Application-oriented Testing of a Power Swing Blocking


Function using the corresponding RelaySimTest
Template

Author
Jens Baumeister | Jens.Baumeister@omicron.at

Date
May 16, 2015

Related OMICRON Product


CMC - RelaySimTest

Application Area
Power Swing Detection

Keywords
RelaySimTest, Power Swing, Application-oriented Testing,

Version
v1.0

Document ID
ANS_15020_ENU

Abstract
This application note describes the Power Swing Test Template of the RelaySimTest Software.
General information

OMICRON electronics GmbH including all international branch offices is henceforth referred to as
OMICRON.
The product information, specifications, and technical data embodied in this application note represent the
technical status at the time of writing and are subject to change without prior notice.
We have done our best to ensure that the information given in this application note is useful, accurate and
entirely reliable. However, OMICRON does not assume responsibility for any inaccuracies which may be
present.
OMICRON translates this application note from the source language English into a number of other
languages. Any translation of this document is done for local requirements, and in the event of a dispute
between the English and a non-English version, the English version of this note shall govern.

All rights including translation reserved. Reproduction of any kind, for example, photocopying, microfilming,
optical character recognition and/or storage in electronic data processing systems, requires the explicit
consent of OMICRON. Reprinting, wholly or partly, is not permitted.
OMICRON 2015. All rights reserved. This application note is a publication of OMICRON.

OMICRON 2015 Page 2 of 33


Table of content

1 Safety Instructions ................................................................................................................................4


2 About this Application Note .................................................................................................................5
2.1 General Requirements....................................................................................................................5
2.2 What this Application Note describes .............................................................................................5
2.3 Power Swing ...................................................................................................................................5
3 System Under Test ............................................................................................................................. 11
3.1 Application Example Protected Line and Time Grading ........................................................... 11
3.2 Settings of the System Under Test Menu in RelaySimTest ........................................................ 12
4 Test Cases ........................................................................................................................................... 15
4.1 Application Example Grid Topology ......................................................................................... 16
4.2 Suitable Test Cases ..................................................................................................................... 16
4.2.1 General Information ........................................................................................................................ 17
4.2.2 Synchronize to TransView Feature ................................................................................................. 19
4.2.3 Test Case 1 and 2 Stable Power Swing....................................................................................... 20
4.2.4 Test Case 3 and 4 Stable Power Swing with Load ...................................................................... 22
4.2.5 Test Case 5 and 6 Stable Power Swing with Fault ...................................................................... 23
4.2.6 Test Case 7 and 8 Unstable Power Swing ................................................................................... 24
4.2.7 Test Case 9 and 10 Unstable Power Swing with Load ................................................................ 26
4.2.8 Test Case 11 and 12 Unstable Power Swing with Fault .............................................................. 26
4.3 Measurement and Assessment ................................................................................................... 27
5 Test Sets Configuration ..................................................................................................................... 28
6 Performing the Test ............................................................................................................................ 30
7 List of Literature ................................................................................................................................. 32

OMICRON 2015 Page 3 of 33


1 Safety Instructions
This application note may only be used in combination with the relevant product manuals which contain all
safety instructions. The user is fully responsibility for any application that makes use of OMICRON products.
Instructions are always characterized by a symbol even if they are included to a safety instruction.

DANGER
Death or severe injury caused by high voltage or current if the respective
protective measures are not complied.

Carefully read and understand the content of this application note as well as
the manuals of the involved systems before starting its practical application.
Please contact OMICRON before you continue the process if you do not
understand the safety instructions, operating instructions, or parts of it.
Follow each instruction mentioned there especially the safety instructions
since this is the only way to avoid danger that can occur when working at
high voltage or high current systems.
Furthermore, only use the involved equipment according to its intended
purpose to guarantee a safe operation.
Existing national safety standards for accident prevention and
environmental protection may supplement the equipments manual.

