Sei sulla pagina 1di 34

ES 16

Instruction book
Atlas Copco

ES 16

Instruction book
Original instructions

Copyright Notice
Any unauthorized use or copying of the contents or any part thereof is prohibited.
This applies in particular to trademarks, model denominations, part numbers and drawings.

This instruction book is valid for CE as well as non-CE labelled machines. It meets the
requirements for instructions specified by the applicable European directives as identified
in the Declaration of Conformity.

2012 - 03
No. 2920 1800 00

www.atlascopco.com
Instruction book

Table of contents

1 Safety precautions..........................................................................................................3

1.1 SAFETY ICONS...................................................................................................................................3

1.2 SAFETY PRECAUTIONS DURING INSTALLATION...........................................................................................3

1.3 SAFETY PRECAUTIONS DURING OPERATION..............................................................................................4

1.4 SAFETY PRECAUTIONS DURING MAINTENANCE OR REPAIR...........................................................................5

2 General description........................................................................................................7

2.1 INTRODUCTION...................................................................................................................................7

2.2 ES FEATURES...................................................................................................................................9

3 Installation.....................................................................................................................14

3.1 DIMENSION DRAWING........................................................................................................................14

3.2 MOUNTING INSTRUCTIONS..................................................................................................................15

4 Operating instructions.................................................................................................20

4.1 PREPARING THE MACHINES TO BE CONNECTED TO THE ES SYSTEM...........................................................20

4.2 USER INTERFACE.............................................................................................................................20

5 Parts list.........................................................................................................................30

5.1 CUBICLE AND OPTIONS .....................................................................................................................30

2 2920 1800 00
Instruction book

1 Safety precautions

1.1 Safety icons

Explanation

Danger for life

Warning

Important note

1.2 Safety precautions during installation


All responsibility for any damage or injury resulting from neglecting these precautions, or
non observance of the normal caution and care required for installation, operation,
maintenance and repair, even if not expressly stated, will be disclaimed by the
manufacturer.

Precautions during installation


1. The machine must only be lifted using suitable equipment in accordance with the applicable safety
regulations. Loose or pivoting parts must be securely fastened before lifting. It is strictly forbidden to
dwell or stay in the risk zone under a lifted load. Lifting acceleration and deceleration must be kept within
safe limits. Wear a safety helmet when working in the area of overhead or lifting equipment.
2. The unit is designed for indoor use. If the unit is installed outdoors, special precautions must be taken;
consult your supplier.
3. Place the machine where the ambient air is as cool and clean as possible. If necessary, install a suction
duct. Never obstruct the air inlet. Care must be taken to minimize the entry of moisture at the inlet air.
4. Any blanking flanges, plugs, caps and desiccant bags must be removed before connecting the pipes.
5. Air hoses must be of correct size and suitable for the working pressure. Never use frayed, damaged or
worn hoses. Distribution pipes and connections must be of the correct size and suitable for the working
pressure.
6. The aspirated air must be free of flammable fumes, vapours and particles, e.g. paint solvents, that can lead
to internal fire or explosion.
7. Arrange the air intake so that loose clothing worn by people cannot be sucked in.
8. Ensure that the discharge pipe from the compressor to the aftercooler or air net is free to expand under
heat and that it is not in contact with or close to flammable materials.
9. No external force may be exerted on the air outlet valve; the connected pipe must be free of strain.
10. If remote control is installed, the machine must bear a clear sign stating: DANGER: This machine is
remotely controlled and may start without warning.
The operator has to make sure that the machine is stopped and that the isolating switch is open and locked
before any maintenance or repair. As a further safeguard, persons switching on remotely controlled

2920 1800 00 3
Instruction book

machines shall take adequate precautions to ensure that there is no one checking or working on the
machine. To this end, a suitable notice shall be affixed to the start equipment.
11. Air-cooled machines must be installed in such a way that an adequate flow of cooling air is available and
that the exhausted air does not recirculate to the compressor air inlet or cooling air inlet.
12. The electrical connections must correspond to the applicable codes. The machines must be earthed and
protected against short circuits by fuses in all phases. A lockable power isolating switch must be installed
near the compressor.
13. On machines with automatic start/stop system or if the automatic restart function after voltage failure is
activated, a sign stating "This machine may start without warning" must be affixed near the instrument
panel.
14. In multiple compressor systems, manual valves must be installed to isolate each compressor. Non-return
valves (check valves) must not be relied upon for isolating pressure systems.
15. Never remove or tamper with the safety devices, guards or insulation fitted on the machine. Every pressure
vessel or auxiliary installed outside the machine to contain air above atmospheric pressure must be
protected by a pressure relieving device or devices as required.
16. Piping or other parts with a temperature in excess of 80C (176F) and which may be accidentally touched
by personnel in normal operation must be guarded or insulated. Other high temperature piping must be
clearly marked.
17. For water-cooled machines, the cooling water system installed outside the machine has to be protected by
a safety device with set pressure according to the maximum cooling water inlet pressure.
18. If the ground is not level or can be subject to variable inclination, consult the manufacturer.

