e/wf c3 qmax= c3xQp F.O.S.
(T) (T/M2) (T/M2) Overturning sliding
S9L DL+LL 0.60 39.00 0.00 2.93 0.00 50 57.2 110.072 14.68 0.03 0.00 0.01 0.00 1.1 16.144 < 57.2 56.4 73.4 >1.5 OK
& DL+LL+FR 0.60 39.00 5.90 2.93 28.77 50 57.2 110.072 14.68 0.03 0.26 0.01 0.10 1.6 23.482 < 57.2 56.4 73.4 >1.5 OK
S9R DL+LL+WL(T)+FR 6.50 39.00 0.00 31.70 0.00 62.5 69.7 110.072 14.68 0.29 0.00 0.10 0.00 1.5 22.014 < 69.7 5.2 6.8 >1.5 OK
DL+LL+WL(T)-FR 0.60 39.00 5.90 2.93 28.77 62.5 69.7 110.072 14.68 0.03 0.26 0.01 0.10 1.6 23.482 < 69.7 56.4 73.4 >1.5 OK
DL+LL+WL(L)+FR 10.70 50.30 0.00 52.18 0.00 62.5 69.7 121.372 16.18 0.43 0.00 0.14 0.00 1.8 29.129 < 69.7 3.5 4.5 >1.5 OK
DL+LL+WL(L)-FR 4.80 50.30 5.90 23.41 28.77 62.5 69.7 121.372 16.18 0.19 0.24 0.06 0.09 1.9 30.748 < 69.7 7.8 10.1 >1.5 OK
DL+LL-WL(T)+FR -5.30 39.00 0.00 25.85 0.00 62.5 69.7 110.072 14.68 0.23 0.00 0.08 0.00 1.5 22.014 < 69.7 6.4 8.3 >1.5 OK
DL+LL-WL(T)-FR 0.60 39.00 5.90 2.93 28.77 62.5 69.7 110.072 14.68 0.03 0.26 0.01 0.10 1.6 23.482 < 69.7 56.4 73.4 >1.5 OK
DL+LL-WL(L)+FR -1.10 27.70 0.00 5.36 0.00 62.5 69.7 98.772 13.17 0.05 0.00 0.02 0.00 1.1 14.487 < 69.7 27.6 35.9 >1.5 OK
DL+LL-WL(L)-FR 4.80 27.70 5.90 23.41 28.77 62.5 69.7 98.772 13.17 0.24 0.29 0.08 0.12 1.7 22.388 < 69.7 6.3 8.2 >1.5 OK
DL+LL+SL(T)+FR 6.50 43.00 0.00 31.70 0.00 62.5 69.7 114.072 15.21 0.28 0.00 0.09 0.00 2.2 33.461 < 69.7 5.4 7.0 >1.5 OK
DL+LL+SL(T)-FR 0.60 43.00 9.20 2.93 44.87 62.5 69.7 114.072 15.21 0.03 0.39 0.01 0.16 1.5 22.814 < 69.7 58.5 76.0 >1.5 OK
DL+LL+SL(L)+FR 0.60 39.00 5.90 2.93 28.77 62.5 69.7 110.072 14.68 0.03 0.26 0.01 0.10 1.6 23.482 < 69.7 56.4 73.4 >1.5 OK
DL+LL+SL(L)-FR 6.50 39.00 0.00 31.70 0.00 62.5 69.7 110.072 14.68 0.29 0.00 0.10 0.00 1.5 22.014 < 69.7 5.2 6.8 >1.5 OK
DL+WL(L) 0.50 31.30 0.00 2.44 0.00 62.5 69.7 102.372 13.65 0.02 0.00 0.01 0.00 1.1 15.015 < 69.7 63.0 81.9 >1.5 OK
DL-WL(T) 0.50 31.30 0.00 2.44 0.00 62.5 69.7 102.372 13.65 0.02 0.00 0.01 0.00 1.1 15.015 < 69.7 63.0 81.9 >1.5 OK 10
RAJASTHAN RAJYA VIDYUT UTPADAN LIMITED
UTPADAN NIGAM LIMITED

DESIGN CRITERIA FOR HRSG FOUNDATION PROJECT NAME: 1x160 MW CCPP , RRVUNL . RAMGARH RAJASTHAN\ PACKAGE/ SYSTEM , CIVIL

DESIGN OF FOOTING MARK F'1L AND F'1R TO F'3L AND F'3R

DEPTH OF FOOTING BELOW N.G.L. , h= 4.000 M


HEIGHT OF PEDESTAL ABOVE N.G.L. , h1'= 0.889 M
UNIT WT. OF RCC = g rcc 2.500 (T/M3)
UNIT WT. OF SOIL = g soil 1.800 (T/M3)
HT. OF SOIL ABOVE THE FOOTING h1 =165.7-161-t 4.200 M
NET SAFE BEARING CAPACITY = 50.000 (T/M2)
LENGTH OF FOOTING = Lf 2.000 (M)
WIDTH OF FOOTING = wf 2.000 (M)
AREA OF FOOTING = A 4.000 (M2)
ASSUME THICKNESS OF FOOTING = t 0.500 M
ASSUME WIDTH OF PEDESTAL wp 0.850 M
ASSUME LENGTH OF PEDESTAL Lp 0.850 M
WEIGHT OF PEDESTAL Wped =Lpxwpx(h+h1')xg rcc 7.928 ton
WEIGHT OF SOIL OVER FOOTING Wsoil =((Lfxwf)-(Lpxwp))xh1xg soil 24.778 ton
SELF WEIGHT OF FOOTING Wf =Lfxwfxtxg rcc 5.000 ton
Wself 37.706 ton

CHECKING OF SOIL PRESSURE FOR GROSS LOAD

REFER DRAWING NUMBER NO 1-00-281-53214

BASE PALTE SIZE 25X650X650 , Assume pedestal size 1.0x1.5 m

Load Data
Vertical Load Horizontal Load
Dead Load Max V DL = 22.7 ton , Max Fx = 1.1 ton
Min V DL = 20.6 ton , Min Fx = 1 ton

Live Load LL(V) = 3.6 ton

Wind Load (longitudnal wl(V) = 0.0 ton wl(Fx) = 0 ton

wind Load (transverse) wt(V) = 5.6 ton wt(Fy) = 4.2 ton

seismic Load (longtidu sl(V) = 0.0 ton sl(Fx) = 0 ton

Seismic Load (transver st(V) = 4.5 ton st(Fy) = 3.5 ton

Friction Load fl(Fy) = 4.000 ton


fl(Fx) = 4.000 ton
For C3 coefficient value please refer Handbook of concrete engineering by MARK FINTEL , refer page number 147

