Sei sulla pagina 1di 6

CAIROMATIC OWNER CAPW

MISR CONSULT
33 Ahmed Tayseer St. CLIENT
P.Dr / SAMEH ABDEL GAWAD
PROJECT ARAB CONTRACTORS
Heliopolis - Cairo - Egypt NEW CAIRO COMPACT WATER TREATMENT PLANT
TEL. : +202 24173424 30,000M3/DAY
FA*. : +202 24173373 Proj Ref. Title CWT-01-2015-ELEC SH. OF REV. DATE
E-MAIL: INFO@CAIROMATIC.COM Doc. Title Cable Trench & Sleevs Calculations 1 2 1 Dec-15

Cable Size # of Cable Dia. Cable C.S Tot. Cables

Ser.
FROM TO Div 1 Div 2 Div 3
(mm2 ) Cables (mm) (mm2 ) C.S (mm2 )

1 MCC 1 FCP 1 - Control Cable 7*1.5 6 12.7 126.7 760.1 M1R1 M1R7

2 MCC 1 FCP 1 - Feeder Cable 4*4 1 14.8 172.0 172.0 M1R1 M1R7

3 MCC 1 FCP 2 - Control Cable 7*1.5 6 12.7 126.7 760.1 M1R1 M1R7

4 MCC 1 FCP 2 - Feeder Cable 4*4 1 14.8 172.0 172.0 M1R1 M1R7

5 MCC 1 MCP - Control Cable 7*1.5 2 12.7 126.7 253.4 M1R1 M1R11 M1R14

6 MCC 1 BWP 1 - Control Cable 5*1.5 1 9.3 67.9 67.9 M1R1 M1R11 M1R14

7 MCC 1 BWP 2 - Control Cable 5*1.5 1 9.3 67.9 67.9 M1R1 M1R11 M1R14

8 MCC 1 FCP 3 - Control Cable 7*1.5 6 12.7 126.7 760.1 M1R2 M1R5

9 MCC 1 FCP 3 - Feeder Cable 4*4 1 14.8 172.0 172.0 M1R2 M1R5

10 MCC 1 FCP 4 - Control Cable 7*1.5 6 12.7 126.7 760.1 M1R2 M1R5

11 MCC 1 FCP 4 - Feeder Cable 4*4 1 14.8 172.0 172.0 M1R2 M1R5

12 MCC 1 Gentle Mixer - Control Cable 5*1.5 1 9.3 67.9 67.9 M1R2 M1R11 M1R16

13 MCC 1 Flash Mixer - Control Cable 5*1.5 1 9.3 67.9 67.9 M1R2 M1R11 M1R16

14 MCC 1 MCP - Feeder Cable 4*4 1 14.8 172.0 172.0 M1R2 M1R11 M1R14

15 MCC 1 BWP 1 - Power Cable 4*16 2 20.9 343.1 686.1 M1R4 M1R9 M1R12

16 MCC 1 BWP 2 - Power Cable 4*16 2 20.9 343.1 686.1 M1R4 M1R9 M1R12

17 MCC 1 Gentle Mixer - Power Cable 4*4 1 14.8 172.0 172.0 M1R4 M1R9 M1R15

18 MCC 1 Flash Mixer - Power Cable 4*2.5 1 12.4 120.8 120.8 M1R4 M1R9 M1R15

19 FCP 1 MCP - Control Cable 7*1.5 4 12.4 120.8 483.1 M1R17

20 FCP 2 MCP - Control Cable 7*1.5 4 12.4 120.8 483.1 M1R17

21 FCP 3 MCP - Control Cable 7*1.5 4 12.4 120.8 483.1 M1R14

22 FCP 4 MCP - Control Cable 7*1.5 4 12.4 120.8 483.1 M1R14

23 MCP Clarifier & Flocculator Pneumatic Valves 5*1.5 5 12.4 120.8 603.8 M1R14 M1R16

24 MCP Inlet Modulated Valve - Signal 2*1.5 Sh 2 9.1 65.0 130.1 M1R13 M1R16

25 MCP Inlet Magnetic Flow Transmitter - signal 2*1.5 Sh 1 9.1 65.0 65.0 M1R13 M1R16

26 MCP pH Transmitter - signal 2*1.5 Sh 1 9.1 65.0 65.0 M1R13 M1R16

27 MCP Flocc Level Switch - signal 3*1.5 1 9.6 72.4 72.4 M1R13 M1R16

28 MCP Clarifier Level Switch - signal 7*1.5 1 12.4 120.8 120.8 M1R13 M1R16

Electrical Conduits for underground cables :