Also consult following safety precautions: Safety precautions during operation and Safety
precautions during maintenance.
These precautions apply to machinery processing or consuming air or inert gas.
Processing of any other gas requires additional safety precautions typical to the application
which are not included herein.
Some precautions are general and cover several machine types and equipment; hence
some statements may not apply to your machine.

1.3 Safety precautions during operation


All responsibility for any damage or injury resulting from neglecting these precautions, or
non observance of the normal caution and care required for installation, operation,
maintenance and repair, even if not expressly stated, will be disclaimed by the
manufacturer.

Precautions during operation


1. Never touch any piping or components of the compressor during operation.
2. Use only the correct type and size of hose end fittings and connections. When blowing through a hose or
air line, ensure that the open end is held securely. A free end will whip and may cause injury. Make sure
that a hose is fully depressurized before disconnecting it.
3. Persons switching on remotely controlled machines shall take adequate precautions to ensure that there
is no one checking or working on the machine. To this end, a suitable notice shall be affixed to the remote
start equipment.
4. Never operate the machine when there is a possibility of taking in flammable or toxic fumes, vapors or
particles.
5. Never operate the machine below or in excess of its limit ratings.

4 2920 1800 00
Instruction book

6. Keep all bodywork doors shut during operation. The doors may be opened for short periods only, e.g. to
carry out routine checks. Wear ear protectors when opening a door.
On compressors without bodywork, wear ear protection in the vicinity of the machine.
7. People staying in environments or rooms where the sound pressure level reaches or exceeds 80 dB(A)
shall wear ear protectors.
8. Periodically check that:
All guards are in place and securely fastened
All hoses and/or pipes inside the machine are in good condition, secure and not rubbing
There are no leaks
All fasteners are tight
All electrical leads are secure and in good order
Safety valves and other pressure relief devices are not obstructed by dirt or paint
Air outlet valve and air net, i.e. pipes, couplings, manifolds, valves, hoses, etc. are in good repair, free
of wear or abuse
9. If warm cooling air from compressors is used in air heating systems, e.g. to warm up a workroom, take
precautions against air pollution and possible contamination of the breathing air.
10. Do not remove any of, or tamper with, the sound-damping material.
11. Never remove or tamper with the safety devices, guards or insulations fitted on the machine. Every pressure
vessel or auxiliary installed outside the machine to contain air above atmospheric pressure shall be
protected by a pressure relieving device or devices as required.

Also consult following safety precautions: Safety precautions during installation and Safety
precautions during maintenance.
These precautions apply to machinery processing or consuming air or inert gas.
Processing of any other gas requires additional safety precautions typical to the application
which are not included herein.
Some precautions are general and cover several machine types and equipment; hence
some statements may not apply to your machine.

1.4 Safety precautions during maintenance or repair


All responsibility for any damage or injury resulting from neglecting these precautions, or
non observance of the normal caution and care required for installation, operation,
maintenance and repair, even if not expressly stated, will be disclaimed by the
manufacturer.

Precautions during maintenance or repair


1. Always use the correct safety equipment (such as safety glasses, gloves, safety shoes, etc.).
2. Use only the correct tools for maintenance and repair work.
3. Use only genuine spare parts.
4. All maintenance work shall only be undertaken when the machine has cooled down.
5. A warning sign bearing a legend such as "Work in progress; do not start" shall be attached to the starting
equipment.
6. Persons switching on remotely controlled machines shall take adequate precautions to ensure that there
is no one checking or working on the machine. To this end, a suitable notice shall be affixed to the remote
start equipment.
7. Close the compressor air outlet valve before connecting or disconnecting a pipe.
8. Before removing any pressurized component, effectively isolate the machine from all sources of pressure
and relieve the entire system of pressure.

