Design Criteria
1. Water Fixture Units Refer to Table 6-5 of UPCP
2. Number of occupancy is based on the number of furniture. For large area, Area method is used
3. Per Capita Consumption of occupants:
Students and Visitors 5gal/day
Employess 30gal/day
0 Computation
165.5 TDH
79.5 Minimum residual Pressure: 34.65
72.5 Static Pressure 81.75
202 hf velocity 1
62.5 hf due to friction 6.61
206.5 Total Dynamic Head 124
788.5
use Q 120
use EFF 60%
Using the formula above W is: 6.26
say W 7.50 HP
Capacity of Cistern
V= WD*PD*FR*FS
Where: V is the volume of the cistern (GAL)
WD is the water demand of the entire bldg. (GPM)
PD is Peek Consumption Duration (mins)
FR is the frequency of Peek Consumption
FS is the facotor of safety
Given WD 190
PD 30
FR 2
FS 1.25
Computation
TDH
Minimum residual Pressure: 34.65
Static Pressure 6.54
hf velocity 1
hf due to friction 0.45
Total Dynamic Head 43
use Q 70
use EFF 60%
Using the formula above W is: 1.26
say W 1.50 HP
00gal