1. INTRODUCTION 3
2. PURPOSE OF THE DOCUMENT 3
3. SOIL DATA 3
4. DESIGN REFERECES 4
5. DESIGN PARAMETERS 4
5.1 Shoring Piles 5
5.2 Bracing Beams 6
5.3 Steel Strut 6
6. MODELING OF SHORING SYSTEM 6
7. ANALYSIS & DESIGN OF SHORING SYSTEM 8
7.1 Structural Design of Pile 9
7.2 Analysis & Design of Bracing Beams 9
7.3 Analysis & Design of Strut 10
7.4 Analysis & Design of Capping Beam 10
8. SAFETY 10
9. MONITORING OF SHORING SYSTEM 11
ANNEXURES
The project is called as extension of Amiri Diwan is located at Doha Qatar. The
extension includes the construction of new offices at the North side of the existing
building, facing towards the Corniche road.
Civil work of the project is awarded to Contraco and Ammico is involved in the project
as a shoring sub-contractor.
The site shall be excavated down from 7 to 8m below the existing ground for the
construction of new office buildings. To retain such a deep excavation in loose strata,
adequate shoring system is required. Based on the depth of loose strata and adjacent
structure following types of shoring systems have been designed at different sections;
Section 1: 600@650mm diameter contiguous pile with capping beam, ring beam and strut
Section 2: 600@650mm diameter contiguous pile with capping beam and strut
Section 3: 900@950mm cantilever diameter contiguous pile
This report contains the analysis and design philosophy of above mentioned shoring
system.
3. SOIL DATA
Reference has been made to Geotechnical Investigation Report for Extension of Amiri
Diwan Project, Report No: S17000102 Rev 0 dated April 2017 by ACES. As per the
soil report, one investigation borehole has been drilled at an area where existing ground
level is around at 6.0m QNHD. Due to backfilling, existing ground near the shoring area
is higher about 11.0 to 12.0m QNHD. Hence, thickness of this backfill stratum along
with other strata revealed by the investigation borehole has been considered in the
analysis of shoring system.
The soil parameters used for the design of shoring system are given below;
As per the soil investigation report, the ground water was found at depths of -2.0m
QNHD. The soil profile is attached herewith in Annexure-1. Complete soil report is
attached under Annexure 10.
4. DESIGN REFERECES
CODES
CIRIA C580 Embedded Retaining Walls Guidance for Economic Design
BS 8004: 1986 Code of Practice for Foundations
BS 8110-1: 1997 Code of Practice for Design & Construction
BS5950 - Part 1 (2000) Steelwork
ICE Specification for Piling and Embedded Retaining Walls
QCS 2014
Project Specification
SOFTWARE
PLAXIS 2D AE Version 2015
ACECOMS GEAR V3
LOADS
Soil Loads
Surcharge Loads
MATERIAL
C40 grade concrete (non-durable) for all shoring elements
500 grade black deformed reinforcing bars for all shoring elements
S275 grade steel pipe for the strut
5. DESIGN PARAMETERS
Shoring system had been analyzed and designed to resist the lateral forces generated
by soil and surcharge loads for retaining height. The shoring details for the considered
sections are available at annexure 2 and summary is given below;
Section 1
This section is situated near the existing wall of courtyard. Site will be excavated for the
installation of lift which will provide the access in between new offices and existing Amiri
Diwan. The retain height is 8m. The designed shoring for this section is 600mm
diameter contiguous piles. The spacing of piles will be 650mm c/c and overall the
shoring piles will for a circle shape. A capping beam will be constructed at the top of
piles and during the excavation; one layer of bracing beam will be constructed at
circular shape (ring beam). Additionally, two layers of struts shall be installed (one will
be at capping beam and the other is at ring beam).
Section 2
This section is located along the access tunnel. The retain height is 7m and this portion
has been divided into two sections. Section 2a is still within the vicinity of surcharge
load of existing Amiri Diwan building and Section 2b is under 20 kPa surcharge load
only. The 600mm diameter contiguous piles with 650mm c/c spacing will continue at
this section with a capping beam and strut.
Section 3
This section is placed along the existing plant boxes: The retain height is 7m. The
designed shoring system is cantilever 900mm diameter contiguous piles.
.
Based on the above description, following table shows the shoring details;
It is to be noted that existing ground water level is lower than the excavation level and
shoring system has been designed without considering the water force. Therefore,
during the shoring and civil works, it must be ensured no water force shall come to the
shoring system. Other parameters considered for the analysis are as follows;
The Section 1 and Section shall be supported by bracing beams. These beams will be
capping beam and ring beam at the Section 1 and only capping beam at Section 2.
They will be reinforced concrete beams and the parameters used for the modeling of
ring/capping beam are available at the table given below;
Two and one layer of steel struts will be installed at Section 1 and 2 respectively. At
Section 1, strut will be installed only at junction of Section 1 and 2 as shown in the
annexure 2. Following parameters have been used in the modeling;
The shoring system thus analyzed using geotechnical software Plaxis v2016. The
design sequences are as follows;
During the structural calculations software outputs (shear & moments) are factorized
with 1.5 to reach the Ultimate Limit State on the structural failure. Reinforcement for
shoring piles are designed for (a) bending moments or stresses (b) shear forces
manually as per BS 8110 charts. Designed outputs (steel reinforcement) for shoring
piles are rechecked by using Acecom Gear Software. The detailed calculations for each
section is attached under Annexure 5 respectively. Summary of the structural
calculation has been tabulated as shown below.
Uniform distributed load for the beams have been obtained from the output of
geotechnical analysis (performed by Plaxis) of shoring system. Following table shows
the bracing beam force for unit length.
