-MEMORIA DE CALCULO

A.- CLCULO DE LA SECCIN DEL ALIMENTADOR GENERAL

Segn el plano de arquitectura se tiene:


2
Area Techada 357.23 m C.Unitaria = 25
2
1 Piso: 164.34 m
2
2 Piso: 192.89 m

2
Area Libre: 6.60 m C Unitaria = 5

1 THERMA = 100 L 90
2 ELECTROBOMBA = 1HP

1.- CLCULO DE LA POTENCIA INSTALADA

P1= Area techada x C.Unitaria= 357.23 x 25= 8931 Watts


P2= Area Libre x C.Unitaria = 6.60 x 5 = 33 Watts
P3= 1 Therma = 1200 = 1200 Watts
P4= 2 electrobomba = 2x750 x0.5 = 750 Watts
P5= Potencia de Reserva = 1500 = 1500 Watts
Potencia Total = 12414 Watts

2.- CLCULO DE LA MXIMA DEMANDA

MD1=(2000 x1)+(4038x0.35) = 4426 Watts


MD2= 33 x 1 = 33 Watts
MD3= 1200 x 1 = 1200 Watts
MD4= 1200 x 1 = 750 Watts
MD5=1500 x 1 = 1500 Watts
MDT = 7909 Watts

6628 Watts 3000 Watts

Entonces el conductor es trifsico : k= 3

3.- CLCULO DE INTENSIDAD DE CORRIENTE

MDT 7909 = 23.06 A


I= =
K x V x COS 3 x 220 x 0.9

FACTOR DE SEGURIDAD = 12%


Segn el CNE
Id = I x 1.12
Id = 23.06 x 1.12 = 25.83 A

Luego los conductores deben trabajar al 80% de su capacidad nominal

Id' = 25.83 / 0.8 = 32.29 A


Con el Id' vamos a la tabla2 y escogemos la seccin del alimentador

SECCIN DEL ALIMENTADOR = 10 mm2

Clculamos la seccin del conductor neutro


Scd = Scv
2
2
Scd = 10 = 5 mm
2

Scd = 5 mm2

4.- VERIFICACIN DE LA CAIDA DE TENSIN

Vperm<2.5%(220) = 5.5

L= 7.87

V= K x Id x x L
S

V= 3 x 25.83x 0.0175 x 13.10 = 0.616


10

0.616 < 5.5 OK

2
S= 10 mm ln= 42 A

Interruptor = 42 x 0.8 33.6 35A

PVC - SAP= 20 mm

3*35A

ALIMENTADOR GENERAL

3x10mm2 TW + 1x5 mm2 - PVC - SAP - 20 mmp


E.-CALCULO DE LA SECCIN DE LOS CONDUCTORES DERIVADOS

CLCULO DE LA SECCIN DE ILUMINACIN 1 PISO

CIRCUITO #1: 6 centros de luz de 100 watts c/u

Potencia Instalada:
P1= 6 x 100 = 600 W

Mxima Demanda:
MD= 500 x 1 = 600 W

W 600 = 3.03 A
I= =
K x V x COS 1 x 220 x 0.9

FACTOR DE SEGURIDAD = 12%

Id = 3.03 x 1.12 = 3.39 A

Id' = 3.39 / 0.8 = 4.24 A


Usamos la tabla2 para determinar la seccin

SECCIN MINIMA 2.5 mm2

VERIFICACIN DE DV
V < 1.5% (220) = 3.3 VOLTIOS


V=

20.0175
V= 2.60 100 + 2.93 2 100 + 5.26 3 100 + 2.08 4 100 + 1.66 100 + 3.08 100
220 2.5
0.237 < 3.3 OK
2
S= 2.5 mm In = 18 A