NET GROSS
FX Force-V FY MX MY BEARING BEARING
CASES (Mton) (Mton) (Mton) (Mton-M) (Mton-M) CAPACITY CAPACITY GROSS FY Qp = P/A ex=MX/FY eY=MY/FY e/Lf e/wf c3 qmax= c3xQp F.O.S.
(T/M2) (T/M2) (T/M2) Overturning sliding
DL+LL 1.10 26.30 0.00 5.38 0.00 50 57.2 64.006 16.00 0.08 0.00 0.04 0.00 1.2 19.202 < 57.2 11.9 23.3 >1.5 OK
DL+LL+FR 1.10 26.30 4.00 5.38 19.56 50 57.2 64.006 16.00 0.08 0.31 0.04 0.15 2.1 33.603 < 57.2 11.9 23.3 >1.5 OK
DL+LL+WL(T)+FR 5.10 26.30 0.00 24.93 0.00 62.5 69.7 64.006 16.00 0.39 0.00 0.19 0.00 2 32.003 < 69.7 2.6 5.0 >1.5 OK
DL+LL+WL(T)-FR 1.10 26.30 4.00 5.38 19.56 62.5 69.7 64.006 16.00 0.08 0.31 0.04 0.15 2.1 33.603 < 69.7 11.9 23.3 >1.5 OK
DL+LL+WL(L)+FR 9.30 31.90 0.00 45.47 0.00 62.5 69.7 69.606 17.40 0.65 0.00 0.33 0.00 3 52.204 < 69.7 1.5 3.0 >1.5 OK
DL+LL+WL(L)-FR 5.30 31.90 4.00 25.91 19.56 62.5 69.7 69.606 17.40 0.37 0.28 0.19 0.14 2.8 48.724 < 69.7 2.7 5.3 >1.5 OK
DL+LL-WL(T)+FR -2.90 26.30 0.00 14.18 0.00 62.5 69.7 64.006 16.00 0.22 0.00 0.11 0.00 1.2 19.202 < 69.7 4.5 8.8 >1.5 OK
DL+LL-WL(T)-FR 1.10 26.30 4.00 5.38 19.56 62.5 69.7 64.006 16.00 0.08 0.31 0.04 0.15 2.1 33.603 < 69.7 11.9 23.3 >1.5 OK
DL+LL-WL(L)+FR 1.30 20.70 0.00 6.36 0.00 62.5 69.7 58.406 14.60 0.11 0.00 0.05 0.00 1.2 17.522 < 69.7 9.2 18.0 >1.5 OK
DL+LL-WL(L)-FR 5.30 20.70 4.00 25.91 19.56 62.5 69.7 58.406 14.60 0.44 0.33 0.22 0.17 3.3 48.185 < 69.7 2.3 4.4 >1.5 OK
DL+LL+SL(T)+FR 5.10 27.20 0.00 24.93 0.00 62.5 69.7 64.906 16.23 0.38 0.00 0.19 0.00 2 32.453 < 69.7 2.6 5.1 >1.5 OK
DL+LL+SL(T)-FR 1.10 27.20 7.50 5.38 36.67 62.5 69.7 64.906 16.23 0.08 0.56 0.04 0.28 3 48.679 < 69.7 12.1 23.6 >1.5 OK
DL+LL+SL(L)+FR 1.10 26.30 4.00 5.38 19.56 62.5 69.7 64.006 16.00 0.08 0.31 0.04 0.15 2.1 33.603 < 69.7 11.9 23.3 >1.5 OK
DL+LL+SL(L)-FR 5.10 26.30 0.00 24.93 0.00 62.5 69.7 64.006 16.00 0.39 0.00 0.19 0.00 2 32.003 < 69.7 2.6 5.0 >1.5 OK
DL+WL(L) 1.00 20.60 0.00 4.89 0.00 62.5 69.7 58.306 14.58 0.08 0.00 0.04 0.00 1.2 17.492 < 69.7 11.9 23.3 >1.5 OK
DL-WL(T) 1.00 20.60 0.00 4.89 0.00 62.5 69.7 58.306 14.58 0.08 0.00 0.04 0.00 1.2 17.492 < 69.7 11.9 23.3 >1.5 OK 11
RAJASTHAN RAJYA VIDYUT UTPADAN LIMITED

DESIGN CRITERIA PROJECT NAME: 1x160 MW CCPP , PACKAGE/ SYSTEM


FOR HRSG FOUNDATION RRVUNL , RAMGARH RAJASTHAN CIVIL

DESIGN OF COLUMN PEDESTALS (P1)

Grade of Concrete M 25
Characteristic Strength of Reinf. N/mm 2
415
Width of Column b mm 1500
Depth of Column D mm 900
Unsupported Length of Column lx m 3.8
Unsupported Length of Column ly m 3.8
Clear Cover to Reinf. mm 50
Diameter of Bar mm 25
Fy (REFER PAGE 5,L/C5 DL+LL+WL+FR) T 184.3
Moment Mxx Tm 0
Moment Myy Tm 113.6 Design factor
Factored Load Pu kN 2711.9745 1.5
Factored Moment Mux kN.m 0 1.5
Factored Moment Muy kN.m 1671.624 1.5
Effective Length of Column lex mm 4.56 1.2
ley mm 4.56 1.2
0 lex/D 5.0667 <12- Short Column
0 ley/b 3.0400 <12- Short Column
Additional Moment due to Slender Max kN.m 0
Additional Moment due to Slender May kN.m 0
Percentage of Reinf. p % 0.8
Gross Area of Cross Section Ag mm2 1350000.00
Refer clause 3.4( SP-16) Puz/Ag N/mm2 17.2
Ultimate Axial Load Puz kN 18428
d'/D (about x-x axis) 0.07
d'/D (about y-y axis) 0.041666667 0.219
Refer SP-16 ( Table 60 ) k1 0.207 0.207
k2 0.328 0.196
Pbx kN 7340 0.184
k1 0.219
k2 0.424
Pby kN 7849
kx 1.000
ky 1.000
Minimum Eccentricity ex mm 30.0076
ey mm 50.0076
Moments due to min. eccentricity Mex kN.m 81.37984601 >0
Moments due to min. eccentricity Mey kN.m 135.619336 < 1671.624
12
Total Moments for which the column is to be designed are

Mux kN.m 81.380


Muy kN.m 1671.624
The section is to be checked for biaxial bending
Pu/fckbD = 4850.064*10^3/(25X1500*1000) 0.080
p/fck 0.03
Referring to Chart 48 (d'/D is0.07) Mu/fckbD2 0.070 43
44 Mux1 kN.m 2126.25
Referring to Chart 47 (d'/D = 0.0416666 Mu/fckbD
2
0.070
43 Muy1 kN.m 3543.75
Mux/Mux1 0.038
Muy/Muy1 0.472
Pu/Puz 0.148 0
Mux/Mux1 + Muy/Muy1 0.510 < 1 OK

Area of Reinforcement As mm2 10800


Minimum no of to be provided 16
No of Bars to be required Nos. 23
Provide 26 Nos of bars of 25Diameter equally on all faces.

TRANSVERSE REINFORCEMENT

Use 8 mm dia lateral ties at a spacing of the least of the following:


1) Least lateral dimension of 900 mm
2) compression member
16 times dia of longitudnal reinf. 400 mm
3) 300 mm

Hence provide 8mm dia lateral ties at a spacing of 200mm c/c


13
RAJASTHAN RAJYA VIDYUT UTPADAN LIMITED

DESIGN CRITERIA PROJECT NAME: 1x160 MW CCPP , PACKAGE/ SYSTEM


FOR HRSG FOUNDATION RRVUNL , RAMGARH RAJASTHAN CIVIL

DESIGN OF COLUMN PEDESTALS (P2)

Grade of Concrete M 25
Characteristic Strength of Reinf. N/mm2 415
Width of Column b mm 850
Depth of Column D mm 850
Unsupported Length of Column lx m 3.8
Unsupported Length of Column ly m 3.8
Clear Cover to Reinf. mm 50
Diameter of Bar mm 20
Fy (REFER PAGE 11,L/C5 DL+LL+WL+FR) T 31.9
Moment Mxx Tm 34.41
Moment Myy Tm 0 Design factor
Factored Load Pu kN 469.4085 1.5
Factored Moment Mux kN.m 506.34315 1.5
Factored Moment Muy kN.m 0 1.5
Effective Length of Column lex mm 4.56 1.2
ley mm 4.56 1.2
0 lex/D 5.3647 <12- Short Column
0 ley/b 5.3647 <12- Short Column
Additional Moment due to Slender Max kN.m 0
Additional Moment due to Slender May kN.m 0
Percentage of Reinf. p % 0.8
Gross Area of Cross Section Ag mm2 722500.00
Refer clause 3.4( SP-16) Puz/Ag N/mm2 17.2
Ultimate Axial Load Puz kN 9862
d'/D (about x-x axis) 0.071
d'/D (about y-y axis) 0.070588235 0.219
Refer SP-16 ( Table 60 ) k1 0.207 0.207
k2 0.328 0.196
Pbx kN 3929 0.184
k1 0.207
k2 0.328
Pby kN 3929
kx 1.000
ky 1.000
Minimum Eccentricity ex mm 28.34093333
ey mm 28.34093333
Moments due to min. eccentricity Mex kN.m 13.303475 < 506.3432
Moments due to min. eccentricity Mey kN.m 13.303475 >0
14
Total Moments for which the column is to be designed are