2920 1800 00 5
Instruction book

9. Never use flammable solvents or carbon tetrachloride for cleaning parts. Take safety precautions against
toxic vapours of cleaning liquids.
10. Scrupulously observe cleanliness during maintenance and repair. Keep dirt away by covering the parts
and exposed openings with a clean cloth, paper or tape.
11. Never weld or perform any operation involving heat near the oil system. Oil tanks must be completely
purged, e.g. by steam cleaning, before carrying out such operations. Never weld on, or in any way modify,
pressure vessels.
12. Whenever there is an indication or any suspicion that an internal part of a machine is overheated, the
machine shall be stopped but no inspection covers shall be opened before sufficient cooling time has
elapsed; this to avoid the risk of spontaneous ignition of the oil vapour when air is admitted.
13. Never use a light source with open flame for inspecting the interior of a machine, pressure vessel, etc.
14. Make sure that no tools, loose parts or rags are left in or on the machine.
15. All regulating and safety devices shall be maintained with due care to ensure that they function properly.
They may not be put out of action.
16. Before clearing the machine for use after maintenance or overhaul, check that operating pressures,
temperatures and time settings are correct. Check that all control and shut-down devices are fitted and that
they function correctly. If removed, check that the coupling guard of the compressor drive shaft has been
reinstalled.
17. Every time the separator element is renewed, examine the discharge pipe and the inside of the oil separator
vessel for carbon deposits; if excessive, the deposits should be removed.
18. Protect the motor, air filter, electrical and regulating components, etc. to prevent moisture from entering
them, e.g. when steam cleaning.
19. Make sure that all sound-damping material and vibration dampers, e.g. damping material on the bodywork
and in the air inlet and outlet systems of the compressor, is in good condition. If damaged, replace it by
genuine material from the manufacturer to prevent the sound pressure level from increasing.
20. Never use caustic solvents which can damage materials of the air net, e.g. polycarbonate bowls.
21. The following safety precautions are stressed when handling refrigerant:
Never inhale refrigerant vapours. Check that the working area is adequately ventilated; if required, use
breathing protection.
Always wear special gloves. In case of refrigerant contact with the skin, rinse the skin with water. If
liquid refrigerant contacts the skin through clothing, never tear off or remove the latter; flush
abundantly with fresh water over the clothing until all refrigerant is flushed away; then seek medical
first aid.

Also consult following safety precautions: Safety precautions during installation and Safety
precautions during operation.
These precautions apply to machinery processing or consuming air or inert gas.
Processing of any other gas requires additional safety precautions typical to the application
which are not included herein.
Some precautions are general and cover several machine types and equipment; hence
some statements may not apply to your machine.

6 2920 1800 00
Instruction book

2 General description

2.1 Introduction

General view

General view of the ES 16 Central control system

Function
Today customers want more than just peace of mind. They want to continuously reduce their production costs
without jeopardizing the availability of compressed air. Moreover, environmental awareness calls upon
industrial facilities to limit CO2 emissions by reducing their energy consumption. Compressed air
installations, with their significant power needs, are an important area for improvement.
The Atlas Copco central controller is the perfect solution to meet these needs by:
improving the efficiency of the complete compressed air system
reducing the life cycle cost to the absolute minimum
monitoring the operation of the compressed air system
meeting stringent environment legislation.
Certain features of the central controller can be limited or disabled due to licence restriction.

Description
The core of the installation is the ES device which retrieves and processes information coming from the
compressors, dryers and other measurement equipment. The ES can be connected to 1 pressure air net and a
total number of 16 machines. Additionally, the ES can be configured with lots of analog inputs and digital
in- and outputs to connect to other auxiliary equipment.
Compressors and dryers must be connected to the ES device by means of a CAN network.

2920 1800 00 7
Instruction book

Over this network, the ES is able to receive data from the dryers (monitoring) and receive data from and send
commands to the compressors (monitoring and control). Based on a set of rules, dryers or other auxiliary
equipment can be controlled through digital signals, to be hardwired between the equipment and the ES. Per
air net, one or multiple 4-20 mA pressure transmitters can be connected. A flow meter, dewpoint meter, etc
are optional.

In case the control feature is available, the ES regulates the net pressure of the connected air nets by starting/
stopping machines and selecting their operating points. The ES regulates the net pressure within a selectable
and changeable pressure band, applying a selectable optimization profile; see section Features.
The ES stores all machine and sensor data locally on the ES device (up to one week of data). This allows the
user to see graphs on the ES user interface.
In case the datawarehouse monitoring feature is available, the monitored information is uploaded to a central
Atlas Copco Airpower datawarehouse. The customer can consult his data via webbrowser and receive warning
and error notifications over SMS or email.