Based on the above stated load, analysis of the bracing beams (ring and capping) has
been carried out in structural software (STAAD.Pro). Complete design of the ring along
with STAAD.Pro output has been attached under Annexure 6.
From the analysis of bracing beams with STAAD.Pro, there will be forces at the
restraint points which will be the required forces to design the struts. Following table
shows the load and type for each strut;
Strut design is carried out as per BS 5950 and detailed calculation is attached under
Annexure 7.
Each shoring pile is designed individually at Section 3 to take the all types of loads (i.e.
soil, and surcharge etc.). Thus, there is no structural requirement for the capping beam
except to homogenize the deformation of different shoring pile. Hence, a capping beam
of nominal size to be installed.
Size of the capping beam is 900 x 600mm. Complete design of capping beam is
available under Annexure 8.
8. SAFETY
Plaxis (Finite Element Method) works based on Serviceability Limit State where
improved accuracy for predicting stresses, forces and deformations under working load
in soil structure integration problem is reached. To adapt the FEM analysis to Ultimate
Limit State, reduction on soil parameters (C-) had been made in the Plaxis stage-5
until the equilibrium cant be satisfied. This approach will determine the safety factor.
Plaxis output showing the safety factor for several points defined in the model is
available under annexure-4.
In order to ensure that the behavior of shoring system during and after excavation down
to formation level is in line with the analysis/design of the shoring, proper monitoring of
the lateral movement shall be undertaken.
The monitoring of shoring wall will be performed with total station by survey readings
from targets mounted on the shoring wall.
A survey target shall be consisted of a reflective target with precision cross hairs that
give accurate readings in three dimensions. Conventional total stations will be used to
take readings. An individual method statement shall be submitted in due course.
P-5
P-6
Excavation Level
+4.0m QNHD
P-8
Basement Wall Basement Wall Basement Wall
Outer Line Outer Line Outer Line
P-9
P-10
2nd Bracing Beam 2nd Bracing Beam
(300x600mm) (300x600mm)
P-11 +7m QNHD +7m QNHD
P-12
SOIL SIDE EXCAVATION SIDE SOIL SIDE EXCAVATION SIDE
P-13
UC (305x305x118)
SOIL SIDE EXCAVATION SIDE
P-14
GENERAL NOTES
P-15 SOIL SIDE EXCAVATION SIDE
SOIL SIDE EXCAVATION SIDE CONTIGUOUS PILES
1. The drawing is based on the site survey was undertaken by surteqa surveys on
P-16 600mm@ 650mmC/C December 2016.
CONTIGUOUS PILES 2. All dimensions, coordinates and elevations are in meters unless otherwise noted.
900mm@ 950mmC/C
P-17 3. All coordinates are related to qatar national datum '95 (qnd '95). All elevations
CONTIGUOUS PILES
are related to (QNHD).
P-18 CONTIGUOUS PILES CONTIGUOUS PILES 4. C40 grade concrete for all shoring elements (non-durable).
600mm@ 650mmC/C
3 3 600mm@ 650mmC/C 600mm@ 650mmC/C
5. B500 grade reinforcing steel for all shoring elements (black deformed).
P-19
Excavation Level Excavation Level Excavation Level 6. The connection detail of steel strut and wailer beam will be provided with another
P-20 +4.0m QNHD +4.0m QNHD +4.0m QNHD shop drawing.
Capping Beam
P-21
P-24
P-25
P-26
+11.0m QNHD
P-27
Basement Wall
Outer Line
CONTIGUOUS PILES
P-28
LEGENDS
900mm@950C/C
P-29
600mm Pile Type "A"
P-30
600mm Pile Type "B"
P-31
P-33
900mm Pile Type "D"
P-34
P-35
DOCUMENT REVIEW STATUS
P-36
Toe Level Toe Level Toe Level Toe Level STATUS A: APPROVED
P-37 -3.0m QNHD -3.0m QNHD -3.0m QNHD -3.0m QNHD
STATUS B: APPROVED WITH COMMENTS
0.60 0.60 0.60 0.60
CONTIGUOUS PILES P-38
STATUS C: NOT APPROVED REJECTED
600mm@650C/C SECTION -1a SECTION -1b SECTION -2a SECTION -2b
P- P-39
WITH 1 ROW OF STRUT 4 STATUS D: COMMENTED AND RESUBMIT
P- 0
P- 41
)
18
P- 4 2 Basement Wall
x1
P- 43
3
Outer Line
)
Toe Level
2b
05
P- 44 -5.0m QNHD
.
x3
ec
P- 45
(S
05
P-180
P-179
P-178
P-177
P-176
P-175
P-174
P-173
P-171
P-172
0.90
P-170
P-169
P-168
P-167
P-166
P-165
P-164
P-161
46 P-163
P-159
P-158
P-155
P-154
P-156
P-157
P-160
P-162
(3
D
P-
H
P- 47
C
2b SECTION -3
N
P- 48
Q
5
1.