Mux kN.m 506.343


Muy kN.m 13.303475
The section is to be checked for biaxial bending
Pu/fckbD 0.026
p/fck 0.03
Referring to Chart 48 (d'/D is0.071) Mu/fckbD 2
0.060 43
44 Mux1 kN.m 921.1875
Referring to Chart 48 (d'/D = 0.0705882 Mu/fckbD
2
0.060
44 Muy1 kN.m 921.1875
Mux/Mux1 0.550
Muy/Muy1 0.014
Pu/Puz 0.048 0a
Mux/Mux1 + Muy/Muy1 0.564 < 1 OK

Area of Reinforcement As mm2 5780


Minimum no of to be provided 12
No of Bars to be required Nos. 19
Provide 19 Nos of bars of 20Diameter equally on all faces.

TRANSVERSE REINFORCEMENT

Use 8 mm dia lateral ties at a spacing of the least of the following:


1) Least lateral dimension of 850 mm
2) compression member
16 times dia of longitudnal reinf. 320 mm
3) 300 mm

Hence provide 8mm dia lateral ties at a spacing of 200mm c/c


15
RAJASTHAN RAJYA VIDYUT UTPADAN LIMITED

DESIGN CRITERIA PROJECT NAME: 1x160 MW CCPP , PACKAGE/ SYSTEM


FOR HRSG FOUNDATION RRVUNL , RAMGARH RAJASTHAN CIVIL

DESIGN OF COLUMN PEDESTALS (P3)

Grade of Concrete M 25
Characteristic Strength of Reinf. N/mm2 415
Width of Column b mm 700
Depth of Column D mm 700
Unsupported Length of Column lx m 3.8
Unsupported Length of Column ly m 3.8
Clear Cover to Reinf. mm 50
Diameter of Bar mm 20
Fy (drawing no 1-00-281-53214-R1) T 25
Moment Mxx Tm 4.5
Moment Myy Tm 0 Design factor
Factored Load Pu kN 367.875 1.5
Factored Moment Mux kN.m 66.2175 1.5
Factored Moment Muy kN.m 0 1.5
Effective Length of Column lex mm 4.56 1.2
ley mm 4.56 1.2
0 lex/D 6.5143 <12- Short Column
0 ley/b 6.5143 <12- Short Column
Additional Moment due to Slender Max kN.m 0
Additional Moment due to Slender May kN.m 0
Percentage of Reinf. p % 0.8
Gross Area of Cross Section Ag mm2 490000.00
Refer clause 3.4( SP-16) Puz/Ag N/mm2 17.2
Ultimate Axial Load Puz kN 6689
d'/D (about x-x axis) 0.086
d'/D (about y-y axis) 0.085714286 0.219
Refer SP-16 ( Table 60 ) k1 0.207 0.207
k2 0.328 0.196
Pbx kN 2664 0.184
k1 0.207
k2 0.328
Pby kN 2664
kx 1.000
ky 1.000
Minimum Eccentricity ex mm 23.34093333
ey mm 23.34093333
Moments due to min. eccentricity Mex kN.m 8.58654585
Moments due to min. eccentricity Mey kN.m 8.58654585
Total Moments for which the column is to be designed are

Mux kN.m 8.587


Muy kN.m 8.58654585
The section is to be checked for biaxial bending
Pu/fckbD 0.030
p/fck 0.03
Referring to Chart 44 (d'/D is0.086) Mu/fckbD 2
0.050 43
44 Mux1 kN.m 428.75
Referring to Chart 44 (d'/D = 0.0857142 Mu/fckbD
2
0.050
44 Muy1 kN.m 428.75
Mux/Mux1 0.020
Muy/Muy1 0.020
Pu/Puz 0.056 0a
Mux/Mux1 + Muy/Muy1 0.040 < 1 OK

Area of Reinforcement As mm2 3920


Minimum no of to be provided 8
No of Bars to be required Nos. 12
Provide 12 Nos of bars of 20Diameter equally on all faces.

TRANSVERSE REINFORCEMENT

Use 8 mm dia lateral ties at a spacing of the least of the following:


1) Least lateral dimension of 700 mm
2) compression member
16 times dia of longitudnal reinf. 320 mm
3) 300 mm

Hence provide 8mm dia lateral ties at a spacing of 200mm c/c


17
HRSG FOUNDATION DESIGN

` FOR FOOTING MARK F1L AND F1R


FOUNDATION DESIGN

Y
Grade of Concrete M 25
Grade of Steel Fe 415
Net allowable bearing capacity T/m2 50.0 kN/m2 490.35
Gross bearing Capacity T/m2 57.20 kN/m2 560.9604 b
Net allowable bearing capacity with seismic/wind effect T/m2 62.50 kN/m2 612.9375
Gross allowable bearing capacity with seismic/Wind effect T/m2 69.70 kN/m2 683.5479 a
Length of Footing L x mm 3500 3500
Width of Footing B y mm 2500 1500
Depth of Footing Df mm 700 X X
Depth of Column D mm 1500
Width of Column W mm 900
Depth of Foundation below ground level. mm 4000 900
Weight of Footing & Soil kN 672.875
Load from Column (refer page 5 L/c 5DL+LL+WL+FR) P 185.000 T kN 1814.85
Moment Mx 113.000 T-M kNm 1108.53
Moment Mz 0.000 T-M kNm 0 2500
Eccentricity of loading e mm 445.600 e<L/6
Partial Safety Factor 1.2 Y
For " e " < L/6 1
Max. Base Pressure kN/m2 501.492816
Min. Base Pressure kN/m2 67.130 0.06713

For L/3 > " e " > L/6 0


Max. Base Pressure kN/m2 379.342 0 1
Max. Net Pressure from top 76.90 kN/m2 9.77 1

Max. Base Pressure kN/m2 501.493 OK....Safe against Gross Pressure


Min. Base Pressure kN/m2 0
Net Base Pressure (NBP) =501.493-3.3x18-0.7x25 = kN/m2 424.593 OK....Safe against Net Pressure
18
HRSG FOUNDATION DESIGN

