Sei sulla pagina 1di 20

30XA080-500

Air-Cooled Liquid Chillers


with COMFORTLINK Controls
60 Hz

Wiring Diagrams
INDEX
POWER SCHEMATICS
30XA Unit Size Voltage Figure Number Label Diagram
080-120 All 1 00PSN500128400A
380, 460, 575 1 00PSN500128400A
140-200
200, 230 2 00PSN500140900A
200, 230 2 00PSN500140900A
220, 240
380, 460, 575 3 00PSN500128500A
260 All 3 00PSN500128500A
280 All 4 00PSN500128600A
300 All 3 00PSN500128500A
325, 350 All 4 00PSN500128600A
All 1 00PSN500128400A
400
All (Circuit C) 5 00PSN500128800A
All 3 00PSN500128500A
450, 500
All (Circuit C) 5 00PSN500128800A

BOARD CONTROL SCHEMATICS


30XA Unit Size Voltage Figure Number Label Diagram
080 All 6 00PSN500128200A
090-350 All 7 00PSN500128300A
400-500 All 8 00PSN500140800A

UNIT CONTROL SCHEMATICS


30XA Unit Size Voltage Figure Number Label Diagram
080-350 All 9 00PSN500128100A
All 9 00PSN500128100A
400-500
All (Circuit C) 10 00PSN500128700A

COMPONENT ARRANGEMENTS
30XA Unit Size Voltage Control Box Type Figure Number Label Diagram
200, 230, Power Box 11 TH703002
080-120 380 Display Control Box 12 TH703007
460, 575 Combination Power Box/Display Control Box 13 TH703003
Breaker Box 14 TH703004
200, 230 Power Box 15 TH703006
140-200 Display Control Box 12 TH703007
380, 460, Power Box
575 Display Control Box
Breaker Box 14 TH703004
200, 230 Power Box 15 TH703006
220-240 Display Control Box 12 TH703007
380, 460, Power Box
575 Display Control Box
380, 460, Power Box 15 TH703006
260-350
575 Display Control Box 12 TH703007
A/B Power Box 15 TH703006
400-500 380, 460, Display Control Box 12 TH703007
575
Circuit C Power Box 16 TH703005

FIELD WIRING
30XA UNIT SIZE Voltage Figure Number Label Diagram
080-500 All 17 00DCN500002600A

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 533-00070 Printed in U.S.A. Form 30XA-1W Pg 1 310 2-07 Replaces: New
GENERAL SEQUENCE OF OPERATION
This publication contains Wiring Diagram information for NOTE: For operating sequence, refer to the Controls, Start-Up,
the 30XA080-500 air-cooled liquid chillers with electronic Operation, Service, and Troubleshooting literature.
controls. These chillers are equipped with ComfortLink con-
trols and electronic expansion valves.