Only experienced and competent professionals that are trained for working in high voltage or high current
environments may perform this application note. Additional the following qualifications are required:
authorized to work in environments of energy generation, transmission or distribution and familiar
with the approved operating practices in such environments.
familiar with the five safety rules.
good knowledge of the OMICRON CMC test sets and RelaySimTest

OMICRON 2015 Page 4 of 33


2 About this Application Note

2.1 General Requirements

Before you get started with this application note, read the Getting Started manual [1] of RelaySimTest.
Please make sure that you also have a good knowledge about the CMC test system.

2.2 What this Application Note describes


The application note describes the relay tests of the RelaySimTest predefined Power Swing template. It
covers the following content of the test template.

1. Power Swing (general information)


2. System Under Test
3. Test Cases
4. Test Sets Configuration

The application note doesnt describe wiring checks and parameter tests. To test the protection thoroughly
such tests are also recommended.

2.3 Power Swing

In a power grid static load flow is generated by a stationary voltage difference. In a mostly inductive grid the
difference is mainly given by an angle deviation between the ends in order to transport active power while a
difference in magnitude would produce reactive power. Figure 1 shows a grid with two infeeds, while Figure
2 illustrates the corresponding node voltages and the grid current.

Infeed 1 Line 1 Infeed 2


Z Q1 Z L Z Q2
D I A B C

V ZQ1 V L
V ZQ2
V Q1 V Q2
V AE

Figure 1: Power Transmission

OMICRON 2015 Page 5 of 33


C

V ZQ2

V Q2
B

V L

V AE E
A I
V ZQ1
V Q1
D
Figure 2: Voltages and Current

According to Figure 2 the source voltage VQ1 is leading compared to VQ2. That means there is an active
power transmission from infeed 1 to infeed 2. The amount of power depends on the impedances, on the
magnitudes of VQ1 and VQ2 and last but not least on the angle between them. If the active resistances of ZQ1,
ZL and ZQ2 are neglected and only X as the sum of their reactive resistances is taken into consideration
Equation 1 describes the amount of transmitted active power.

Equation 1

2 sin
= 1

During normal operation of the power grid the actual load always equals the generation. But caused by load
changes, switching operations and faults this balance can be disturbed. Power grids with their connected
electrical machines and their control systems are dynamic systems that react on any transient disturbance
by a usually damped oscillating reaction (due to the inertia of the electrical machines and the control
systems) until a new stable state is reached. Any change in active power consumption causing the
generators to accelerate or decelerate until the supplied real power equals the consumed real power and all
oscillations have ceased due to damping elements in the system. Acceleration and deceleration of
generators mean increasing and decreasing angles between there generated voltages and consequently
increasing and decreasing grid currents causing oscillating power. This means a power swing takes place.
The static stability limit of a generator is at a load angle of 90. At this operating point the generator delivers
its maximum active power. During dynamic processes like a power swing the load angle can be higher than
90. As long as the electrical load of the generator is higher than the power supplied to its turbine (e. g.
water or steam power) the generator can fall back to a stable condition with a load angle smaller than 90. In
that case it is a stable power swing. But it can also happen that generators do not find a stable condition
after the disturbance. This means their load angle increases continuously and they fall out of step.

OMICRON 2015 Page 6 of 33


If the power swing is stable, it is not necessary to disconnect generators or loads. To stop an unstable power
swing it is necessary to split the grid at certain predefined nodes to get a stable condition again, where the
actual load equals the generation.

The impedances of the grid shown in Figure 1 appear if the voltages of Figure 2 are divided by the current.
Figure 3 shows the impedances.

X C

Z Q2

ZL

Z Load E
A
Z Q1 R

Figure 3: Impedance Plane

Figure 1 assumes node A as location of a distance protection relay. During a power swing the load
impedance ZLoad measured by the distance relay changes depending on the voltage angle changes of VQ1
and VQ2. If both source voltages have the same magnitude, the impedance ZLoad would move on a line, while
angle changes. Figure 4 illustrates this. The figure shows also a tripping zone of the distance protection
function. It is possible that during a power swing the impedance measured by the relay moves into such a
tripping zone. But the distance protection function should not trip during a power swing, if there is no grid
fault.

