Sei sulla pagina 1di 109

Health Technical

Memorandum 05-02: Firecode


Guidance in support of
functional provisions
(Fire safety in the design of
healthcare premises) 2014 edition

April 2014
Health Technical Memorandum
05-02: Firecode
Guidance in support of
functional provisions
(Fire safety in the design of
healthcare premises)
2014 edition
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

Crown copyright 2014

You may re-use this information (not including logos) free of charge in any format or
medium, under the terms of the Open Government Licence. To view this licence, visit www.
nationalarchives. gov.uk/doc/open-government-licence/ or write to the Information Policy
Team, The National Archives, Kew, London TW9 4DU, or email: psi@nationalarchives.gsi.gov.
uk.
This document is available from our website at https://www.gov.uk/government/collections/
health-technical-memorandum-disinfection-and-sterilization

iv
Preface

About Health Technical Memoranda It is not the intention within this suite of
documents to unnecessarily repeat international
Health Technical Memoranda (HTMs) give or European standards, industry standards or
comprehensive advice and guidance on the UK Government legislation. Where appropriate,
design, installation and operation of specialised these will be referenced.
building and engineering technology used in the
delivery of healthcare. Healthcare-specific technical engineering
guidance is a vital tool in the safe and efficient
The focus of Health Technical Memorandum operation of healthcare facilities. Health
guidance remains on healthcare-specific Technical Memorandum guidance is the main
elements of standards, policies and up-to-date source of specific healthcare-related guidance
established best practice. They are applicable for estates and facilities professionals.
to new and existing sites, and are for use at
various stages during the whole building The core suite of nine subject areas provides
lifecycle (see diagram below). access to guidance which:
Healthcare providers have a duty of care to is more streamlined and accessible;
ensure that appropriate governance
arrangements are in place and are managed encapsulates the latest standards and best
effectively. The Health Technical Memorandum practice in healthcare engineering,
series provides best practice engineering technology and sustainability;
standards and policy to enable management of
this duty of care. provides a structured reference for healthcare
engineering.

DISPOSAL CONCEPT

REUSE
DESIGN&IDENTIFY
OPERATIONAL OPERATIONAL
MANAGEMENT REQUIREMENTS

Ongoing SPECIFICATIONS

MAINTENANCE TECHNICAL&OUTPUT

Review

PROCUREMENT
COMMISSIONING

CONSTRUCTION
INSTALLATION

Figure 1 Healthcare building life-cycle

v
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

Structure of the Health Technical Health Technical Memorandum 05


Fire safety
Memorandum suite
The series contains a suite of nine core Health Technical Memorandum 06
subjects: Electrical services

Health Technical Memorandum 00 Health Technical Memorandum 07


Policies and principles (applicable to all Environment and sustainability
Health Technical Memoranda in this series)
Health Technical Memorandum 08
Choice Framework for local Policy and Specialist services
Procedures 01
Decontamination All Health Technical Memoranda are supported
by the initial document Health Technical
Health Technical Memorandum 02 Memorandum 00 which embraces the
Medical gases management and operational policies from
previous documents and explores risk
Health Technical Memorandum 03 management issues.
Heating and ventilation systems
Some variation in style and structure is reflected
Health Technical Memorandum 04 by the topic and approach of the different
Water systems review working groups.

FIC DOC
H SPECI UM
L T EN
A TS
HE
HTM08
HTM01
Specialist
Services Decontamination

S T R Y S TA N D A
DU RD
IN S
& EUROPEAN
NAL ST
HTM07
IO HTM02
T

AN
NA

Environment& Medical
DA
H E A LT H S P E

INTER

CUMENTS

Sustainability Gases
RDS

HTM00
RDS
INTER

Policiesand
Principles
DA
NA

AN

IO
ST
T

NA
DO

HTM06 L& N HTM03


Electrical
IN EUROPEA S Heating&
DU D
C

Services STR AR Ventilation


IF I

IC

Y S TA N D Systems
IF
C

EC
D

HTM05 HTM04
O

Fire
SP

U Water
C

M Safety Systems H
EN T
TS AL
HE
Figure 2 Engineering guidance

vi
Preface

DH Estates and Facilities Division wishes to Activity DataBase (ADB)


acknowledge the contribution made by The Activity DataBase (ADB) data and software
professional bodies, engineering consultants, assists project teams with the briefing and
healthcare specialists and NHS staff who have design of the healthcare environment. Data is
contributed to the production of this guidance. based on guidance given in the Health Building
Notes and Health Technical Memoranda.
Other resources in the DH Estates
For ADB technical queries only, contact the
and Facilities knowledge series ADB Helpdesk. Telephone number: 01939
291684; email: support@talonsolutions.co.uk
Health Building Notes
Health Building Notes give best practice For new ADB customers and licence renewals
guidance on the design and planning of new only, email: adblicencerenewals@dh.gsi.gov.uk
healthcare buildings and on the adaptation/
extension of existing facilities.
How to obtain publications
They provide information to support the briefing Health Technical Memoranda are available
and design processes for individual projects in from the UK Goverments website at:
the NHS building programme.. https://www.gov.uk/government/collections/
health-technical-memorandum-disinfectionand-
All Health Technical Memoranda should be sterilization
read in conjunction with the relevant parts of
the Health Buidling Note series. Health Building Notes are available from the
same site at:
https://www.gov.uk/government/collections/
health-building-notes-core-elements