Route : M1R1 M1R2 M1R3 M1R4 M1R5 M1R6 M1R7 M1R8 M1R9

Sum of cables C.S inside the conduit [mm2] 2253.4 2172.1 0.0 1665.1 1864.2 0.0 1864.2 0.0 1665.1

Minimum space required to provide 60% space inside conduit [mm2] 5633.5 5430.2 0.0 4162.7 4660.5 0.0 4660.5 0.0 4162.7

Minimum conduit diam [mm] 84.7 83.2 0.0 72.8 77.0 0.0 77.0 0.0 72.8

Final conduit diameter = mm 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0

Route : M1R10 M1R11 M1R12 M1R13 M1R14 M1R15 M1R16 M1R17

Sum of cables C.S inside the conduit [mm2] 0.0 697.1 1372.3 453.3 2131.2 292.8 1193.0 966.1

Minimum space required to provide 60% space inside conduit [mm2] 0.0 1742.8 3430.7 1133.3 5327.9 732.0 2982.4 2415.3

Minimum conduit diam [mm] 0.0 47.1 66.1 38.0 82.4 30.5 61.6 55.5

Final conduit diameter = mm 100.0 100.0 100.0 75.0 100.0 75.0 75.0 75.0
CAIROMATIC OWNER CAPW

MISR CONSULT
33 Ahmed Tayseer St. CLIENT
P.Dr / SAMEH ABDEL GAWAD
PROJECT ARAB CONTRACTORS
Heliopolis - Cairo - Egypt NEW CAIRO COMPACT WATER TREATMENT PLANT
TEL. : +202 24173424 30,000M3/DAY
FA*. : +202 24173373 Proj Ref. Title CWT-01-2015-ELEC SH. OF REV. DATE

E-MAIL: INFO@CAIROMATIC.COM Doc. Title Cable Trench & Sleevs Calculations 1 2 1 Dec-15

Cable Size # of Cable Diam. Cable C.S Total Cables

Ser.
FROM TO 2 Div 1 Div 2 Div 3
(mm ) Cables (mm) (mm2 ) C.S (mm2 )