` FOR FOOTING MARK F1L AND F1R


FOUNDATION DESIGN
Max. Moment along the face of column Mx = NBPXb^2/2 kNm/m 212.297
Moment along face of column (trans.) My = NBPXa^2/2 kNm/m 135.870
Diameter of Main Reinf. (bottom) mm 16
Diameter of Transverse Reinf. (bottom) mm 16
Diameter of Main Reinf. (top) mm 10
Thickness of Base Slab mm 700
Minimum Clear cover to Main Reinf. mm 50
Effective Depth for main reinf. bars d mm 642
Mux/bd2 N/mm2 0.650
Percentage of Steel pt % 0.18578592
Min. percentage of steel = % 0.12 0.18578592
Area of Steel Ast mm2/m 1163.01984
Reqd. 16 mm dia @ 170 c/c bottom
Provide 16 mm dia @ 150 c/c bottom
Provided percentage of steel = 0.214 %
Effective Depth for trans. reinf. bars d mm 626
Muy/bd2 N/mm2 0.396
Percentage of Steel pt % 0.12
Min. percentage of steel = % 0.12 0.12
Area of Steel Ast mm2/m 770.4
Reqd, 16 mm dia @ 260 c/c bottom
Provide 16 mm dia @ 200 c/c bottom
Provided percentage of steel = 0.157 %
Effective Depth for top main reinf. bars d mm 645
Max. Moment along the face of column Mx1 kNm/m 4.885
Mux1/bd2 N/mm2 0.014
Percentage of Steel pt % 0.0
Area of Steel Ast mm2/m 387
Provide bothways 10 mm dia @ 200 c/c top
Minimum Steel 0.06 % 420 mm2/m
Provide minimum steel bothways 10 mm dia @ 180 c/c top 19
HRSG FOUNDATION DESIGN

` FOR FOOTING MARK F1L AND F1R


FOUNDATION DESIGN

Check for OneWay Shear ::

Shear Force , S.F.= (a-effective depth)x1xNBP = 152 KN per m length


Factored shear force , Vu = 182.405 KN per m length
Calculated Shear Stress = S.F./(effective depthx1000) = 0.284 N/mm2
Min % Of Steel provide = 0.214 %
Shear strength of conc. = 0.34078 N/mm2

SAFE FOR ONE WAY SHEAR

Check for Two-Way Shear ::

Factored Max. load on column = 222 T


P = 2177.82 KN
Depth of column = 1500 mm
Width of column = 900 mm
Punching shear = 0.92 N/mm2

Permissible stress = ks.tc


ks = 0.5+Bc but not greater than 1
Bc = 0.6
ks = 1.10
.tc = 0.25 X fck N/mm2
Permissible stress = 1.25 N/mm2

OK FOR PUNCHING SHEAR


20
HRSG FOUNDATION DESIGN

` FOR FOOTING MARK F9L and F9R


FOUNDATION DESIGN

Y
Grade of Concrete M 25
Grade of Steel Fe 415
Net allowable bearing capacity T/m2 50.0 kN/m2 490.35
Gross bearing Capacity T/m2 54.86 kN/m2 538.01202 b
Net allowable bearing capacity with seismic/wind effect T/m2 62.50 kN/m2 612.9375
Gross allowable bearing capacity with seismic/Wind effect T/m2 67.36 kN/m2 660.59952 a
Length of Footing L x mm 3500 3500
Width of Footing B y mm 2500 1500
Depth of Footing Df mm 700 X X
Depth of Column D mm 1500
Width of Column W mm 900
Depth of Foundation below ground level. mm 2700 900
Weight of Footing & Soil kN 468.125
Load from Column (refer page 5 L/c 5DL+LL+WL+FR) P 185.000 T kN 1814.85
Moment Mx 83.340 T-M kNm 817.5654
Moment Mz 0.000 T-M kNm 0 2500
Eccentricity of loading e mm 358.114 e<L/6
Partial Safety Factor 1.2 Y
For " e " < L/6 1
Max. Base Pressure kN/m2 421.087507
Min. Base Pressure kN/m2 100.735 0.100735

For L/3 > " e " > L/6 0


Max. Base Pressure kN/m2 0 0 1
Max. Net Pressure from top 53.50 kN/m2 0.00 0

Max. Base Pressure kN/m2 421.088 OK....Safe against Gross Pressure


Min. Base Pressure kN/m2 0
Net Base Pressure (NBP) =421.088-2x18-0.7x25 = kN/m2 367.588 OK....Safe against Net Pressure
18
HRSG FOUNDATION DESIGN

` FOR FOOTING MARK F9L and F9R


FOUNDATION DESIGN
Max. Moment along the face of column Mx = NBPXb^2/2 kNm/m 183.794
Moment along face of column (trans.) My = NBPXa^2/2 kNm/m 117.628
Diameter of Main Reinf. (bottom) mm 16
Diameter of Transverse Reinf. (bottom) mm 16
Diameter of Main Reinf. (top) mm 10
Thickness of Base Slab mm 700
Minimum Clear cover to Main Reinf. mm 50
Effective Depth for main reinf. bars d mm 642
Mux/bd2 N/mm2 0.563
Percentage of Steel pt % 0.16013921
Min. percentage of steel = % 0.12 0.16013921
Area of Steel Ast mm2/m 1002.47146
Reqd. 16 mm dia @ 200 c/c bottom
Provide 16 mm dia @ 150 c/c bottom
Provided percentage of steel = 0.214 %
Effective Depth for trans. reinf. bars d mm 626
Muy/bd2 N/mm2 0.342
Percentage of Steel pt % 0.12
Min. percentage of steel = % 0.12 0.12
Area of Steel Ast mm2/m 770.4
Reqd, 16 mm dia @ 260 c/c bottom
Provide 16 mm dia @ 200 c/c bottom
Provided percentage of steel = 0.157 %
Effective Depth for top main reinf. bars d mm 645
Max. Moment along the face of column Mx1 kNm/m 0.000
Mux1/bd2 N/mm2 0.000
Percentage of Steel pt % 0.0
Area of Steel Ast mm2/m 387
Provide bothways 10 mm dia @ 200 c/c top
Minimum Steel 0.06 % 420 mm2/m
Provide minimum steel bothways 10 mm dia @ 180 c/c top 19
HRSG FOUNDATION DESIGN

` FOR FOOTING MARK F9L and F9R


FOUNDATION DESIGN

Check for OneWay Shear ::

Shear Force , S.F.= (a-effective depth)x1xNBP = 131.597 KN per m length


Factored shear force , Vu = 157.916 KN per m length
Calculated Shear Stress = S.F./(effective depthx1000) = 0.246 N/mm2
Min % Of Steel provide = 0.214 %
Shear strength of conc. = 0.34078 N/mm2

SAFE FOR ONE WAY SHEAR

Check for Two-Way Shear ::

Factored Max. load on column = 222 T


P = 2177.82 KN
Depth of column = 1500 mm
Width of column = 900 mm
Punching shear = 0.92 N/mm2

Permissible stress = ks.tc


ks = 0.5+Bc but not greater than 1
Bc = 0.6
ks = 1.10
.tc = 0.25 X fck N/mm2
Permissible stress = 1.25 N/mm2

OK FOR PUNCHING SHEAR


20
HRSG FOUNDATION DESIGN

` FOR FOOTING MARK F8L , F8R , F6L ,F6R , F4L And F4R
FOUNDATION DESIGN

Y
Grade of Concrete M 25
Grade of Steel Fe 415
Net allowable bearing capacity T/m2 50.0 kN/m2 490.35
Gross bearing Capacity T/m2 57.20 kN/m2 560.9604 b
Net allowable bearing capacity with seismic/wind effect T/m2 62.50 kN/m2 612.9375
Gross allowable bearing capacity with seismic/Wind effect T/m2 69.70 kN/m2 683.5479 a
Length of Footing L x mm 4200 4200
Width of Footing B y mm 2800 1500
Depth of Footing Df mm 800 X X
Depth of Column D mm 1500
Width of Column W mm 900
Depth of Foundation below ground level. mm 4000 900
Weight of Footing & Soil kN 912.576
Load from Column (refer page 8 L/c 5DL+LL+WL+FR) P 228.100 T kN 2237.661
Moment Mx 126.400 T-M kNm 1239.984
Moment Mz 0.000 T-M kNm 0 2800
Eccentricity of loading e mm 393.616 e<L/6
Partial Safety Factor 1.2 Y
For " e " < L/6 1
Max. Base Pressure kN/m2 418.507034
Min. Base Pressure kN/m2 117.248 0.117248