vii
Executive summary

This is the 2014 edition of Health Technical CQC Code Service type
Memorandum (HTM) 05-02 Guidance in
support of functional provisions (Fire safety in ACS Acute services
the design of healthcare premises). The
document has been revised to reflect changes HBC Hyperbaric chamber services
in legislation, guidance, the structure of the
HPS Hospice services
NHS, and government policy and direction on
health and social care. A summary of major LTC Long-term condition services
changes since previous editions is provided at
the end of this Executive Summary. MLS Hospital services for people with
mental health needs, and/or
This 2014 edition supersedes all previous learning disabilities, and/or
versions of HTM 05-02. problems with substance misuse

Scope RHS Rehabilitation services

HTM 05-02 and the series of which it is part RSM Residential substance misuse
provide specific guidance on fire safety in the and treatment/rehabilitation
design of new healthcare premises and major services
new extensions to existing healthcare premises.
While not intended to cover every possible DTS Doctors treatment services
scenario, the standards and principles it
advocates recognise that fire safety in DSS Diagnostic and/or screening
healthcare premises is dependent on the services
interaction between physical fire precautions,
the dependency of the patient, the fire hazards UCS Urgent care services
and the availability of sufficient and
HTM 05-02 should allow the current statutory
appropriately trained staff to safely evacuate
regulations to be applied sensibly within a
patients in a fire emergency.
framework of understanding and if applied
The guidance is applicable to all premises correctly, will satisfy all the requirements of
regulated by the Care Quality Commission Part B of Schedule 1 of the 2010 Building
(CQC), irrespective of ownership, that provide Regulations.
the following types of service:
Dependent on the requirements, this document
should also be read in conjunction with the

viii
Executive summary

relevant HTMs and Health Building Notes Structure


(HBNs).
The guidance in HTM 05-02 has been
restructured to reflect the requirements of
Aim Part B of Schedule 1 of the 2010 Building
The aim of HTM 05-02 is to ensure that Regulations:
everyone concerned with the management, Chapter 1 provides an overview of the
design, procurement and use of the healthcare application of HTM 05-02.
facility understands the requirements of fire
safety in order to ensure optimum safety for all Chapter 2 describes the principles of fire
who are present in the building. Only by having safety in healthcare premises.
knowledge of these requirements can the Chapter 3 describes the requirements to
organisations board and senior managers meet B1 Means of warning and
understand their legal duties to provide safe, escape.
efficient, effective and reliable systems which
are critical in supporting direct patient care. Chapter 4 describes the requirements to
meet B2 Internal fire spread (linings).
By following this guidance and applying it to
the particular needs of their local healthcare Chapter 5 describes the requirements to
organisation, boards and individual senior meet B3 Internal fire spread (structure).
managers should be able to demonstrate Chapter 6 describes the requirements to
compliance with their responsibilities. meet B4 External fire spread.
Chapter 7 describes the requirements to
Users of the guidance meet B5 Access and facilities for the
The guidance is aimed at a wide range of users fire and rescue service.
including:
Providers of NHS-funded healthcare and List of major changes since the
operating facilities in England; 2007 edition
Design teams, including architects and Chapter 1 recognises the role of the Care
engineers; Quality Commission in regulating NHS-
funded care and limits the application of
Local building control authorities and HTM 05-02 to premises providing
approved inspectors; and specific regulated services types; the
Fire and rescue services. guidance on consultation has been
expanded and the need to prepare
Commissioners of NHS-funded health and care fire safety information to comply with
expect that the facilities to which they refer Regulation 38 of the Building Regulations
patients will provide a safe, caring environment and the Regulatory Reform (Fire Safety)
that aids a patients recovery and does not Order emphasised.
expose them to undue risk. Documented The glossary of terms has been moved to
evidence that shows compliance with this Appendix A.
guidance should provide supporting material to
underpin evaluation within the NHS Premises Chapter 2 (previously Chapter 3) now
Assurance Model (NHS PAM) and provide includes comprehensive guidance on the
confidence of standards to the board of designing for fire safety in premises
directors and the Care Quality Commission providing in-patient mental health
(CQC).

ix
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

services and in-patient accommodation superseded document and include a


for people with learning disabilities. number of technical changes particularly
in relation to fire hazard rooms and the
Chapter 3 combines guidance on location and operation of fire dampers,
detection and alarm, and means of and fire and smoke dampers.
escape, and includes revised guidance
on the provision and use of escape lifts. The guidance on access and facilities for
the fire rescue service is essentially
Chapters 4, 5, 6 and 7 provide guidance unchanged.
that was previously in Chapter 6 of the

x
Policy and regulatory overview

This section of guidance provides an overview provide people with safe, effective,
of the policy and regulatory framework relevant compassionate, high-quality care and to
to HTM 05-02. encourage care services to improve.