OMICRON 2015 Page 7 of 33


X C
distance protection tripping zone
Z Q2

ZL
E
E
Z Load
Z Load E
A I
Z Q1 R

D
Figure 4: ZLoad calculated by relay A changes during a power swing

But how does the relay distinguish between a stable power swing, an unstable one and a fault?
While the impedance change during a power swing is rather slow, the impedance vector jumps directly into
the tripping zone at a fault occurrence. At a stable power swing the measured impedance enters the
distance protection zones from one side, then turns around and leaves at the same side. During an unstable
power swing the impedance crosses the X axis completely and leaves the zones on the other side.
Therefore the angle increases continuously. Figure 5 illustrates an unstable power swing. The moment
when ZLoad crosses the dashed red line, angle is 180 - this is the theoretical limit for a stable power swing.

OMICRON 2015 Page 8 of 33


X C

Z Q2

ZL
E
E

Z Load E
A I
Z Q1 R

D
Figure 5: Load Impedance during an Instable Power Swing

The relay manufacturers developed different algorithms to decide which case is present. The relay could use
for example a power swing detection zone. This zone surrounds the tripping or the starting zones of the
distance protection. If the impedance is calculated within this area for a given number of measurement
cycles, it is recognized as slowly changing and thus a power swing. Another possibility is to determine the
time the trajectory needs to move through this area. Position and size of this frame are important parameters
and can be set for some protection relays.

X C
distance protection tripping zone
Z Q2

B power swing detection zone

ZL
E
E

Z Load E
A I
Z Q1 R

D
Figure 6: Power Swing Detection Zone

OMICRON 2015 Page 9 of 33


There are two different power swing functions in modern numerical relays:
1. Power Swing Blocking: The whole distance protection or only assigned zones are blocked when a
power swing occurs.
2. Power Swing Tripping: The relay trips after detecting an unstable power swing.
Whether any one of these functions is used or if even both functions are used depends on the requirements
at the corresponding grid node where the distance protection relay is installed. As example for this
Application Note it is assumed that the distance protection relay uses only the first function (Power Swing
Blocking).

For more information about power swing see [2] and [3].

OMICRON 2015 Page 10 of 33


3 System Under Test

3.1 Application Example Protected Line and Time Grading

The following figure shows the line protected by a Distance Protection Relay with Power Swing Blocking
that is used as example in the RelaySimTest template.

1 Line Data
50 Hz
Solidly grounded
110 kV
600 A
32.5 km
R = 0.193 Ohm/km
X = 0.4 Ohm/km
RN/R = 0.6
XN/X = 0.6

A 2 80% Z2 B

Z1

3
CT A
600 A / 1 A

4
VT A
110 kV / 100 V
Relay
A

Figure 7: Example Line protected by Distance Protection Relay using Power Swing Blocking

Figure 7 shows that the distance relay protects the line with Zone 1 (Z1) and 2 (Z2), while Figure 8 illustrates
the time grading of the distance protection. The first zone has no time delay, which means the nominal trip
time is 0 s. In the second zone the nominal trip time is 400 ms.

OMICRON 2015 Page 11 of 33


2

Z2
0.4 s
Z1
0s
A

Figure 8: Time Grading

Figure 9 shows distance protection zones of the example in the impedance pane using secondary values.

Figure 9: Distance Zones - Impedance Pane

3.2 Settings of the System Under Test Menu in RelaySimTest


The parameters of the protected line, the protection concept and the substations with their bays and relays
according to the example (see chapter 3.1 ) are set in the System Under Test menu.
The red numbers in Figure 10 correspond to the numbers of Figure 7 and Figure 8 to show where the
different parameters are defined.

OMICRON 2015 Page 12 of 33


Comments:

> Number 1 Protected line: The settings use primary values.

> Number 2 Protection concept: The test template was tested with a Siemens 7SA63 relay.
According to the relays manual a tolerance of 5% for each zone is appropriate.