LEGEND
A Alarm FIOP Factory-Installed Option
ALM R Alarm Relay FM Fan Motor
ALT R Alert Relay FN Fan
CA Contactor XL-A Circuit FU Fuse
CA-1M Contactor Main YD A Circuit GFI-CO Ground Fault Interrupter - Convenience Outlet
CA-2M Contactor Delta YD A Circuit GND Ground
CA-S Contactor Wye YD A Circuit HGBP Hot Gas Bypass
CB Contactor XL-B Circuit HTR Heater
CB-1M Contactor Main YD B Circuit ISO Isolation
CB-2M Contactor Delta YD B Circuit ISOL VLV Relay Isolation Valve
CB-S Contactor Wye YD B Circuit LEN Local Equipment Network
CB1 Base Board Mini Circuit Breaker LS Level Switch
CB2 Fan Board A Mini Circuit Breaker LWT Leaving Water Temperature
CB3 EXV Board Mini Circuit Breaker MBB Main Base Board
CB4 CPM Board A Mini Circuit Breaker MLV Minimum Load Valve
CB5 Fan Board B Mini Circuit Breaker MM Low Ambient Temperature Head Pressure Control
CB6 EXV Board B Mini Circuit Breaker NEC National Electrical Code (U.S.A.)
CB7 CPM Board B Mini Circuit Breaker OAT Outdoor Air Temperature
CB8 EMM Board Mini Circuit Breaker OPT Oil Pressure Transducer
CB12 Isolation Valve Relays Mini Circuit Breaker PL Plug
CB-13 115v Feed Circuit Breaker PMP Chilled Water Pump
CB14 HGBP/Pump Board Mini Circuit Breaker PMPI Chilled Water Pump Interlock
CB-A Circuit Breaker A Circuit RUN R Run Relay
CB-B Circuit Breaker B Circuit SGT Suction Gas Temperature
CB-FNA1 Fan Circuit Breaker A Circuit SHD R Shutdown Relay
CB-FNB1 Fan Circuit Breaker B Circuit SPT Suction Pressure Transducer
CC Contactor XL-C Circuit SW Switch
CCN Carrier Comfort Network T Thermistor
CC-1M Contactor Main YD C Circuit TB Terminal Block
CC-2M Contactor Delta YD C Circuit TEMP Temperature
CC-S Contacter Wye YD C Circuit TRAN Transformer
CH Channel XL Across-the-line
CLR HR Cooler Heater Relay Y-Delta Wye-Delta
CLR HTR Cooler/Heater Terminal Block Connection
COMM Communication
COMP Compressor Marked Terminal
CPM Compressor Protection Module
CT Current Transformer Unmarked Terminal
CWFS Chilled Water Flow Switch
CWP Chilled Water Pump Unmarked Splice
DGT Discharge Gas Thermistor
DPT Discharge Pressure Transducer Factory Wiring
ECEXV Economizer Electronic Expansion Valve Optional Wiring
ECT Economizer Temperature
EMM Energy Management Module Indicates common potential. Does not represent wiring.
EPT Economizer Pressure Transducer FIOP or Accessory
EQUIP Equipment
EXV Electronic Expansion Valve Wire Tag
FC Fan Contactor
NOTES
1. Factory wiring is in accordance with Underwriters Laboratories (UL) 1995 standards. Field modifications or additions must be in compliance
with all applicable codes.
2. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
Incoming wire size range for the terminal block is 4 AWG to 500 kcmil.
Incoming wire size range for non-fused disconnect with MCA up to 599.9 amps is 3/0 to 500 kcmil.
Incoming wire size range for non-fused disconnect with MCA from 600 to 799.9 amps is 1/0-500 kcmil.
Incoming wire size range for non-fused disconnect with MCA from 800 to 1199.9 amps is 250-500 kcmil.
3. Terminals 9 and 10 of TB5 are for field external connections for remote on-off. The contacts must be rated for dry circuit application capable of
handling a 24 vac load up to 50 mA.
4. Terminals 1 and 2 of TB5 are for external connections of chilled water pump interlock. The contacts must be rated for dry circuit application
capable of handling a 24 vac load up to 50 mA.
5. Terminals 11 and 13 of TB5 are for control of chilled water pump 1 (PMP1) starter. Terminals 13 and 15 of TB5 are for control of chilled water
pump 2 (PMP2) starter. The maximum load allowed for the chilled water pump relay is 5 va sealed, 10 va inrush at 24 v. Field power supply is
not required. External pump control accessory required.
6. For control of chilled water pumps, a set of normally open contacts rated for dry circuit application must be supplied from field-supplied pump
starter relay. Connect contacts to violet and pink wires in harness from main base board channel 18. Wires in harness are marked PMP1-13
and PMP1-14.
7. Terminals 12 and 13 of TB5 are for an alarm relay. The maximum load allowed for the alarm relay is 10 va sealed, 25 va inrush at 24 v. Field
power supply is not required.
8. Make appropriate connections to TB6 as shown for energy management board options. The contacts for occupancy override, demand limit
and ice done options must be rated for dry circuit application capable of handling a 24 vac load up to 50 mA.
9. Terminal blocks, TB5 and TB6 are located in the display panel box for all units. Refer to certified dimensional drawing for each unit to get the
exact locations.
10. Refer to certified dimensional drawings for exact locations of the main power and control power entrance locations.
11. Terminals J3-24 and 25 of the EMM board are for the run relay and shutdown relay. The maximum load allowed for the alarm relay is 10 va
sealed, 25 va inrush at 24 v. Field power supply is not required.