At the time of preparing this document for


Assurance of estates and facilities publication, registration requirements are
One of the governments key priorities is set out in the Care Quality Commission
delivering better health outcomes for patients. (Registration) Regulations 2009 (CQC
Regulations) and include requirements
The quality and fitness-for-purpose of the relating to:
healthcare estate is vital for high-quality, safe
safety and suitability of premises;
and efficient healthcare, and this document
sets out the general principles of fire safety safety, availability and suitability of
used in the construction of the healthcare equipment; and
estate.
cleanliness and infection control.
Quality and fitness-for-purpose of the estate are
assessed against a set of legal requirements Note on amendment to the CQC
and standards. Adherence to the guidance Regulations
outlined in this Health Technical Memorandum
(HTM) will be taken into account as evidence New regulations are due to come into effect
towards compliance with these legal during 2014 and will apply to all providers of
requirements and standards. health and social care that are required to
register with the CQC.
Where the principles of the guidance are not to
be followed, organisations should document
The CQC is responsible for assessing
how expectations are being met by equal and
whether providers are meeting the registration
alternative means.
requirements (see the CQCs Guidance about
compliance (2010)). Failure to comply with the
Care Quality Commission: Essential CQC Regulations is an offence and, under the
Health and Social Care Act 2008 (Regulated
standards of quality and safety Activities) Regulations 2010, CQC has a wide
The Care Quality Commission (CQC) regulates range of enforcement powers that it can use
all providers of regulated health and adult social if the provider is not compliant. These include
care activities in England. The CQCs role is to the issue of a warning notice that requires
make sure health and social care services improvement within a specified time,

xi
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

prosecution, and the power to cancel a are safe for the occupants and those in the
providers registration, removing its ability to immediate vicinity. Responsibility for complying
provide regulated activities. with the Fire Safety Order rests with the
responsible person, which for the majority of
Outcome 10 of the CQCs Guidance about healthcare organisations will be the employer.
compliance focuses on the safety and
suitability of premises and decrees that A full explanation of the requirements of the
people receive care in, work in or visit safe Fire Safety Order is contained in HTM 05-01.
surroundings that promote their wellbeing.
HTMs are specifically referenced in the CQCs
schedule of applicable publications as a NHS Constitution
means of compliance with Outcome 10. The NHS Constitution sets out the rights to
which patients, public and staff are entitled.
It also outlines the pledges that the NHS is
Building Regulations committed to achieve, together with
The Building Regulations set out requirements responsibilities that the public, patients and
with which individual aspects of building design staff owe to one another to ensure that the
and construction must comply in the interests NHS operates fairly and effectively. All
of: healthcare organisations will be required by law
to take account of this Constitution in their
the health and safety of building users; decisions and actions.
energy conservation; and
Healthcare organisations need to ensure that
access to and use of buildings. services are provided in a clean and safe
environment that is fit for purpose, based on
Part B of Schedule 1 of the Building national best practice (pledge).
Regulations details the functional requirements
to provide for fire safety. Guidance on the In order to deliver on this pledge, it specifically
application of the regulations is provided in advises NHS organisations to take account of:
approved codes of practice The Approved
Documents; Approved Document B Fire national best-practice guidance for the
Safety (Volume 2 Buildings other than design and operation of healthcare
dwelling houses) provides guidance on facilities;
compliance with fire safety requirements for the NHS Premises Assurance Model
some of the more common building types. (NHS PAM).
HTM 05-02 has been prepared in order to
provide specific guidance for healthcare NHS Premises Assurance Model
premises to demonstrate compliance with
The NHS has developed, with the support of
Part B of Schedule 1 of the Building
DH, the NHS Premises Assurance Model (NHS
Regulations.
PAM), whose remit is to provide assurance for
the healthcare environment and to ensure that
Regulatory Reform (Fire Safety) patients, staff and visitors are protected against
risks associated with hazards such as unsafe
Order 2005 premises.
The Regulatory Reform (Fire Safety) Order
2005 (Fire Safety Order) imposes a general Primarily aimed at providing governance and
duty to take such fire precautions as may be assurance to boards of organisations, it allows
reasonably required to ensure that premises organisations that provide NHS-funded care

xii
Policy and regulatory overview

and services to better understand the Healthcare organisations need to be mindful


