1s IEEE International Conference on Power Electronics. Intelligent Control and Energy Systems (ICPEICES-2016)
Abstract-Power quality shows the fitness of electrical II. TOPOLOGY TO GET MUL TIPULSES
power system. In recent years, efforts are made to upgrade
power quality. Multi pulse converters are used to achieve To get phase displacement,
good quality of electrical power. Phase shift transformer is Phase shifting angle=360/no of pulses
used to obtain 12 and 24 pulses as outputs. The quality of The 12 pulse rectifier acquires the two 3-phase system
power mainly depends on some parameters like, variation in with a characterized phase shift between them using the
voltage magnitude, transients in voltage/current, harmonic interconnection of three single-phase transformers.
content in waveforms etc. So in this paper, improvement in So to get 12 pulses, 30 degree phase shift is needed
power quality is shown by comparing the THD (total
and it is obtained by combination of star-star and star-delta
harmonic distortion) of 6, 12 & 24 pulses. In this paper, the
with common primary.
results of MATLAB are verified with the hardware results.
The Fig. 1 shows vector diagram for star-star and star
Keywords-Power Quality; Harmonic Reduction; Phase
Shift Transformer; MATLAB Simulation; Hardware delta connection. So, here the phase displacement between
line voltage of primary and secondary is 30 degree. [1]
I. INTRODUCTION Similarly, The 24 pulse rectifier requires the four 3-
phase transformer-rectifier unit with a characterized phase
In power system, the equipment's require pure ac
shift between them using the interconnection of three
current. But now a days, due to the use of power
phase transformers. To get 24 pulses, 15 degree phase
electronics converter, distortion in input side also
displacement is required. Zig zag connection provides the
increases. Here, the main converter used is AC to DC
phase displacement between 0-30 degrees.[I]
converter. To get multi pulse,phase shifting transformer is
used. In this paper, it is presented that as the number of
pulses increases the distortion in input current decreases.
The multi-pulse rectifier provides more than six pulse
of de output voltage per cycle. Harmonic current can
cause many problems in electrical installations including
the heating of instruments, power loss and reduced
efficiency. It causes the core losses due to increase in iron
losses such as eddy current loss and hysteresis loss.
Hysteresis loss is directly proportional to the frequency
whereas eddy current loss is proportional to the square of Fig. I: Vector Diagram for Star-star and Star-delta
the frequency. Hence, harmonic content increases the
frequency which leads to the increase in the iron losses.
In this paper, it is represented that, Lower order
harmonics has more effect on the load as the higher order
harmonics can be easily removed. In case of 6 pulse
rectifier, the dominant harmonics will be of 5th and 7th
order, which are eradicated using the 12 pulse rectifier,
where the most dominant hannonics will be of 11 th and
13th order which reduces the THD. In case of 24 pulse
rectifiers, the most dominant harmonics are of the order of
d
23r and 25th, which will further reduce the THD as even
11 and 13th order harmonics are also eliminated from the
th
!:
zig zag connection. Here a +15 phase shift is obtained 1.
........... ..... \..... . .. : ............ ..... ..... . : j ...... ........... : ........... .... +.... ..........
. . . . ,
00 ........ .......... ............ .
!tS?11
, . . . , , ,
Time
Here, o/p voltage for 6 pulses is kept constant which
is 75V. So it will be 150 V approx for 12 pulses and Fig. 5: olp Voltage and ilp Current for 6 Pulses
approx 300V for 24 pulses. And load current is also kept
For 12 pulses
constant for all configurations.
Input voltage =415V
For 6 pulses
Output Voltage = 147.5 V DC
Input voltage =415V
Output current =4.1 A
Output Voltage = 73 V DC
Output current =4.1 A Load = 3611
Actualload = 18.811
20
8
Ql
"E E
6
15
"
c:
::l
l.L
l.L '0 4
10
'0
'"
5
10 15 20
2 4 6 10
Harmonic order
Harmonic order
[2]
t
1s IEEE International Conference on Power Electronics. Intelligent Control and Energy Systems (ICPEICES-2016)
Fig. 12
V. HARDWARE RESULTS
Fig. 9: 24 Pulse Circuit Diagram
FFT an alysis
2. 5
'"
2
LL
1.5
'0
'"
i 0_5
------- -------
:./ " ./ '"'l
, "'-
'-------'
./ . " '-------' ./
I. , .. .., ... ,.
Time
,., ,. .." ,.
Fig. II: olp Voltage and ilp Current for 24 Pulses Fig. 14: Actual ilp Current for 12 Pulses
[3]
t
1s IEEE International Conference on Power Electronics. Intelligent Control and Energy Systems (ICPEICES-2016)
No of Pulses 6 I2 24
THD ("/0) Hardware 25.68 12.1 4.79
Simulated 25.50 10.64 3.46
olp voltage(v) Hardware 68 133 262
Simulated 73 148 294
olp current (A) Hardware 3.20 4.6 4.7
Fig. IS: Actual THD for 6 Pulses
Simulated 3.20 4.6 4.7
Load(O) Hardware 18.8 18.8 36
Simulated 23 32 62
VII. CONCLUSION