Sei sulla pagina 1di 8

Concrete Solutions Grantham et al.

(Eds)
2014 Taylor & Francis Group, London, ISBN 978-1-138-02708-4

Evaluation and repair of fire damage to the concrete structures


of a high-rise building

Chuanming Zhai
C+E Center for Engineering Research Test and Appraisal, Beijing, China

Yu Lou
China Electronics Engineering Design Institute, Beijing, China

Yufei Guo
C+E Center for Engineering Research Test and Appraisal, Beijing, China

Yan Lu
School of Civil Engineering, Tianjin University, Tianjin, China

ABSTRACT: Structural fire design and fire prevention management face new challenges as more high-rise
buildings are constructed. The evaluation of fire damage to such structures can help formulate efficient structural
fire design and fire prevention management. The procedure for evaluating fire damage to concrete structures was
discussed using a burnt high-rise building as an example. Such procedures included an emergency investigation
of the fire site, an estimation of fire temperature, the initial division of floors and areas based on the visual damage
they showed and the inspection of burnt structural members. The concrete structures were evaluated according
to the degree of fire damage they received as well as their characteristics. Lastly, rehabilitation. measures for the
concrete structures were proposed based on fire damage grades.

1 INTRODUCTION 29-05:2007; EN 1992-1-2:2004). Several Chinese


researchers also made remarkable achievements in
Numerous high-rise buildings were constructed in designing fire-resistant structures. Among them are
China during the past decade as a result of the rapid Li (Li G. et al. 2006), who summarized the calculation
development of the economy of the country. A number methods for fire-resistant designs of steel and steel
of these structures even became landmarks in several concrete composite structures; and Han (Han et al.
large and medium-sized cities. These buildings devel- 2012), who systematically introduced the principles
oped higher chances of catching fire because of their for fire-resistant designs of steelconcrete compos-
complex structural designs and large space utiliza- ite structures in terms of fire-resistant performance,
tion. Moreover, the scale, damage, and economic loss design methods, and protection measures. The level of
caused by fires in high-rise buildings are more serious structural fire protection has significantly improved
than those observed in ordinary buildings. For exam- in recent years because of the rapid development
ple, the 9/11 attacks on the North and South Towers of computer simulation technologies and the gradual
of the World Trade Center in the United States (which advancement of structural fire design methods.
both had more than 100 floors) caused huge explosions However, the current theoretical system for inspect-
and fires which led to the meltdown and collapse of ing and evaluating fire damage in building structures
the two buildings. This event resulted in a significant remains imperfect. An explicit standard for selecting
number of casualties, tremendous property losses, and an evaluation index and for developing an evalua-
adverse social impact. tion system for structural damage caused by fires is
Several research institutions abroad have studied still not available despite the recent advancements in
fire resistance of building structures over the past fire damage inspection techniques and methods. Most
years. These studies mainly focused on the devel- existing evaluation methods are qualitative instead
opment process of fires in buildings, the structural of quantitative (Li M., 2005). A number of newly
behavior of elements in fires, structural fire design developed mathematical models have been recently
methods, and evaluating fire damage to structures adopted to establish an evaluation system for fire dam-
(Fan & Lv 1999; Li G. et al. 2008). A number of age to concrete structures. Li (Li M. et al. 2008)
corresponding standards and codes were published proposed a comprehensive evaluation model for fire
along with these studies (GB 50016:2012; ASCE damage to high-concrete structures based on fuzzy

485
mathematics, which considered strength loss, durabil-
ity damage, spalling degree, and crack width as evalu-
ation indicators. Fang (Fang et al. 2010) established
a fire damage evaluation model for concrete struc-
tures using the projection pursuit evaluation method
and a genetic algorithm, with evaluation indicators
based on the model proposed by Li (Li M. et al. 2008).
Wang (Wang et al. 2008) considered strength loss, anti-
permeability loss, spalling degree, and crack width as
evaluation indicators; in addition, Wang established
the matter element evaluation model for burnt con-
crete structures. Although the aforementioned studies
contribute to the development of an evaluation theory
for burnt concrete structures, such quantitative meth-
ods exhibit several disadvantages, which are described Figure 1. The south side of the high-rise building.
Downloaded by [Nanyang Technological University (NTU)] at 00:14 17 July 2017

