Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
building code and the installation requirements are contained within the referenced
edition of NFPA 14, Standard for the Installation of Standpipe and Hose Systems,
there is often disagreement between the responsible design professional, the fire
protection contractor, and the Authority Having Jurisdiction (AHJ) on the proper
design and installation of the system. This article will attempt to simplify the
requirements for these systems by addressing the following issues:
When are standpipes required and what are the installation requirements?
When is a standpipe system required?
What type of standpipe system is required?
Where are the required hose outlets located?
What is the required pressure at the hose outlet(s)?
What is the required flow rate of the system?
What are the requirements for the fire department connection (FDC)?
Which outlets are flowed in a hydraulic calculation?
How is the fire department apparatus defined and used in a hydraulic calculation?
Required Installation and Installation Requirements
During the design of a building two questions must be answered to determine the
requirements for a standpipe system:
Other uses for which the IBC requires a standpipe system are:
A building that has an assembly occupancy with an occupant load exceeding 1,000
Covered and open mall buildings
Buildings that contain a stage greater than 1,000 ft2
Underground buildings
Buildings with a helistop and heliports
Marinas and boatyards
Rooftop gardens and landscaped roofs
If the building does not meet any of the eight criteria listed above, a
standpipe system is not required by the IBC.
In most buildings the standpipe system can be designed as a Class I system due the
provision of Exception I to Section 905.3.1 of the IBC for buildings protected
throughout by automatic sprinkler systems. NFPA 14 permits Class I standpipe
systems to be manual wet systems for buildings not classified as a high-
rise, therefore all further discussions in this article will be based on the requirements
for a Class I wet manual standpipe system.
The maximum flow rate is 1,000 gpm for buildings protected throughout with an
automatic sprinkler system and 1,250 gpm for buildings that are not. For a Class I
horizontal standpipe system with three or more connections on any floor the
minimum flow rate for the most hydraulically demanding horizontal standpipe is
750 gpm.
As with the standpipe system itself the requirements for the installation of the fire
department connection (FDC) are contained in the IBC and NFPA 14. Section 912 of
the IBC contains requirements on the location, inlet fire hose threads, access,
and signage for the FDC. The main issue to remember with these requirements
is that the final location of and access to the FDC shall be approved by the fire chief,
which may not be the same individual as the fire code official mentioned previously.
Section 7.12 of NFPA 14 contains the installation requirements for the FDC. The most
commonly misunderstood requirement during the system design and installation by
both the designers and the local fire department is the requirement under section
7.12.3 that the FDC be sized based on the standpipe system demand and that one 2-
inch inlet be provided for every 250 gallons per minute of design flow. Therefore,
a standpipe system with a design flow of 1,000 gallons per minute is required to
have an FDC with four 2- inch inlets.
The author once had a local fire chief state that the designed four 2- inch inlets
were not correct and it should be replaced by a two 2- inch inlet. When the author
explained that the four 2- inch inlet FDC was required by code, the fire chief
responded that his firefighters would not know which two inlets to attach to, as their
standard fire ground operations were to provide two supply lines to the FDC from
the pumper. After a discussion on the system design and operation, the chief
understood the requirement for the four inlets and planned to modify the
departments standard operating procedure and training for supporting buildings
with standpipe systems.
Which
Outlets are Flowed in a Hydraulic Calculation
The requirements for completing a hydraulic calculation for a standpipe system are
contained in Section 7.10.1.2 of NFPA 14. The procedure is similar to the calculation
method for a sprinkler system. To perform the system hydraulic calculation the
required flow and pressure at the most hydraulically remote hose outlet is
determined and the demand is calculated back to the city supply accounting for
flows at additional standpipes, elevation changes, and friction loss through the
system pipes and fittings, and fixed or mobile pumps.
As stated above, a Class I standpipe system is required to flow 500 gpm at the most
hydraulically remote standpipe through the two most remote outlets. An additional
250 gpm is added at the most hydraulically remote outlet for each additional
standpipe in the building, to a maximum of 1,000 gpm for a sprinklered building. If
the standpipe calculated system demand is less than the supply, the design is
acceptable.
The pump on the fire department apparatus is added to the hydraulic calculation
after the fire department connection when calculating the system demand as stated
above. At the fire department connection the flow is calculated back to the
apparatus through the connecting hoses to the apparatus pump. The local fire
department must be contacted at this point to determine their standard operating
procedure for supporting a building standpipe system. Typical operations are to
supply the fire department connection with 2- inch lines or 3-inch lines with 2-
couplings, although some departments are known to use large diameter hose with
Stortz connections. One method of determining the friction loss in fire hose for 2-
inch rubber lined hose is calculated as FL = 2Q2L where:
FL = Friction Loss
And the friction loss in 3-inch rubber lined hose with 2- couplings is calculated as
FL = 0.8Q2L
Assuming the local fire department standard operating procedure was to connect to
the FDC with 100 feet of 2- inch line to each inlet, the friction loss in each line
would be 2(2.5)2(1) or 12.5 psi.
These losses can be included in the hydraulic calculation as fixed losses between the
fire department connection and the apparatus pump. Other methods of calculating
friction loss in hoses are available and the designer should verify which method is
acceptable with the Authority Having Jurisdiction.
Conclusion
In determining the requirements for and designing a standpipe system for a building
the responsible engineer needs to know the requirements of both the local building
code and referenced NFPA standard. In addition to these documents the responsible
engineer needs to consult and work with the fire protection contractor and AHJs to
ensure that all parties understand the design and installation requirements and that
the design supports the responding fire department operational tactics.