P- 51 P- P-182
P- 52 2b P- 153 Contiguous Pile
Capping Beam Ring Beam Excavation Side
3
53 P-
15 P-183 CLIENT:
P-
15 2 600mm @ 650mm c/c
P- 54 P +11.0m QNHD
-1 1 with 2 Row of Ring Beam
P- 55 P- 50 Excavation Level P-184
m
P- 56 2b P- 149
300m
a)
2a
.2
P- 57 P- 148
+11.0m QNHD
P-185 Capping Beam
ec
P- 58 P- 147
(S
P- 59 P- 146 P-186
6 14
l
n D
ve
P- 0 P- 5
tio NH
P- 61 2a P- 44 P-187
2b
b)
va Q
E= 231353.290
P- 62 P- 143 900mm@950C/C CONSULTANT:
.2
ca m
1
ec
63
Ex 4.0
P- 42 P-188
(S
P- 141
+
mm
P-66
P- 140
+4.0m QNHD
P-189
P- 139 650m
700
P- m
700m
13
P- 64 P- 8 CONTIGUOUS PILES P-190
65 P - 137 600mm
P-70
2a
P-69
P-71
P-68
P-72
P- 136
m
4
P-191
P-7
P- 135
P-7 6
P- 131 P- 134
5
7
P- 8
P-192
P- 130 P- 133
77
Soil Side
P- 79
Existing Wall
LEAD ARCHITECT:
D
1 2a
7
13
P-
P- 29
H
P- 2 P-193
N
N= 393165.061 8 12
P- 0
Q
Capping Beam
)
8
2a
E= 231348.335 8
0m
P-8 1 P-194
c.
2
(S
+1
P -8
1a 3 +3.0m QNHD P-195 UAE-QATAR-KSA
P-84 P-127
Excavation Level P.O.Box : 11490 - Doha, Qatar
1b
P-85 P-126
P-196 Tel:+974 4414 6652, Fax:+974 4414 6653, Qatar:+974 6 6499010
n-
1a P-125
io
P-86
Excavation Side
ct
P-87
P-123 600mm @ 650mm c/c
P-88 P-122 Basement Wall MAIN CONTRACTOR:
100mm
7 P-198 with 1 Row of Strut
400mm
P-89 .06 Capping Beam
R7 P-121 Outer Line UC (305x305x118)
P-90 P-12 P-199
1 0 N= 393158.359 Basement Wall
P-9
P-9
2 2nd Bracing Beam
P-1
P-1 19
E= 231365.176
P-200 Outer Line Contraco W.L.L
3 (300x600mm) 18 Construction Company
P-9 4 P
P- -117
0.3
N= 393157.964 5
P- 113
P-202
P-
P- 7
P- 12
11
9
E= 231348.421
P- 11
98
4
99
P-1
00
1
P-1
CONTIGUOUS PILES
01
P-203
P-10
P-
2
P-1
P-103
P-10
Soil Side
10
600mm@650C/C
9
P-204
8
100mm
P-209 Basement Wall Capping Beam
900mm @ 950mm c/c
Outer Line EXTENSION OF AMIRI DIWAN BUILDING
P-210
DOHA, QATAR
550mm
P-211
+11.0m QNHD
+11.0m QNHD
P-212 TITLE
P-213
SHORING PILES LAYOUT PLAN
P-214
MODULATION PLAN & SHORING PILES SECTION
P-215
900mm 950mm Soil Side
P-216 THIS IS A CAD DRAWING AND MUST NOT BE ALTERED MANUALLY
Modulation Plan for Section - 3
P-217 DRAWING NUMBER: SCALE NTS ORIG. DWG SIZE: A1 REV.
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
ANNEXURE - 4
PLAXIS ANALYSIS RESULTS
-8.00 0.00 8.00 16.00 24.00 32.00 40.00 48.00 56.00 64.00 72.00 80.00 88.00 96.00 [m]
16.00
0.28
8.00
0.24
0.00
0.2
-8.00
0.16
-16.00
0.12
-24.00
0.08
-32.00
0.04
-40.00
600 @ 650 Sec 1 (2 Rings ... 140 Ammico Contracting Co. W.L.L.
Output Version 2016.1.21797.15047
-8.00 0.00 8.00 16.00 24.00 32.00 40.00 48.00 56.00 64.00 72.00 80.00 88.00 96.00 [kN m/m]
6000
16.00
8.00
5000
0.00
4000
-8.00
3000
-16.00
-24.00
2000
-32.00
1000
-40.00
600 @ 650 Sec 1 (2 Rings ... 180 Ammico Contracting Co. W.L.L.
Output Version 2016.1.21797.15047
-8.00 0.00 8.00 16.00 24.00 32.00 40.00 48.00 56.00 64.00 72.00 80.00 88.00 96.00 [kN/m]
16.00
2800
8.00
2400
0.00
2000
-8.00
1600
-16.00
1200
-24.00
800
-32.00
400
-40.00
600 @ 650 Sec 1 (2 Rings ... 180 Ammico Contracting Co. W.L.L.
Project description : 600 @ 650 Sec 1 (2 Rings) Rev 1 Output Version 2016.1.21797.15047
User name : Ammico Contracting Co. W.L.L. Step : 140
Project filename : 600 @ 650 Sec 1 (2 Rings) Rev 1 Date : 6/5/2017
Output : Calculation results, Fixed-end anchor, Final Ex [Phase_7] (25/140), Table of fixed-end anchors Page : 1
Chart 1
Curve 1
5
4
Msf []
0
0 100 200 300 400
Step []
600 @ 650 Sec 1 (2 Rings ... 380 Ammico Contracting Co. W.L.L.