effectiveness, quality and safety with which of the Climate Change Act and the resultant
they manage their estates and facilities services measures that need to be taken, particularly
and how that links to patient experience and with regard to flooding, drought, hot weather
patient safety. and freezing temperatures (for further guidance,
see Health Building Note (HBN) 00-07
Key questions are underpinned by prompt Planning for a resilient healthcare estate).
questions that require the production of
evidence. Healthcare organisations should There are two main areas of focus for action
prepare and access this evidence to support with respect to climate change:
their assessment of the NHS PAM.
Mitigation which reduces the impact
The model also includes reference to evidence of business functions on the climate
and guidance as a helpful aide-memoire to through the lowering of carbon emissions
assist in deciding the level of NHS PAM from energy use, the reduction of water
assurance applicable to a particular healthcare consumption, improved efficiency of
site or organisation. transport etc. Under the Climate Change
Act, the government has set up the
NHS PAM is designed to be available as a CRC Energy Efficiency Scheme, which
universal model to apply across a range of requires large public and private sector
estates and facilities management services. organisations to achieve energy-saving
targets.
For more information on how to use the tool,
visit the NHS PAM website. Adaptation which requires measures
be put in place to minimise the adverse
effects of climate change (for example
Impact from, and adapting to, flooding, storms, heatwaves and impact
climate change on air quality). With respect to buildings
and infrastructure, flooding is identified as
Requirements under Part B of the Building the main threat by the current UK Climate
Regulations and the guidance in this HTM are Change Risk Assessment. The next
made for the purpose of ensuring the health update to this assessment is expected
and safety of people in and around buildings. in 2017.
The Environment Agency publishes guidance All public sector bodies are required by
on the design and construction of buildings government under the National Adaptation
for the purpose of protecting the environment. Programme (NAP) to put plans in place to
This includes Pollution Prevention Guidelines address both the causes and consequences of
(PPG18) on Managing Fire Water and Major climate change.
Spillages, which seeks to minimise the effects
of water run-off from firefighting. The Sustainable Development Unit (SDU) has
promoted the development of a sustainable
It should be noted that compliance with the development management plan (SDMP) by all
Building Regulations does not depend upon healthcare provider organisations. Further
compliance with other such guidance. details can be found on the SDUs website.

xiii
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

Contents

Preface v
Executive summaryviii
Policy and regulatory overview xi

Assuranceofestatesandfacilities xi

CareQualityCommission:Essentialstandardsofqualityandsafety xi

BuildingRegulations xii

RegulatoryReform(FireSafety)Order2005 xii

NHSConstitution xii

NHSPremisesAssuranceModel xii

Impactfrom,andadaptingto,climatechange xiii

1. Introduction1

Generalapplication 1

BuildingRegulations 1

Firesafetyinformation 2

Consultationandqualitativedesignreview 3

Alternativesolutions 4

Usebycompetentpersons 5

RelationshipwithConstruction(DesignandManagement)Regulations2006 5

Firesafetyduringbuildingoperations 5

Certificationschemes 5

2. Principles of fire safety in healthcare premises6

Introduction 6

Firesafetyphilosophy 6

Progressivehorizontalevacuation 7

Hospitalstreets 7

Verticalescape 8

Specificconsiderationsbasedonpatientdependency 8

HealthcarepremisesinPurposeGroup5AssemblyandRecreation 10

Facilitiesprovidingin-patientmentalhealthservicesandin-patientaccommodationforpeople

withlearningdisabilities 10

Separationofpatient-accessareasfromotherpartsofhealthcarepremises 13

Staffinglevels 13

xiv
Contents

3. Means of warning and escape 17


Firedetectionandalarm 17

Principlesofmeansofescape 17

Progressivehorizontalevacuation 18

Sub-compartmentation 21

Traveldistances 22

Hospitalstreets 24

Widthofescaperoutes 27

Verticalescape 27

Assistedpatientevacuation 28

Finalexits 31

Externalescaperoutes 31

Departmentsprovidingintensivecare 31

Operatingdepartments 32

Emergencyandescapelighting 33

Plantareas 33

Security 34

4. Internal fire spread (linings)35

Rooflights 35

Thermoplasticmaterials 36

5. Internal fire spread (structure)38

Elementsofstructure 38

Compartmentation 40

Elementsofstructureandcompartmentwalls 40

Sub-compartmentwalls 41

Protectedshafts 41

Protectedlobbies 43

Firestopping 44

Firehazardroomsandareas 44

Ventilationsystems 45

Cavitybarriers 48

Sprinklers 50

6. External fire spread53

Spaceseparation 53

Surfacesofexternalwalls 55

Surfacesofroofs 55

Junctionofwallsandlow-levelroofs 55

Junctionofcompartmentandsub-compartmentwallsandexternalwalls 57

Additionalrequirementsforcarparks 57

7. Access and facilities for the fire-and-rescue service60

Siteaccess 60

Accessaroundthebuilding 61

xv
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

Accessandfacilitiesforthefireservice 63

Designandconstructionoffire-fightingshafts 64

Firemains 64

Ventingofbasements 65

Appendix A: Glossary of terms67


Appendix B: Periods of fire resistance71
Appendix C: Doors and doorsets73

Doorclosers 74

Identification 74

Doorsonescaperoutes 74

Appendix D: Thermoplastic materials 76


Appendix E: Construction and fixing of cavity barriers78
Appendix F: Fire behaviour of insulating core panels79