For L/3 > " e " > L/6 0


Max. Base Pressure kN/m2 0 0 1
Max. Net Pressure from top 77.60 kN/m2 0.00 0

Max. Base Pressure kN/m2 418.507 OK....Safe against Gross Pressure


Min. Base Pressure kN/m2 0
Net Base Pressure (NBP) =418.507-3.2x18-0.8x25 = kN/m2 340.907 OK....Safe against Net Pressure
21
HRSG FOUNDATION DESIGN

` FOR FOOTING MARK F8L , F8R , F6L ,F6R , F4L And F4R
FOUNDATION DESIGN
Max. Moment along the face of column Mx = NBPXb^2/2 kNm/m 310.652
Moment along face of column (trans.) My = NBPXa^2/2 kNm/m 153.834
Diameter of Main Reinf. (bottom) mm 16
Diameter of Transverse Reinf. (bottom) mm 16
Diameter of Main Reinf. (top) mm 10
Thickness of Base Slab mm 800
Minimum Clear cover to Main Reinf. mm 50
Effective Depth for main reinf. bars d mm 742
Mux/bd2 N/mm2 0.677
Percentage of Steel pt % 0.19376633
Min. percentage of steel = % 0.12 0.19376633
Area of Steel Ast mm2/m 1437.74618
Reqd. 16 mm dia @ 130 c/c bottom
Provide 16 mm dia @ 110 c/c bottom
Provided percentage of steel = 0.246 %
Effective Depth for trans. reinf. bars d mm 726
Muy/bd2 N/mm2 0.350
Percentage of Steel pt % 0.12
Min. percentage of steel = % 0.12 0.12
Area of Steel Ast mm2/m 871.2
Reqd, 16 mm dia @ 230 c/c bottom
Provide 16 mm dia @ 200 c/c bottom
Provided percentage of steel = 0.138 %
Effective Depth for top main reinf. bars d mm 745
Max. Moment along the face of column Mx1 kNm/m 0.000
Mux1/bd2 N/mm2 0.000
Percentage of Steel pt % 0.0
Area of Steel Ast mm2/m 447
Provide bothways 10 mm dia @ 170 c/c top
Minimum Steel 0.06 % 480 mm2/m
Provide minimum steel bothways 10 mm dia @ 160 c/c top 22
HRSG FOUNDATION DESIGN

` FOR FOOTING MARK F8L , F8R , F6L ,F6R , F4L And F4R
FOUNDATION DESIGN

Check for OneWay Shear ::

Shear Force , S.F.= (a-effective depth)x1xNBP = 212.726 KN per m length


Factored shear force , Vu = 255.271 KN per m length
Calculated Shear Stress = S.F./(effective depthx1000) = 0.352 N/mm2
Min % Of Steel provide = 0.246 %
Shear strength of conc. = 0.36234 N/mm2

SAFE FOR ONE WAY SHEAR

Check for Two-Way Shear ::

Factored Max. load on column = 273.72 T


= 2685.1932 KN
Depth of column = 1500 mm
Width of column = 900 mm
Punching shear = 0.96 N/mm2

Permissible stress = ks.tc


ks = 0.5+Bc but not greater than 1
Bc = 0.6
ks = 1.10
.tc = 0.25 X fck N/mm2
Permissible stress = 1.25 N/mm2

OK FOR PUNCHING SHEAR


23
HRSG FOUNDATION DESIGN

` FOR FOOTING MARK F7L , F7R , F5L AND F5R


FOUNDATION DESIGN

Y
Grade of Concrete M 25
Grade of Steel Fe 415
Net allowable bearing capacity T/m2 50.0 kN/m2 490.35
Gross bearing Capacity T/m2 57.20 kN/m2 560.9604 b
Net allowable bearing capacity with seismic/wind effect T/m2 62.50 kN/m2 612.9375
Gross allowable bearing capacity with seismic/Wind effect T/m2 69.70 kN/m2 683.5479 a
Length of Footing L x mm 4700 4700
Width of Footing B y mm 2800 1500
Depth of Footing Df mm 1000 X X
Depth of Column D mm 1500
Width of Column W mm 900
Depth of Foundation below ground level. mm 4000 900
Weight of Footing & Soil kN 1039.64
Load from Column (refer page 9 L/c 5DL+LL+WL+FR) P 262.000 T kN 2570.22
Moment Mx 242.400 T-M kNm 2377.944
Moment Mz 0.000 T-M kNm 0 2800
Eccentricity of loading e mm 658.736 e<L/6
Partial Safety Factor 1.2 Y
For " e " < L/6 1
Max. Base Pressure kN/m2 504.979726
Min. Base Pressure kN/m2 43.631 0.043631

For L/3 > " e " > L/6 0


Max. Base Pressure kN/m2 365.927 0 1
Max. Net Pressure from top 79.00 kN/m2 35.37 1

Max. Base Pressure kN/m2 504.98 OK....Safe against Gross Pressure


Min. Base Pressure kN/m2 0
Net Base Pressure (NBP) =504.98-3x18-1x25 = kN/m2 425.98 OK....Safe against Net Pressure
24
HRSG FOUNDATION DESIGN

` FOR FOOTING MARK F7L , F7R , F5L AND F5R


FOUNDATION DESIGN
Max. Moment along the face of column Mx = NBPXb^2/2 kNm/m 545.254
Moment along face of column (trans.) My = NBPXa^2/2 kNm/m 192.223
Diameter of Main Reinf. (bottom) mm 20
Diameter of Transverse Reinf. (bottom) mm 16
Diameter of Main Reinf. (top) mm 10
Thickness of Base Slab mm 1000
Minimum Clear cover to Main Reinf. mm 50
Effective Depth for main reinf. bars d mm 940
Mux/bd2 N/mm2 0.740
Percentage of Steel pt % 0.21259901
Min. percentage of steel = % 0.12 0.21259901
Area of Steel Ast mm2/m 1998.43068
Reqd. 20 mm dia @ 150 c/c bottom
Provide 20 mm dia @ 120 c/c bottom
Provided percentage of steel = 0.278 %
Effective Depth for trans. reinf. bars d mm 922
Muy/bd2 N/mm2 0.271
Percentage of Steel pt % 0.12
Min. percentage of steel = % 0.12 0.12
Area of Steel Ast mm2/m 1106.4
Reqd, 16 mm dia @ 180 c/c bottom
Provide 16 mm dia @ 175 c/c bottom
Provided percentage of steel = 0.125 %
Effective Depth for top main reinf. bars d mm 945
Max. Moment along the face of column Mx1 kNm/m 45.272
Mux1/bd2 N/mm2 0.061
Percentage of Steel pt % 0.0
Area of Steel Ast mm2/m 567
Provide bothways 10 mm dia @ 130 c/c top
Minimum Steel 0.06 % 600 mm2/m
Provide minimum steel bothways 10 mm dia @ 130 c/c top 25
HRSG FOUNDATION DESIGN

` FOR FOOTING MARK F7L , F7R , F5L AND F5R


FOUNDATION DESIGN

Check for OneWay Shear ::

Shear Force , S.F.= (a-effective depth)x1xNBP = 288.814 KN per m length


Factored shear force , Vu = 346.577 KN per m length
Calculated Shear Stress = S.F./(effective depthx1000) = 0.376 N/mm2
Min % Of Steel provide = 0.278 %
Shear strength of conc. = 0.38214 N/mm2

SAFE FOR ONE WAY SHEAR

Check for Two-Way Shear ::

Factored Max. load on column = 314.4 T


= 3084.264 KN
Depth of column = 1500 mm
Width of column = 900 mm
Punching shear = 0.79 N/mm2

