Model 1151
Model 1151 Alphaline
Pressure Transmitters
.
PROVEN ROSEMOUNT
VALUE AND PERFORMANCE
Versatile application: Ranges from 00.5
inH 20 to 6,000 psig (1.24 kPa to 41370 kPa)
Easy maintainance and upgradeability with
solid-state, plug-in circuit boards; adjustable
damping; and local span and zero
adjustments
Compact, rugged, construction for easy
installation and long-lasting performance
Smart, analog, or low-power electronics to fit
almost every application
Over 30 years of proven Rosemount quality
and technology
Model 1151
Pressure-173
Model 1151 Alphaline Pressure Transmitters
APPLICATIONS
Lead Wires Model 1151 Pressure Transmitters are available in a
variety of configurations for differential, flow, gage,
Capacitor Plates absolute, vacuum, liquid level, and specific gravity
measurement applications. The transmitter model
number, determined from the ordering information
Sensing Diaphragm tables, specifies available features such as pressure
ranges, outputs, and materials of construction that
Rigid Insulation are basic to each transmitter. Additional options,
such as accessories, certifications, and special
Oil Fill manufacturing procedures are also available.
11510142A
Isolating
Welded Seals OPERATION
Diaphragm
During operation, the isolating diaphragms and fill
fluid on the high and low sides transmit the process
FIGURE 1. Cross Section of the Rosemount d-Cell Sensor. pressure to the oil fill fluid. The fluid in turn
transmits the process pressure to a sensing dia-
phragm in the center of the d-cell sensor. The
sensing diaphragm functions as a stretched spring
INTRODUCTION element that deflects in response to differential
This product data sheet highlights Rosemount pressure across it (in GP transmitters, atmospheric
Model 1151 differential, absolute, gage, and high-line pressure is transmitted in a like manner to the low
pressure transmitter features and options. For side of the sensing diaphragm). In AP transmitters,
information about the draft range, liquid level a reference pressure is maintained on the low side.
transmitters, transmitters with remote seals, and The displacement of the sensing diaphragm, a
additional information on smart transmitters, refer to maximum movement of 0.004 in. (0.10 mm), is
their respective data sheets referenced on the back proportional to the pressure. Capacitor plates on
page of this data sheet. both sides detect the position of the sensing
diaphragm. The differential capacitance between the
sensing diaphragm and the capacitor plates is
INDUSTRY-LEADING PERFORMANCE converted electronically to an appropriate current,
voltage, or digital HART (Highway Addressable
AND FEATURES Remote Transducer) output signal.
Model 1151
Pressure-174
Rosemount Inc.
PRODUCT OFFERING
MODELS 1151DP, GP, AND AP
DIFFERENTIAL, GAGE, AND ABSOLUTE
PRESSURE TRANSMITTERS
Superior performance: 0.1% accuracy,
15:1 rangeability
Differential pressures from
30 inH2O to 1,000 psi (7.5 to 6895 kPa)
Gage pressures from
30 inH2O to 6,000 psig (7.5 to 41369 kPa)
Absolute pressures from
150 inH2O to 1,000 psia (37.4 to 6895 kPa)
Smart, analog, or low-power electronics
1151-41A
Compact, rugged construction resistant to
vibration
Modular construction, adjustable damping, and
local span and zero adjustments
Model 1151
Modular construction, adjustable damping, and
local span and zero adjustments
1151-41B
MODEL 1151LT FLANGE-MOUNTED
LIQUID LEVEL TRANSMITTER
Liquid level measurement with 0.25% accuracy
Pressures from
025 to 02,770 inH2O (06.2 to 0690 kPa)
Flush, 2-, 4-, and 6-inch extended diaphragms
Many optional fill fluids to meet application
requirements
Up to 600% elevation or 500% suppression
1151-41C
Adjustable damping
Stainless steel, Hastelloy C-C276, and Tantalum
wetted materials
Pressure-175
Model 1151 Alphaline Pressure Transmitters
OPTIONS
The following sections describe a variety of available B3 Flat Bracket for 2-in. Pipe Mounting
options for the Model 1151 Transmitter.
Bracket for vertical mounting of transmitter on
These options permit greater application flexibility.
2-in. pipe.
Mounting Brackets Constructed of carbon steel with carbon
steel U-bolt.
B1 Bracket for 2-in. Pipe Mounting
Bracket for mounting transmitter on 2-in. pipe. Coated with polyurethane paint.
Constructed of carbon steel with carbon B6 Flat Bracket for 2-in. Pipe with 316 SST Bolts
steel U-bolt. Same bracket as Option Code B3 with 316 SST
bolts.
Coated with polyurethane paint.
B9 304 SST Flat Bracket and 316 SST Bolts
B4 Bracket for 2-in. Pipe with 316 SST Bolts
for 2-in. Pipe Mounting
Same bracket as Option Code B1 with 316 SST bolts.