8 2920 1800 00
Instruction book

2.2 ES features

Control
The ES can control and monitor compressors over a CAN connection. A maximum of 16 pieces of equipment
can be connected and controlled over the CAN connection.
In case a compressor is controlled by ES, it is called integrated. In the other case, the compressor runs on
its own local control regulator and local pressure transmitter and is called isolated. In case a compressor is
isolated, the ES is still capable of monitoring that compressor.
With the proper user permissions, the user can integrate and isolate compressors as desired.
In case a dryer is connected over CAN, it can be monitored by the ES.
Control of dryers is possible via rule-based control over digital outputs. In this case the ES digital outputs
need to be connected to the dryers digital inputs.

Data logging and data upload


The ES monitors all measured and calculated machine data, air net data and connected analog inputs. Data
of up to one week are logged. Graphs can be made of each logged datapoint on the ES user interface.
The ES can upload all data to an Atlas Copco datawarehouse over a direct internet connection, or over analog
or GPRS modem. These data can be consulted via a webbrowser from any PC. Warning and error notifications
can be sent by SMS or email.

Smooth pressure control


The ES regulates the load/unload compressors inside a narrow user-defined pressure band.
In case variable flow machines (VSDs, turbos etc) are connected to the system, the ES will regulate towards
the airnet pressure setpoint. The regulation has a fast response without over- or undershoot.

2920 1800 00 9
Instruction book

In order to obey the rules and optimization profiles, the ES can decide to switch the compressors, i.e. start
one or more machines combined with also stopping one or more machines. In this case, the ES calculates the
optimal timing of the compressor commands to keep the pressure inside the pressure band and to minimize
the influence of the switch on the pressure.

Pressure transmitters
Per air net, multiple pressure transmitters can be used.
In case one pressure transmitter fails or in case the deviation with respect to the other transmitters is too large,
the system generates a warning but can continue regulating.
In case the deviation between the remaining transmitters is too large, the ES system will send all machines
of the affected air net(s) to local control in order to guarantee the pressure in these air net(s) by the local
control algorithm of the machines and their local pressure transmitter.

System pressure settings management


Per air net different sets of pressure bands and setpoints can be defined. The settings to be applied can be
chosen manually, can be time triggered, or can be selected by an external input such as a digital signal. With
the correct user permissions, the pressure settings can be selected or changed.
The ES regulates each air net to the specified pressure band and setpoint. When changing from one System
Pressure Setting (SPS) to another, the setpoint and pressure bands move smoothly to their new setting during
a short transition period.
For each pressure setting, also a low and high pressure warning level and a low and high pressure shutdown
level are defined. In case the air net pressure reaches a warning level, a warning message is generated. In case
the air net pressure reaches a shutdown level, a shutdown message is generated and all the machines of the
air net are sent to local control mode. The pressure in the air net is then regulated by the local control algorithm
of the machines and their local pressure transmitter. The local machine controllers are hence used as a
redundancy for the ES system and its pressure transmitters to guarantee air net pressure at all times.

Optimization profiles
The ES can regulate each air net with following optimization profiles:
optimized energy savings
forced sequence
equal wear
group management
Optimized energy savings means that the ES selects the machines that can produce the requested flow demand
with the lowest energy cost.
Forced sequence means that the ES triggers the start and stop of machines according to a specified sequence.
Equal wear means that the ES keeps the running hours of the different machines within a programmable range.
Group management means that groups and subgroups can be made with the machines. In each of the
(sub)groups any of the above optimization profiles can be defined. Over the (sub) groups a forced sequence
or equal wear algorithm can be activated.
On top of this, on airnet level, a central stop or local control profile can be defined. Central stop means that
the ES stops all integrated machines. Local control means that the ES sends all integrated compressors to their
local control.

10 2920 1800 00
Instruction book

The optimization profile(s) for each air net are selected manually, or based on a timer, or based on a flow
demand. E.g. depending on the calculated flow demand, an air net can be automatically regulated into another
forced sequence profile.

Optimal operating point


The optimization profile determines which machines to run. On top of this, whatever the chosen optimization
profile is, the ES continuously regulates the running machines towards the most energy efficient operating
point.
For instance, a forced sequence determines which machines are to be turned on or off. The ES continuously
adapts the operating points of the running machines such that the flow is produced at the lowest possible
energy cost.
If desired, it is possible to define base load units which are not taken into consideration for operating point
optimization; see section Rules. These units will run at full load.

Load after shutdown


In the unfortunate event of a compressor shutdown, the ES does not wait for the pressure to dip down, but
instead starts a machine immediately and as such the ES minimizes the pressure influence of the event.