Figure 10: System under Test menu

> Number 3 Bay A: This menu item contains the sub menu Instrument transformers that includes the
CT direction and the VT location settings.

Figure 11: Instrument Transformers Menu

> Number 4 Relay A: This menu item contains the test voltage and current limits. Relay manuals
specify a voltage and a current that does not cause damage to the relay. The limits of RelaySimTest
have to be adapted according to the current and voltage limits of the relay manual. Nevertheless it is
important to do breaks between the tests to ensure that the relay is not stressed too much!
The binary outputs of the relay under test that are used are described in chapter 4.2.1 .
OMICRON 2015 Page 13 of 33
Figure 12: System Under Test Menu

OMICRON 2015 Page 14 of 33


4 Test Cases
Figure 13 shows the Test cases menu. It contains the tests with their corresponding grid topology (1), test
scenarios (2) and test steps (3). The next three chapter describe these menus referring to the test template
of the application note.

Figure 13: Test Cases Menu

OMICRON 2015 Page 15 of 33


4.1 Application Example Grid Topology

The line of the application example is part of the grid that is shown in Figure 14.

Figure 14: Grid Topology

4.2 Suitable Test Cases

This chapter describes the tests of the corresponding RelaySimTest template. At first some general test
information are explained.

OMICRON 2015 Page 16 of 33


4.2.1 General Information
According to [4] a power swing in the European UCTE-grid (Union for the Co-ordination of Transmission of
Electricity) occurs with a frequency of 0.2 to 1.5 Hz. Therefore the test template that corresponds with this
Application Note uses a power swing frequency of 1 Hz. For another grid the frequency has to be adapted.

When a power swing is induced with both ends reacting in a differing manner (e. g. swing speed, magnitude)
the voltage difference between the infeeds will vary accordingly, driving a similarly varying current. For
easier interpretation it is assumed that infeed 1 is not swinging at all while infeed 2 performs a phase slip.
The phase slip causing a stable power swing is defined by the slip angle and the slip time period. Both
parameters are defined in the Model power system tab of the menu Test Cases.

Figure 15: Model editor showing the Phase Slip parameters

It is also possible to access the phase slip parameters of an infeed in the corresponding widget on the
dashboard of the Design test scenario tab.

Figure 16: Phase Slip parameters in the Design test scenario tab

For a stable power swing the phase slip of infeed 2 is enabled, its slip time period is 1000 ms to realize a
power swing frequency of 1 Hz. The power swing starts at the beginning of the simulation, after the slip time
period the circuit breaker of infeed 2 is opened to stop the stable power swing. The simulation duration is
set to 1500 ms, to ensure that all the relay reactions can be recorded during the test. The slip angle of infeed
2 defines the maximum phase difference between both ends that occurs during the slip time period.

OMICRON 2015 Page 17 of 33


Figure 17: Test Scenario Stable Power Swing

To create an unstable power swing these two parameters are not used, instead a frequency difference of 1
Hz between the two infeeds defines the unstable power swing frequency. After one power swing period (1 s)
the circuit breaker of infeed 2 is opened to stop the unstable power swing. Sometimes it can be necessary to
test with multiple power swing cycles, in that case the opening of circuit breaker 2 has to be adapted.

To keep the template simple, test cases with faults use only the following Fault types:

> L1-N
> L2-L3
> L1-L2-L3

Depending on the relay under test, on the relays parameters and on the grid where the protection system is
used, it can be necessary to add more fault types.

All test cases should have an adequate simulation time to cover the whole test scenario and to ensure that
the relay has enough time to show its reaction on the test.

The test template uses by default the following binary relay signals:

Relay Signal Abbreviation used in the template


Distance Protection Trip DP Trip
Distance Protection Pickup DP Pickup
Power Swing Detection PS Detection
Power Swing Unstable PS Unstable
Power Swing Trip PS Trip

OMICRON 2015 Page 18 of 33


4.2.2 Synchronize to TransView Feature
The OMICRON TransView software is useful to analyze the test results. Here it is possible to display the
impedance and power trajectories resulting from the test voltages and currents. The feature Synchronize to
TransView in RelaySimTest offers the export of the signals.

