Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
S12R-
Engine ref.
F1PTAW2
Alternator ref. KH04450T
Performance class G3
GENERAL CHARACTERISTICS
Frequency (Hz) 50 Hz
Voltage (V) 400/230
Standard Control Panel NA
Optional control panel M80
Optional Control Panel APM403
Optional control panel APM802
POWER
ESP PRP DCC (*)
Voltage kW kW kW Standby Amps
kVA kVA kVA
e e e
415/24
1320 1650 1200 1500 1200 1500 2296
0
400/23
1320 1650 1200 1500 1200 1500 2382
0
380/22
DESCRIPTIVE 1280 1600 1164 1455 1164 1455 2431
0
Electronic governor
Mechanically welded chassis with antivibration
suspension
DIMENSIONS COMPACT VERSION
Radiator for core temperature of 48/50C max with Length (mm) 5090
mechanical fan Width (mm) 2200
Protective grille for fan and rotating parts (CE option) Height (mm) 2510
Exhaust compensators with flanges
Dry weight (kg) 12043
24 V charge alternator and starter
Delivered with oil and coolant -30C
Tank capacity (L)
Manual for use and installation
DIMENSIONS SOUNDPROOFED VERSION
Type soundproofing ISO20 Si
Length (mm) 6058
Width (mm) 2438
Height (mm) 2896
Dry weight (kg) 17307
Tank capacity (L) 500
POWER DEFINITION
PRP : Prime Power is available for an unlimited number of annual Acoustic pressure level @1m in dB(A) 98
operating hours in variable load applications, in accordance with ISO
8528-1. ESP : The standby power rating is applicable for supplying
Sound power level guaranteed (Lwa) 119
emergency power in variable load applications in accordance with ISO Acoustic pressure level @7m in dB(A) 89
8528-1. Overload is not allowed.
*DCC : Data Center Continuous Power ratings apply to Data Center
installations where a reliable utility power is available and comply with
Uptime institute Tier III and IV requirements.
TERMS OF USE
According to the standard, the nominal power assigned by the genset is
given for 25C Air Intlet Temperature, of a barometric pressure of 100
kPA (100 m A.S.L), and 30 % relative humidity. For particular conditions
in your installation, refer to the derating table.
ASSOCIATED UNCERTAINTY
For the generating sets used indoor, where the acoustic pressure levels
depends on the installation conditions, it is not possible to specify the
ambient noise level in the exploitation and maintenance instructions .
You will also find in our exploitation and maintenance instructions a
warning concerning the air noise dangers and the need to implement
appropriated preventive measures.
24/06/2017
This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this document without notice, in a constant effort to
improve the quality of its products. *ISO 8528.
T1650C
ENGINE CHARACTERISTICS
EMISSIONS
Emission PM (mg/Nm3) 5% O2 50
Emission CO (mg/Nm3) 5% O2 650
Emission HC+NOx (g/kWh) 8,83
Emission HC (mg/Nm3) 5% O2 150
24/06/2017
This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this document without notice, in a constant effort to
improve the quality of its products. *ISO 8528.
T1650C
ALTERNATOR CHARACTERISTICS
DIMENSIONS
Contener dimensions ISO20 version Contener dimensions CPU40 soundproofed
Type soundproofing ISO20 Si version
Length (mm) 6058 Type soundproofing CPU40 Si
Width (mm) 2438 Length (mm) 12192
Height (mm) 2896 Width (mm) 2438
Dry weight (kg) 17307 Height (mm) 2896
Tank capacity (L) 500 Dry weight (kg) 22440
Acoustic pressure level @1m in dB(A) 98 Tank capacity (L) 500
Sound power level guaranteed (Lwa) 119 Acoustic pressure level @1m in dB(A) 86
Acoustic pressure level @7m in dB(A) 89 Sound power level guaranteed (Lwa) 109
Acoustic pressure level @7m in dB(A) 78
Contener dimensions CPU40 super
soundproofed version
Type soundproofing CPU40 SSi
Length (mm) 12192
Width (mm) 2438
Height (mm) 2896
Dry weight (kg) 23460
24/06/2017
This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this document without notice, in a constant effort to
improve the quality of its products. *ISO 8528.
Tank capacity (L) 500
Acoustic pressure level @1m in dB(A) 79
Sound power level guaranteed (Lwa) 102
Acoustic pressure level @7m in dB(A) 71
24/06/2017
This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this document without notice, in a constant effort to
improve the quality of its products. *ISO 8528.
T1650C
CONTROL PANEL
The control unit can be used as a basic terminal block for The M80 is a dual-function control unit. It can be used as a
connecting a control box. basic terminal block for connecting a control box and as an
instrument panel with a direct read facility, with displays
Offers the following functions: giving a global view of your generating set's basic
parameters.
emergency stop button, customer connection terminal
block, CE. Offers the following functions:
24/06/2017
This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this document without notice, in a constant effort to
improve the quality of its products. *ISO 8528.
APM403, basic generating set and power plant APM802 dedicated to power plant management
control
24/06/2017
This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this document without notice, in a constant effort to
improve the quality of its products. *ISO 8528.