Spare capacity
Selecting a spare capacity means that the ES keeps on running one or multiple machines which have the
immediate possibility to produce extra flow. The amount of extra flow is defined as the spare capacity.
The spare capacity can reduce the pressure fluctuations in case of a compressor shutdown or a sudden large
increase in flow demand. In some particular installations, these pressure fluctuations could result in production
loss. For these installations the energy costs of having extra spare capacity available are justified.
Two types of spare capacity are possible:
the spare capacity is to be foreseen by compressors running in unload. This option guarantees the
immediate availability of air to avoid pressure undershoot due to shutdown of one of the loaded
compressors.
the spare capacity can consist of the available upload flow of the loaded compressors. This option
guarantees the immediate availability of air to avoid pressure undershoot due to a sudden increase in the
flow demand.

Compressor timers and limitations


The ES takes all critical machine settings and limitations into account such as idling time, minimum stop time,
maximum motor speed, number of starts per day, etc.

Time controlled isolation


On some occasions the ES needs to send multiple machines at once to local control, e.g. when the central stop
control profile is selected, or when a pressure shutdown occurs on an air net. However, in case the ES would
send all compressors at the same time to local control, they would be started simultaneously. The time
controlled isolation option takes care that the running compressors (loaded and unloaded) are isolated first,
and then all stopped compressors are isolated one by one with a set time between the isolation events.

Rule based control


Following rules are predefined:

2920 1800 00 11
Instruction book

baseload compressors:
Baseload compressors take care of the baseload flow by running fully loaded. The operating points of
these compressors are not optimized with the energy optimization algorithm.
backup compressors:
Backup compressors are standby and only to be used in case one or more specified compressors become
unavailable. In other words, as long as the specified compressors are available, the backup compressors
are the last to be started.
Customer specific programming of the digital outputs is possible. The digital outputs can be triggered
based on a combination of timers, machine states, measurement values and digital inputs (PLC logic). In
this way, the ES can control auxiliary machines or alarms with digital control inputs.

Inputs/Outputs
The standard ES 16 device has two analog 4-20 mA inputs. As an option the ES 16 can have eight analog
4-20 mA inputs, four digital inputs and four digital relay outputs. Using extension IO blocks, the ES can
connect to up to 100 digital outputs, 100 digital inputs and 16 analog 4-20 mA inputs.
At least one analog input per air net is preserved for pressure sensing, the remaining I/O are free for customer
specific use.
The analog and digital input measurements can be:
used in the programming of digital output rules
displayed on the air net or main screens (actual value, up to 4 measurements per air net)
viewed in the graph screens (data graph of last month)
uploaded to the datawarehouse

Field bus connectivity


Some field bus connectivity to read out parameters or select settings is available. Contact Atlas Copco to
know the possibilities for your field bus.

Automatic functions
If desired, the ES can automatically reintegrate compressors after an event-triggered isolation.
Following automatic functions are available:
automatic integration after voltage failure.
At a voltage failure of the ES, the compressors start regulating in local control. After the voltage failure,
the ES reboots. In case this option is enabled, the ES will re-integrate previously integrated compressors.
The behavior of this function can be influenced with the value of a digital input, a delay timer and a
maximum ES down time.
automatic integration after communication failure.
When a communication error between the ES and a machine occurs, the machine starts regulating in local
control. When the communication problem is solved and in case this option is enabled, the ES will re-
integrate the machine.
automatic integration after not responding.
Under ES control, the ES monitors whether the machines react as expected. At unexpected behavior, the
machine will be sent to local control. In case this option is enabled, the ES will try to re-integrate the
machine. The behavior of this function can be influenced with a delay timer and a maximum number of
retries in a set period.
automatic integration after LAN selection.

12 2920 1800 00
Instruction book

In case the machines are switched from LAN to local control on the local compressor regulator, the
machine starts regulating in local control. In case this option is enabled, the ES will automatically re-
integrate the machine when it is put back in LAN mode.
automatic integration after pressure shutdown.
In case the pressure should exceed the pressure shutdown levels, the ES will send all machines to local
control. In case this option is enabled, the ES will try to re-integrate the compressors. The behavior of this
function can be influenced with a delay timer and a maximum number of retries in a set period.

