Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Current and voltage transformers insulate the secondary circuits from the primary circuit
and provide quantities in the secondary which are proportional to those in the primary.
Current and voltage instrument transformer of the system are the inputted
1. To metering system for measuring and recording
2. To protective relay system as sensing quantity for relaying
System current and voltage are very high as such it can not be fed to the metering or relay unit and it can not be
measured.
Current and voltage are to be scale down to a suitable and safe value to feed measuring and relay units.
Also circuit has to be isolated from high voltage and currents for safety.
Thus requires a suitable voltage and current instrumental transformers:-
Current transformer is to reduce the very high primary current isolate from very high voltage and provide
a low current measurements.
Voltage transformer or potential transformer is to reduce high primary voltage, isolate from very high
voltage and provide a low voltage measurement.
The function of Instrumental transformer are:-
1. To reduce very high primary voltage or current to safe handling by meter and relay circuits.
2. Electrically isolating very high primary voltage from
Primary circuit to secondary voltage for safety.
Standardize meter and relay current /voltage so that the meter /relay are can be manufactured standard rating and
can be applied to all the system irrespective of primary voltage and current. For example 1/5amps current,
110/63.5 Voltage relay.
Instrument transformers are interface between actual primary power system and their measuring and
(protection)relay system on which reliable performance of measuring and protection depending.
In broad the construction and principle of operation is similar to power transformers.
Primary and secondary windings are magnetically coupled by magnetic core and electrically insulated by the
insulation.
Current transformer has small nos of large size of primary turns which is connected in series to primary system
large number of secondary are connected to measurement and for protections are to secondary system of the
circuit. All components required current are connected in series.
Voltage transformer has large number of primary turns which is connected in parallel to the primary system
smaller no. of secondary are connected to measurement and for protection are to the secondary system of the
circuit. All the components required voltage are connected in parallel.
Power handling are small hence no cooling system is required as required by the power transformer.
The instrument transformer are designed to at much lower than the saturation level of flux density to reduce error
where as power transformer are designed to operate nearer to saturation level for economize cost and size of the
power transformer.
There is no great distinction between a protective voltage transformer and a measuring voltage transformer the
difference only being the nature of the voltages transformed. Quite often some time the same transformer can
serve the both purposes.
Voltage transformer:-
Ideally the voltage transformer should produced a secondary voltage which is exactly proportional to the
primary voltage and exactly opposite in phase. This can never be achieved in practice.
The voltage drops in primary and secondary windings due largely to the magnitude and power factor of the
secondary burden results in ratio and phase angle errors. This Ratio error is given by the expression
Knvs -v p
%error =------------ x100.
vp
N2 Ip
Where Kn = Nominal Ratio. =---------- =--------
N1 Is
Vp = Primary terminal voltage.
Vs = Secondary terminal voltage.
If the error is positive, the secondary voltage exceeds the Nominal value. The turns
ratio of the transformer need not be equal to the nominal ratio; small turns
compensation will usually be employed, so that the error will be positive for low
burdens and negative for high burdens
The phase angle error is the phase difference between the reversed secondary and
the primary voltage vectors. It is positive when the reversed secondary voltage leads
the primary vector.
For protection purposes, accuracy of voltage measurement may be important during
fault conditions, as the system voltage might be reduced by the fault to a low value.
Effect of errors:-
Phase angle error:- The measurement value are not in phase with actual value. This
affects measurement of power, energy, powerfactor etc is because of the phased angle
between the measured voltages and measured current is not same as the phase angle
between primary voltage and primary current. However this will not affect single value
measurement like voltage, current, frequency etc.
Phase angle error does not affect protection circuit much.
Methods to reduce errors:-
Large size high permeability core to reduce magnetizing current.
Turns compensation.
Classification of Instrumental transformer (CT/PT):-
1.Classification by application
Metering CT/PT.
Protection CT/PT.
Metering CT/PT:-
Accuracy of measurement with both low ratio and phase angle error is
the requirement. But the range at which the accuracies are required is near the
normal operating range. Beyond this the accuracy is not required.
Protection CT/PT:-
Accuracy requirement is less. But the protection has to correctly
operate during system faults when currents are high and voltage is low.
Sustenance of accuracy at the abnormal condition is more important .
Rated current/Voltages
Rated current/Voltages Ratio.
Burdens:- The maximum impedance in case of Current
transformer and admittance in case of voltage with specified Pf that can be
connected to secondary with out loss in accuracy and performance. It can be
expressed in terms of volt-amps.
Instrument transformers are also used to isolate instruments from power lines and to
permit instrument circuits to be grounded.
Current Transformers
Classification of Transformers:-
1 .Classification by primary :-
Wound primary.
Bar Primary.
2.Classification by insulation media:-
Resin cast insulated Instrument Transformers.
Oil filled Instrument Transformers.
Gas filled Instrument Transformers.
3.Classification by construction:-
Bar type.
Bushing Type.
Window type.
Wound type.
a) Bar CT: - This is constructed with no primary winding and is installed around the
primary conductor, but has a permanent bar installed as a primary conductor.
b) Bushing CT: - This is window CT specially constructed to fit around a bushing and it
cannot be accessed.
c) Window CT: - This is constructed with no primary winding and is installed around the
primary conductor.
d) Wound CT: - This CT has a primary & secondary winding like a normal transformer. This
CT is rare and is used at very low ratios and currents, typically in CT secondary circuits to
compensate for low currents, to match different CT ratios in summing applications, or to
isolate different CT circuits. The type of primary winding depends upon the type of CT
insulation i.e. whether
Live tank Design
Dead Tank Design
Hair Pin Design
Eye Bolt Design
Hair Pin Design Eye Bolt Design
Choice of ratios: - 1.As per the standards the rated secondary currents is 1Amps or 5
amps.
2. Choice between 1 Amp or 5
Amps is made to see that turns ratio is limited. If rated primary current is high above
2000Amps and If the control room is nearer to the out door yard [ODY] then 5amps
secondary is chosen.
3. 1 amps secondary requires smaller size of leads but higher Current
Transformer
winding resistance.
Polarity marking and connection:-
- Correct polarity of primary and secondary polarities is important for all differential
protections, distance protections, power and energy metering.
- Wong polarity connection leads to addition of two sides currents. When subtraction is
required and vice-versa in case of differential protections.
- Direction of power and energy will be wrongly indicated in case of metering.
- The polarity makings on Current Transformer is marked as P1 and P2 for
primary and S1, S2 for corresponding secondary terminals. It means that
when Primary current enters P1, the secondary leaves at S1.