Permissible stress = ks.tc


ks = 0.5+Bc but not greater than 1
Bc = 0.6
ks = 1.10
.tc = 0.25 X fck N/mm2
Permissible stress = 1.25 N/mm2

OK FOR PUNCHING SHEAR


26
HRSG FOUNDATION DESIGN

` FOR FOOTING MARK F2L and F2R


FOUNDATION DESIGN

Y
Grade of Concrete M 25
Grade of Steel Fe 415
Net allowable bearing capacity T/m2 50.0 kN/m2 490.35
Gross bearing Capacity T/m2 57.20 kN/m2 560.9604 b
Net allowable bearing capacity with seismic/wind effect T/m2 62.50 kN/m2 612.9375
Gross allowable bearing capacity with seismic/Wind effect T/m2 69.70 kN/m2 683.5479 a
Length of Footing L x mm 6000 6000
Width of Footing B y mm 2800 1500
Depth of Footing Df mm 1200 X X
Depth of Column D mm 1500
Width of Column W mm 900
Depth of Foundation below ground level. mm 4000 900
Weight of Footing & Soil kN 1350.72
Load from Column (refer page 6 L/c 5DL+LL+WL+FR) P 325.000 T kN 3188.25
Moment Mx 315.540 T-M kNm 3095.4474
Moment Mz 0.000 T-M kNm 0 2800
Eccentricity of loading e mm 681.971 e<L/6
Partial Safety Factor 1.2 Y
For " e " < L/6 1
Max. Base Pressure kN/m2 454.429607
Min. Base Pressure kN/m2 85.924 0.085924

For L/3 > " e " > L/6 0


Max. Base Pressure kN/m2 0 0 1
Max. Net Pressure from top 80.40 kN/m2 0.00 0

Max. Base Pressure kN/m2 454.43 OK....Safe against Gross Pressure


Min. Base Pressure kN/m2 0
Net Base Pressure (NBP) =454.43-2.8x18-1.2x25 = kN/m2 374.03 OK....Safe against Net Pressure
27
HRSG FOUNDATION DESIGN

` FOR FOOTING MARK F2L and F2R


FOUNDATION DESIGN
Max. Moment along the face of column Mx = NBPXb^2/2 kNm/m 946.763
Moment along face of column (trans.) My = NBPXa^2/2 kNm/m 168.781
Diameter of Main Reinf. (bottom) mm 25
Diameter of Transverse Reinf. (bottom) mm 20
Diameter of Main Reinf. (top) mm 10
Thickness of Base Slab mm 1200
Minimum Clear cover to Main Reinf. mm 50
Effective Depth for main reinf. bars d mm 1137.5
Mux/bd2 N/mm2 0.878
Percentage of Steel pt % 0.25389461
Min. percentage of steel = % 0.12 0.25389461
Area of Steel Ast mm2/m 2888.05115
Reqd. 25 mm dia @ 160 c/c bottom
Provide 25 mm dia @ 150 c/c bottom
Provided percentage of steel = 0.288 %
Effective Depth for trans. reinf. bars d mm 1115
Muy/bd2 N/mm2 0.163
Percentage of Steel pt % 0.12
Min. percentage of steel = % 0.12 0.12
Area of Steel Ast mm2/m 1338
Reqd, 20 mm dia @ 230 c/c bottom
Provide 20 mm dia @ 200 c/c bottom
Provided percentage of steel = 0.141 %
Effective Depth for top main reinf. bars d mm 1145
Max. Moment along the face of column Mx1 kNm/m 0.000
Mux1/bd2 N/mm2 0.000
Percentage of Steel pt % 0.0
Area of Steel Ast mm2/m 687
Provide bothways 10 mm dia @ 110 c/c top
Minimum Steel 0.06 % 720 mm2/m
Provide minimum steel bothways 10 mm dia @ 100 c/c top 28
HRSG FOUNDATION DESIGN

` FOR FOOTING MARK F2L and F2R


FOUNDATION DESIGN

Check for OneWay Shear ::

Shear Force , S.F.= (a-effective depth)x1xNBP = 424.524 KN per m length


Factored shear force , Vu = 509.429 KN per m length
Calculated Shear Stress = S.F./(effective depthx1000) = 0.380 N/mm2
Min % Of Steel provide = 0.288 %
Shear strength of conc. = 0.39 N/mm2

SAFE FOR ONE WAY SHEAR

Check for Two-Way Shear ::

Factored Max. load on column = 390 T


= 3825.9 KN
Depth of column = 1500 mm
Width of column = 900 mm
Punching shear = 0.74 N/mm2

Permissible stress = ks.tc


ks = 0.5+Bc but not greater than 1
Bc = 0.6
ks = 1.10
.tc = 0.25 X fck N/mm2
Permissible stress = 1.25 N/mm2

OK FOR PUNCHING SHEAR


29
HRSG FOUNDATION DESIGN

` FOR FOOTING MARK F3L and F3R


FOUNDATION DESIGN

Y
Grade of Concrete M 25
Grade of Steel Fe 415
Net allowable bearing capacity T/m2 50.0 kN/m2 490.35
Gross bearing Capacity T/m2 57.20 kN/m2 560.9604 b
Net allowable bearing capacity with seismic/wind effect T/m2 62.50 kN/m2 612.9375
Gross allowable bearing capacity with seismic/Wind effect T/m2 69.70 kN/m2 683.5479 a
Length of Footing L x mm 5000 5000
Width of Footing B y mm 2800 1500
Depth of Footing Df mm 1100 X X
Depth of Column D mm 1500
Width of Column W mm 900
Depth of Foundation below ground level. mm 4000 900
Weight of Footing & Soil kN 1115.8
Load from Column (refer page 7 L/c 5DL+LL+WL+FR) P 280.600 T kN 2752.686
Moment Mx 258.600 T-M kNm 2536.866
Moment Mz 0.000 T-M kNm 0 2800
Eccentricity of loading e mm 655.777 e<L/6
Partial Safety Factor 1.2 Y
For " e " < L/6 1
Max. Base Pressure kN/m2 493.766086
Min. Base Pressure kN/m2 58.875 0.058875

For L/3 > " e " > L/6 0


Max. Base Pressure kN/m2 368.604 0 1
Max. Net Pressure from top 79.70 kN/m2 20.83 1

Max. Base Pressure kN/m2 493.766 OK....Safe against Gross Pressure


Min. Base Pressure kN/m2 0
Net Base Pressure (NBP) =493.766-2.9x18-1.1x25 = kN/m2 414.066 OK....Safe against Net Pressure
30
HRSG FOUNDATION DESIGN

` FOR FOOTING MARK F3L and F3R


FOUNDATION DESIGN
Max. Moment along the face of column Mx = NBPXb^2/2 kNm/m 634.039
Moment along face of column (trans.) My = NBPXa^2/2 kNm/m 186.847
Diameter of Main Reinf. (bottom) mm 25
Diameter of Transverse Reinf. (bottom) mm 20
Diameter of Main Reinf. (top) mm 10
Thickness of Base Slab mm 1100
Minimum Clear cover to Main Reinf. mm 50
Effective Depth for main reinf. bars d mm 1037.5
Mux/bd2 N/mm2 0.707
Percentage of Steel pt % 0.20258608
Min. percentage of steel = % 0.12 0.20258608
Area of Steel Ast mm2/m 2101.83057
Reqd. 25 mm dia @ 230 c/c bottom
Provide 25 mm dia @ 175 c/c bottom
Provided percentage of steel = 0.270 %
Effective Depth for trans. reinf. bars d mm 1015
Muy/bd2 N/mm2 0.218
Percentage of Steel pt % 0.12
Min. percentage of steel = % 0.12 0.12
Area of Steel Ast mm2/m 1218
Reqd, 20 mm dia @ 250 c/c bottom
Provide 20 mm dia @ 200 c/c bottom
Provided percentage of steel = 0.155 %
Effective Depth for top main reinf. bars d mm 1045
Max. Moment along the face of column Mx1 kNm/m 31.889
Mux1/bd2 N/mm2 0.035
Percentage of Steel pt % 0.0
Area of Steel Ast mm2/m 627
Provide bothways 10 mm dia @ 120 c/c top
Minimum Steel 0.06 % 660 mm2/m
Provide minimum steel bothways 10 mm dia @ 110 c/c top 31
HRSG FOUNDATION DESIGN