User management
All settings and control actions that influence the ES regulation are protected by user permissions. The ES
will prompt for login at such actions. Only users with the required permission are allowed to execute the
requested change.
Users can be created and assigned with any combination of the following permissions:
integrate/isolate machines
select or edit pressure settings
select optimization profile settings
select central stop
edit spare capacity settings
enable/disable rules
edit automatic function settings
edit user settings

2920 1800 00 13
Instruction book

3 Installation

3.1 Dimension drawing

Dimensions

Reference Description
(1) Section A-A
(2) Section B-B
(3) Detail of mounting plate
(4) Detail of cubicle box
(5) Detail of cubicle door

14 2920 1800 00
Instruction book

3.2 Mounting instructions

Procedure
The ES consists of a generic enclosure containing electrical components.
On the bottom of the enclosure, ten conduit routings closed with nuts allow to enter cables. Ten matching
cable glands are provided. Note that the glands are in metric dimensions and that an adapter is necessary in
case of use of 1/2 inch conduits.
The ES is wall mountable, the overall weight is about 15 kg, depending on the ordered options.
Select the place on the wall to mount the ES taking into account the maximum cable length of the CAN and/
or Ethernet networks and a maximum length of 1000 m to the pressure transmitters.
Four mounting brackets are included in the ES. Use appropriate fasteners to fix the unit to the wall. See section
Dimension drawing for the dimensions.

Stick labels on the control panels of the machines connected to the ES as well as on an
obvious place inside these machines, warning the operator that the machine is remotely
started and stopped by a separate controller. These labels must warn the operator that, also
after voltage failure, the ES can remotely start and stop the machine.

Pressure transmitters
The pressure transmitters should preferably be connected :
to an air receiver to avoid pressure pulsations (vibrations should also be avoided)
via valves, allowing the pressure transmitter to be removed after isolating and depressurizing it
in vertical position to avoid influence of condensate.
Isolate and depressurize that part of the air net to which the pressure transmitters will be connected.
The pressure transmitters have a working temperature limit from 30 C to 125 C (-22 F to 257 F). Use
an extension pipe for high temperatures to cool off the air.

Connect the transmitters to the analog inputs of the ES using double twisted pairs shielded 0.75 mm2 cable.
The maximum allowable length of the cables is 1000 m.

In case the pressure transmitters have a fixed cable with shielding attached, the shielding
must not be connected to the shielding of the ES to prevent loop-currents in the system.

2920 1800 00 15
Instruction book

Compressor/dryer communication (CAN)


In case the machines are equipped with an Elektronikon regulator of generation 4, a CAN bus needs to be
wired starting from the CAN0 and/or CAN1 connectors on the ES regulator A500. Up to 16 machines can be
connected per CAN port.
The CAN cable is a three-wire shielded cable, two signal wires and one ground. CAN network cables have a
maximum length of 250 m.

Datawarehouse upload
In case data upload to the central datawarehouse is needed, an internet connection is required. This can be a
direct internet connection (ETH1 connector on the ES regulator A500), or a connection over analog modem
(T800) or GSM/GPRS modem (T801). The modem is installed in the ES upon ordering the modem upload
feature. The access to the internet itself (internet provider, phone line, SIM card) is a responsibility of the
customer.

Electrical diagram

Connect a 110-240 VAC, 50/60 Hz power supply to terminals L1 and L2 of the ES controller.
Make sure the earthing cable is connected to terminal PE.

16 2920 1800 00
Instruction book

Provide a branch circuit protection and a disconnect possibility.

Inputs/Outputs
The ES device has an I/O block K010 with either two or eight 4-20 mA analog inputs, four digital inputs and
four digital outputs. The digital outputs can be further wired to four relays: K101, K102, K103 and K104.

Electrical connections should be done by qualified personnel and according to the local
standards.

Technical data of the I/O:


Digital inputs:

Input type 24V three-wire interface (24V, GND, input)


Input voltage range Low= -3V to +5V, high: +15V to +30V
Isolated 2 kV to each port and to the system
Input filter 5 ms = 200Hz
Input protection 8 kV to ESD
Input impedance Minimum 1.5k ohm, maximum 6k ohm at 30V
Powered 24V +- 10% not protected
Protection Voltage: max 30V, current max 40 mA for all ports
Switching time Max 100 ms
Input current 6.6 mA at 24V

Digital outputs (optional)

2920 1800 00 17
Instruction book

Contact type three-wire interface (24V, GND, output)


Switching voltage 24V DC
Switching current 0.5A
Switching delay time Ton = 10 ms, Toff = 10 ms
Isolation 2 kV process to system
Debouncing no

Relay outputs

Contact type 3 connection points per output: one of which refers to normally open, and one
to normally closed. Dual use possible.
Actuating voltage 24V DC
Nominal switching capacity AC:
250 VAC: 10A
DC:
30V DC: 10A
110V DC: 0.25A
220V DC: 0.12A
The power is not to be supplied by the ES control box.