Introduction 79

Firebehaviourofthecorematerialsandfixingsystems 79

Designrecommendations 80

Specifyingpanelcorematerials 80

General 80

Appendix G: Fire drawings81

Provisionofdrawings 81

Firedrawings 81

Appendix H: Care Quality Commission types of service83

Healthcareservices 83

Appendix J: Qualitative Design Review87


Appendix K: References89

ActsandRegulations 89

Europeanlegislation 89

Firecodepublications 89

HealthBuildingNotes 90

HealthTechnicalMemoranda 90

BritishandEuropeanStandards 90

Otherpublications 92

xvi
1. Introduction

General application A full definition of services is contained in


Appendix H.
1.1 This Health Technical Memorandum
provides recommendations and guidance on 1.3 HTM 05-02 should be used in the
the design of fire safety in healthcare premises. design of:
It supersedes HTM 05-02 Guidance in
support of functional provisions for healthcare a. new healthcare buildings;
premises, published in January 2007. b. new extensions to existing healthcare
buildings;
1.2 The guidance in this document is applicable
to premises regulated by the Care Quality c. those parts of existing healthcare
Commission (CQC), irrespective of ownership, buildings that are used as means of
that provide the following types of service: escape from a new healthcare
extension;
CQC Code Service type
d. alterations to existing healthcare

ACS Acute services buildings;

HBC Hyperbaric chamber services e. change of use of an existing building,


or parts of an existing building, to
HPS Hospice services healthcare use.

LTC Long-term condition services Please note: paragraphs 1.3d and 1.3e apply
irrespective of whether the alterations and
MLS Hospital services for people with change of use constitute building work as
mental health needs, and/or defined by the Building Regulations 2010.
learning disabilities, and/or
problems with substance misuse
Building Regulations
RHS Rehabilitation services 1.4 The purpose of this document is to provide
guidance on the minimum standards of fire
RSM Residential substance misuse safety expected in healthcare premises to
and treatment/rehabilitation comply with Part B of Schedule 1 of the
services Building Regulations 2010. It is a guidance
document that recognises the problems special
DTS Doctors treatment services
to healthcare and allows the current statutory
DSS Diagnostic and/or screening regulations to be applied sensibly within a
services framework of understanding. To that end, the
following functional provisions are expected to
UCS Urgent care services be met:

1
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

B1: To ensure satisfactory provision of appropriate to the needs of the relevant


means of giving an alarm of fire and a persons in the building and their levels of
satisfactory standard of means of escape dependency; additional guidance is provided in
for persons in the event of fire in a paragraphs 2.332.36.
building (Chapter 3).
B2: To ensure fire spread over the BS 5588
internal linings of buildings is inhibited 1.7 HTM 05-02 refers to the guidance
(Chapter 4). contained in parts of the BS 5588 series of
standards as a means of showing compliance
B3: To ensure the stability of buildings in
with the requirements of Part B (Fire safety) of
the event of fire; to ensure that there is
Schedule 1 to the Building Regulations. In
a sufficient degree of fire separation
doing so the Department of Health follows
within buildings and between adjoining
the practice adopted by the Department of
buildings; to provide automatic fire
Communities and Local Government (DCLG)
suppression where necessary; and to
in relation to Approved Document B and
inhibit the unseen spread of fire and
references to BS 5588 remain part of HTM
smoke in concealed spaces in buildings
05-02 until such time that it is next revised.
(Chapter 5).
B4: To ensure external walls and roofs 1.8 Where designers elect to follow the relevant
have adequate resistance to the spread guidance in BS 9999 they will need to satisfy
of fire over the external envelope, and themselves and the building control body that
that spread of fire from one building to this guidance adequately addresses the
another is restricted (Chapter 6). requirements of Part B. It is strongly
recommended that in such cases designers
B5: To ensure satisfactory access for fire discuss their proposals with the building control
appliances to buildings and the provision body before starting work.
of facilities in buildings to assist fire
fighters in the saving of life of people in 1.9 Withdrawn BS standards are readily
and around buildings (Chapter 7). available from:

1.5 Health Technical Memorandum 05-02 The BSI Knowledge Centre


should be used as guidance on fire safety in British Standards Institution
all parts of healthcare buildings, classed as 389 Chiswick High Road
Purpose Group 2a Residential (Institutional),1 London, W4 4AL
including departments or areas providing Email: knowledgecentre@bsigroup.com
ancillary services which are planned as an Tel: +44 (0)20 8996 7004
integral part of a healthcare building. The
guidance it contains follows the structure of the
requirements set out in Part B Schedule 1 of Fire safety information
the Building Regulations. 1.10 Regulation 38 of the Building Regulations
requires that where building work is carried out
1.6 Some of the premises listed in paragraph that affects fire safety, and where the building
1.2 above may be classed as Purpose Group 5 affected will be covered by the Fire Safety
Assembly and Recreation; for these premises Order, the person carrying out the work must
the application of HTM 05-02 should be limited provide sufficient information for persons to
to those measures necessary to provide a safe operate and maintain the building in reasonable
patient environment for the time necessary to safety. This information will assist the eventual
effect an evacuation. Such measures should be owner/occupier/employer to meet their
1 AsdefinedinApprovedDocumentB
statutory duties under the Fire Safety Order.