Same bracket as Option Code B3 with all
B7 304 SST Bracket and 316 SST Bolts 316 SST materials.
for 2-in. Pipe Mounting
Same bracket as Option Code B1 with all Bolts and Nuts for Flanges and Adapters
SST materials. Options permit bolts and nuts for flanges and
B2 Bracket for Panel Mounting adapters in the specified material.
Bracket for mounting transmitter on panel or wall. L3 ANSI/ASTM A - 193-B7
Constructed of carbon steel with carbon steel bolts. L4 Austenitic 316 SST
Coated with polyurethane paint. L5 ANSI/ASTM A193-B7M
B5 Bracket for Panel with 316 SST Bolts
Same bracket as Option Code B2 with
316 SST bolts.
Model 1151
Drain/Vent
Plug
Flange
Bolts
Flange
Adapter
Bolts
1151-1151B04B
Process Flange
Flange Adapter
Pressure-176
Rosemount Inc.
1.65 3.87
3.75 (42)
(95) (98)
2.625 5.625
(67) (143)
1151-1151D, A06A
2.62
(67)
2.625
4.97 (67)
(127) 5.625
2.81
3051-3051B19A
(143)
(71)
NOTE
Dimensions are in inches (millimeters).
3.75 3.87
(95) (98)
1.65
(42)
1151-1151E06A
Mounting Holes
0.375 (10) Diameter
2.81 (71)
Typical
3051-3051A19A 1151-0244A
2.81 (71)
1.40 (46) Typical
2.81 (71)
Typical
2.625
Model 1151
4.5 1.40
(114) (36) (67)
NOTE
Dimensions are in inches (millimeters).
2.125
(54)
1.62
(41) 8.0
(203)
2.81
(71)
1151-1151F06B
3051-3051H19B
NOTE
Dimensions are in inches (millimeters).
FIGURE 5. Flat Mounting Bracket Option Codes B3, B6, and B9.
Pressure-177
Model 1151 Alphaline Pressure Transmitters
Meters LCD
Analog 4-digit display.
Meters have 2-in. (50.8 mm) scale. Indication accuracy 0.25% of calibrated span
Plug-in mounting configuration. 1 digit.
Indication accuracy 2%. Display resolution at 0.5% of calibrated span
1 digit.
Operating temperature limit: 40 to 150 F
(40 to 65 C). Operating temperature limit: 4 to 158 F
(20 to 70 C).
Meters are enclosed in a housing certified by
Factory Mutual as explosion proof for Class I, Plug-in mounting configuration.
Division 1, Groups B, C, and D; Class II, Division Meters are enclosed in a housing certified by
1, Groups E, F, and G and Class III, Division 1. Factory Mutual as explosion proof for Class I,
For optional CSA explosion-proof approval, see Division 1, Groups B, C, and D; Class II, Division
certification Option Code E6. 1, Groups E, F, and G and Class III, Division 1.
M1 Linear Analog Meter, 0100% Scale For Optional CSA explosion-proof approval, see
certification Option Code E6.
M2 Square Root Analog Meter,
0100% Flow Scale M4 Linear LCD Meter, 0 to 100%
M3 Special Scaling Analog Meter M7 Special Scale LCD Meter (Specify Range,
(Specify Range) Mode, and Engineering Units)
M6 Square Root Analog Meter, 010 Scale M8 Square Root LCD Meter, 0 to 100%
M9 Square Root LCD Meter, 010 Scale
NOTES
Meter Options are not available with Output Codes L or M,
or Option Codes V2 or V3.
Meter Options M2, M6, M8, and M9 are not available with
Output Code J.
Optional Meter
Cover Removal
(Typical)
OPTION CODE M1
LINEAR SCALE
9.0 Max.
(229)
OPTION CODE M4
LINEAR SCALE
NOTE
DImensions are in inches (millimeters).
Pressure-178
Rosemount Inc.
Process Connections K1 1
/418 NPT Kynar Process Flange Insert
1
D1 Side Drain/Vent-Top K2 /214 NPT Kynar Process Flange Insert
Drain/vent valve mounted in side of flange. Options provide Kynar plastic process flange
insert that prevents process from coming in
Top position used to vent gas buildup in liquid
contact with the metal of the flange. One
process applications with transmitter mounted
process insert for Models 1151AP, GP and LT;
vertically.
two inserts for Model 1151DP.
Plug of same material as requested flange
Process connections are from the side.
inserted in end of flange opposite adapter.
Available with carbon steel and stainless steel
D2 Side Drain/Vent-Bottom
process flanges only.
Drain/vent valve mounted in side of flange.
Pressure Maximum: 200 psi at 200 F with
Bottom position used to drain liquid buildup in Kynar impulse piping; 300 psi at 200 F with
gas process applications with transmitter metal impulse piping.
mounted vertically.