1 MCC 2 MCP - Control Cable 7*1.5 2 12.7 126.7 253.4 M2R1 M2R11 M2R14

2 MCC 2 BWP 1 - Control Cable 5*1.5 1 9.3 67.9 67.9 M2R1 M2R11 M2R14

3 MCC 2 BWP 2 - Control Cable 5*1.5 1 9.3 67.9 67.9 M2R1 M2R11 M2R14

4 MCC 2 MCP - Feeder Cable 4*4 1 14.8 172.0 172.0 M2R1 M2R11 M2R14

5 MCC 2 Gentle Mixer - Control Cable 5*1.5 1 9.3 67.9 67.9 M2R1 M2R11 M2R16

6 MCC 2 Flash Mixer - Control Cable 5*1.5 1 9.3 67.9 67.9 M2R1 M2R11 M2R16

7 MCC 2 FCP 3 - Control Cable 7*1.5 6 12.7 126.7 760.1 M2R5

8 MCC 2 FCP 4 - Control Cable 7*1.5 6 12.7 126.7 760.1 M2R5

9 MCC 2 FCP 3 - Feeder Cable 4*4 1 14.8 172.0 172.0 M2R5

10 MCC 2 FCP 4 - Feeder Cable 4*4 1 14.8 172.0 172.0 M2R5

11 MCC 2 FCP 1 - Control Cable 7*1.5 6 12.7 126.7 760.1 M2R7

12 MCC 2 FCP 2 - Control Cable 7*1.5 6 12.7 126.7 760.1 M2R7

13 MCC 2 FCP 1 - Feeder Cable 4*4 1 14.8 172.0 172.0 M2R7

14 MCC 2 FCP 2 - Feeder Cable 4*4 1 14.8 172.0 172.0 M2R7

15 MCC 2 BWP 1 - Power Cable 4*16 2 20.9 343.1 686.1 M2R4 M2R9 M2R12

16 MCC 2 BWP 2 - Power Cable 4*16 2 20.9 343.1 686.1 M2R4 M2R9 M2R12

17 MCC 2 Gentle Mixer - Power Cable 4*4 1 14.8 172.0 172.0 M2R4 M2R9 M2R15

18 MCC 2 Flash Mixer - Power Cable 4*2.5 1 12.4 120.8 120.8 M2R4 M2R9 M2R15

19 FCP 1 MCP - Control Cable 7*1.5 4 12.4 120.8 483.1 M2R17

20 FCP 2 MCP - Control Cable 7*1.5 4 12.4 120.8 483.1 M2R17

21 FCP 3 MCP - Control Cable 7*1.5 4 12.4 120.8 483.1 M2R14

22 FCP 4 MCP - Control Cable 7*1.5 4 12.4 120.8 483.1 M2R14

23 MCP Clarifier & Flocculator Pneumatic Valves 5*1.5 5 12.4 120.8 603.8 M2R14 M2R16

24 MCP Inlet Modulated Valve - Signal 2*1.5 Sh 2 9.1 65.0 130.1 M2R13 M2R16

25 MCP Inlet Magnetic Flow Transmitter - signal 2*1.5 Sh 1 9.1 65.0 65.0 M2R13 M2R16

26 MCP pH Transmitter - signal 2*1.5 Sh 1 9.1 65.0 65.0 M2R13 M2R16

27 MCP Flocc Level Switch - signal 3*1.5 1 9.6 72.4 72.4 M2R13 M2R16

28 MCP Clarifier Level Switch - signal 7*1.5 1 12.4 120.8 120.8 M2R13 M2R16

Electrical Conduits for underground cables :

Route : M2R1 M2R2/3 M2R4 M2R5 M2R6 M2R7 M2R8 M2R9

Sum of cables C.S inside the conduit [mm2] 697.1 0.0 1665.1 1864.2 0.0 1864.2 0.0 1665.1

Minimum space required to provide 60% space inside conduit [mm2] 1742.8 0.0 4162.7 4660.5 0.0 4660.5 0.0 4162.7

Minimum conduit diam [mm] 47.1 0.0 72.8 77.0 0.0 77.0 0.0 72.8

Final conduit diameter = mm 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0

Route : M2R10 M2R11 M2R12 M2R13 M2R14 M2R15 M2R16 M2R17

Sum of cables C.S inside the conduit [mm2] 0.0 697.1 1372.3 453.3 2131.2 292.8 1193.0 966.1

Minimum space required to provide 60% space inside conduit [mm2] 0.0 1742.8 3430.7 1133.3 5327.9 732.0 2982.4 2415.3

Minimum conduit diam [mm] 0.0 47.1 66.1 38.0 82.4 30.5 61.6 55.5

Final conduit diameter = mm 100.0 100.0 100.0 75.0 100.0 75.0 75.0 75.0
CAIROMATIC OWNER CAPW

MISR CONSULT
33 Ahmed Tayseer St. CLIENT
P.Dr / SAMEH ABDEL GAWAD
PROJECT ARAB CONTRACTORS
Heliopolis - Cairo - Egypt NEW CAIRO COMPACT WATER TREATMENT PLANT
TEL. : +202 24173424 30,000M3/DAY
FA*. : +202 24173373 Proj Ref. Title CWT-01-2015-ELEC SH. OF REV. DATE

E-MAIL: INFO@CAIROMATIC.COM Doc. Title Cable Trench & Sleevs Calculations 1 2 1 Dec-15

Cable Size # of Cable Diam. Cable C.S Total Cables

Ser.
FROM TO 2 Div 1 Div 2 Div 3
(mm ) Cables (mm) (mm2 ) C.S (mm2 )

