Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
On
HIGH VOLTAGE DIRECT CURRENT TRANSMISSION
(HVDC)
Submitted by
RAHUL RANJAN
903123
Dean
Name: Prof. A. Dasgupta
School of Electrical Engineering
KIIT University, Bhubaneswar-24
ABSTRACT
INTRODUCTION.2
WHY WE USE DC TRANSMISSION.3
HVDC CONVERTER ARRANGEMENT...4
TYPES OF HVDC LINK .6
APPLICATION OF HVDC CONVERTER..7
ENVIORNMENTEL CONSIDERATIONS..8
HVDC CONTROL AND OPERATION...9
COMPARISON OF AC AND DC TRANSMISSION..11
INHERENT PROBLEMS ASSOCIATED WITH HVDC13
CONCLUSION..15
REFERENCE ....16
Introduction :
1. MONOPOLAR CONFIGURATION
In case of mono polar arrangement one pole is used at a d.c. voltage level and
ground is the permanent return path. Mono polar arrangement is used for long
submarine/underground cables.
2.BIPOLAR CONFIGURATION
The bi polar arrangement uses two poles, one positive pole and other negative
earthed, the current carried by the ground, is However less if one of the poles is
2. The steady and direct magnetic field of DC transmission line near at the
edge of transmission right-of-way will be about the same value in
magnitude as the earths naturally occurring magnetic field. For this
reason alone, it seems unlikely that this small contribution by HVDC
transmission lines to the background geometric field would be the basis
of concern.
3. The static and steady electric field from DC transmission at the levels
experienced beneath lines or edges of the right-of way have no known
adverse biological effects. There is no theory or mechanism to explain
how a static electric field at the levels produced by DC transmission
lines could effect human health.
Electric fields from ac transmission lines have been under more intense
scrutiny than fields generated from dc transmission lines.
4. The ion and corona effects of dc transmission line lead to a small
contribution of ozone production to higher naturally occurring
background concentrations. Exacting long term measurements are
required to detect such concentrations.
5. If ground return is used with mono polar operation, the resulting dc
magnetic field can cause error in magnetic compass readings taken in the
vicinity of the DC line or cable. This impact is minimized by providing a
conductor or cable return path in close proximity to the main conductor
or cable for magnetic cancellation. Another concern with continuous
ground current is that some of return current may flow in metallic
structures and intensify corrosion if cathodic protection is not provided.
For conventional HVDC transmission one line sets while the other terminal
regulates the DC current by controlling its output voltage relative to that
maintained by the voltage setting terminal. Since the DC line resistance is low
large changes in current and hence power can be made with relatively small
changes in firing angle a. two independent method exist for controlling the
converter dc output voltage.
These are
1) By changing the ratio between direct voltage and AC voltage by varying
delay angle .
2) By changing the converter AC voltage via load tap changers (LTC) on the
converter transformer.
Whereas the former method is rapid the later method is slow due to the limited
speed of response of the LTC.
Use of high delay angles to achieve the larger dynamic range, however
increases the converter reactive power consumption. To minimize the reactive
power demand while still providing adequate dynamic control range and
commutation margin, the LTC is used at the rectifier terminal to give the delay
angle within its desired steady state range .Example: 13-18 degrees and at the
inverter to keep the extinction angle within its desired range, E.g.: 17-20
degrees if the angle is used for DC voltage control or to maintain rated DC
voltage if operating in minimum commutation margin control mode.
VSC-Based HVDC
Advantages of DC:
1. More power can be transmitted per conductor per circuit: The
capabilities of power transmission of an AC link and DC link are
different. For the same insulation, the direct voltage is equal to the
peak value of the alternating voltage. For the same conductor size, the
current can transmitted with both AC and DC, if skin effect is not
considered. In practice, AC transmission is carried out using either
single circuit or double circuit 3 phase transmission using 3 or 6
conductors. For DC only one-half the amount of copper is required for
the same power transmission.
2. Smaller Tower Size: The DC insulation level for the same power
transmission is likely to be lower than the corresponding AC level.
Also the DC line will only need two conductors whereas three
Thus both electrical and mechanical considerations dictate a smaller
tower.
3. HVDC With Voltage Source Converter And Extruded Cables For Up to +/-
300kv and 1000MW- B.Jacobson, V. Jiang-Hafner, Rey, G. Asplund