SECTION 2a
0.00 8.00 16.00 24.00 32.00 40.00 48.00 56.00 64.00 72.00 80.00 88.00 [m]
16.00
0.25
8.00
0.225
0.2
0.00
0.175
-8.00
0.15
-16.00 0.125
0.1
-24.00
0.075
-32.00 0.05
0.025
-40.00
0.00 8.00 16.00 24.00 32.00 40.00 48.00 56.00 64.00 72.00 80.00 88.00 [kN m/m]
16.00
5000
8.00
4500
4000
0.00
3500
-8.00
3000
-16.00 2500
2000
-24.00
1500
-32.00 1000
500
-40.00
0.00 8.00 16.00 24.00 32.00 40.00 48.00 56.00 64.00 72.00 80.00 88.00 [kN/m]
16.00
2500
8.00
2250
2000
0.00
1750
-8.00
1500
-16.00 1250
1000
-24.00
750
-32.00 500
250
-40.00
2.7
Chart 1
2.4
Curve 1
2.1
1.8
Msf []
1.5
1.2
0.9
0.6
0.3
0
0 20 40 60 80 100 120 140 160 180
Step []
-8.00 0.00 8.00 16.00 24.00 32.00 40.00 48.00 56.00 64.00 72.00 80.00 88.00 96.00 [m]
0.12
16.00
8.00
0.1
0.00
0.08
-8.00
0.06
-16.00
-24.00
0.04
-32.00
0.02
-40.00
-8.00 0.00 8.00 16.00 24.00 32.00 40.00 48.00 56.00 64.00 72.00 80.00 88.00 96.00 [kN m/m]
6000
16.00
8.00
5000
0.00
4000
-8.00
3000
-16.00
-24.00
2000
-32.00
1000
-40.00
-8.00 0.00 8.00 16.00 24.00 32.00 40.00 48.00 56.00 64.00 72.00 80.00 88.00 96.00 [kN/m]
16.00
2800
8.00
2400
0.00
2000
-8.00
1600
-16.00
1200
-24.00
800
-32.00
400
-40.00
2.7
Chart 1
2.4
Curve 1
2.1
1.8
Msf []
1.5
1.2
0.9
0.6
0.3
0
0 20 40 60 80 100 120 140 160 180
Step []
-8.00 0.00 8.00 16.00 24.00 32.00 40.00 48.00 56.00 64.00 72.00 80.00 88.00 96.00 [m]
1.2
16.00
8.00
1
0.00
0.8
-8.00
0.6
-16.00
-24.00
0.4
-32.00
0.2
-40.00
-8.00 0.00 8.00 16.00 24.00 32.00 40.00 48.00 56.00 64.00 72.00 80.00 88.00 96.00 [*103 kN m/m]
12
16.00
8.00
10
0.00
-8.00
6
-16.00
-24.00
4
-32.00
-40.00
0
-3
Bending moments M (scaled up 5.00*10 times)
-8.00 0.00 8.00 16.00 24.00 32.00 40.00 48.00 56.00 64.00 72.00 80.00 88.00 96.00 [kN/m]
6000
16.00
8.00
5000
0.00
4000
-8.00
3000
-16.00
-24.00
2000
-32.00
1000
-40.00
1.6
Chart 1
1.4 Curve 1
1.2
1
Msf []
0.8
0.6
0.4
0.2
0
0 20 40 60 80 100 120 140 160
Step []
Design Basis
Yield strength of steel, fy = 500 MPa Ref:2
Compressive strength of concrete, fcu = 40 MPa
Diameter of pile, D = 600 mm
Pile length, L = 14.00 m
Self-weight = 99.0 kN
Clear cover = 75.0 mm
Diameter of shear reinforcement = 10.0 mm
Diameter of main reinforcement = 20.0 mm
C/C Spacing of piless, s = 0.65 m
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Shear Reinforcement Design
Reinforced Concrete Circular Section
Shear Load (kN) 136.40 Concrete grade 40 Area of steel (mm2) 2827.4
Rebar no 9 Concrete Cover (mm) 75 Es (MPa) 200000.0
Main Bar dia (mm) 20 Moment (kNm) 227.66 Ec (Mpa) 26,587.0
Rebar Yield 500 Vertical load (kN) 98.96
Povided
Final 10 bars @ 150 mm spacing
Reference :
Clarke, J.L. and Birjandi, F.K. (2004). The behaviour of reinforced concrete circular sections in shear, The Structural Engineer, Vol.71, No.5, 73-81.
ACECOMS GEAR: RC Column Section Design Version: 3.0 (Rev. 0)
Project Information:
Title = Section 1
Client = Shaker
Organization = Ammico
Engineer = MN
Design Criteria
RC Column Section
Material
Calculations
Solution found
Design Basis
Yield strength of steel, fy = 500 MPa Ref:2
Compressive strength of concrete, fcu = 40 MPa
Diameter of pile, D = 600 mm
Pile length, L = 14.00 m
Self-weight = 99.0 kN
Clear cover = 75.0 mm
Diameter of shear reinforcement = 10.0 mm
Diameter of main reinforcement = 25.0 mm
C/C Spacing of piless, s = 0.65 m
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Shear Reinforcement Design
Reinforced Concrete Circular Section
Shear Load (kN) 136.79 Concrete grade 40 Area of steel (mm2) 4417.9
Rebar no 9 Concrete Cover (mm) 75 Es (MPa) 200000.0
Main Bar dia (mm) 25 Moment (kNm) 320.29 Ec (Mpa) 26,587.0
Rebar Yield 500 Vertical load (kN) 98.96
Povided
Final 10 bars @ 150 mm spacing
Reference :
Clarke, J.L. and Birjandi, F.K. (2004). The behaviour of reinforced concrete circular sections in shear, The Structural Engineer, Vol.71, No.5, 73-81.