2
1. Introduction

The exact amount of information and level of this document will be safe: it needs to be
detail necessary will vary depending on the supported by a fully developed emergency
nature and complexity of the buildings design. plan. This is also a legal requirement imposed
Further guidance is provided in paragraphs by the Fire Safety Order.
1.131.19 below.
1.16 The preparation of the emergency
1.11 For all healthcare premises covered by the evacuation plan commences during the design
guidance in this document a detailed record of phase and should be developed through the
the fire safety strategy, evacuation procedures, user consultation process. It is important to
patient dependency and staffing levels, stress that in relation to the design of
together with information on the operation and appropriate fire precautions, each type of
maintenance of any fire protection measures of clinical service will present its own unique set of
the building, will be required. problems which will only fully emerge during the
design phase. It is therefore essential that
1.12 Guidance on the application of the Fire architects and designers, through the client
Safety Order to healthcare premises is provided user group consultation process, fully
in HTM 05-01. understand and record the fire safety issues
associated with the clinical service being
provided and the patients being treated.
Consultation and qualitative design
review 1.17 The fire safety measures and the
1.13 Health Technical Memorandum 05-02 emergency evacuation strategy should be
has been written on the assumption that the developed and agreed through discussions
premises will be properly managed. Building with:
Regulations do not impose any requirement a. Client user group generally involving
on the management of a building; however, in clinicians, nurses, managers, the fire
developing an appropriate fire safety design for safety advisor and the local security
healthcare premises it is essential to consider management specialist;
the way in which it will be managed, as fire
safety in healthcare premises relies on well- b. Design team architects and engineers;
trained staff to implement a pre-agreed c. Fire service representative; and
emergency plan; this is especially important
where care is provided for dependent or very d. Building control or approved inspector.
high dependency patients.
1.18 For very large and complex projects, it is
1.14 A design that relies on an unrealistic or recommended that a Qualitative Design Review
unsustainable management regime cannot be (QDR), as detailed in PD 7974-0:2002, be
considered to have met the requirements of the carried out by a study team involving one or
Building Regulations. more fire safety engineers, other members of
the design team and the client user group.
1.15 It is therefore essential that the design It might also be appropriate to include
team have a full understanding of the type of representatives of approval bodies or the
care being provided and the dependency of insurers to ensure that their views can be
the patients, and that the client team fully accounted for. Further guidance on the
appreciate the constraints imposed by the application of QDR to healthcare premises is
design on the movement and evacuation of contained in Appendix J.
patients, visitors and staff. The design team and
approving authorities should not assume that a
design which complies with the requirements in

3
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

1.19 The outcome of these discussions will (v) smoke-control system(s) (or HVAC
be all the information required to support system with a smoke-control
Regulation 38 and should include: function) design, including mode of
operation and control systems;
a. the emergency evacuation plan
including all assumptions in relation to: e. any high-risk areas (for example heating
machinery) and particular hazards;
(i) the availability of adequately trained
staff to manage an evacuation; f. as-built plans of the building showing
the locations of the above;
(ii) the design of the fire safety
systems (such as fire load); g. specifications of any fire safety
equipment provided, including
(iii) any risk assessments or risk operational details, operator manuals,
analysis; software, system zoning, routine
b. all assumptions in the design of the fire inspection, and testing and maintenance
safety arrangements regarding the schedules, together with records of any
management of the building; acceptance or commissioning tests;

c. escape routes (including stairs and h. any other details appropriate for the
lifts), escape strategy (for example specific building; and
simultaneous or phased) and muster i. for large and/or complex premises, the
points; findings of the QDR.
d. details of all fire safety measures,

including (but not exhaustively):

Alternative solutions
(i) compartmentation, cavity barriers, 1.20 The range of NHS premises providing
fire doors, self-closing fire doors patient care facilities is extensive, and the
and other doors equipped with guidance in this document may not be
relevant hardware (for example appropriate for all types of building. However,
electronic security locks), and fire it is expected that NHS clients, designers,
and smoke dampers; building control and fire authorities will exercise
(ii) automatic fire detection systems, a degree of judgement based on a full
emergency communication understanding of the problem, taking into
systems, CCTV, fire safety signage, account the full implications of the dependency
emergency lighting, fire and medical conditions of the patients being
extinguishers; treated.