Figure 18: Synchronize to TransView Button

It is also possible to display the distance zones in the TransView Circle Diagrams, if they are available as
RIO file for example in the Menu Test Object of the OMICRON Test Universe.
The RIO file can be exported from the Test Universe Test Object as follows:
1. Select File in the Test Object main menu.
2. Select Export in the submenu.
3. Select RIO file type and enter %TEMP%\SIMULATIONTEST.RIO as file name. The RIO file will be
saved in the same location where the RelaySimTest signal export is saved
(C:\Users\UserName\AppData\Local\Temp).
4. Save the file.

Figure 19: RIO export from the menu Test Object of the OMICRON Test Universe

Arrangement: In this application note the impedance resulting from the test voltages and currents is called
ZLoad.

OMICRON 2015 Page 19 of 33


4.2.3 Test Case 1 and 2 Stable Power Swing
These test cases should show, that the relay detects a power swing. Furthermore it should show that its
power swing blocking function prevents the tripping of the distance protection even if the measured
impedance is within a distance protection tripping zone.

> For test case 1 (TC 1) a slip angle of -180 is used. This angle is the theoretical limit for a stable power
swing. It ensures that the impedance ZLoad resulting from the test voltages and currents is close to the
line impedance. Hence it is probably seen in Zone 1 (Z1) of the distance protection function. Figure 20
shows the impedance pane while Figure 21 illustrates the power swing. Both figures were created with
the Synchronize to TransView feature.

Figure 20: Test Case 1 - Impedance Pane

OMICRON 2015 Page 20 of 33


Figure 21: Test Case 1 Power Swing

> For test case 2 a slip angle of +180 is used. While in TC 1 infeed 1 leads infeed 2 during the power
swing, in TC 2 the situation is reversed. Therefore in TC 1 the impedance ZLoad moves from the right to
the left site of the impedance plane and in TC 2 it moves from the left to the right site.

OMICRON 2015 Page 21 of 33


Figure 22: Test Case 2

> During both test cases the impedance ZLoad moves into the distance protection tripping zones. Hence the
distance protection may pickup, if the pickup criteria are fulfilled. The relay should detect the stable power
swing. Therefore it is not allowed to trip.

4.2.4 Test Case 3 and 4 Stable Power Swing with Load


These test cases are similar to test case 1 and 2. But in contrast to them now a load current exists due to
different phase angles of the infeeds.

> If there is no phase angle difference between the infeeds, the impedance ZLoad is infinity and no load
current is flowing. For test case 3 the parameter phase angle of infeed 1 is 20 while the phase angle of
infeed 2 stays at 0. This causes a load current and changes the impedance ZLoad. That means while in
all previous test cases at the beginning of a power swing period ZLoad was infinity (phase angle of infeed
1 and 2 are 0), now it differs from infinity. It has a certain finite value that depends on the phase angle
difference of the infeeds. It is useful to take an angle difference that fits to the system under test. Figure
23 shows a power swing with a finite starting point.

> For test case 3 a slip angle of -160 is used. That means the maximum phase angle difference between
the infeeds is -180 (-20 phase angle and 160 slip angle).

OMICRON 2015 Page 22 of 33


Figure 23: Finite Starting Point

> For test case 4 the phase angle of infeed 1 is -20, while the phase angle of infeed 2 stays at 0.
Furthermore a slip angle of +160 is used.

> In the beginning of both test cases the impedance ZLoad has a finite value due to the phase angle
difference of the infeeds. During the power swing this impedance changes and moves into the distance
protection tripping zones. Hence the distance protection may pickup, if the pickup criteria are fulfilled. The
relay should detect the stable power swing. Therefore it is not allowed to trip.