ACECOMS GEAR: RC Column Section Design Version: 3.0 (Rev. 0)
Project Information:
Title = Section 2a
Client = Client1
Organization = Ammico
Engineer = MN
Design Criteria
RC Column Section
Material
Calculations
Solution found
Design Basis
Yield strength of steel, fy = 500 MPa Ref:2
Compressive strength of concrete, fcu = 40.0 MPa
Diameter of pile, D = 600 mm
Pile length, L = 14.00 m
Self-weight = 99.0 kN
Clear cover = 75 mm
Diameter of shear reinforcement = 10 mm
Diameter of main reinforcement = 20 mm
C/C Spacing of piless, s = 0.65 m
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Shear Reinforcement Design
Reinforced Concrete Circular Section
Shear Load (kN) 124.51 Concrete grade 40 Area of steel (mm2) 3927.0
Rebar no 8 Concrete Cover (mm) 75 Es (MPa) 200000.0
Main Bar dia (mm) 25 Moment (kNm) 268.13 Ec (Mpa) 26,587.0
Rebar Yield 500 Vertical load (kN) 98.96
Povided
Final 10 bars @ 150 mm spacing
Reference :
Clarke, J.L. and Birjandi, F.K. (2004). The behaviour of reinforced concrete circular sections in shear, The Structural Engineer, Vol.71, No.5, 73-81.
ACECOMS GEAR: RC Column Section Design Version: 3.0 (Rev. 0)
Project Information:
Title = Section 2b
Client = Client1
Organization = Ammico
Engineer = MN
Design Criteria
RC Column Section
Material
Calculations
Solution found
Design Basis
Yield strength of steel, fy = 500 MPa Ref:2
Compressive strength of concrete, fcu = 40 MPa
Diameter of pile, D = 900 mm
Pile length, L = 16.00 m
Self-weight = 254.5 kN
Clear cover = 75.0 mm
Diameter of shear reinforcement = 10.0 mm
Diameter of main reinforcement = 32.0 mm
C/C Spacing of piless, s = 0.95 m
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Sheet 8 of 9
Prepared by: M N
EXTENSION OF AMIRI DIWAN
Checked by: G D
Date 17-May-17
7T32
-4.00
Shoring Level
-8.00
7T32+7
T32
-12.00
7T32
-16.00
Ultimate Bending Moment Per Pile (kNm)
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Shear Reinforcement Design
Reinforced Concrete Circular Section
Shear Load (kN) 595.22 Concrete grade 40 Area of steel (mm2) 11259.5
Rebar no 14 Concrete Cover (mm) 75 Es (MPa) 200000.0
Main Bar dia (mm) 32 Moment (kNm) 1397.21 Ec (Mpa) 26,587.0
Rebar Yield 500 Vertical load (kN) 254.47
Povided
Final 16 bars @ 250 mm spacing
Reference :
Clarke, J.L. and Birjandi, F.K. (2004). The behaviour of reinforced concrete circular sections in shear, The Structural Engineer, Vol.71, No.5, 73-81.
ACECOMS GEAR: RC Column Section Design Version: 3.0 (Rev. 0)
Project Information:
Client = Client1
Organization = Ammico
Engineer = MN
Design Criteria
RC Column Section
Material
Calculations
Solution found
Project Information:
Client = Client1
Organization = Ammico
Engineer = MN
Design Criteria
RC Column Section
Material
Calculations
Stress in Rebars:
Result Summary:
Analysis Results
Design Results
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Sheet 2 of 3
Prepared by: M N
EXTENSION OF AMIRI DIWAN
Checked by: G D
Date 21-May-17
References
Provided shear rebar at VF = 1nos T10@200mm stirrups Ref:5
Provided shear rebar at HF = 1nos T10@200mm stirrups Ref:5
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Sheet 3 of 3
Prepared by: A A
EXTENSION OF AMIRI DIWAN
Checked by: G D
Date 21-May-17
= 147 kN
Width of waller = 600 mm
Effective depth , d = 530 mm
Shear stirrups spacing = 200 mm
Applied shear stress in concrete, Vs = Vu/bd Ref. 4
/ /
100 400 1
Shear resistance of concrete for C25 = 0.79 Ref. 4
where
/ (1/3)
= (0.223402144255274)
= 0.61 < 3
< 3
By Date09-Apr-17 Chd
Max:
Max: -31.399
-31.399 kN-m
kN-m
Max: -40.019 kN-mkN-m
15.699 Max: -31.398 kN-m
14.354 kN-m
8.336
Max: -34.815 kN-m
kN-m 15.700 kN-m
Max: -40.015 kN-m
14.616 kN-m 8.337 kN-m
Max: -27.459 kN-m Max: -34.816 kN-m
X
Z Max: 28.687 kN-m Max: 25.479 kN-m
Print Time/Date: 07/06/2017 14:22 STAAD.Pro V8i (SELECTseries 6) 20.07.11.70 Print Run 1 of 1
Job No Sheet No Rev
1
Part
Software licensed to Ammico
Job Title Ref
By Date09-Apr-17 Chd
Max: 94.033 kN
Max: 95.306 kN
1.363 kN 0 kN
Max: 96.3962.635
kN kN Max: -92.671 kN -1.362
Max: -94.033 kN kN
5.268 kN -5.090 kN
Y 5.088 kN -5.269 kN
X Max: 97.234 kN
Max: -97.759 kN
Z 4.563 kN -5.088 kN
Max: -97.232 kN
Max: 96.395 kN
3.725 kN -4.562 kN
Max: -96.397 kN
Max: 95.306 kN -3.726
2.635 kN Max: -95.305 kNkN Load 1 : Shear Z
Force - kN
-2.634 kN