as follows. First, the fixed values of the evaluation


indexes for the entire structure are difficult to deter- special materials, such as the glass curtain walls in
mine. Second, the weight of the evaluation indexes and the north and south, and the titanium zinc plates in
the classification criteria for structural damage grades the east and west. The melting point of titanium zinc
are influenced by human factors. Therefore, qualita- plates is 418 C. Moreover, the inner parts of the plates
tive and empirical methods are primarily used in the were made of extruded sheets and ethylene propylene
actual evaluation of structural damage, and quantita- diene monomer rubber, which are flammable, ther-
tive calculation methods serve as supplements. The mally insulated, and waterproof materials. The fire
evaluation of fire damage to concrete structures of a melted the titanium zinc plates and ignited the mate-
high-rise building presented in this paper can serve as rials beneath them, which produced huge amounts of
a guide in inspecting burnt concrete structures. toxic fumes. Third, the fire spread in an unusual direc-
tion. The fire was ignited at the top-middle part of
the main building near the west. The combustion of
2 OVERVIEW OF THE HIGH-RISE BUILDING the burning materials of the curtain wall decoration
AND THE FIRE INCIDENT spread the fire in a vertical direction, thus causing it
to spread rapidly and in a reverse manner (from top to
A high-rise building, constructed in 2004, is located bottom and from outside to inside). Given these char-
in the Beijing central business district. The building is acteristics, this fire incident was classified as rare in
159.68 m high, and its architectural area is 103,648 m2 . the history of the nation.
It has 30 floors and 2 additional underground floors.
The building (Figure 1) consists of a main building and
a skirt building. The main building uses a frame shear
3 PROCEDURE FOR INSPECTION AND
wall system composed of a huge steel-support cross-
EVALUATION OF FIRE DAMAGE TO
hybrid structure which is divided into the north and
CONCRETE STRUCTURES
south wings. Both wings are connected by a cylindri-
cal shear wall to the east side, thus forming an atrium.
The flowchart of the inspection and evaluation proce-
The huge steel-support cross-hybrid structure is placed
dure for the burnt concrete structures of the aforeme-
at the west side. The skirt building has reinforced
tioned high-rise building is shown in Figure 2.
concrete structures. The entire roofs of the main and
Several professionals conducted an emergency
skirt buildings are covered with large-span steel struc-
investigation and damaged zone division of the high-
tures, and thus, the space underneath them becomes
rise building after the fire incident. Their main objec-
the indoor environment. The outer decoration of the
tives were as follows.
curtain wall of the building comprises titanium zinc
plates, glass, and composite aluminum plates. (1) Investigating the site. Each floor and room in the
In February 2009, the building caught fire after building was investigated, and all zones were doc-
its main structure was completed. The fire spread umented through photographs and videos. Fire
to 21,333 m2 of the building, and the total burned damage to the structures and decorations of the
area was 8,490 m2 . The fire lasted for approximately building were observed. The burned range, burned
six hours. It was caused by high-temperature fire- area, fire extinguishing materials, fuel types, and
work sparks which ignited the combustible materials their placements were ascertained. The danger
on the roof of the main building. The fire rapidly zones with falling debris were marked. The burned
spread to the outer wall decoration and to the lower local zone of the building is shown in Figure 3.
floors. This particular fire incident demonstrated sev- (2) Determining the temperature of the fire. The
eral characteristics. First, the high-rise building had duration of the fire was different in each floor,
special structures, such as its large scale, complex lay- room, and structural component of the high-rise
out, and multiple tortuous internal channels. Second, building. Therefore, the possible maximum tem-
the curtain wall of the building was decorated with perature and the duration of the fire could be

486
Downloaded by [Nanyang Technological University (NTU)] at 00:14 17 July 2017

Figure 3. The damaged structures inside the building after


the fire incident. a. The steel bars of the concrete roof slab
were exposed. b. Cracks and map cracks were formed on the
surface of the column. c. The concrete walls were spalled. d.
The elevator doors were severely deformed.

Table 1. The characteristics of each zone based on the


degree of damage.
Figure 2. The inspection and evaluation procedure for the Zone Zone characteristics
fire damage to the concrete structural components. division