Plug of same material as requested flange
inserted in end of flange opposite adapter.
1
D3 /418 NPT Process Connection
Option provides 1/418 NPT process connection
on flanges rather than standard 1/214 NPT.
Flange adapters are deleted to provide desired
connection.
D6 316 SST Low Side Flange
(Models 1151GP and 1151AP Only)
1151-1151D17A
Standard Drain/Vent Kynar
Replaced with Plug Insert 18 or 14 NPT
Process Connection
Alternate Side
Drain/Vent Top Position
(Option Code D1)
FIGURE 8. Flange Insert.
Model 1151
Alternate Side Drain/Vent Bottom S1 Assembled with One Remote Diaphragm Seal
Position (Option Code D1)
14 NPT S2 Assembled with Two Remote Diaphragm
Connection
on Adapters
Seals
(18 NPT Options provide for the assembly of one or two
1151-1151B04A
Pressure-179
Model 1151 Alphaline Pressure Transmitters
1151-1151B17B
Static pressure maximum limit is 3,000 psig.
Wetted
Wetted materials are available that comply O-rings
with NACE MR 01-75(90).
Available only with Ranges 2, 3, 4, and 5.
FIGURE
FIGURE10.
1. Flange Exploded View.
For integral orifice selection,
see Product Data Sheet 00813-0100-4686. Standard: Viton (2)
W2 Buna N
W3 Ethylene-Propylene
W4 Aflas
W5 Copper O-ring for Vacuum Service
(Nonwetted - Model 1151LT only)
OPTIONAL W6 Spring-Loaded Teflon
3-VALVE MANIFOLD Contains a Hastelloy spring that is in contact
with the process fluid. Consult factory if
Hastelloy is unacceptable.
Procedures
Standard Configuration
Unless otherwise specified, transmitter will
Model 1151
be shipped as follows:
1151-1151A21A
Pressure-180
Rosemount Inc.
Model 1151
1151DR 1,500 psi
calibration range.
Calibration temperature will be printed on
P1 Hydrostatic Testing instrument tag specified by customer, or on a tag
Each transmitter is hydrostatic tested wired to the transmitter if no tag is specified.
according to Table 1. Rosemount Procedure 27823B outlines the
Test medium is water. calibration procedure.
This option provided for transmitters with
remote diaphragm seal on application only.
Rosemount Procedure 1746 outlines the
testing procedure.
Pressure-181
Model 1151 Alphaline Pressure Transmitters
Pressure-182
Rosemount Inc.
Model 1151
Output Code G 30 to 85 V dc with no load.
Output Code L 5 to 12 V dc.
Output Code M 8 to 14 V dc.
Where:
Rmax
RL
Operating
Region
Rmin
0 V min VS V max
TABLE 2. Rangeability.
Minimum Span
Output Code Maximum Span
(URL=Upper Range Limit)
S (DP and GP, SST, Range 38; HP SST, Range 47) URL/15 2 3 URL(1)
(1)
S (All Others) URL/6 2 3 URL
E, G, J URL/6 URL
L URL/1.1 URL
M URL/2 URL
(1) Transmitter is capable of measuring from URL to URL.
TABLE 3. Model 1151 Transmitter Range Availability by Model (URL = Upper Range Limit).
Range Code Model 1151 Ranges (URL) DP HP GP DP/GP/Seals AP LT
3 30 inH20 (7.46 kPa) NA NA NA NA
4 150 inH20 (31.08 kPa)
5 750 inH20 (186.4 kPa)
6 100 psi (689.5 kPa)
7 300 psi (2,068 kPa) NA
8 1,000 psi (6,895 kPa) NA NA NA
9 3,000 psi (20,684 kPa) NA NA NA NA NA
0 6,000 psi (41,369 kPa) NA NA NA NA NA
Pressure-184
Rosemount Inc.
Temperature Limits
Model 1151AP
Electronics Operating 0 psia to 2,000 psia (0 to 13.79 MPa) without
Code S 40 to 185 F (40 to 85 C). damage to transmitter. Operates within
Code E 40 to 200 F (40 to 93 C). specifications from 0 psia to the upper range limit
Code G, L, M 20 to 200 F (29 to 93 C). of the transmitter.
Code J 20 to 150 F (29 to 66 C). Model 1151GP
Sensing Element Operating 0 psia to 2,000 psig (0 to 13.79 MPa) for ranges to
1,000 psig (6.90 MPa), 4,500 psig (31.02 MPa) for
Silicone fill 40 to 220 F (40 to 104 C). the 3,000 psig (20.68 MPa) range, and 7,500 psig
Inert fill 0 to 160 F (18 to 71 C). (51.71 MPa) for the 6,000 psig (41.37 MPa) range,
Storage without damage to the transmitter. Operates
Code S 60 to 185 F (51 to 85 C). within specifications from 0.5 psia (3.45 kPa) to the
Codes E, G, L, M 60 to 250 F (51 to 121 C). upper range limit of the transmitter.