Interruptor = 18 x 0.8 = 14.4 15 A

2
PVC - SAP= 20 mm

2*15A

C -1 ALUMBRADO
2 x2.5 mm2 TW - PVC - SAP - 20 mm
TABLERO DE DISTRIBUCION 1 - PRIMER PISO

CIRCUITO # 14: 2 ELECTROBOMBA = 1HP

Potencia Instalada:
P1= 750x0.5x2 = 750 W

Mxima Demanda:
MD= 750 x 1 = 750 W

W 750 = 3.79 A
I= =
K x V x COS 1 x 220 x 0.9

FACTOR DE SEGURIDAD = 12%

Id = 3.79 x 1.12 = 4.24 A

Id' = 4.52 / 0.8 = 5.30 A

Usamos la tabla 2 para determinar la seccin

SECCIN MINIMA = 2.5 mm2

VERIFICACIN DE DV

V < 1.5% (220) = 3.3 VOLTIOS

L = 3.09 m
K = 2.00

V= K x Id x x L = 2x 4.24 x 0.0175 x 3.09= 0.184


S 2.5
0.184 < 3.3 OK
2
S= 2.5 mm In = 18 A

Interruptor = 18 x 0.8 = 14.4 15 A

2
PVC - SAP= 20 mm

2*15A

C -14 2 ELECTROBOMBA

2 x 2.5 mm2 TW - PVC - SAP - 20 mm


CLCULO DE LA SECCIN DE ILUMINACIN 2 PISO

CIRCUITO #5: 8 centros de luz de 100 watts c/u

Potencia Instalada:
P1= 8 x 100 = 800 W

Mxima Demanda:
MD= 1000 x 1 = 800 W

W 800 = 4.04 A
I= =
K x V x COS 1 x 220 x 0.9

FACTOR DE SEGURIDAD = 12%

Id = 5.05 x 1.12 = 4.53 A

Id' = 4.53 / 0.8 = 5.66 A


Usamos la tabla 2 para determinar la seccin

SECCIN MINIMA = 2.5 mm2

VERIFICACIN DE DV

V < 1.5% (220) = 3.3 VOLTIOS

V=


V= 20.0175
1.75 100 + 4.12 2 100 + 4.06 3 100 + 2.39 4 100 + 5.27 5
220 2.5
100 + 5.32 6 100 + 2.65 7 100 + 6.74 8 100
1.034 < 3.3 OK
2
S= 2.5 mm In = 18 A

Interruptor = 18 x 0.8 = 14.4 15 A

PVC - SAP= 20 mm2

2*15A

C -7 ALUMBRADO

2 x 2.5 mm2 TW - PVC - SAP - 20 mm


CIRCUITO # 7: 7 centros de luz de 100 watts c/u

Potencia Instalada:
P1= 7 x 100 = 700 W

Mxima Demanda:
MD= 1000 x 1 = 700 W

W 700 = 3.54 A
I= =
K x V x COS 1 x 220 x 0.9

FACTOR DE SEGURIDAD = 12%

Id = 3.54 x 1.12 = 3.96 A

Id' = 3.96 / 0.8 = 4.95 A

Usamos la tabla2 para determinar la seccin

SECCIN MINIMA = 2.5 mm2

VERIFICACIN DE DV

V < 1.5% (220) = 3.3 VOLTIOS


V=

V= 20.0175
2.70 100 + 3.48 2 100 + 3.66 3 100 + 1.32 4 100 + 5.83 5
220 2.5
100 + 3.11 100 + 2.71 100
0.387 < 3.3 OK
2
S= 2.5 mm In = 18 A