` FOR FOOTING MARK F3L and F3R


FOUNDATION DESIGN

Check for OneWay Shear ::

Shear Force , S.F.= (a-effective depth)x1xNBP = 304.339 KN per m length


Factored shear force , Vu = 365.206 KN per m length
Calculated Shear Stress = S.F./(effective depthx1000) = 0.352 N/mm2
Min % Of Steel provide = 0.270 %
Shear strength of conc. = 0.37727 N/mm2

SAFE FOR ONE WAY SHEAR

Check for Two-Way Shear ::

Factored Max. load on column = 336.72 T


= 3303.2232 KN
Depth of column = 1500 mm
Width of column = 900 mm
Punching shear = 0.73 N/mm2

Permissible stress = ks.tc


ks = 0.5+Bc but not greater than 1
Bc = 0.6
ks = 1.10
.tc = 0.25 X fck N/mm2
Permissible stress = 1.25 N/mm2

OK FOR PUNCHING SHEAR


32
HRSG FOUNDATION DESIGN

` FOR FOOTING MARK F'1L , F'1R , F'2L , F'2R , F'3L AND F'3R
FOUNDATION DESIGN

Y
Grade of Concrete M 25
Grade of Steel Fe 415
Net allowable bearing capacity T/m2 50.0 kN/m2 490.35
Gross bearing Capacity T/m2 57.20 kN/m2 560.9604 b
Net allowable bearing capacity with seismic/wind effect T/m2 62.50 kN/m2 612.9375
Gross allowable bearing capacity with seismic/Wind effect T/m2 69.70 kN/m2 683.5479 a
Length of Footing L x mm 2000 2000
Width of Footing B y mm 2000 850
Depth of Footing Df mm 500 X X
Depth of Column D mm 850
Width of Column W mm 850
Depth of Foundation below ground level. mm 4000 850
Weight of Footing & Soil kN 302
Load from Column (refer page 11 L/c 5DL+LL+WL+FR) P 31.900 T kN 312.939
Moment Mx 34.100 T-M kNm 334.521
Moment Mz 0.000 T-M kNm 0 2000
Eccentricity of loading e mm 543.991 L/3>e>L/6
Partial Safety Factor 1.2 Y
For " e " < L/6 0
Max. Base Pressure kN/m2 0
Min. Base Pressure kN/m2 0.000 -0.097156

For L/3 > " e " > L/6 1


Max. Base Pressure kN/m2 205.226 449.50749 1
Max. Net Pressure from top 75.50 kN/m2 75.50 1

Max. Base Pressure kN/m2 449.507 OK....Safe against Gross Pressure


Min. Base Pressure kN/m2 0
Net Base Pressure (NBP) =449.507-3.5x18-0.5x25 = kN/m2 374.007 OK....Safe against Net Pressure
33
HRSG FOUNDATION DESIGN

` FOR FOOTING MARK F'1L , F'1R , F'2L , F'2R , F'3L AND F'3R
FOUNDATION DESIGN
Max. Moment along the face of column Mx = NBPXb^2/2 kNm/m 61.828
Moment along face of column (trans.) My = NBPXa^2/2 kNm/m 61.828
Diameter of Main Reinf. (bottom) mm 12
Diameter of Transverse Reinf. (bottom) mm 12
Diameter of Main Reinf. (top) mm 10
Thickness of Base Slab mm 500
Minimum Clear cover to Main Reinf. mm 50
Effective Depth for main reinf. bars d mm 444
Mux/bd2 N/mm2 0.376
Percentage of Steel pt % 0.10610876
Min. percentage of steel = % 0.12 0.12
Area of Steel Ast mm2/m 532.8
Reqd. 12 mm dia @ 210 c/c bottom
Provide 12 mm dia @ 200 c/c bottom
Provided percentage of steel = 0.127 %
Effective Depth for trans. reinf. bars d mm 432
Muy/bd2 N/mm2 0.398
Percentage of Steel pt % 0.12
Min. percentage of steel = % 0.12 0.12
Area of Steel Ast mm2/m 518.4
Reqd, 12 mm dia @ 210 c/c bottom
Provide 12 mm dia @ 200 c/c bottom
Provided percentage of steel = 0.131 %
Effective Depth for top main reinf. bars d mm 445
Max. Moment along the face of column Mx1 kNm/m 12.481
Mux1/bd2 N/mm2 0.076
Percentage of Steel pt % 0.0
Area of Steel Ast mm2/m 267
Provide bothways 10 mm dia @ 200 c/c top
Minimum Steel 0.06 % 300 mm2/m
Provide minimum steel bothways 10 mm dia @ 200 c/c top 34
HRSG FOUNDATION DESIGN

` FOR FOOTING MARK F'1L , F'1R , F'2L , F'2R , F'3L AND F'3R
FOUNDATION DESIGN

Check for OneWay Shear ::

Shear Force , S.F.= (a-effective depth)x1xNBP = 53.483 KN per m length


Factored shear force , Vu = 64.1796 KN per m length
Calculated Shear Stress = S.F./(effective depthx1000) = 0.149 N/mm2
Min % Of Steel provide = 0.131 %
Shear strength of conc. = 0.27356 N/mm2

SAFE FOR ONE WAY SHEAR

Check for Two-Way Shear ::

Factored Max. load on column = 38.28 T


= 375.5268 KN
Depth of column = 850 mm
Width of column = 850 mm
Punching shear = 0.34 N/mm2

Permissible stress = ks.tc


ks = 0.5+Bc but not greater than 1
Bc = 1
ks = 1.50
.tc = 0.25 X fck N/mm2
Permissible stress = 1.25 N/mm2

OK FOR PUNCHING SHEAR


35
HRSG FOUNDATION DESIGN

` FOR FOOTING MARK F'4L AND F'4R


FOUNDATION DESIGN

Y
Grade of Concrete M 25
Grade of Steel Fe 415
Net allowable bearing capacity T/m2 50.0 kN/m2 490.35
Gross bearing Capacity T/m2 57.20 kN/m2 560.9604 b
Net allowable bearing capacity with seismic/wind effect T/m2 62.50 kN/m2 612.9375
Gross allowable bearing capacity with seismic/Wind effect T/m2 69.70 kN/m2 683.5479 a
Length of Footing L x mm 3000 3000
Width of Footing B y mm 2500 1500
Depth of Footing Df mm 600 X X
Depth of Column D mm 1500
Width of Column W mm 900
Depth of Foundation below ground level. mm 4000 900
Weight of Footing & Soil kN 571.5
Load from Column (refer page 10 L/c 5DL+LL+WL+FR) P 50.300 T kN 493.443
Moment Mx 52.180 T-M kNm 511.8858
Moment Mz 0.000 T-M kNm 0 2500
Eccentricity of loading e mm 480.670 e<L/6
Partial Safety Factor 1.2 Y
For " e " < L/6 1
Max. Base Pressure kN/m2 278.49528
Min. Base Pressure kN/m2 5.490 0.00549

