ST MARK ACADEMY

Design Criteria
1. Water Fixture Units Refer to Table 6-5 of UPCP
2. Number of occupancy is based on the number of furniture. For large area, Area method is used
3. Per Capita Consumption of occupants:
Students and Visitors 5gal/day
Employess 30gal/day

WATER FIXTURE TABLE


WC
FLOOR FT FV LV UR PS&KS HB
RD 0 0 0 0 0 0
5th 0 4 5 4 0 1
4th 1 2 3 0 1 1
3rd 0 2 1 0 1 0
2nd 0 8 8 3 1 1
GF 0 1 1 1 1 0
LG 0 8 6 4 0 1

WATER FIXTURE UNIT TABLE


FLOOR WC LV UR PS&KS HB
FT FV
RD 0 0 0 0 0 0
5th 0 105 5 53 0 2.5
4th 2.5 70 3 0 1.5 2.5
3rd 0 70 1 0 1.5 0
2nd 0 145 8 45 1.5 2.5
GF 0 40 1 20 1.5 0
LG 0 145 6 53 0 2.5

OCCUPANCY LOADING TABLE


FLOOR EMP STD/V
RD 0 87
5th 2 123
4th 4 20
3rd 18 64
2nd 32 108
GF 26 76
LG 0 36

PER CAPITA CONSUMPTION TABLE


FLOOR EMP STD/V total (gal)
RD 0 435 435
5th 60 615 675
4th 120 100 220
3rd 540 320 860
2nd 960 540 1500
GF 780 380 1160
LG 0 180 180
5030

PIPE SIZING TABLE (Water Fixture Units)


Water Demand
PIPE Flow Type WFU (GPM) Headloss (PSI) Velocity (ft/s) Diameter (in)
RD main booster 0 0 0 0 0
5th Flr Main booster 165.5 80 2.3 5.5 2.5
4th Flr Main booster 79.5 60 3.5 6 2
3rd Flr Main gravity 72.5 58 1.3 4 2.5
2nd Flr Main gravity 202 85 1 4 3

GF Main gravity 62.5 57 1.3 4 2.5


LG Main gravity 206.5 86 1 4 3
CW Riser Booster 788.5 190 3.5 8 3
CWF gravity 543.5 150 0.6 4 4
CWBF booster 245 100 3 6.5 2.5
Duplex Booster Pump
W = [Q *(TDH)]/[396
Where: W is the power of the pump
Q is the discharge needed

Cold Water Riser Duplex Pump

Given: EFF 60%


F.S. 25%
Total Q = Q1 = Q2 118.8

0 Computation
165.5 TDH
79.5 Minimum residual Pressure: 34.65
72.5 Static Pressure 81.75
202 hf velocity 1
62.5 hf due to friction 6.61
206.5 Total Dynamic Head 124
788.5
use Q 120
use EFF 60%
Using the formula above W is: 6.26

say W 7.50 HP

Use 120GPM vs 124TDH w/ 7.5 HP Electric Motor Duplex

Capacity of Cistern
V= WD*PD*FR*FS
Where: V is the volume of the cistern (GAL)
WD is the water demand of the entire bldg. (GPM)
PD is Peek Consumption Duration (mins)
FR is the frequency of Peek Consumption
FS is the facotor of safety

Given WD 190
PD 30
FR 2
FS 1.25

Computed 'V' using the formula stated above 14250

Needed Cistern Capacity 15000gal


Duplex Booster Pump Design
W = [Q *(TDH)]/[3960*(EFF)]
TDH is the Total Dynamic Head
EFF is the Efficiency of the pump

mp Cold Water Feed Booster Duplex Pump

Given: EFF 60%


F.S. 25%
Q = Q1 = Q2 62.5

Computation
TDH
Minimum residual Pressure: 34.65
Static Pressure 6.54
hf velocity 1
hf due to friction 0.45
Total Dynamic Head 43

use Q 70
use EFF 60%
Using the formula above W is: 1.26

say W 1.50 HP

ic Motor Duplex Use 70GPM vs 43TDH w/ 1.5 HP Electric Motor Duplex

Capacity of Elevated Water Tank


V = 0.3*VofCistern
Where: V is the volume of the Elevated Water Tank (GAL)
tire bldg. (GPM) Given V of cistern 15000
Computed 'V' using the formula stated above 4500
Needed total Elevated Water Tank Capacity 5000gal. Use two 2500gal
Elevated Water Tank