(iii) dry or wet risers and other fire- 1.21 This document describes a way of
fighting equipment, other interior achieving an acceptable standard of fire safety
facilities for the fire-and-rescue within new and modified healthcare buildings,
service, emergency control rooms, but it is recognised that there may be other
location of hydrants outside the ways of satisfying the functional requirements
building, and other exterior facilities by adopting a fire safety engineering approach.
for the fire-and-rescue service; A fire safety engineering approach that takes
into account the total fire safety package can
(iv) sprinkler system(s) design, provide an alternative approach to fire safety. If
including isolating valves and such an approach is used, the responsibility is
control equipment; and placed upon those promoting the alternative
approach to demonstrate that the alternative

4
1. Introduction

satisfies the functional requirements and fire conduct of contractors should be adequately
safety objectives of this document. supervised and controlled. Adequate
precautions against fire should be in place,
and regular contact with contractors should
Use by competent persons be maintained to ensure that local fire safety
1.22 The guidance in this document has been policies are being complied with.
prepared on the understanding that it will be
used by competent persons. For the purposes 1.26 It is also important to ensure that when
of this document, a competent person is new buildings are being constructed and
defined as a person recognised as having handed over in phases due consideration is
sufficient technical training and actual given to fire safety after handover. There must
experience, or technical knowledge and other be no conflict in the operation of the alarm and
qualities, both to understand fully the dangers detection system between the healthcare-
involved, and to undertake properly the occupied part of the premises and the
statutory and Firecode provisions referred to in construction area. Of equal importance is the
this Health Technical Memorandum. need to ensure that means of escape is readily
available at all times.

Relationship with Construction


(Design and Management) Certification schemes
1.27 There are many UK product certification
Regulations 2006 schemes. Such schemes certify compliance
1.23 The purpose of this document is with the requirements of a recognised
to provide guidance on the fire safety document which is appropriate to the purpose
requirements for the completed building. It for which the material is used. Materials that are
does not address the risk of fire during the not certified may still conform to a relevant
construction work, which is covered by the standard.
Construction (Design and Management)
Regulations 2006 and the Fire Safety Order. 1.28 Many certification bodies which approve
The Health and Safety Executive (HSE) has such schemes are accredited by United
issued HSG 168: Fire safety in construction Kingdom Accreditation Service (UKAS). Since
work (ISBN: 0 71761 332 1), which provides the fire performance of a product, component
relevant guidance on fire safety in construction. or structure is dependent upon satisfactory site
installation and maintenance, independent
1.24 When the construction work is being schemes of certification and accreditation of
carried out on an occupied building, the Fire installers and maintenance firms can offer
and Rescue Authority is responsible for the confidence in the standard of workmanship
enforcement of the 2005 Regulations in those provided.
parts which remain occupied.
1.29 Schemes such as those identified above
may be accepted by building control bodies as
Fire safety during building evidence of compliance; however, a building
operations control body may want to establish before work
commences that the scheme is adequate for
1.25 A significant number of fires occur as a
approval purposes.
result of certain building activities. The site

5
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

2. Principles of fire safety in healthcare

premises

Introduction ensures that the concept of inclusive design


has been applied.
2.1 In healthcare buildings, particularly in
patient access areas, the immediate and total 2.4 Healthcare premises accommodating
evacuation of the building in the event of fire dependent and very high dependency
would be a major logistics exercise and, from patients should be divided into a series of
a patient safety perspective, not desirable. compartments that may be further divided
Patients with restricted mobility, patients who into sub-compartments which should be
use wheelchairs, and patients confined to bed constructed to provide the appropriate level of
cannot negotiate escape routes, particularly fire safety (see Chapters 3 and 5).
stairways, unaided. Patients under medication
may require staff assistance, and patients who 2.5 Where the evacuation involves very high
are dependent on electrical/mechanical dependency patients, additional consideration
equipment for their survival cannot always be must be given to the distance of travel that
disconnected and moved rapidly without might be necessary to reach a place of safety
serious consequences. where essential treatment and care could be
recommenced.
2.2 HTM 05-02 assumes that there are
sufficient adequately trained staff on duty in
the building to implement the emergency plan. Fire safety philosophy
However, while the total evacuation of smaller
buildings, or smaller healthcare premises within Fire evacuation strategy
other buildings, accommodating occupants 2.6 The basic strategy for fire evacuation of
considered to be independent might be dependent and very high dependency patients
practical, the evacuation of an entire hospital in should be to move them on their bed or in a
the event of fire would be an enormous exercise wheelchair to a safer area (refuge or place of
in which patients might be placed at risk due to relative safety) on the same floor and then (if
trauma or their medical condition. required) to evacuate the patients to another
floor in the building or to outside.
2.3 Should evacuation become necessary,
except for those premises with independent 2.7 There are three main stages of evacuation:
occupants, it should be based on the concept
of progressive horizontal evacuation, with only a. Stage 1 horizontal evacuation from
those people directly at risk from the effects of the area where the fire originates to
fire being moved. Adopting this approach an adjoining sub-compartment or
compartment;