comprehensively analyzed and determined based Undamaged The concrete structures were not damaged by
on apparent damage (surface color, cracking zone the fire, and only the exterior of local walls
and spalling), field-combustible residues, and the (Zone A) fell off. The surface of the structural
standard temperaturetime curve set by the Inter- components was blackened or had no
national Standardization Organization (ISO). The obvious indicator of burns. The maximum
ISO 834 curve (ISO 843:2002), which is used temperature reached less than 300 C.
frequently in China, is represented as follows: Slightly The structures around the elevator were not
damaged damaged by the fire. Spalled concrete covers
zone were only observed on local walls. The steel
(Zone B) bars were slightly exposed. The concrete had
where T ( C) is the average furnace air temperature a pink color, and the maximum temperature
at t minutes after the fire, and T0 ( C) is the initial ranged from 300 C to 600 C.
temperature in the testing furnace. Seriously Fire damage near the elevator was serious,
damaged and the elevator doors were severely deformed
zone (Fig. 3.d). Cracks were observed on the slab
3.1 Fire site emergency investigation and damaged (Zone C) bottom and beam surface, and the steel bars
zone division in a large area of the concrete roof slab were
exposed. The concrete cover of wall spalled,
The maximum temperature of the fire was at approxi- and the masonry burned down. The color of
mately 1200 C, which was calculated based on Eq. (1). the concrete ranged from whitish gray to light
yellow. The maximum temperature reached
(3) Dividing the building zones according to the more than 600 C.
degree of damage. The zones of each floor in
the building were divided into three levels, which
were preliminarily based on the results of the are shown in Table 1. The division according to the
emergency investigation, the fire damage to the degree of damage is shown in Figure 4, with the
inner structures, and the maximum temperature of 10th floor (where the cylindrical shear wall was
the fire. The primary characteristics of each level located) as the main zone.

487
determine accurately by merely observing change in
color because the interior and exterior of the con-
crete can reach different maximum temperature levels.
Therefore, the use of devices and tests to measure con-
crete strength, rather than a simple observation of its
appearance, is necessary. The rebound method and the
drilling core sampling method were used in this study
to determine concrete residual strength.
The inspection results show that the main struc-
tural components (beams, plates, columns, and walls)
exhibited discoloration, crazing, cracking, and hollow-
ing in different degrees; moreover, a few of these com-
ponents demonstrated concrete spalling and reinforce-
ment damage (Fig. 3.a). The strength of all undamaged
concrete structural components satisfied the original
Downloaded by [Nanyang Technological University (NTU)] at 00:14 17 July 2017

design requirements, and the surface strength of the


damaged structures was reduced to different degrees.
Figure 4. The main zone division of the 10th floor according The strength loss ratio of the seriously damaged struc-
to the degree of damage. tural components was between 13.8% and 31.1%. The
damage depth of all burnt concrete structural compo-
The preliminary division of the damaged areas was nents was between 5 mm and 100 mm, although in a
finished after the emergency investigation. The seri- few of them, damage was beyond the thickness of their
ously damaged zones were found to be the floors above protective cover.
the 9th floor because the water cannons could only The rebound hammer test combined with core sam-
reach a height of approximately 55 m, which was pling test were used to test the concrete strength for
located near the 9th floor of the building. This situ- most burnt structural members of the building. And
ation caused the fire to spread to the substructures of the test results for the components of the 10th floor
the building. Based on the results of the fire site emer- show in Table 2 and Table 3. For this building, the con-
gency investigation and the preliminary fire damage crete type of shear wall and column were C60 while
evaluation, a conclusion was made that the main struc- the one of floor slab was C40 (according to Chinese
tures of the building were lightly damaged by the fire, code GB 50010:2010). The rebound hammer test was
but some of its local structures were seriously dam- refer to Chinese code JGJ/T 23:2011, which provides
aged. The state of the building after the fire posed no the empirical value of concrete strength obtained from
danger of overall collapse, but risks of falling objects rebound hammer test.
were present in several local areas. Therefore, relevant
precautions were recommended. 3.2.2 Inspection of steel bars and calculation of
structural components
The reinforcement of the structural components, the
3.2 Inspection of structural components
mechanical properties of the steel bars, the size of
The inspection plan was developed based on the dam- each section, and the deformation of the structures
age assessment for each floor. The plan could be were inspected using the aforementioned plan. The
roughly divided into two parts: (1) the inspection strength of the steel bars was reduced after the concrete
of concrete strength and damage depth, and (2) the structures were exposed to the fire. The bond strength
inspection of steel bars and the calculation of struc- between concrete and steel also declined because of
tural components. The lightly damaged zone (zone B) the differences in their expansion coefficients, which
and the seriously damaged zone (zone C) were the resulted in poor performance of the overall structure.
main focus of the inspection. Several inspection methods were adopted to determine
the strength loss of the steel bars and the changes
3.2.1 Inspection of concrete strength and damage in bond strength and section size after the fire. A
depth magnetic induction device was used to examine the
Concrete structure appearance, concrete strength, and structural reinforcement. The steel bars were sampled
damage depth were inspected using the aforemen- in the spalled and exposed zones, and a mechanical test
tioned plan.The loss of concrete strength was primarily was performed on the samples. The effect of the fire
influenced by factors such as temperature during on the mechanical properties of the steel bars was also
heating, method of cooling, and duration of stor- analyzed. A measuring tape was used to determine the
age after the fire. Water cooling may further reduce dimension errors of the section size.
the compressive strength of the concrete by 30% to The results of the inspection showed that the num-
35% (Annerel & Taerwe 2012). The loss of concrete ber of beams, plates, columns, and walls in the main
strength can be measured according to the maxi- building satisfied the original design requirements.
mum temperature reached by its surface. However, Moreover, the mechanical properties of the steel bars
loss of concrete strength is extremely difficult to in the burnt zone satisfied the corresponding national