The relays are used for signalling or controlling external devices based on certain states
of the software. They are designed for use in UL Class 2 circuits.

Analog inputs, 4-20 mA

18 2920 1800 00
Instruction book

Input type 5 three-wire interfaces (24V, GND, input+, input-, shield)


Load Max load current per channel is 120mA with a max total of all 8 channels of
600 mA
Ranges Current: 4-20 mA
Resolution 10 bit
Accuracy <1.5%
Throughput rate 100 Hz
Isolated 2kV to process to system
Input filter 200 Hz
Input protection 8 kV to ESD
Input impedance Current: 23.5 ohm
Powered 24V
Protection Voltage: max 30V, current max 140 mA

Optional extra IO blocks can be added outside the ES enclosure by wiring a CAN open network starting from
the CAN connector on the IO block K010. Using these optional IO blocks, the ES can connect to up to 100
digital outputs, 100 digital inputs and 16 analog inputs.

ES commissioning
Contact the Atlas Copco service engineer to commission the ES system.

2920 1800 00 19
Instruction book

4 Operating instructions

4.1 Preparing the machines to be connected to the ES system

Description
The ES can be connected to compressors and dryers equipped with an Elektronikon generation 4 and 5.
In order to be able to take control, the Elektronikon regulators of the connected machines must be set to LAN
control and an individual node address must be programmed in the regulator (consult the relevant instruction
book of the machine).

It is not necessary to stop machines in order to integrate them into ES control.

4.2 User interface

Description
The ES has a 17.5 cm (7") color touch screen. A contemporary user interface allows the user to navigate
through all available system information and to change the system settings.

20 2920 1800 00
Instruction book

Menu and navigation


On top of each screen on the left a navigation dock is displayed.
In the standard position it shows the navigation to the current screen.

Clicking on this dock will open the screen and allow to navigate to any other screen.

In addition to the navigation menu, most parts of each screen are shortcuts to related
screens (e.g. when clicking on a compressor in the air net screen, the device screen of
that compressor will be shown ). The navigation menu always shows the navigation to the
current screen, independent of whether it was obtained by using the menu or a shortcut.

On the top right of the screen 3 buttons are available:

The logout button is used to log out.

The settings button is a link to all system settings.

The system status shows the warnings and errors when they occur.

When no warnings are present, the system displays an OK icon:

Warnings of machines or air nets (e.g. service warning, low pressure warning) are indicated by a triangle:

Shutdowns of machines or air nets (e.g. emergency stop pressed, high pressure shutdown) are indicated by a
stop sign:

2920 1800 00 21
Instruction book

Air net screen

The ES has an air net screen showing :


the pressure graph indicating the pressure, the pressure settings and the selected ES optimization profile
some measured and calculated data points, to be selected at commissioning time
the used capacity bar, indicating the used capacity compared to the total available capacity for that air net
(sum of all available compressors)
the machines connected to the air net, indicating the name, machine type, integration status icon
(integrated/isolated) and the actual status of the machine (loaded, unloaded, stopped, not available,
unknown). The compressors also have a capacity bar indicating how much air the machine delivers
compared to its maximum.
When a machine becomes unavailable to an air net because of valve settings, the machine is greyed out on
the user interface. All controls are still available, but only from the air net screen to which the machine belongs
at this time.
In case an error or warning is valid for a machine, an icon appears over the machine icon:

A question mark is shown in case the warning is ES related, for instance when there is no
communication between the ES and the machine, or when the machine does not react as
expected.

An exclamation mark is shown in case the warning is machine related, for instance when
one of the internal machine sensors has reached a warning level.

A service key is shown in case the service interval of the machine has expired.

A stop sign is shown in case the machine is shut down, for instance when the emergency
stop button is pressed.

More detailed information about the error or warning is also available in the status bar on top.
The integration status icon indicates whether the ES is controlling the machine:

22 2920 1800 00
Instruction book

The machine is Isolated, meaning that the machine is at this time not controlled by the ES. The machine
is controlled by its local controller to its local settings based on the local pressure transmitter.
Pressing the button will integrate the machine and the icon changes into:

This can be done by any user with the required permissions.


The machine is Integrated, meaning that the ES is controlling this machine, based on the ES settings and
ES pressure transmitters.
Pressing the button will isolate the machine and the icon changes into:

This can be done by any user with the required permissions.