Print Time/Date: 07/06/2017 14:24 STAAD.Pro V8i (SELECTseries 6) 20.07.11.70 Print Run 1 of 1
Sheet 1 of 4
Prepared by: M N
EXTENSION OF AMIRI DIWAN
Checked by: G D
Date 21-May-17
Analysis & Design of Barcing Beam 2 (Ring) Section 1 References
Ref:1- PLAXIS ANALYSIS RESULTS
Ref:2- STAAD.PRO ANALYSIS RESULTS
Ref:3- BS 8110-1:1997
Ref:4- ACECOM GEAR
Ref:5- SHEAR CALCULATION SHEETS
Analysis Results
Design Results
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Sheet 2 of 4
Prepared by: M N
EXTENSION OF AMIRI DIWAN
Checked by: G D
Date 21-May-17
References
Required shear rebar at VF = 1nos T16@175mm stirrups Ref:5
Required shear rebar on HF = 1nos T16@175mm stirrups Ref:5
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Sheet 3 of 4
Prepared by: A A
EXTENSION OF AMIRI DIWAN
Checked by: G D
Date 21-May-17
= 256 kN
Width of waller = 600 mm
Effective depth , d = 226 mm
Shear stirrups spacing = 175 mm
Applied shear stress in concrete, Vs = Vu/bd Ref. 4
/ /
100 400 1
Shear resistance of concrete for C25 = 0.79 Ref. 4
where
/ (1/3)
= (0.523598775598299)
= 0.81 < 3
< 3
= 16 kN
Width of waller = 300 mm
Effective depth , d = 493 mm
Shear stirrups spacing = 175 mm
Applied shear stress in concrete, Vs = Vu/bd Ref. 4
/ /
100 400 1
Shear resistance of concrete for C25 = 0.79 Ref. 4
where
/ (1/3)
= (0.174532925199433)
= 0.56 < 3
< 3
By Date09-Apr-17 Chd
Print Time/Date: 07/06/2017 14:27 STAAD.Pro V8i (SELECTseries 6) 20.07.11.70 Print Run 1 of 1
Job No Sheet No Rev
1
Part
Software licensed to Ammico
Job Title Ref
By Date09-Apr-17 Chd
Max: 163.937 kN
Max: 166.100 kN Max: 161.610 kN
Y 8.683 kN -8.987 kN
X Max: -170.291 kN
Z Max: 169.390 kN
7.782 kN -8.682 kN
Max: -169.394 kN
Max: -166.104 kN kN
-6.353
Max: 166.1024.493
kN kN Load 1 : Shear Z : Displacement
Force - kN
-4.495 kN
Print Time/Date: 07/06/2017 14:28 STAAD.Pro V8i (SELECTseries 6) 20.07.11.70 Print Run 1 of 1
Sheet 1 of 3
Prepared by: M N
EXTENSION OF AMIRI DIWAN
Checked by: G D
Date 21-May-17
Analysis & Design of Bracing Beam (Capping) for Section 2a & 2b References
Ref:1- PLAXIS ANALYSIS RESULTS
Ref:2- STAAD.PRO ANALYSIS RESULTS
Ref:3- BS 8110-1:1997
Ref:4- ACECOM GEAR
Ref:5- SHEAR CALCULATION SHEETS
Analysis Results
Design Results
Main Rebar at vertical face on shoring side = 7 T 20 0.61 % Ref:4
Required rebar on vertical face at exc. side = 4 T 20 0.35 % Ref:4
Provided rebar on vertical face at exc. side = 7 T 20 0.61 % Ref:4
Main rebar on top face of ring beam = 4 T 16 0.22 % (min rebar) Ref:4
Main rebar on bottom face of ring beam = 4 T 16 0.22 % (min rebar) Ref:4
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Sheet 2 of 3
Prepared by: M N
EXTENSION OF AMIRI DIWAN
Checked by: G D
Date 21-May-17
References
Provided shear rebar at VF = 1nos T16@200mm stirrups Ref:5
Provided shear rebar at HF = 1nos T16@200mm stirrups Ref:5
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Sheet 3 of 3
Prepared by: A A
EXTENSION OF AMIRI DIWAN
Checked by: G D
Date 21-May-17
= 520 kN
Width of waller = 600 mm
Effective depth , d = 524 mm
Shear stirrups spacing = 200 mm
Applied shear stress in concrete, Vs = Vu/bd Ref. 4
/ /
100 400 1
Shear resistance of concrete for C25 = 0.79 Ref. 4
where
/ (1/3)
= (0.610865238198015)
= 0.85 < 3
< 3
Required area of shear reinforcement, Asv (Vs- 0.4) x Sv x bv /(0.87 x fy) Ref. 4
By Date09-Apr-17 Chd
215.758
Max: 215.758
kN-m kN-m -97.773 kN-m
0 kN-m
Load 1 : Bending Y
Moment - kN-m
Print Time/Date: 21/05/2017 14:54 STAAD.Pro V8i (SELECTseries 6) 20.07.11.70 Print Run 1 of 1
Job No Sheet No Rev
1
Part
Software licensed to Ammico
Job Title Ref
By Date09-Apr-17 Chd
X
Z
Print Time/Date: 21/05/2017 14:54 STAAD.Pro V8i (SELECTseries 6) 20.07.11.70 Print Run 1 of 1
ANNEXURE - 7
DESIGN OF STRUT
= 0.89
Outstand flange element, b = wf - t Ref. 2
2
= 307.4 - 12
2
= 147.7 mm
Flanges Web
Plastic = 9 = 8.035 Plastic = 80 = 71.42
Compact = 10 = 8.928 Compact = 100 = 89.28
Sem-compact = 15 = 13.39 Sem-compact = 120 = 107.1
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Sheet 2 of 2
Prepared by: M N
EXTENSION OF AMIRIR DIWAN
Checked by: A A
Date 12-May-15
Hence, the section can be classified into Class 1: Plastic as per BS: 5950 -1 2000
Considering strut element as "pinned" at both ends, effective length shall be equal to length of strut.