488
Table 2. The rebound hammer test result of concrete struc- Table 3. The core sampling test result of concrete structural
tural components in the 10th floor. components in the 10th floor.

Calculated Structural Strength


strength (MPa)
Empirical NO. type Condition (MPa)
Structural value
NO. type AVE STDEV Min (MPa) 16-17-4/G2-5/G2 floor slab burnt 57.1
1/14-1/15-5/G2-2/H2 floor slab burnt 48.2
12-13/E2-2.1/E2 floor slab 47.5 0.47 46.9 46.7 1/15-1/G2-4/G2 shear wall burnt 57
15-16/E2-3.2/E2 floor slab 48 0.92 46.2 46.5 (outward)
11-12-1/D2-1.6/D2 floor slab 47.2 0.87 45.4 45.8 1/15-3/F2-0/G2 shear wall burnt 64.6
1/15-16-0/G2-1/G2 floor slab 48.9 0.92 48.1 47.4
(outward)
1/15-16-4/G2-5/G2 floor slab 49.4 0.91 48 47.9
17-18-3/F2 shear wall burnt 57.5
1/16-17-4/G2-5/G2 floor slab 42.9 1.09 40.1 41.1
17-18-2/H2 shear wall 65.5 0.65 64.8 64.4 (outward)
1/14-2/H2-5/G2 wall 65.1 1 63.3 63.5 1/15-1/G2-4/G2 shear wall unburnt 61.1
1/15-3/G2-4/G2 wall 66.4 0.52 65.6 65.5 (inner)
Downloaded by [Nanyang Technological University (NTU)] at 00:14 17 July 2017

16-1/16-3/F2 wall 65.3 0.51 64.6 64.5 1/15-3/F2-0/G2 shear wall unburnt 72.4
3/F2-0/G2-1/15 wall 66.7 0.44 65.4 66 (inner)
15-3/H2 column 66 1.69 63.6 63.2 17-18-3/F3 shear wall unburnt 58.2
13-3/H2 column 66 2.26 62.5 62.3 (inner)
11-3/H2 column 67.9 2.2 65.2 64.3 17-18-3/H2 shear wall burnt 68
15-3/E2 column 64.9 1.62 62.5 62.2 17-18-3/H2 shear wall unburnt 82
12-3/H2 column 64 1.42 62 61.7 16-3/H2 column burnt 71.8
12-13-2.1/E2 beam 46.6 1.16 44.1 44.7 13-3/H2 column burnt 65.3
16-1.3/E2-3/F2 beam 46.5 0.7 44.8 45.3 16-3/H2 column unburnt 82.2
11-1/D2-1.6/D2 beam 52.3 2.56 48.7 48.1
12-1.1/E2-2.1/E2 beam 45.9 3.12 42.9 40.8
17-3.2/E2-2/F2 beam 47.6 1.03 46 45.9
16-17-2/F2 beam 47.3 1.4 44.5 45
experiences, and project-specific conditions should be
combined to evaluate damage in burnt buildings. Four
fire damage grades are determined to evaluate dam-
standard in China (GB 50010:2010). The fire had no age on concrete structural components. The evaluation
significant effect on the mechanical properties of the criteria for each damage grade are described in Table 4.
steel bars in the concrete structures and its effect on The concrete structural components in the burnt
the mechanical properties of the steel bars in other high-rise building were evaluated and graded based
structural components was not serious. The section on the criteria described in Table 4. Based on the eval-
size of the inspected structural components satisfied uation results, no grade IV damage on the concrete
design requirements; however, the deflections of sev- structural components in all floors of the building
eral structural components exceeded the maximum was observed. The 1st, 3rd, 4th, 6th, 26Eth, and 28th
allowable value in the Chinese national standard (GB floors both suffered slight fire damage, and the high-
50010:2010). est grade of fire damage to their structural components
was grade I. The 19th, 20nd, 24th, and 26Ath floors
both suffered medium fire damage, the highest grade
3.2.3 Evaluation of fire damage to structural of their structural components was II. The 2nd, 5th,
components 7th to 13th, 15th, 17th, 26Dth, and 27th floors both
The Shanghai City standard DBJ 08-291 (DBJ 08- suffered more serious fire damage, and the damage
291:1996) and the national technology standard CECS grades of structural components reached III.
252 (CECS 252:2009) are used in China for evalu-
ating fire damage to concrete structures. The former
classifies fire damage to concrete structural compo-
4 SUGGESTIONS FOR REPAIRING AND
nents into four grades primarily based on three aspects,
REINFORCING DAMAGED CONCRETE
namely, structural bearing capacity, cracks, and defor-
STRUCTURES
mation. The latter provides a more comprehensive
evaluation criteria based on concrete appearance,
The following measures are recommended for repair-
strength loss, cracks, bond strength between the con-
ing and reinforcing damaged structures:
crete and the steel bars, deformation, and other factors.
Both standards are divided into four grades. Several (1) For slightly damaged structural components
Chinese researchers also proposed their own evalu- (grade I), the dirt on the surface and the burnt paint
ation criteria for assessing fire damage to concrete layers should be cleaned first before the structures
structures based on different projects and experiences could be redecorated and repainted.
(Yuan 1997; Min 2000; Zhai et al. 2009; Guo & (2) For structural components with medium damage
Shi 2011). However, current evaluation criteria are (grade II), the depths of damage and spalling are
mostly qualitative, and usually serve as guides in prac- less than the thickness of the protective layer of the
tical applications. Therefore, current standards, expert concrete, and no steel bar is exposed. Therefore,