Code J 60 to 180 F (51 to 82 C). Model 1151LT
TABLE 7. Flange Pressure Rating.
TABLE 6. Fill Fluid Specifications.
Stainless
Coeff. of Standard Class/Rating Carbon Steel
Viscosity Steel
Temperature Specific Therm. Exp.
Fill Fluid at 25 C
Limits(1) Gravity cc/cc/F ANSI 150 285 psig(1) 275 psig(1)
centistokes
(cc/cc/C) (1)
ANSI 300 740 psig 720 psig(1)
D.C. 200 40 to 400 F 0.00060 ANSI 600 1,480 psig (1)
1,440 psig(1)
0.934 9.5
Silicone (40 to 205 C) (0.00108)
DIN PN 1040 40 bar(2) 40 bar(2)
D.C. 704 60 to 400 F 0.00053
1.07 44 DIN PN 10/16 16 bar (2)
16 bar(2)
Silicone (15 to 205 C) (0.00095)
(2)
50 to 350 F 0.0004 DIN PN 25/40 40 bar 40 bar(2)
Inert Fill 1.85 6.5
(45 to 177 C) (0.000864) (1) At 100 F (38 C); the rating decreases with increasing
temperature.
Syltherm 50 to 400 F 0.00052
0.934 9.5 (2) At 248 F (120 C); the rating decreases with increasing
800, Silicone (45 to 205 C) (0.000936)
temperature.
Syltherm 100 to 300 F 0.000666
XLT, Silicone (73 to 149 C)
0.85
(0.001199)
1.6 Burst Pressure All Models
Glycerin 0 to 200 F 0.00019
10,000 psig (68.95 MPa) proof pressure on
and (17 to 93 C) 1.13 (0.00034) 12.5 the flanges.
Water(2) Humidity Limits
Propylene 0 to 200 F 0.00019 0 to 100% relative humidity.
Glycol (17 to 93 C) (0.00034)
Model 1151
1.02 2.85
and Volumetric Displacement
Water(3) Less than 0.01 in3 (0.16 cm3).
Neobee 0 to 400 F 0.00056
M-20
(3)
(17 to 205 C)
0.900
(0.001008)
9.8 Failure Mode Alarm (Output Code S)
(1) Temperature limits are reduced in vacuum service. Contact your
If self-diagnosis detects a gross transmitter failure,
local Rosemount representative for assistance. the analog signal will be driven below 3.9 mA or
(2) Glycerin and Water and Propylene Glycol and Water are not above 21 mA to alert the user. High or low alarm
suitable for vacuum service. signal is user selectable.
(3) Not compatible with Buna-N or Ethylene-Propylene O-ring
material. 420 mA 420 mA
Level Saturation Alarm
Static Pressure and Overpressure Limits
Value Value
Model 1151DP
Low 3.9 mA 3.8 mA
0 psia to 2,000 psig (0 to 13.79 MPa) on either side
without damage to transmitter. Operates within High 20.8 mA 21.75 mA
specifications from static line pressures of 0.5 psia
Transmitter Security (Output Code S)
(3.45 kPa) to 2,000 psig (13.79 MPa).
Activating the transmitter security function
Model 1151HP prevents changes to the transmitter configuration,
0 psia to 4,500 psig (0 to 31.02 MPa) on either side including local zero and span adjustments. Security
without damage to transmitter. Operates within is activated by an internal switch.
specifications from 0.5 psia (3.45 kPa) to 4,500 psig
(31.02 MPa).
Pressure-185
Model 1151 Alphaline Pressure Transmitters
(Zero-based calibrated ranges, reference conditions, silicone oil fill, (56 C) for Range 3.
316 SST isolating diaphragms.)
Static Pressure Effect
Accuracy
DP Transmitters
Output Code S
Zero Error
Ranges 3 through 8, DP and GP transmitters; 0.25% of URL for 2,000 psi (13790 kPa)
Ranges 4 through 7, HP transmitters for Range 4 and 5 or 0.5% for other ranges,
0.1 of calibrated span for spans from 1:1 to correctable through rezeroing at line pressure.
10:1 of URL. Between 10:1 and 15:1 of URL. Span Error
Correctable to 0.25% of input reading per
accuracy = 0.02 -------------- 0.1 % of calibrated span
URL
span 1,000 psi (6895 kPa), or to 0.5% for Range 3.
For Output Code J, the span error is
All other ranges and transmitters correctable to 0.125% of output reading per
0.25% of calibrated span. 1,000 psi, or to 0.25% for Range 3.