Both sides of the strut are supported at the capping beam installed at the shoring wall.
Effective length of strut, Le = 5.6 m
Slenderness ratio in x-direction, =Le/r = 42.0
Slenderness ratio in x-direction, =Le/r = 73.0
Buckling strength in x-direction, pcx = 321 MPa Ref: 2
Buckling strength in y-direction, pcy = 255 MPa Ref: 2
Buckling capacity in x-direction, Pbx = 4815 > 1835 kN Ref: 2
Buckling capacity in x-direction, Pby = 3825 > 1835 kN Ref: 2
Moment due to self-weight, Mx = 4.5 kNm
Shear due to self-weight, Fv = 3.2 kN
Check for Shear Reference
Shear Area, Av = Dt Ref. 2
= 314.5x12
= 3774.00 mm2
Shear Capacity, Pv = 0.6pyAv Ref. 2
= 781.2 > 3.24 kN
Max. shear force exerted in the strut, Fv = 3.24 < 781.2 kN O.K
Check for Moment
Type of shear
0.6 Pv = 468.7 > 3.241 kN
"Low Shear" Ref. 2
Moment Capacity, Mc = pyS Ref. 2
= 345 x 1958000
= 675510000 Nmm
= 675.5 kNm
Max. moment exerted in the strut = 4.54 < 675.5 kNm
Fc Mx My
+ + 1
Aeffpy Mcx Mcy
0.355 + 0.01 + 0 = 0.365 1 OK
Hence, the Strut UC: 356x406x287 will be used
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Job No Sheet No Rev
1
Part
Software licensed to Ammico
Job Title Ref
By Date09-Apr-17 Chd
X = FREE
Y = 0.000 kN X = FREE
Z = FREE Y = 0.000 kN
MX = FREE Z = FREE
MY = -18.134 kN-m MX = FREE
X = FREE
MZ = FREE MY = 18.138 kN-m
Y = 0.000 kN
MZ = FREE
Z = FREE X = FREE
MX = FREE Y = 0.000 kN
MY = -43.779 kN-m Z = FREE
MZ = FREE MX = FREE
MY = 43.781 kN-m
Y X = FREE
Y = 0.000 kN
MZ = FREE
X Z = FREE X = FREE
Z MX = FREE
MY = -9.046 kN-m
Y = 0.000 kN
Z = FREE
MZ = FREE MX = FREE
X = -611.937 kN
MY = 9.045 kN-m
Y = 0.000 kN X = 1188.816 kN
MZ = FREE
Z = -1066.786 kN Y = 0.000 kN
MX = FREE Z = 314.982 kN
MY = FREE MX = FREE
MZ = FREE MY = FREE Load 1
MZ = FREE
Print Time/Date: 07/06/2017 14:28 STAAD.Pro V8i (SELECTseries 6) 20.07.11.70 Print Run 1 of 1
Sheet 1 of 2
Prepared by: M N
EXTENSION OF AMIRIR DIWAN
Checked by: A A
Date 21-May-17
Strut Design for Section 2a & 2b Reference
Ref 1 - Project Specification
Ref 2 - BS 5950-1:2000
Ref 3 - PLAXIS Model
A) Steel Beam
Beam Type considered = UC: 305x305x118 Ref 1
Grade of Steel = S355 grade
Length of Beam = 5.6 m
Overll depth of beam, D = 314.5 mm
Flange width, wf = 307.4 mm
Thickness of flange, T = 18.7 mm
Depth of web, d = 277.1 mm
Thickness of web, t = 12.0 mm
Plastic Modulus, Sx = 1958000 mm3
Plastic Modulus, Sy = 895000 mm3
Elastic Modulus, Zx = 1760x103 mm3
Elastic Modulus, Zy = 589x103 mm3
Area of section, Ag = 15000.0 mm2
Radius of gyration, rx = 136.0 mm
Radius of gyration, ry = 77.7 mm
Design strength, p y = 345 MPa Ref. 2
Analysis Details
Maximum axial load for strut 1, 2 & 3 = 649.1 kN Ref. 2
Ultimate axial load = 973.7 kN
Type of Section
Parameter, = Ref. 2
= 0.89
Outstand flange element, b = wf - t Ref. 2
2
= 307.4 - 12
2
= 147.7 mm
Flanges Web
Plastic = 9 = 8.035 Plastic = 80 = 71.42
Compact = 10 = 8.928 Compact = 100 = 89.28
Sem-compact = 15 = 13.39 Sem-compact = 120 = 107.1
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Sheet 2 of 2
Prepared by: M N
EXTENSION OF AMIRIR DIWAN
Checked by: A A
Date 12-May-15
Hence, the section can be classified into Class 1: Plastic as per BS: 5950 -1 2000
Considering strut element as "pinned" at both ends, effective length shall be equal to length of strut.
Both sides of the strut are supported at the capping beam installed at the shoring wall.