489
Table 4. Fire damage grades and their evaluation criteria for case of a high-rise building in Beijing which caught
concrete structural components. fire in 2009. The procedure can be summarized as
follows: emergency investigation of a fire site, deter-
Grade Evaluation criteria mination of maximum temperature reached, division
of fire-damaged zones, inspection of concrete struc-
I (Slight) The structural components have no obvious
tural components, and comprehensive evaluation of
damage. The color of the concrete surface
is either unchanged or is merely blackened these components. A scientific and reasonable pro-
by smoke. Loss of concrete strength is not cedure for inspecting and evaluating fire damage to
apparent. The maximum temperature structures is generally more useful than a qualitative
reaches less than 300 C. approach
II (Medium) The structural components are slightly Such a procedure enables accurate determination
damaged. The color of the concrete of the degree of damage to structural components,
surface ranges from pink to rusty red. and consequently, proposes economical and reliable
Cracking and spalling occur on the local repair and reinforcement measures. A scientific and
surface of the structural components. reasonable procedure also provides more efficient fire-
Downloaded by [Nanyang Technological University (NTU)] at 00:14 17 July 2017

Loss of concrete strength is slight. None of resistant structure designs developed based on prior
the reinforcing bars are exposed, and the experiences with fire incidents. Given that no perfect
damage depth is less than 20 mm. The bond
procedure or standard for inspecting and evaluating
strength between the concrete and the steel
bars is slightly damaged. The maximum fire damage to structures is yet available, existing
temperature ranges from 300 C to 600 C. methods are frequently combined, whether external
or internal, qualitative or quantitative, or technology-
III (Serious) The structural components are obviously
damaged. The color of the concrete surface or experience-based. However, the results of these
ranges from white to grey. The structural methods are usually affected by subjective factors
components have numerous cracks. Loss of which may vary to a certain extent. Therefore, research
concrete strength is considerable. The steel on indicators and criteria for evaluating fire dam-
bars are exposed in the local area, and the age should be strengthened. Moreover, the theoretical
damage depth is greater than 20 mm. system for inspecting and evaluating fire damage to
The bond strength between the concrete concrete structures should be improved further.
and the steel bars is seriously damaged.
The maximum temperature ranges from
600 C to 900 C.
REFERENCES
IV (Extreme) The structural components are seriously
damaged. The color of the concrete surface Annerel, E. & Taerwe, L. 2012. Innovative materials and tech-
is light yellow. The structural components niques in concrete construction: Chapter 18Assessment of
have numerous wide cracks in the vertical the fire damage of concrete members after fire exposure:
and horizontal directions. Loss of concrete 283290. New York:Springer.
strength is serious. The reinforcing bars are ASCE 29-05:2007. 2007. Standard calculation methods for
exposed in most areas, and the concrete structural fire protection. American Society of Civil
covers have spalled off. The bond strength Engineers, Reston.
between the concrete and the steel bars is CECS 252:2009. 2009. China Standard: Standard for build-
seriously damaged, and several steel bars are ing structural assessment after fire. China Project Con-
burned down or distorted. The maximum struction Association, Beijing: Plan Press of China.
temperature reaches more than 900 C. DBJ 08-21:1996. 1996. Shanghai Standard: Criteria of