Interruptor = 18 x 0.8 = 14.4 15 A

PVC - SAP= 20 mm2

2*15A

C -7 ALUMBRADO

2 x 2.5 mm2 TW - PVC - SAP - 20 mm


CLCULO DE LA SECCIN DE TOMACORRIENTE DEL 1 PISO Y SEGUNDO PISO

PRIMER PISO

CIRCUITO # 8: 4 tomacorrientes de 150 watts c/u

Potencia Instalada:
P1= 4x 150 = 600 W

Mxima Demanda:
MD= 600 x 1 = 600 W

W 600 = 3.03 A
I= =
K x V x COS 1 x 220 x 0.9

FACTOR DE SEGURIDAD = 12%

Id = 3.03 x 1.12 = 3.39 A

Id' = 3.39 / 0.8 = 4.24 A


Usamos la tabla2 para determinar la seccin

SECCIN MINIMA = 4.0 mm2

VERIFICACIN DE DV

V < 1.5% (220) = 3.3 VOLTIOS


V=

20.0175
V= 6.5 150 + 6.95 2 150 + 4.93 3 150 + 0.43 4 150
220 4
0.220 < 3.3 OK
2
S= 4.0 mm In = 24 A

Interruptor = 24 x 0.8 = 19.2 20 A

2
PVC - SAP= 20 mm

2*20A

C-8 TOMACORRIENTES

2x 4 mm2 TW + 1x2.5mm2 - PVC - SAP - 20 mm


SEGUNDO PISO

CIRCUITO #9: 17 tomacorrientes de 150 watts c/u

Potencia Instalada:
P1= 17 x 150 = 2400 W

Mxima Demanda:
MD= 2400 x 1 = 2400 W

I= W 2400 = 12.12 A
=
K x V x COS 1 x 220 x 0.9

FACTOR DE SEGURIDAD = 12%

Id = 12x 1.12 = 13.58 A

Id' = 7.36/ 0.8 = 16.97 A

Usamos la tabla2 para determinar la seccin

SECCIN MINIMA = 4.0 mm2

VERIFICACIN DE DV

V < 1.5% (220) = 3.3 VOLTIOS

V=

20.0175
V= 6.5 150 + 6.95 2 150 + 4.93 3 150 + 0.43 4 150
220 4
0.490 < 3.3 OK

2
S= 4.0 mm In = 24 A

Interruptor = 24 x 0.8 = 19.2 20 A

2
PVC - SAP= 20 mm

2*20A

TOMACORRIENTE
C -9
2 x4 mm2 TW - PVC - SAP - 20 mm
TABLERO DE DISTRIBUCIN 3 - PRIMER PISO

CIRCUITO # 13: 6 tomacorrientes de 150 watts c/u

Potencia Instalada:
P1= 6 x 150 = 900 W

Mxima Demanda:
MD= 900 x 1 = 900 W

W 900 = 4.55 A
I= =
K x V x COS 1 x 220 x 0.9

FACTOR DE SEGURIDAD = 12%

Id = 6.57 x 1.12 = 5.09 A

Id' = 7.36 / 0.8 = 6.36 A

Usamos la tabla2 para determinar la seccin

SECCIN MINIMA = 4.0 mm2

VERIFICACIN DE DV

V < 1.5% (220) = 3.3 VOLTIOS


V=

V= 20.0175
4.79 150 + 2.63 2 150 + 2.32 3 150 + 1.90 4 150
220 4
+ 2.51 5 150 + 0.77 6 150
0.300 < 3.3 OK
2
S= 4.0 mm In = 24 A

Interruptor = 24 x 0.8 = 19.2 20 A

2
PVC - SAP= 20 mm

2*20A

C -6 TOMACORRIENTES

2 x4mm2 TW - PVC - SAP - 20 mm


TABLERO DE DISTRIBUCIN 2 - PRIMER PISO

CIRCUITO # 11: 6 tomacorrientes de 150 watts c/u

Potencia Instalada:
P1= 6 x 150 = 900 W

Mxima Demanda:
MD= 900 x 1 = 900 W

W 900 = 4.55 A
I= =
K x V x COS 1 x 220 x 0.9

FACTOR DE SEGURIDAD = 12%

Id = 6.57 x 1.12 = 5.09 A

Id' = 7.36 / 0.8 = 6.36 A

Usamos la tabla2 para determinar la seccin

SECCIN MINIMA = 4.0 mm2

VERIFICACIN DE DV

V < 1.5% (220) = 3.3 VOLTIOS


V=

V= 20.0175
1.95 150 + 3.76 2 150 + 5.24 3 150 + 4.45 4 150
220 4
+ 2.87 5 150 + 1.81 6 150
0.407 < 3.3 OK
2
S= 4.0 mm In = 24 A

Interruptor = 24 x 0.8 = 19.2 20 A

2
PVC - SAP= 20 mm

2*20A

C -11 TOMACORRIENTES

2 x4mm2 TW - PVC - SAP - 20 mm


CLCULO DE LA SECCIN DE THERMA

CIRCUITO #6:

Potencia Instalada:
P1= 1200 = 1200 W

Mxima Demanda:
MD= 1200 x 1 = 1200 W

W 1200 = 6.06 A
I= =
K x V x COS 1 x 220 x 0.9

FACTOR DE SEGURIDAD = 12%

Id = 6.06 x 1.12 = 6.79 A

Id' = 6.79 / 0.8 = 8.48 A

Usamos la tabla2 para determinar la seccin

SECCIN MINIMA = 2.5 mm2

VERIFICACIN DE DV

V < 1.5% (220) = 3.3 VOLTIOS

L= 4.87

V= K x Id x x L = 2x6.79 x0.0175 x 4.87= 0.463


S 2.5
0.463 < 3.3 OK
2
S= 2.5 mm In = 18 A

Interruptor = 18 x 0.8 = 14.4 15 A

2
PVC - SAP= 13 mm

2*15A

THERMA
C -6
2x 2.5 mm2 TW - PVC - SAP - 15 mml
C.- CLCULO DE LA SECCIN DEL ALIMENTADOR DEL TABLERO DE DISTRIBUCION 2

Segn el plano de arquitectura se tiene:


2
Area Techada ( TIENDA 01) = 91.56 m C.Unitaria = 25

1.- CLCULO DE LA POTENCIA INSTALADA

P1= Area techada x C.Unitaria= 91.56 x 20 = 1831 Watts


P2= Potencia de Reserva = 1500 Watts
Potencia Total = 3331 Watts

2.- CLCULO DE LA MXIMA DEMANDA

MD1=(2000 x1)+(289x0.35) = 1831.20 Watts


MD2=1500 x 1 = 1500 Watts
MDT = 3331.20 Watts

3331.20 Watts 3000 Watts

Entonces el conductor es trifsico : k= 3

3.- CLCULO DE INTENSIDAD DE CORRIENTE

I= MDT = 3331.20 = 9.71 A


K x V x COS 3 x 220 x 0.9

FACTOR DE SEGURIDAD = 12%


Segn el CNE
Id = I x 1.12
Id = 9.71 x 1.12 = 10.88 A

Luego los conductores deben trabajar al 80% de su capacidad nominal

Id' = 10.88 / 0.8 = 13.60 A

Con el Id' vamos a la tabla2 y escogemos la seccin del alimentador

SECCIN DEL ALIMENTADOR = 4 mm2


4.- VERIFICACIN DE LA CAIDA DE TENSIN

Vperm<2.5%(220) = 5.5

L= 10.32

V= K x Id x x L
S

V= 3 x 10.80x 0.0175 x 13.10 = 0.851


4

0.851 < 5.5 OK

2
S= 4 mm ln= 24 A

Interruptor = 24 x 0.8 19.2 20A

PVC - SAP= 20 mm

3*20A

ALIMENTADOR TD-2

3x4mm2 TW - PVC - SAP - 20 mmp


B.- CLCULO DE LA SECCIN DEL ALIMENTADOR DEL TABLERO DE DISTRIBUCION 1

Segn el plano de arquitectura se tiene:

2 ELECTROBOMBA = 1HP

1.- CLCULO DE LA POTENCIA INSTALADA

P1= 2 electrobomba = 750.00 x 2x0.5 = 750 Watts


P2= Potencia de Reserva = 1500 Watts
Potencia Total = 2250 Watts

2.- CLCULO DE LA MXIMA DEMANDA

MD1=750*1 = 750 Watts


MD2=1500 x 1 = 1500 Watts
MDT = 2250 Watts

2250 Watts 3000 Watts

Entonces el conductor es trifsico : k= 2

3.- CLCULO DE INTENSIDAD DE CORRIENTE

I= MDT = 2250 = 5.68 A


K x V x COS 2 x 220 x 0.9

FACTOR DE SEGURIDAD = 12%


Segn el CNE
Id = I x 1.12
Id = 7.14 x 1.12 = 6.36 A

Luego los conductores deben trabajar al 80% de su capacidad nominal

Id' = 9.80/ 0.8 = 7.95 A

Con el Id' vamos a la tabla2 y escogemos la seccin del alimentador

SECCIN DEL ALIMENTADOR = 2.5 mm2


TABLERO DE DISTRIBUCION 2 - PRIMER PISO

CIRCUITO #10: 4 centros de luz de 100 watts c/u

Potencia Instalada:
P1= 4 x 100 = 400 W

Mxima Demanda:
MD= 400x 1 = 400 W

W 400 = 2.02 A
I= =
K x V x COS 1 x 220 x 0.9

FACTOR DE SEGURIDAD = 12%

Id = 2.02 x 1.12 = 2.26 A

Id' = 2.26 / 0.8 = 2.83 A

Usamos la tabla2 para determinar la seccin

SECCIN MINIMA 2.5 mm2

VERIFICACIN DE DV
V < 1.5% (220) = 3.3 VOLTIOS


V=

20.0175
V= 1.83 100 + 4.73 2 100 + 2.22 3 100 + 2.10 100
220 2.5
0.128 < 3.3 OK
2
S= 2.5 mm In = 18 A

Interruptor = 18 x 0.8 = 14.4 15 A

2
PVC - SAP= 20 mm

2*15A

C -10 ALUMBRADO

2 x2.5 mm2 TW - PVC - SAP - 20 mm


TABLERO DE DISTRIBUCION 3 - PRIMER PISO

CIRCUITO #12: 4 centros de luz de 100 watts c/u

Potencia Instalada:
P1= 4 x 100 = 400 W

Mxima Demanda:
MD= 400x 1 = 400 W

W 400 = 2.02 A
I= =
K x V x COS 1 x 220 x 0.9

FACTOR DE SEGURIDAD = 12%

Id = 2.02 x 1.12 = 2.26 A

Id' = 2.26 / 0.8 = 2.83 A


Usamos la tabla2 para determinar la seccin

SECCIN MINIMA 2.5 mm2

VERIFICACIN DE DV
V < 1.5% (220) = 3.3 VOLTIOS


V=

20.0175
V= 2.29 100 + 4.68 2 100 + 1.93 3 100 + 1.04 4 100
220 2.5
0.137 < 3.3 OK
2
S= 2.5 mm In = 18 A

Interruptor = 18 x 0.8 = 14.4 15 A

2
PVC - SAP= 20 mm

2*15A

C -12 ALUMBRADO

2 x2.5 mm2 TW - PVC - SAP - 20 mm


D.- CLCULO DE LA SECCIN DEL ALIMENTADOR DEL TABLERO DE DISTRIBUCION 3

Segn el plano de arquitectura se tiene:


2
Area Techada ( TIENDA 02) = 47.45 m C.Unitaria = 25

1.- CLCULO DE LA POTENCIA INSTALADA

P1= Area techada x C.Unitaria= 47.45 x 20 = 949 Watts


P2= Potencia de Reserva = 1500 Watts
Potencia Total = 2449 Watts

2.- CLCULO DE LA MXIMA DEMANDA

MD1=(2000 x1)+(23.25x0.35) = 949 Watts


MD2=1500 x 1 = 1500 Watts
MDT = 2449 Watts

2449 Watts 3000 Watts

Entonces el conductor es trifsico : k= 2

3.- CLCULO DE INTENSIDAD DE CORRIENTE

I= MDT = 2449 = 6.18 A


K x V x COS 3 x 220 x 0.9

FACTOR DE SEGURIDAD = 12%


Segn el CNE
Id = I x 1.12
Id = 7.14 x 1.12 = 6.93 A

Luego los conductores deben trabajar al 80% de su capacidad nominal

Id' = 8.00/ 0.8 = 8.66 A

Con el Id' vamos a la tabla2 y escogemos la seccin del alimentador

SECCIN DEL ALIMENTADOR = 4 mm2


4.- VERIFICACIN DE LA CAIDA DE TENSIN

Vperm<2.5%(220) = 5.5

L= 10.93

V= K x Id x x L
S

V= 3 x 8.00x 0.0175 x 13.10 = 0.574


4

0.574 < 5.5 OK

2
S= 4 mm ln= 24 A

Interruptor = 24 x 0.8 19.2 20A

PVC - SAP= 20 mm

2*20A

ALIMENTADOR TD-3

2x4mm2 TW - PVC - SAP - 20 mmp


4.- VERIFICACIN DE LA CAIDA DE TENSIN

Vperm<2.5%(220) = 5.5

L= 7.75

V= K x Id x x L
S

V= 3 x 9.80x 0.0175 x 13.10 = 0.598


2.5

0.598 < 5.5 OK

2
S= 2.5 mm ln= 18 A

Interruptor = 18 x 0.8 14.4 15A

PVC - SAP= 20 mm

2*15A

ALIMENTADOR TD-1

2x2.5mm2 TW - PVC - SAP - 20 mmp