Effective length of strut, Le = 5.6 m
Slenderness ratio in x-direction, =Le/r = 42.0
Slenderness ratio in x-direction, =Le/r = 73.0
Buckling strength in x-direction, pcx = 321 MPa Ref: 2
Buckling strength in y-direction, pcy = 255 MPa Ref: 2
Buckling capacity in x-direction, Pbx = 4815 > 974 kN Ref: 2
Buckling capacity in x-direction, Pby = 3825 > 974 kN Ref: 2
Moment due to self-weight, Mx = 4.5 kNm
Shear due to self-weight, Fv = 3.2 kN
Check for Shear Reference
Shear Area, Av = Dt Ref. 2
= 314.5x12
= 3774.00 mm2
Shear Capacity, Pv = 0.6pyAv Ref. 2
= 781.2 > 3.24 kN
Max. shear force exerted in the strut, Fv = 3.2 < 781.2 kN O.K
Check for Moment
Type of shear
0.6 Pv = 468.7 > 3.241 kN
"Low Shear" Ref. 2
Moment Capacity, Mc = pyS Ref. 2
= 345 x 1958000
= 675510000 Nmm
= 675.5 kNm
Max. moment exerted in the strut = 4.54 < 675.5 kNm
Fc Mx My
+ + 1
Aeffpy Mcx Mcy
0.188 + 0.01 + 0 = 0.198 1 OK
Hence, the Strut UC: 356x406x287 will be used
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Job No Sheet No Rev
1
Part
Software licensed to Ammico
Job Title Ref
By Date09-Apr-17 Chd
X = 0.000 kN
Y = 0.000 kN
Z = -602.862 kN
MX = FREE
X = 0.000 kN MY = FREE
Y = 0.000 kN MZ = FREE
Z = -528.841 kN
MX = FREE
Y X = 0.000 kN MY = FREE
X Y = 0.000 kN
Z = -649.129 kN
MZ = FREE
Z MX = FREE
MY = FREE
MZ = FREE
Load 1
Print Time/Date: 21/05/2017 14:56 STAAD.Pro V8i (SELECTseries 6) 20.07.11.70 Print Run 1 of 1
ANNEXURE - 8
CAPPING BEAM DESIGN
Capping beam
Retained Soil
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Sheet 2 of 2
Prepared by: M N
EXTENSION OF AMIRIR DIWAN
Checked by: G D
Date 21-May-17
References
Shear force , SF1 = wxl /2 kN
= 1.83 kN
Capping beam design
Based on the analyses results, minimum steel is required to resist the said forces
4T20 rebar will be provided on the each vertical and horizontal face of the capping beam.
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
ANNEXURE - 9
STRUCTURAL DETAILS OF SHORING SYSTEM
Ground Level Ground Level Ground Level Ground Level THIS AREA
+11.0m QNHD +11.0m QNHD +11.0m QNHD +11.0m QNHD
0.6m
0.6m
0.6m
0.6m
1st Ring Beam Capping Beam Capping Beam Capping Beam
(600x600mm) (600x600mm) (600x600mm) (900x600mm)
A A B B C C D D
L=12.0 m
L=12.0 m
L=12.0 m
L=12.0 m
10 T20
7 T 32
8 T 25
9 T20
Spirals Spirals
T10 @150 T10 @150
14.0m
14.0m
14.0m
Main Bar Main Bar
8T25 10T20
+3.25m QNHD
LEGENDS
16.0m
Spirals
T10 @150 600mm Pile Type "A"
E E
DOCUMENT REVIEW STATUS
L=6.0 m
7 T 32
STATUS A: APPROVED
1.60m
STATUS D: COMMENTED AND RESUBMIT
Main bar
1.25m
7T32
1.0m
1.0m
Main Bar
7T32
L=2.9 m
L=3.2 m
L=2.9 m
L=5.5 m
10 T20
8 T 25
7 T 32
9 T20
CLIENT:
-2.75m QNHD
Toe Level Toe Level Toe Level
-3.0m QNHD -3.0m QNHD -3.0m QNHD
0.1m
0.1m
0.1m
0.60m 0.60m 0.60m
CONSULTANT:
SECTION -1a & 1b SECTION -2a SECTION -2b
(Pile Type A) (Pile Type B) (Pile Type C)
75mm
75mm 75mm Toe Level
-5.0m QNHD
LEAD ARCHITECT:
0.1m
0.90m
MAIN BAR MAIN BAR MAIN BAR SECTION -3
SPIRAL
(9T20) SPIRAL (8T25) SPIRAL (10T20) UNii Engineering Consultancy
(T10@150) (T10@150) (T10@150) (Pile Type D) UAE-QATAR-KSA
P.O.Box : 11490 - Doha, Qatar
600mm 600mm 600mm Tel:+974 4414 6652, Fax:+974 4414 6653, Qatar:+974 6 6499010
SECTION A-A SECTION B-B SECTION C-C
75mm
MAIN CONTRACTOR:
Contraco W.L.L
Construction Company
MAIN BAR Address: Haloul st, Al Mamoura, Doha, Qatar
SPIRAL (7T32) Phone:+974 4410 9333
(T16@250)
SHORING SUB-CONTRACTOR:
900mm
4T20 3+3T20
SECTION D-D Ammico Contracting Co. W.L.L.
2nd Ring Beam P.O. BOX :14330
4T20 (300x600mm) DOHA - QATAR
Capping Beam TEL. +974 4886581 FAX. +974 4886507
Pile 600mm 75mm
4T16 (600x600mm)
3T16 Shear Reinforcement
4T20 Shear Reinforcement (T16@175mm c/c) PROJECT NAME:
(T10@200mm c/c) MAIN BAR
5T25
4T16 (7T32)
Capping Beam 4T20 EXTENSION OF AMIRI DIWAN BUILDING
1st Ring Beam 1+1T20
(600x600mm)
(600x600mm) Shear Reinforcement
Shear Reinforcement (T16@200mm c/c)
DOHA, QATAR
5T25 SPIRAL MAIN BAR
4T16 (T10@200mm c/c) (T16@250) (7T32)
4T16
3T16 TITLE
900mm
2nd Ring Beam Detail for SECTION E-E
SHORING PILES COORDINATES &
Capping Beam Detail for (Section-1)