2
LOW AMBIENT TEMPERATURE
HEAD PRESSURE CONTROL OPERATION
FIOP/ACCESSORY

PUMP OPTION
a30-4543 FOR 090-160 ONLY, ALL VOLTAGES

Fig. 1 Power Schematic, 30XA080-120 and 400 (All Voltages); 30XA140-200 (380, 460, 575 v)

3
PUMP OPTION
FOR 090-160 ONLY, ALL VOLTAGES

LOW AMBIENT TEMPERATURE


HEAD PRESSURE CONTROL OPERATION
FIOP/ACCESSORY

a30-4544

Fig. 2 Power Schematic, 30XA140-240 (200, 230 v)

4
LOW AMBIENT TEMPERATURE
HEAD PRESSURE CONTROL OPERATION
FIOP/ACCESSORY

a30-4545

Fig. 3 Power Schematic, 30XA220, 240 (380, 460, 575 v); 30XA260, 300, 450, 500 (All Voltages)

5
LOW AMBIENT TEMPERATURE HEAD
PRESSURE CONTROL OPERATION
FIOP/ACCESSORY

a30-4546

Fig. 4 Power Schematic, 30XA280, 325, 350 (All Voltages)

6
LOW AMBIENT TEMPERATURE HEAD
PRESSURE CONTROL OPERATION
FIOP/ACCESSORY

a30-4547

Fig. 5 Power Schematic, 30XA400-500 (All Voltages Circuit C Only)

7
*

*Field-Supplied.
a30-4548

Fig. 6 Board Control Schematic, 30XA080 (All Voltages)

8
*

*Field-Supplied.
a30-4549

Fig. 7 Board Control Schematic, 30XA090-350 (All Voltages)

9
*

*Field-Supplied.

a30-4550

Fig. 8 Board Control Schematic, 30XA400-500 (All Voltages)

10
a30-4551

Fig. 9 Unit Control Schematic, 30XA080-500 (All Voltages)

11
a30-4552

Fig. 10 Unit Control Schematic, 30XA400-500 (All Voltages Circuit C Only)

12
A/B POWER BOX 30XA080-120 FOR 200, 230 V

a30-4553

13
*Fuse block replaces fan connector on units with low ambient temperature head pressure control option installed.
Fig. 11 Component Arrangement, 30XA080-120 (200, 230 v)
DISPLAY CONTROL BOX 30XA080-500 FOR ALL VOLTAGES

a30-4554

14
Fig. 12 Component Arrangement, 30XA080-500 (All Voltages)
A/B POWER BOX DISPLAY CONTROL BOX INCLUDED 30XA080-120 FOR 460 V

a30-4541

15
Fig. 13 Component Arrangement, 30XA080-120 (460 v)
A/B BREAKER BOX 30XA140-240 FOR ALL VOLTAGES

a30-4555

16
Fig. 14 Component Arrangement, 30XA140-240 (All Voltages)
A/B POWER BOX 30XA140-500 FOR ALL VOLTAGES

a30-4556

17
Fig. 15 Component Arrangement, 30XA140-500 (All Voltages)
CIRCUIT C POWER BOX 30XA400-500 FOR 460 V

a30-4557

18
Fig. 16 Component Arrangement, 30XA400-500 (460 v)
NOTES:

1. FACTORY WIRING IS IN ACCORDANCE WITH UL 1995 STANDARDS. FIELD MODIFICATIONS


OR ADDITIONS MUST BE IN COMPLIANCE WITH ALL APPLICABLE CODES.
2. WIRING FOR MAIN FIELD SUPPLY MUST BE RATED 75C MINIMUM. USE COPPER FOR ALL UNITS.
INCOMING WIRE SIZE RANGE FOR THE TERMINAL BLOCK IS #4 AWG TO 500 KCMIL.
INCOMING WIRE SIZE RANGE OF NON-FUSED DISCONNECT WITH MCA UP TO 599.9 AMPS IS 3/0 TO 500 KCMIL.
INCOMING WIRE SIZE RANGE OF NON-FUSED DISCONNECT WITH MCA FROM 600 TO 799.9 AMPS IS 1/0 TO 500 KCMIL.
INCOMING WIRE SIZE RANGE OF NON-FUSED DISCONNECT WITH MCA FROM 800 TO 1199.9 AMPS IS 250 KCMIL TO 500 KCMIL.
3. TERMINALS 9 AND 10 OF TB5 ARE FOR FIELD EXTERNAL CONNECTIONS FOR REMOTE ON-OFF.
THE CONTACTS MUST BE RATED FOR DRY CIRCUIT APPLICATION CAPABLE OF HANDLING A
TB1A OR TBIB
24VAC LOAD UP TO 50 MA.
4. TERMINALS 1 AND 2 OF TB5 ARE FOR EXTERNAL CONNECTIONS OF CHILLED WATER PUMP INTERLOCK.
THE CONTACTS MUST BE RATED FOR DRY CIRCUIT APPLICATION CAPABLE OF HANDLING A

a30-4542
24VAC LOAD UP TO 50 MA. 21 22 23
5. TERMINALS 11 AND 13 OF TB5 ARE FOR CONTROL OF CHILLED WATER PUMP 1 (PMP 1) STARTER. TERMINALS 13 AND 15
OF TB5 ARE FOR CONTROL OF CHILLED WATER PUMP 2 (PMP 2) STARTER. THE MAXIMUM LOAD ALLOWED FOR THE CHILLED