4.2.5 Test Case 5 and 6 Stable Power Swing with Fault


These test cases should show, that the relay detects a fault during a power swing and that it reacts to it in an
appropriate manner.

> The fault location defines the tripping zone the relay has to use. For the first test steps the fault is
located at 50% of the line (Zone 1 of the distance protection). For the last test steps it is located at 100%
(Zone 2).
> The moment when the fault occurs defines the impedance jump, from the power swing to the fault
impedance. Figure 24 illustrates this. It is useful to create different test cases with different times for the
fault occurrence. To keep the test template simple it uses only one where the fault occurs 0.25 s after the
beginning of the power swing (slip time period is 1 s).
> For test case 5 a slip angle of -180 is used.
> For test case 6 a slip angle of 180 is used.

OMICRON 2015 Page 23 of 33


Figure 24: Test Case 5

> In the beginning of both test cases the impedance ZLoad moves due to the power swing relatively slowly.
The relay should detect the power swing. The moment the fault occurs ZLoad jumps into the distance
protection tripping zones. The distance protection has to trip using the corresponding tripping zone.

4.2.6 Test Case 7 and 8 Unstable Power Swing


These test cases should show, that the relay detects an unstable power swing. Furthermore it should show
that its power swing blocking function prevents the tripping of the distance protection even if the measured
impedance is within a distance protection tripping zone. (According to the application example, the relay
should not trip even if there is an unstable power swing, s. chapter 2.3 .)

> For test case 7 the parameter actual frequency of infeed 2 is set to 49 Hz.
> For test case 8 this parameter is set to 51 Hz.
> For both test cases the frequency of infeed 1 is 50 Hz.
> Figure 25 illustrates the unstable power swing of test case 7

OMICRON 2015 Page 24 of 33


Figure 25: Test Case 7 Unstable Power Swing

> The absolute value of the phase angle difference between the infeeds increases in both test cases from
0 to 360. That means both test cases show an unstable power swing. In TC 7 the impedance ZLoad
moves from the right to the left site of the impedance plane, in TC 8 the situation is reversed. In both
cases the impedance crosses the distance protection tripping zones. The relay has to detect the unstable
power swing and the power swing blocking function has to prevent the distance protection from tripping.

OMICRON 2015 Page 25 of 33


4.2.7 Test Case 9 and 10 Unstable Power Swing with Load
These test cases are similar to test case 3 and 4. But in contrast to them now an unstable power swing is
used instead of a stable one.

> The unstable power swing is realized in the way it is realized in the test cases 7 and 8.

Due to the unstable power swing, the impedance ZLoad crosses the distance protection tripping zones in
the impedance plane. The relay has to detect the unstable power swing and the power swing blocking
function has to prevent the distance protection from tripping.

4.2.8 Test Case 11 and 12 Unstable Power Swing with Fault


These test cases should show, that the relay detects a fault during an unstable power swing and that it
reacts to it in an appropriate manner. The test cases are similar to the test cases 5 and 6. But now an
unstable power swing is used instead of a stable one.

> The unstable power swing is realized in the way it is realized in the test cases 7 and 8.

Due to the unstable power swing, the impedance ZLoad crosses the distance protection tripping zones in
the impedance plane. The relay has to detect the unstable power swing and the power swing blocking
function has to prevent the distance protection from tripping.

OMICRON 2015 Page 26 of 33


4.3 Measurement and Assessment
The Define measurements menu of the Test steps tab (Figure 13) is useful to define start and stop events
for time measurements.

By default there is only a trip time measurement defined in the power swing test template:

> The start measuring event is the beginning of the simulation, if the test scenario does not include a
fault event.
> If it includes a fault event the fault inception is the start measuring event.
> In both cases the moment when the trip signal becomes active is the stop measuring event.

Figure 26: Measurement

The Set assessment condition menu (next to the Define measurements menu) defines the assessment of
the test steps. The previous chapter 4.2 describes the expected tripping behavior of the relay for the
different test cases.
> Only for test cases with a fault event a distance protection trip is expected. By default the test template
only includes measurements but no assessments for the trip times of these test cases. The
assessment has to be added according to the requirements of the system that is tested.