Output Code S, square root mode HP Transmitters
Zero Error
2.0% of URL for 4,500 psi (31027 kPa),
0.2 + 0.05 ------------- % of calibrated flow span
URL
span correctable through rezeroing at line pressure.
Span Error
Output Codes E, G, L, and M
Correctable to 0.25% of input reading per
0.2% of calibrated span for Model 1151DP
1,000 psi (6895 kPa).
Ranges 3 through 5. All other ranges and
For Output Code J, the span error is
transmitters, 0.25% of calibrated span.
correctable to 0.125% of output reading per
1,000 psi.
Pressure-186
Rosemount Inc.
Model 1151
Ext. Ext. Ext.
Physical Specifications,
Standard Configuration 2-in., Class 150 18 (8.2) N/A N/A N/A
3-in., Class 150 23 (10.4) 25 (11.3) 26 (11.8) 27 (12.3)
Wetted Materials 4-in., Class 150 29 (13.2) 32 (14.5) 34 (15.4) 36 (16.3)
Isolating Diaphragms 2-in., Class 300 20 (9.1) N/A N/A N/A
3-in., Class 300 28 (12.7) 30 (13.6) 31 (14.1) 32 (14.5)
316L SST, Hastelloy C-276, Monel, gold-plated 4-in., Class 300 38 (17.2) 41 (18.6) 43 (19.5) 45 (20.4)
Monel, or Tantalum. See ordering table for 2-in., Class 600 22 (10.0) N/A N/A N/A
availability per model type. 3-in., Class 600 31 (14.1) 33 (15.0) 34 (15.4) 35 (15.9)
Pressure-187
Model 1151 Alphaline Pressure Transmitters
Default Explosion Proof: Class I, Division 1, Groups Special Conditions: The equipment must be
B, C, and D. Dust-Ignition Proof: Class II, connected to a supply voltage which does not
Division 1, Groups E, F, and G. Suitable for use exceed the rated voltage. The enclosure end
in: Class III, Division 1. Indoor and outdoor caps must be correctly fitted whilst the
use. NEMA 4X. Factory Sealed. equipment is energized.
I5 Intrinsic Safety and Non-incendive Approvals: CESI/CENELEC Flameproof Certification
FM certifications optional for specific Classes, E8 90.C.016: EEx d IIC T6 (without meter).
Divisions, and Groups when connected in 90.C.017: EEx d IIB + H 2 T6.
accordance with the FM entity approvals, CESI/CENELEC Intrinsic Safety Certification
see Table 9. Factory Sealed. I8 EEx ia IIC T6 (Tamb = 40 C); (Pmax = 0.75 W).
K5 Combination of Explosion Proof, Intrinsic EEx ia IIC T5 (Tamb = 55 C); (Pmax = 1.00 W).
Safety, and Non-incendive Approvals. EEx ia IIC T4 (Tamb = 80 C); (Pmax = 1.00 W).
Canadian Standards Association (CSA) Approvals Special Conditions: When transient
E6 Explosion proof for Class I, Division 1, Groups protection terminal options (R1 or R9) are
C and D; Class II, Division 1, Groups E, F, and installed, the transmitter must be supplied
G; Class III, Division 1 Hazardous Locations. from a galvanically isolated i.s. barrier.
Certified for Class I, Division 2, Groups A, B, C, BASEEFA/CENELEC Intrinsic Safety Certification
and D; CSA enclosure type 4X. Factory Sealed. I1 Smart
I6 Intrinsic Safety Approvals CSA certifications EEx ia IIC T5 (Tamb = 40 C).
optional for specific Classes, Divisions, and EEx ia IIC T4 (Tamb = 80 C).
Groups when connected in accordance with the Analog
CSA barrier selection table, Table 10. EEx ia IIC T5.
Temperature Code T2D. Special Conditions: When transient
C6 Combination of I6 and E6, CSA Explosion Proof protection terminal options (R1 or R9) are
and Intrinsic Safety Approval. Factory Sealed. installed, the transmitter must be supplied
K6 CSA/CENELEC Explosion-Proof and Intrinsic from a galvanically isolated i.s. barrier.
Safety Approval. BASEEFA Type N (Non-incendive) Certification
Standards Association of Australia (SAA) N1 Smart
Flameproof Certification Ex N II T5 (Tamb = -40 C to 50 C); Un = 45 V.
E7 Flameproof Ex N II T4 (Tamb = -40 C to 80 C); Un = 45 V.
Ex d IIB + H2 T6. Analog
Class I, Zone 1. Ex N II T5; Un = 45 V.
Dust-Ignition proof Special Conditions: The apparatus must be
Model 1151
Pressure-188
Rosemount Inc.
Model 1151
Retrofitting Procedure
Any Model 1151 Differential, Gage, Absolute, or
Level Transmitter, Ranges 30, can be retrofitted
with smart electronics. The retrofitting procedure
takes just a few minutes. The five simple steps for
converting a Model 1151 Analog Transmitter to
smart operation are as follows:
Step 1 Remove the screws and unplug the
analog electronics.