+
WATER PUMP RELAY IS 5 VA SEALED, 10 VA INRUSH AT 24 V. FIELD POWER SUPPLY IS NOT REQUIRED. EQUIP
11 12 13
6. FOR CONTROL OF CHILLED WATER PUMPS, A SET OF NORMALLY OPEN CONTACTS RATED FOR DRY CIRCUIT APPLICATION MUST GND
BE SUPPLIED FROM FIELD-SUPPLIED PUMP STARTER RELAY. CONNECT CONTACTS TO VIOLET AND PINK WIRES IN HARNESS
FROM MAIN BASE BOARD CHANNEL 18. WIRES IN HARNESS ARE MARKED PMP1-13 AND PMP1-14.

SHLD - COM
7. TERMINALS 12 AND 13 OF TB5 ARE FOR A ALARM RELAY. THE MAXIMUM LOAD ALLOWED FOR THE
ALARM RELAY IS 10 VA SEALED, 25 VA INRUSH AT 24V. FIELD POWER SUPPLY IS NOT REQUIRED.
8. MAKE APPROPRIATE CONNECTIONS TO TB6 AS SHOWN FOR ENERGY MANAGEMENT BOARD OPTIONS. THE
CONTACTS FOR OCCUPANCY OVERRIDE, DEMAND LIMIT AND ICE DONE OPTIONS MUST BE RATED FOR
DRY CIRCUIT APPLICATION CAPABLE OF HANDLING A 24VAC LOAD UP TO 50 MA.
9. TERMINAL BLOCKS, TB5 & TB6 ARE LOCATED IN THE DISPLAY PANEL BOX FOR ALL UNITS. REFER TO
CERTIFIED DIMENSIONAL DRAWING FOR EACH UNIT TO GET THE EXACT LOCATIONS. EMM BOARD
10.REFER TO CERTIFIED DIMENSIONAL DRAWINGS FOR EXACT LOCATIONS OF THE MAIN POWER AND
CONTROL POWER ENTRANCE LOCATIONS.

J6
J3

J4
J4
J4

J4
11.J3 - 24 AND 25 OF EMM BOARD ARE FOR RUN RELAY AND SHUTDOWN RELAY. THE MAXIMUM

J7B

J7A
LOAD ALLOWED FOR THE RUN AND SHUTDOWN RELAY IS 10 VA SEALED, 25 VA INRUSH AT 24V. CH CH CH CH CH CH CH CH CH FIELD POWER SUPPLY
FIELD POWER SUPPLY IS NOT REQUIRED. 5 6 10 2 11A 8 9 24 25
GROUND

R
+
+
+
+
+

S
R
R

S
LEGEND:

5V
5V
3
1
5
5
3
1

4
2
6
6
4
2

3
4
A - ALARM EMM DISCONNECT/BRANCH CIRCUIT
PMPI - CHILLED WATER PUMP INTERLOCK PROTECTION PER NEC
PMP - CHILLED WATER PUMP
FIOP/

VIO
(SEE NOTE #2)

GRN
BLK
GRN
BLK
VIO
VIO
ORN
GRA
GRA
BLU
RED
RED

BLU

ORN
EMM - ENERGY MANAGEMENT ACCESSORY

R
R

SHD
SHD
TB - TERMINAL BLOCK
MLV - MINIMUM LOAD VALVE
TERMINAL BLOCK
NEC - NATIONAL ELECTRIC CODE TB6
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
FIELD POWER WIRING

CB8
FIELD CONTROL WIRING
13

3.2 AMPS
CB-A OR CB-B
TB5

FACTORY INSTALLED WIRING


1 2 3

PUMP POWER BOX


90-160

19
1/2 WATT 250
1/2 WATT 250
+
-

+
-
8
ICE DONE

SIGNAL

SIGNAL
T8

4-20 MA

4-20 MA
GENERATOR

GENERATOR
REMOTE LOCKOUT SWITCH
DATA COM PORT
OCCUPANCY OVERRIDE
DEMAND LIMIT STEP 2

CONTROL POWER ENTRANCE


140-350

RESET
DISPLAY PANEL

LIMIT
140-500 ALL VOLTAGES

TEMP

SETPOINT
CAPACITY
SPACE
(10K)