For L/3 > " e " > L/6 0


Max. Base Pressure kN/m2 189.475 0 1
Max. Net Pressure from top 76.20 kN/m2 70.71 1

Max. Base Pressure kN/m2 278.495 OK....Safe against Gross Pressure


Min. Base Pressure kN/m2 0
Net Base Pressure (NBP) =278.495-3.4x18-0.6x25 = kN/m2 202.295 OK....Safe against Net Pressure
36
HRSG FOUNDATION DESIGN

` FOR FOOTING MARK F'4L AND F'4R


FOUNDATION DESIGN
Max. Moment along the face of column Mx = NBPXb^2/2 kNm/m 56.895
Moment along face of column (trans.) My = NBPXa^2/2 kNm/m 64.734
Diameter of Main Reinf. (bottom) mm 12
Diameter of Transverse Reinf. (bottom) mm 12
Diameter of Main Reinf. (top) mm 10
Thickness of Base Slab mm 600
Minimum Clear cover to Main Reinf. mm 50
Effective Depth for main reinf. bars d mm 544
Mux/bd2 N/mm2 0.231
Percentage of Steel pt % 0.06459152
Min. percentage of steel = % 0.12 0.12
Area of Steel Ast mm2/m 652.8
Reqd. 12 mm dia @ 170 c/c bottom
Provide 12 mm dia @ 150 c/c bottom
Provided percentage of steel = 0.139 %
Effective Depth for trans. reinf. bars d mm 532
Muy/bd2 N/mm2 0.274
Percentage of Steel pt % 0.12
Min. percentage of steel = % 0.12 0.12
Area of Steel Ast mm2/m 638.4
Reqd, 12 mm dia @ 170 c/c bottom
Provide 12 mm dia @ 150 c/c bottom
Provided percentage of steel = 0.142 %
Effective Depth for top main reinf. bars d mm 545
Max. Moment along the face of column Mx1 kNm/m 19.887
Mux1/bd2 N/mm2 0.080
Percentage of Steel pt % 0.0
Area of Steel Ast mm2/m 327
Provide bothways 10 mm dia @ 200 c/c top
Minimum Steel 0.06 % 360 mm2/m
Provide minimum steel bothways 10 mm dia @ 200 c/c top 37
HRSG FOUNDATION DESIGN

` FOR FOOTING MARK F'4L AND F'4R


FOUNDATION DESIGN

Check for OneWay Shear ::

Shear Force , S.F.= (a-effective depth)x1xNBP = 44.1003 KN per m length


Factored shear force , Vu = 52.9204 KN per m length
Calculated Shear Stress = S.F./(effective depthx1000) = 0.099 N/mm2
Min % Of Steel provide = 0.142 %
Shear strength of conc. = 0.28356 N/mm2

SAFE FOR ONE WAY SHEAR

Check for Two-Way Shear ::

Factored Max. load on column = 60.36 T


= 592.1316 KN
Depth of column = 1500 mm
Width of column = 900 mm
Punching shear = 0.32 N/mm2

Permissible stress = ks.tc


ks = 0.5+Bc but not greater than 1
Bc = 0.6
ks = 1.10
.tc = 0.25 X fck N/mm2
Permissible stress = 1.25 N/mm2

OK FOR PUNCHING SHEAR


38
HRSG FOUNDATION DESIGN

` FOR FOOTING MARK F1


FOUNDATION DESIGN

Y
Grade of Concrete M 25
Grade of Steel Fe 415
Net allowable bearing capacity T/m2 50.0 kN/m2 490.35
Gross bearing Capacity T/m2 57.20 kN/m2 560.9604 b
Net allowable bearing capacity with seismic/wind effect T/m2 62.50 kN/m2 612.9375
Gross allowable bearing capacity with seismic/Wind effect T/m2 69.70 kN/m2 683.5479 a
Length of Footing L x mm 1500 1500
Width of Footing B y mm 1500 700
Depth of Footing Df mm 400 X X
Depth of Column D mm 700
Width of Column W mm 700
Depth of Foundation below ground level. mm 4000 700
Weight of Footing & Soil kN 168.3
Load from Column(Refer dwg ": 1-00-281-53214-R1) P 25.000 T kN 245.25
Moment Mx 4.500 T-M kNm 44.145
Moment Mz 0.000 T-M kNm 0 1500
Eccentricity of loading e mm 106.746 e<L/6
Partial Safety Factor 1.2 Y
For " e " < L/6 1
Max. Base Pressure kN/m2 262.28
Min. Base Pressure kN/m2 105.320 0.10532

For L/3 > " e " > L/6 0


Max. Base Pressure kN/m2 0 0 1
Max. Net Pressure from top 74.80 kN/m2 0.00 0

Max. Base Pressure kN/m2 262.28 OK....Safe against Gross Pressure


Min. Base Pressure kN/m2 0
Net Base Pressure (NBP) =262.28-3.6x18-0.4x25 = kN/m2 187.48 OK....Safe against Net Pressure
39
HRSG FOUNDATION DESIGN

` FOR FOOTING MARK F1


FOUNDATION DESIGN
Max. Moment along the face of column Mx = NBPXb^2/2 kNm/m 14.998
Moment along face of column (trans.) My = NBPXa^2/2 kNm/m 14.998
Diameter of Main Reinf. (bottom) mm 12
Diameter of Transverse Reinf. (bottom) mm 12
Diameter of Main Reinf. (top) mm 10
Thickness of Base Slab mm 400
Minimum Clear cover to Main Reinf. mm 50
Effective Depth for main reinf. bars d mm 344
Mux/bd2 N/mm2 0.152
Percentage of Steel pt % 0.04242396
Min. percentage of steel = % 0.12 0.12
Area of Steel Ast mm2/m 412.8
Reqd. 12 mm dia @ 270 c/c bottom
Provide 12 mm dia @ 250 c/c bottom
Provided percentage of steel = 0.131 %
Effective Depth for trans. reinf. bars d mm 332
Muy/bd2 N/mm2 0.163
Percentage of Steel pt % 0.12
Min. percentage of steel = % 0.12 0.12
Area of Steel Ast mm2/m 398.4
Reqd, 12 mm dia @ 280 c/c bottom
Provide 12 mm dia @ 250 c/c bottom
Provided percentage of steel = 0.136 %
Effective Depth for top main reinf. bars d mm 345
Max. Moment along the face of column Mx1 kNm/m 0.000
Mux1/bd2 N/mm2 0.000
Percentage of Steel pt % 0.0
Area of Steel Ast mm2/m 207
Provide bothways 10 mm dia @ 250 c/c top
Minimum Steel 0.06 % 240 mm2/m
Provide minimum steel bothways 10 mm dia @ 250 c/c top 40
HRSG FOUNDATION DESIGN

` FOR FOOTING MARK F1


FOUNDATION DESIGN

Check for OneWay Shear ::

Shear Force , S.F.= (a-effective depth)x1xNBP = 12.7486 KN per m length


Factored shear force , Vu = 15.2984 KN per m length
Calculated Shear Stress = S.F./(effective depthx1000) = 0.046 N/mm2
Min % Of Steel provide = 0.136 %
Shear strength of conc. = 0.27857 N/mm2

SAFE FOR ONE WAY SHEAR

Check for Two-Way Shear ::

Factored Max. load on column = 30 T


= 294.3 KN
Depth of column = 700 mm
Width of column = 700 mm
Punching shear = 0.43 N/mm2

Permissible stress = ks.tc


ks = 0.5+Bc but not greater than 1
Bc = 1
ks = 1.50
.tc = 0.25 X fck N/mm2
Permissible stress = 1.25 N/mm2

OK FOR PUNCHING SHEAR