> For all other test cases the assessment condition is Start but no stop event occurs, because a
distance protection trip is not expected.

OMICRON 2015 Page 27 of 33


Figure 27: Set Assessment Condition

5 Test Sets Configuration


This chapter assumes that the following steps are already done:

> The PC is running RelaySimTest


> The PC is already associated to the CMC used for the test
> The wiring between the CMC and the relay is already done.
> The CMC is already switched on
The menu Test sets configuration defines the CMC and its configuration used for the tests. At first the test
template includes a general CMC as shown in Figure 28. The label on the left site of the CMC icon shows
that the CMC belongs to substation A.

Figure 28: Test sets configuration menu of RelaySimTest

After a click on the Choose test set button on the right site of the CMC icon, a new window opens and
shows the CMC that is connected to the PC. A click on the CMC selects it.

OMICRON 2015 Page 28 of 33


The Getting Started manual of RelaySimTest [1] describes how the wiring between the CMCs and the relays
can be configured in the Test sets configuration menu. To perform the tests of this application note the
following signals have to be configured:

> three test voltages


> three test currents
> the distance protection trip and pickup signal of the relay
> the power swing detection, power swing unstable and power swing trip signal of the relay

OMICRON 2015 Page 29 of 33


6 Performing the Test
Before a test is started it is strongly recommended to do a wiring check.

The execute buttons start the tests. There are different execute buttons - Execute all and Execute
selected. Their meaning depends on the menu where they are:

> If a test case is open a click on the Execute selected button executes only the selected test step. A
click on the Execute all button runs all test steps of the test case sequentially (see Figure 30).
> In contrast to this in the Test Manager menu the Execute selected button runs all selected test cases,
while Execute all runs all test cases (see Figure 31).

Especially after tests with high currents it is meaningful to interrupt the test sequence with the Stop button.
This ensures breaks between the tests to avoid too much stress for the relays. Alternatively the Pause
execution setting of the Properties tab of each test case can be used.

Figure 29: Pause execution

Figure 30: Execute selected and Execute all button for a certain test case

OMICRON 2015 Page 30 of 33


Figure 31: Execute selected and Execute all in the test manager menu

OMICRON 2015 Page 31 of 33


7 List of Literature

[1] Getting started with RelaySimTest; OMICRON electronics GmbH; 2014


[2] Numerical Distance Protection: Principles and Applications; 4th edition; Gerhard Ziegler; PUBLICIS;
2011
[3] SIPROTEC Distance Protection 7SA6 V4.70 Manual, SIEMENS
[4] TransmissionCode2007 Netz und Systemregeln der deutschen bertragungsnetzbetreiber, Verband
der Netzbetreiber VDN e.V. beim VDEW, Version 1.1, August 2007

OMICRON 2015 Page 32 of 33


Support
When you are working with our products we want to provide you with the greatest possible
benefits. If you need any support, we are here to assist you.

24/7 Technical Support Get Support


www.omicron.at/support
www.omicronusa.com/support
At our technical support hotline, you can reach well-educated technicians for all of your
questions. Around the clock competent and free of charge.
Make use of our 24/7 international technical support hotline:
Europe / Middle East / Africa +43 59495 4444
Americas +1 713 830-4660 +1 800-OMICRON
Asia-Pacific +852 3767 5500
Additionally, on our website you can find our Service Center or Sales Partner closest
to you.

Customer Area Stay Informed


www.omicron.at/customer
www.omicronusa.com/customer
The Customer Area on our website is an international knowledge exchange platform.
Download the latest software updates for all our products and share your own experiences
in our user forum.
Browse through the knowledge library and find application notes, conference papers,
articles about daily working experiences, user manuals and much more.

OMICRON Academy Learn More


www.omicron.at/academy
www.omicronusa.com/academy
Learn more about your product in one of the training courses offered by the OMICRON
Academy.

Potrebbero piacerti anche