CONTROL POWER ENTRANCE


080-120 DISPLAY PANEL
DISPLAY PANEL 080-120, 200V, 230V, 380V ONLY
21 22 23 EQUIP
080-120, 460V, 575V ONLY GND

11 12 13
TB5
DISPLAY PANEL
080-120 208/230V ONLY 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

PMPI PMP2
REMOTE A
MLV-A

ON/OFF
SEE
MLV-C
MLV-B

NOTE 3
PMP1
INCOMING POWER DUAL SETPOINT
140-350 ALL VOLTAGES
EXCEPT 200,230V ONLY
DEMAND LIMIT STEP 1

INCOMING POWER CIRCUIT 1


GROUND

400-500 DUAL POINT POWER FIELD POWER SUPPLY

INCOMING POWER CIRCUIT 2


400-500
INCOMING POWER 200,230V DISCONNECT/BRANCH CIRCUIT
220-240 MAIN POWER ENTRANCE PROTECTION PER NEC
CONTROL POWER ENTRANCE 080-120 ALL VOLTAGES
400-500 AND 140-200, 200V, 230V ONLY (SEE NOTE #2)
INCOMING POWER CIRCUIT 1
TYPICAL CONTROL BOX LOCATIONS
400-500 SINGLE POINT POWER OPTION AND MAIN POWER ENTRY
NON-FUSED DISCONNECT

Fig. 17 Field Wiring Schematic, 30XA080-500 (All Voltages)


VOLTAGE POWER AND CONTROL CONNECTIONS
30XA TYPE 3 PH COMBI* PEB1 PEB2
60 Hz Power Control Power Control Power Control
200 Circuit 1 Yes
230 Circuit 1 Yes
SINGLE
380 Circuit 1 Yes
POINT
080 460 Circuit 1 Yes
090 575 Circuit 1 Yes
100
110 200 Circuit 1 and 2 Yes
120 230 Circuit 1 and 2 Yes
DUAL
POINT 380 Circuit 1 and 2 Yes
460 Circuit 1 and 2 Yes
575 Circuit 1 and 2 Yes
200 Circuit 1 Yes
230 Circuit 1 Yes
SINGLE 380 Circuit 1 Yes
POINT
460 Circuit 1 Yes
140
160 575 Circuit 1 Yes
180 200 Circuit 1 and 2 Yes
200
230 Circuit 1 and 2 Yes
DUAL
380 Circuit 1 and 2 Yes
POINT
460 Circuit 1 and 2 Yes
575 Circuit 1 and 2 Yes
200 Yes Circuit 1
230 Yes Circuit 1
SINGLE
380 Circuit 1 Yes
POINT
460 Circuit 1 Yes
220 575 Circuit 1 Yes
240 200 Yes Circuit 1 and 2
230 Yes Circuit 1 and 2
DUAL
POINT 380 Circuit 1 and 2 Yes
460 Circuit 1 and 2 Yes
575 Circuit 1 and 2 Yes
200
230
SINGLE 380 Circuit 1 Yes
POINT
260 460 Circuit 1 Yes
280 575 Circuit 1 Yes
300
325 200
350 230
DUAL
380 Circuit 1 and 2 Yes
POINT
460 Circuit 1 and 2 Yes
575 Circuit 1 and 2 Yes
200
230
SINGLE
POINT 380 Circuit 1 Yes
460 Circuit 1 Yes
400 575 Circuit 1 Yes
450
500 200
230
DUAL 380 Circuit 1 Circuit 2 Yes
POINT
460 Circuit 1 Circuit 2 Yes
575 Circuit 1 Circuit 2 Yes
*COMBI box is located at the end of the unit.
PEB1 and PEB2 boxes are located on the side of the unit. If both boxes are used, the one on the left (viewing from the front of the boxes) is PEB1.

Shaded area means that box is not used on this model.

Fig. 17 Field Wiring Schematic, 30XA080-500 (All Voltages) (cont)

Copyright 2007 Carrier Corporation

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 533-00070 Printed in U.S.A. Form 30XA-1W Pg 20 310 2-07 Replaces: New

Potrebbero piacerti anche