assessment for concrete element after fire. Shanghai:
Shanghai Construction Committee.
only the concrete cover needs to be repaired. How- EN 1992-1-2:2004. 2004. Eurocode 2: design of concrete
ever, loose, burnt concrete should be cleaned first structures. Part 1-2: general rule structural fire design.
CEN, Brussels.
and cracks in the structural components should be Fan, J., and Lv, Z. 1999. Essentials of fireproof research
covered with better-quality concrete before repairs in concrete structure. Architecture Technology 30(05):
begin. The reinforcing bars should be rustproofed. 319320.
(3) For seriously damaged structural components Fang, C., Wei, Q. & Liang, H. 2010. A method of projection
(grade III), the increasing section method can pursuit evaluation based on genetic algorithm on damage
be used to make repairs. The damaged concrete of high strength concrete after exposed to fire. Sichuan
should be completely cleaned, and additional steel Building Science 36(4):8486.
bars should be welded and anchored into a struc- GB 50016:2012. 2012. China Standard: Code for fire pro-
ture. Better-quality concrete should be used to tection design of buildings. Ministry of Housing and
Urban-Rural Development of the Peoples Republic of
repair the structure. China, Beijing: Plan Press of China.
GB 50010:2010. 2010. China Standard: Code for design of
concrete structures. Ministry of Housing and Urban-Rural
5 CONCLUSIONS Development of the Peoples Republic of China, Beijing:
China Architecture & Building Press.
A procedure for inspecting and evaluating fire dam- Guo, Z. & Shi, X. 2011. Experiment and Calculation of Rein-
age to concrete structures is proposed based on the forced Concrete at ElevatedTemperatures: Chapter 14 Fire

490
Resistance Analysis and Damage Grade Evaluation of a Li, Y., Tang, Y. & Zeng, Z. 2008. Development and trend
Structure. Beijing: Tsinghua University Press. of the research on fire resistance of reinforced concrete
Han, L. & Song, T. 2012. Fire safety design theory of steel- structures. Journal of Catastrophology 23(01):102107.
concrete composite structures. Science Press, Beijing. Min, M. 2000. A comprehensive method for evaluating struc-
ISO 834:2002. 2008. Fire resistance tests Elements of build- tures after fire. Architecture Technology 31(6):403404.
ing construction. International Organization for Standard- Wang, W., Su, J., Han,Y., Ma, D. &Yin, C. 2008. A matter ele-
ization, Geneva. ment model for comprehensive evaluation on the degree
JGJ/T 23:2011. 2011. Technical specification for inspect- of fire-damage concrete. Concrete 30(01):2022.
ing of concrete compressive strength by rebound method. Yang, X. 2010. The investigation of the fire accident in CCTV.
Ministry of Housing and Urban-Rural Development of the Journal of labor protection 04:3639.
Peoples Republic of China, Beijing: China Architecture & Yuan, Q. 1997. Evaluation the fire damage to building
Building Press. structures based on a project. Guangdong Civil and
Li, G., Han, L., Lou, G. & Jiang, S. 2006. Fire protection Architecture 02:4247.
design for steel and steel-concrete composite structures of Zhai, C., Dai, W., Wang, W. & Xiao, W. 2009. Safety appraisal
buildings. Beijing: China Architecture & Building Press. and strengthening for a building after fire. Construction
Li, M. 2005. The fire damadge of high strength concrete Technology 38(6):6769.
Downloaded by [Nanyang Technological University (NTU)] at 00:14 17 July 2017

and its comprehensive evaluation. PHD Thesis, Southeast


University, Nanjing.
Li, M., Kao, H. & Qian, C. 2008. Fuzzy comprehensive eval-
uation method on damage of high strength concrete after
exposed to fire. Concrete 30(06):810.

491
Downloaded by [Nanyang Technological University (NTU)] at 00:14 17 July 2017

Potrebbero piacerti anche