Step 2 Insert two spacers and reattach the
In keeping with the Rosemount Inc. design header board.
philosophy of upgrading products without sacrificing Step 3 Plug in the smart electronics and
parts compatibility, the Model 1151 Pressure secure with three screws.
Transmitter, can be converted to microprocessor-
based or smart operation. With its wide range of Step 4 Attach eyelets to the terminal block
product offerings and low cost of ownership, the to allow easy connection of the
Model 1151 is a perfect candidate for smart HART Communicator.
retrofitting, and the Model 1151 Smart Retrofit Kit Step 5 Characterize the transmitter.
makes this possible. For more information, see PDS 00813-0100-4594,
Smart electronics can be installed quickly by Model 1151 Pressure Transmitter Smart Retrofit
removing the analog electronics boards and plugging Kit, or consult your Rosemount Representative.
Pressure-189
Model 1151 Alphaline Pressure Transmitters
Terminal Eyelets
Smart
Electronics
d-Cell Sensing
Module
Blank Flange
for AP and GP
1151-1151A27A
Process
Flange
FIGURE 11. Typical Transmitter Exploded View, Shown with Smart Electronics.
0.75 (19)
7.5 (191) Max. Clearance for
14 NPT with Optional Meter Cover Removal
Conduit (Typical) 4.5 (114)
Connection 4.5 (114) Max. Permanent
(2 Places) Max. Tag (Optional)
Model 1151
Transmitter
Meter Circuitry
Housing this Side
9.0
(229)
Wired-on Tag Max.
(Standard)
Nameplate
1.625
Terminal Connections (41)
this Side Drain/Vent
18 NPT for
Side Drain/Vent Valve
18 NPT on (Optional Top
Flanges for Pressure or Bottom) 3.69
Connection without (94)
Flange Adapters
Blank Flange
14 NPT Used on
on Flange AP and GP
Adapters A Transmitters 3.375
(See Table) (86) Flanges Can
Be Rotated
Flange Distance A Center Flange
to Center Adapter 4.5
Range (114)
inches mm
1151-1151A, B05A
3, 4, 5 2.125 54
6, 7 2.188 56
NOTE
Dimensions are in 8 2.250 57
inches (millimeters). 9 2.281 58
0 2.328 59
11.38 (289) 1
Max. Serrated Face (25)
Gasket Surface
Drain/Vent Valve
Permanent Tag
(optional)
G F
4.5 (114)
D E
Max. E
Flushing
Wired-on Tag Connection
A
(standard)
4.45 (113) 2-, 4-, or 6-in. OPTIONAL FLUSHING
Flange Max. (51, 102, or 152) CONNECTION RING
Adapter Extension
(LOWER HOUSING)
Terminal Connections C
Meter This Side
Housing
3051-3051B27B
Nameplate (Remove for B
Span and Zero Adjust)
7.5
(190.5)
Max. with
Optional
1151-1151B30B 1151-51LTA05A
Meter
4.5 (114)
Max.
Transmitter
Circuitry
This Side
14 NPT for 14 NPT
Conduit Connection on Flange 18 NPT on Flanges
(2 places) Adapters for Pressure Connection
without the Use of Flange
DIAPHRAGM ASSEMBLY
1151-51LTB05A
0.75 (19) Clearance for Adapters
Cover Removal (typical) AND MOUNTING FLANGE
Model 1151
NOTE
Dimensions are in inches (millimeters).
Pressure-191
Model 1151 Alphaline Pressure Transmitters
ORDERING INFORMATION
TABLE 12. Model 1151 Differential, High Line, Gage and Absolute Pressure Transmitters. = Not Applicable = Applicable
Model Transmitter Type (select one) DP HP GP AP
1151DP Differential Pressure Transmitter
1151HP Differential Pressure Transmitter for High Line Pressures
1151GP Gage Pressure Transmitter
1151AP Absolute Pressure Transmitter
Code Pressure Ranges (URL) (select one)For Rangeability, see below DP HP GP AP
3 30 inH2O (7.46 kPa) Rangeability
4 150 inH2O (37.3 kPa)
Output Code Min.Span
5 750 inH2O (186.4 kPa)
S (DP and GP, SST, Range 38; URL/15
6 100 psi (689.5 kPa) HP, SST, Range 47)
7 300 psi (2068 kPa) S (all others) URL/6
8 1,000 psi (6895 kPa) E, G, J URL/6
L URL/1.1
9 3,000 psi (20684 kPa)
M URL/2
0 6,000 psi (41369 kPa)
Pressure-192
Rosemount Inc.