1 MCC 3 FCP 1 - Control Cable 7*1.5 6 12.7 126.7 760.1 M3R1 M3R7

2 MCC 3 FCP 1 - Feeder Cable 4*4 1 14.8 172.0 172.0 M3R1 M3R7

3 MCC 3 FCP 2 - Control Cable 7*1.5 6 12.7 126.7 760.1 M3R1 M3R7

4 MCC 3 FCP 2 - Feeder Cable 4*4 1 14.8 172.0 172.0 M3R1 M3R7

5 MCC 3 MCP - Control Cable 7*1.5 2 12.7 126.7 253.4 M3R1 M3R11 M3R14

6 MCC 3 BWP 1 - Control Cable 5*1.5 1 9.3 67.9 67.9 M3R1 M3R11 M3R14

7 MCC 3 BWP 2 - Control Cable 5*1.5 1 9.3 67.9 67.9 M3R1 M3R11 M3R14

8 MCC 3 FCP 3 - Control Cable 7*1.5 6 12.7 126.7 760.1 M3R2 M3R5

9 MCC 3 FCP 3 - Feeder Cable 4*4 1 14.8 172.0 172.0 M3R2 M3R5

10 MCC 3 FCP 4 - Control Cable 7*1.5 6 12.7 126.7 760.1 M3R2 M3R5

11 MCC 3 FCP 4 - Feeder Cable 4*4 1 14.8 172.0 172.0 M3R2 M3R5

12 MCC 3 Gentle Mixer - Control Cable 5*1.5 1 9.3 67.9 67.9 M3R2 M3R11 M3R16

13 MCC 3 Flash Mixer - Control Cable 5*1.5 1 9.3 67.9 67.9 M3R2 M3R11 M3R16

14 MCC 3 MCP - Feeder Cable 4*4 1 14.8 172.0 172.0 M3R2 M3R11 M3R14

15 MCC 3 BWP 1 - Power Cable 4*16 2 20.9 343.1 686.1 M3R4 M3R9 M3R12

16 MCC 3 BWP 2 - Power Cable 4*16 2 20.9 343.1 686.1 M3R4 M3R9 M3R12

17 MCC 3 Gentle Mixer - Power Cable 4*4 1 14.8 172.0 172.0 M3R4 M3R9 M3R15

18 MCC 3 Flash Mixer - Power Cable 4*2.5 1 12.4 120.8 120.8 M3R4 M3R9 M3R15

19 FCP 1 MCP - Control Cable 7*1.5 4 12.4 120.8 483.1 M3R14

20 FCP 2 MCP - Control Cable 7*1.5 4 12.4 120.8 483.1 M3R14

21 FCP 3 MCP - Control Cable 7*1.5 4 12.4 120.8 483.1 M3R17

22 FCP 4 MCP - Control Cable 7*1.5 4 12.4 120.8 483.1 M3R17

23 MCP Clarifier & Flocculator Pneumatic Valves 5*1.5 5 12.4 120.8 603.8 M3R14 M3R16

24 MCP Inlet Modulated Valve - Signal 2*1.5 Sh 2 9.1 65.0 130.1 M3R13 M3R16

25 MCP Inlet Magnetic Flow Transmitter - signal 2*1.5 Sh 1 9.1 65.0 65.0 M3R13 M3R16

26 MCP pH Transmitter - signal 2*1.5 Sh 1 9.1 65.0 65.0 M3R13 M3R16

27 MCP Flocc Level Switch - signal 3*1.5 1 9.6 72.4 72.4 M3R13 M3R16

28 MCP Clarifier Level Switch - signal 7*1.5 1 12.4 120.8 120.8 M3R13 M3R16

Electrical Conduits for underground cables :

Route : M3R1 M3R2 M3R3 M3R4 M3R5 M3R6 M3R7 M3R8 M3R9

Sum of cables C.S inside the conduit [mm2] 2,253.4 2,172.1 0.0 1,665.1 1,864.2 0.0 1,864.2 0.0 1,665.1

Minimum space required to provide 60% space inside conduit [mm2] 5,633.5 5,430.2 0.0 4,162.7 4,660.5 0.0 4,660.5 0.0 4,162.7

Minimum conduit diam [mm] 84.7 83.2 0.0 72.8 77.0 0.0 77.0 0.0 72.8

Final conduit diameter = mm 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0

Route : M3R10 M3R11 M3R12 M3R13 M3R14 M3R15 M3R16 M3R17 M3R18

Sum of cables C.S inside the conduit [mm2] 0.0 697.1 1372.3 453.3 2131.2 292.8 1193.0 966.1 0.0

Minimum space required to provide 60% space inside conduit [mm2] 0.0 1742.8 3430.7 1133.3 5327.9 732.0 2982.4 2415.3 0.0