The machine is isolated and can not be integrated (e.g. the Elektronikon regulator is not set to LAN control).

Measurement point screens

From any measured or calculated data point, a graph is available. The data are stored up to one month ago.
The graph time frame can be selected.

2920 1800 00 23
Instruction book

Device screens

For each machine connected over the CAN network, a more detailed data view is available. All measured and
calculated values of the machine are shown, including all measured values from its internal sensors.
On this screen also the warning symbols and a button to switch the integrate/isolate status of the machine are
available. The symbols and actions are the same as explained in the section Air net screens.

Log screen

The log screen gives an overview of setting changes, warnings and errors in the system, for the ES system as
well as for the connected machines.

24 2920 1800 00
Instruction book

Log-in dialog

Whenever changing system or air net settings, the user needs to log in by selecting the user name and entering
the correct password. The user permissions are checked to see whether the user is allowed to perform the
requested change.
The user can log out by the log out button on the menu bar:

The user is automatically logged out after a period of inactivity.

Settings

By pressing the settings button, tab pages with the settings appear:

Pressure Settings

2920 1800 00 25
Instruction book

In this screen, an existing set of pressure settings or a timer mode can be modified and pressure settings can
be added or edited by users with the right permissions.
Pressure settings are managed per air net.
For more detailed information on the ES pressure regulation, see section ES features.

Changing the pressure settings has consequences to the net pressure and should only be
done by qualified personnel.

Optimization profile settings

In this screen, an optimization profile, a timer mode or a selection based on flow demand can be activated by
users with the right permissions.
Optimization profiles are managed per air net.
For more detailed information on the ES optimization profiles, see section ES features.

Changing the optimization settings has consequences on the regulation and should only be
done by qualified personnel.

Rules

26 2920 1800 00
Instruction book

In this screen, regulation rules can be enabled or disabled by users with the right permissions.
For more detailed information on the rule based control, see section ES features.

Changing the rules settings has consequences on the regulation and should only be done by
qualified personnel

Automatic functions

In this screen, automatic functions can be enabled or disabled by users with the right permissions.
For more detailed information on the available automatic functions, see section ES features.

2920 1800 00 27
Instruction book

Changing the automatic function settings has consequences on the regulation and should
only be done by qualified personnel.

Be aware that some of the automatic functions will cause machines to start automatically.
Stick labels on the control panels of the machines connected to the ES as well as on an
obvious place inside these machines, warning the operator that the machine is remotely
started and stopped by a separate controller. These labels must warn that, also after a voltage
failure, the ES can remotely start and stop the machine, depending on the air demand and
programmed values.

User management

In this screen, users can be created and assigned any combination of following permissions:
integrate/isolate machines
select pressure settings
edit pressure settings
select profile settings
select central stop
enable/disable rules
edit automatic function settings
edit user settings

28 2920 1800 00
Instruction book

System Preferences

In this screen, some system wide settings such as the measurement units, language, default time frame of the
graphs and savings can be selected.
Version and licensing information

This screen shows the ES version and license information.

2920 1800 00 29
Instruction book

5 Parts list

5.1 Cubicle and options

Reference Part number Name


- 1623 8836 00 Cubicle box
- 1089962001 Analog modem
- 1089962010 Digital modem
- 1089962012 Antenna
- 975810004 Battery
- 1089953702 Relay
- 1623402700 I/O block 8A/4DI/4DO
1 1081042101 Fuse 4A
2 1081042102 Fuse 2A
3 1089940517 Panel PC
4 1623863500 I/O block 2AI
5 1089954402 Power supply 4A
6 981040505 Cf card

30 2920 1800 00
What sets Atlas Copco apart as a company is our conviction that
we can only excel in what we do if we provide the best possible
know-how and technology to really help our customers produce,
grow and succeed.
There is a unique way of achieving that - we simply call it the Atlas
Copco way. It builds on interaction, on long-term relationships
and involvement in the customers process, needs and objectives.
It means having the flexibility to adapt to the diverse demands of
the people we cater for.
Its the commitment to our customers business that drives our
effort towards increasing their productivity through better
solutions. It starts with fully supporting existing products and
continuously doing things better, but it goes much further, creating
advances in technology through innovation. Not for the sake of
technology, but for the sake of our customers bottom line and
peace-of-mind.
That is how Atlas Copco will strive to remain the first choice, to
succeed in attracting new business and to maintain our position
as the industry leader.

No. 2920 1800 00 / 2012 - 03

Potrebbero piacerti anche