Model 1151
M4
(5)
LCD Meter, Linear Meter, 0100%, User Selectable
M6 Analog Scale, Square Root Meter, 110
M7(6) LCD Meter, Linear Meter, Special Configuration
M8(7)
(7)
LCD Meter Square Root Meter, 0100% Flow
M9 LCD Meter, Square Root Meter, 010
(1) Bolts and conduit plugs are plated carbon steel.
(2) On GP and AP transmitters, the low-side flange is plated carbon steel.
For a stainless-steel low-side flange, order process connections Option Code D6.
(3) These selections meet NACE material recommendations per MR 01-75.
(4) Not available with Output Codes L or M, or Option Codes Zx, V2, or V3.
(5) Not available with Output Codes J, L, M, or Option Codes Zx, V2, or V3.
(6) Not available with Output Codes G, L, M, or Option Codes Zx, V2, or V3.
(7) Not available with Output Codes G, J, L, M, or Option Codes Zx, V2, or V3.
Pressure-193
Model 1151 Alphaline Pressure Transmitters
Pressure-194
Rosemount Inc.
D4
Process Adapters Deleted
{ Hastelloy C
Monel
Conformance to DIN 19213 and DIN 50049 3.1B Ranges 3, 4, 5
(Available in Germany Only)
D5 Conformance to DIN 19213 and DIN 50049 3.1B Ranges 6, 7, 8, without
NPT Threads or Drain/Vent Valve Connections (Available in Germany Only)
D6 316 SST Low Side Blank Flange
{
Carbon Steel
316 SST
D9 JIS Process ConnectionRC Flange with RC Flange Adapter
Hastelloy C
Monel
G1 DIN Spacing (Single Entry Port, No Side V/D Hole Flange)
G2 DIN Spacing (Single Entry Port, Two Side V/D Hole Flange)
G3 DIN Spacing (Dual Entry Port, No Side V/D Hole Flange)
G4 DIN Spacing (Dual Entry Port, One Top Side V/D Hole Flange)
G5 DIN Spacing (Dual Entry Port, One Bottom Side V/D Hole Flange)
G6 DIN Spacing (Dual Entry Port, Two Side V/D Hole Flange)
K1(2) Kynar insert, 18 NPT
K2
(2)
Kynar insert, 14 NPT
S1(3) Attachment of One Remote Seal - See PDS 00813-0100-4016
S2
(3)
Attachment of Two Remote Seals - See PDS 00813-0100-4016
S4(4) Attachment of Integral Orifice Assembly - See PDS 00813-0100-4686
(1) Allowable combinations are: D1, D3, D6; D2, D3, D6; and D6, S1.
(2) The maximum working pressure on this option is 300 psig. Available only with materials of construction Option Codes 1x or 2x.
(3) This option may only be used on Ranges 48.
(4) This option has a maximum static pressure rating of 3,000 psi, and is available for factory
assembly only without associated piping and is available only for Ranges 2, 3, 4, and 5.
Model 1151
Pressure-195
Model 1151 Alphaline Pressure Transmitters
C9 (2)
Software Configuration
P1(3) Hydrostatic Testing, 150% Maximum Working Pressure
P2(4) Cleaning for Special Service
P3 Cleaning for <1 PPM Chlorine/Fluorine
P4 Calibrate at Line Pressure
P5 Calibrate at Specific Temperature
P7(5) Improved Temperature Coefficient
P8(6) Calibrate to 0.1% Accuracy
Code Outputs DP HP GP AP
V1 (7)
Reverse Output
V2(8) 420 mV Test Signal
V3
(8)
20100 mV Test Signal
Z1(9) 4-wire, 020 mA Output
Z2
(9)
4-wire, 016 mA Output
Z3
(9)
4-wire, 010 mA Output
Typical Model Number: 1151DP 4 S 52 B3 M1
(1) Contains a Hastelloy spring that is wetted by the process; consult factory for Teflon O-ring without a spring.
(2) Available with Output Code S only.
(3) Hydrostatic testing for Range 0, 125% maximum working pressure.
(4) Fluorolube grease on wetted O-rings.
(5) Not available on Range 10: limited to 1,500 psi on Range 9; not applicable with Output Code S.
(6) Available only with stainless steel isolators and for span of 10 inH2O and greater;
not applicable with Output Code S; available only with Output Codes E, G, L, or M;
not available on AP or DR transmitters.
(7) Reverse output option is not needed with smart electronics; configured via HART-based communicator.
(8) Not available with Output Codes L or M.
(9) Not available with Option Codes Mx, Vx, Ix, or Ex, or Output Codes G, L, M, or S.
Model 1151
Pressure-196
Rosemount Inc.