Minimum conduit diam [mm] 0.0 47.1 66.1 38.0 82.4 30.5 61.6 55.5 0.0

Final conduit diameter = mm 100.0 100.0 100.0 75.0 100.0 75.0 75.0 75.0 100.0
CAIROMATIC OWNER CAPW

MISR CONSULT
33 Ahmed Tayseer St. CLIENT
P.Dr / SAMEH ABDEL GAWAD
PROJECT ARAB CONTRACTORS
Heliopolis - Cairo - Egypt NEW CAIRO COMPACT WATER TREATMENT PLANT
TEL. : +202 24173424 30,000M3/DAY
FA*. : +202 24173373 Proj Ref. Title CWT-01-2015-ELEC SH. OF REV. DATE
E-MAIL: INFO@CAIROMATIC.COM Doc. Title Cable Trench & Sleevs Calculations 1 1 1 Dec-15

Cable Size # of Cable Diam. Total Cables Cable C.S Total Cables

Ser.
FROM TO (mm2 ) Cables (mm) Diam (mm) (mm2 ) C.S (mm2 ) Div 1 Div 2 Div 3

1 MCC 1 Air Blower 1 - Power Cable 4*4 2 14.8 29.6 172.0 344.1 ABR1

2 MCC 1 Air Blower 2 - Power Cable 4*4 2 14.8 29.6 172.0 344.1 ABR1

3 MCC 2 Air Blower 1 - Power Cable 4*4 2 14.8 29.6 172.0 344.1 ABR1

4 MCC 3 Air Blower 1 - Power Cable 4*4 2 14.8 29.6 172.0 344.1 ABR1

5 MCC 3 Air Blower 2 - Power Cable 4*4 2 14.8 29.6 172.0 344.1 ABR1

6 MCC 2 Air Blower 2 - Power Cable 4*4 2 14.8 29.6 172.0 344.1 ABR1

7 MCC 1 Air Blower 1 - Control Cable 5*1.5 1 9.3 9.3 67.9 67.9 ABR2

8 MCC 1 Air Blower 2 - Control Cable 5*1.5 1 10.3 10.3 83.3 83.3 ABR2

9 MCC 1 Pneumatic Valve 1 - Cable 5*1.5 1 9.3 9.3 67.9 67.9 ABR2

10 MCC 1 Pneumatic Valve 2 - Cable 5*1.5 1 9.3 9.3 67.9 67.9 ABR2

11 MCC 1 Air Blower Panel 1 - Control Cable 7*1.5 3 12.7 38.1 126.7 380.0 ABR2

12 MCC 2 Air Blower 1 - Control Cable 5*1.5 1 9.3 9.3 67.9 67.9 ABR2

13 MCC 2 Air Blower 2 - Control Cable 5*1.5 1 10.3 10.3 83.3 83.3 ABR2

14 MCC 2 Pneumatic Valve 1 - Cable 5*1.5 1 9.3 9.3 67.9 67.9 ABR2

15 MCC 2 Pneumatic Valve 2 - Cable 5*1.5 1 9.3 9.3 67.9 67.9 ABR2

16 MCC 2 Air Blower Panel 2 - Control Cable 7*1.5 3 12.7 38.1 126.7 380.0 ABR2

17 MCC 3 Air Blower 1 - Control Cable 5*1.5 1 9.3 9.3 67.9 67.9 ABR2

18 MCC 3 Air Blower 2 - Control Cable 5*1.5 1 10.3 10.3 83.3 83.3 ABR2

19 MCC 3 Pneumatic Valve 1 - Cable 5*1.5 1 9.3 9.3 67.9 67.9 ABR2

20 MCC 3 Pneumatic Valve 2 - Cable 5*1.5 1 9.3 9.3 67.9 67.9 ABR2

21 MCC 3 Air Blower Panel 3 - Control Cable 7*1.5 3 12.7 38.1 126.7 380.0 ABR2

Electrical Conduits for underground cables :

Route : ABR1 ABR2

Sum of cables C.S inside the conduit [mm2] 2064.4 2001.4

Minimum space required to provide 60% space inside conduit [mm2] 5161.0 5003.6

Minimum conduit diam [mm] 81.1 79.8

Final conduit diameter = mm 100.0 100.0

Potrebbero piacerti anche