Code Range
Code Output
Model 1151
Applicable with these High Pressure Side
Code Size Rating Material Diaphragm Sizes
M 2 in. Class 150 CS 2-in./DN 50
A 3 in. Class 150 CS 3-in./DN 80
B 4 in. Class 150 CS 4-in./DN 100
N 2 in. Class 300 CS 2-in./DN 50
C 3 in. Class 300 CS 3-in./DN 80
D 4 in. Class 300 CS 4 in./DN 100
P 2 in. Class 600 CS 2 in./DN 50
E 3 in. Class 600 ANSI CS 3 in./DN 80
X 2 in. Class 150 SST 2 in./DN 50
F 3 in. Class 150 SST 3 in./DN 80
G 4 in. Class 150 SST 4 in./DN 100
Y 2 in. Class 300 SST 2 in./DN 50
H 3 in. Class 300 SST 3 in./DN 80
J 4 in. Class 300 SST 4 in./DN 100
Z 2 in. Class 600 SST 2 in./DN 50
L 3 in. Class 600 SST 3 in./DN 80
Q DN 50 PN 10-40 CS 2 in./DN 50
R DN 80 PN 40 CS 3 in./DN 80
S DN 100 PN 40 CS 4 in./DN 100
V DN 100 PN 10/16 DIN CS 4 in./DN 100
K DN 50 PN 10-40 SST 2 in./DN 50
T DN 80 PN 40 SST 3 in./DN 80
U DN 100 PN 40 SST 4 in./DN 100
W DN 100 PN 10/16 SST 4 in./DN 100
Pressure-197
Model 1151 Alphaline Pressure Transmitters
Pressure-198
Rosemount Inc.
TABLE 14. Flushing Connections Lower Housing Options. available not available
Flushing Connection Ring Flushing Diaphragm Size
Code Size
Material (Lower Housing) Connections
Model 1151
2-in. 3-in. 4-in.
F1 SST 1 -18 NPT
F2 SST 2 -18 NPT
F3(1) Hastelloy C-276 1 -18 NPT
(1)
F4 Hastelloy C-276 2 -18 NPT
FA SST 0
FC(2) Hastelloy C-276 0
F7 SST 1 -14 NPT
F8 SST 2 -14 NPT
F9 Hastelloy C-276 1 -14 NPT
F0 Hastelloy C-276 2 -14 NPT
(1) Not available with high pressure side Option Codes A0, B0, and G0.
(2) Not available with high pressure side Option Code G0.
Pressure-199
STANDARD ACCESSORIES Other Model 1151 Literature
All models are shipped with flange adapters, drain/ 00813-0100-4593
vent valves, and one instruction manual per shipment. Model 1151 Smart Pressure Transmitters
Tagging 00813-0100-4294
The Alphaline Pressure Transmitter will be tagged, Model 1151DR Draft Range Differential
at no charge, in accordance with customer Pressure Transmitter
requirements. All tags are stainless steel. (Pressure-231)
The standard tag is wired to the transmitter. Filled Systems for Pressure Transmitters
Tag character height is 0.125 in. (0.318 cm). A
00813-0100-4594
permanently attached tag is available upon request.
Model 1151 Smart Retrofit Kit
Calibration
Transmitters are factory calibrated to the Rosemount, the Rosemount logotype, and SMART FAMILY are registered
customers specified range. If calibration is not trademarks of Rosemount Inc.
HART is a registered trademark of the HART Communication Foundation.
specified, the transmitters are calibrated at d-Cell, Rosemount System 3, and RMV9000 are trademarks of Rosemount Inc.
maximum range. Calibration is performed at Fluorolube is a registered trademark of Hooker Chemical Co.
ambient temperature and pressure. Hastelloy, Hastelloy C, and Hastelloy C-276 are registered trademarks of Cabot
Corp.
Optional Three-Valve Manifolds Monel is a registered trademark of International Nickel Co.
Viton is a registered trademark of E.I. du Pont de Nemours & Co.
Part No. 01151-0150-0001: Neobee M-20 is a registered trademark of Stepan Chemical Co.
3-valve manifold, carbon steel for DP (Ranges 35), Syltherm and D.C. are registered trademarks of Dow Corning Corp.
HP (Ranges 45). Teflon is a registered trademark of E.I. du Pont de Nemours & Co.
Aflas is a registered trademark of Asahi Glass Co., Ltd.
(Anderson, Greenwood & Co., M4AVIC-TR-68). Kynar is a trademark of Pennwalt Inc.
Part No. 01151-0150-0002: Cover photo: 1151-001AB
3-valve manifold, 316 SST with carbon steel bolts
for DP (Ranges 35), HP (Ranges 45).
(Anderson, Greenwood & Co., M4AVIS-TR-68).
2 Standoffs
2 Board spacers
2 Terminal eyelets
IN
1997 Rosemount Inc. U. S. A. Fax 44 (1243) 867 5541 Tlx RS 61117 FRSPL
http://www.rosemount.com
00813-0100-4360@
00813-0100-4360 Rev. BB 11/98
Pressure-200