6
2. Principles of fire safety in healthcare premises

b. Stage 2 horizontal evacuation from the should give sufficient time for non-ambulant
entire compartment where the fire and partially ambulant patients to be evacuated
originates to an adjoining compartment vertically to a place of safety, should it become
on the same floor. Subsequent necessary to evacuate an entire storey.
additional horizontal evacuation to
adjacent compartments may be 2.11 Active fire protection systems such as
undertaken (thereby putting additional automatic fire detection systems, warning
fire resistance between the building systems and fire suppression systems may be
occupants and the threat) prior to incorporated into the building so that the time
undertaking vertical evacuation; and available for escape is maximised.

c. Stage 3 vertical evacuation to a lower 2.12 Patient-access areas should be designed


floor, or to the outside. to allow for progressive horizontal evacuation
other than in premises where patients fall into
2.8 There are three fire conditions when the independent category.
evacuation is necessary or should be
considered: 2.13 Areas to which patients have access
should not be located on storeys where
a. Extreme emergency where there is an
evacuation in a fire emergency would
immediate threat to safety from fire or
necessitate travelling up a stairway to a
smoke;
final exit.
b. Emergency no immediate threat, but
fire or smoke likely to spread from an
adjoining area;
Hospital streets
2.14 The hospital street provides an essential
c. Precautionary no immediate threat to link between hospital departments and
life or safety, but there is a fire on an stairways and lifts; it is the main circulation
adjoining floor or in an adjacent building. route for staff, patients and visitors. Although
many hospitals will be provided with hospital
2.9 In extreme emergency situations, the
streets, they are not an essential requirement.
sequence of evacuation should be:
In smaller hospitals, such as community
a. those in immediate danger; hospitals, and other healthcare premises,
hospital streets are generally not provided.
b. ambulant patients;
c. the remaining patients who are not 2.15 A hospital street is a special type of
ambulant. compartment that connects final exits, stairway
enclosures and department entrances. It has
two functions from a fire safety aspect:
Progressive horizontal evacuation
a. if the spread of fire within a department
2.10 The principle of progressive horizontal cannot be brought under control, the
evacuation is that of moving occupants from occupants of the department affected
an area affected by fire through a fire-resisting may be evacuated via the hospital street
barrier to an adjoining area on the same level, to parts of the hospital not affected by
designed to protect the occupants from the the fire; and
immediate dangers of fire and smoke (a refuge).
The occupants may remain there until the fire is b. it will serve the fire-and-rescue service
dealt with or await further assisted onward as a fire-fighting bridgehead.
evacuation by staff to another similar adjoining
area or to the nearest stairway. This procedure

7
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

Vertical escape Dependent all patients except those


classified as independent or very high
2.16 Vertical escape in healthcare premises dependency.
should only be conducted if a fire cannot be
controlled within the space of origin and there is Very high dependency those whose
additional risk to occupants outside of the fire clinical treatment and/or condition
compartment of origin. This approach to fire creates a high dependency on staff. This
safety is adopted due to the additional risks that will include those in intensive care areas,
are present to both staff and patients during the operating theatres, coronary care etc and
vertical escape phase. those for whom evacuation would prove
potentially life-threatening.
2.17 In healthcare premises, the practice of
designating certain stairways as escape Independent patients
stairways and others as accommodation
stairways only is not acceptable, since in 2.20 Areas containing independent patients or
an emergency any stairway will be used if occupants who can escape from a fire unaided
necessary. Therefore all stairways should be do not have such a reliance on horizontal
designed as escape stairways other than those evacuation, and therefore the need for
contained wholly within and only serving an compartmentation both horizontally and
atrium. vertically is reduced.

2.18 It is recognised that there are many 2.21 In most cases, the use of Approved
benefits in using lifts to assist with vertical Document B will be sufficient (purpose group
evacuation, especially when evacuating 2a, or 5 depending on the type of premises).
dependent and very high dependency patients, However, where doubt may exist about the
and appropriate guidance is provided in mobility of patients, advice should be sought
Chapter 3. from clinicians to ensure that no part of patient
care or treatment would prevent them from
quickly responding in the event of a fire.
Specific considerations based on
patient dependency 2.22 Based on an assessment of each type
of patient care, it may be necessary in some
2.19 Firecode has three classifications for instances to apply the recommendations within
patient dependency: this document in addition to those of Approved
Independent patients are considered Document B.
to be independent if:
Note
their mobility is not impaired in any
way and they are able to physically Although the occupancy of an area may be
leave the premises without staff identified as independent, consideration
assistance; or should be given to the need for patients
categorised as dependent or very high
they experience some mobility
dependency who may need to be evacuated
impairment and rely on another
through that area. In such circumstances the
person to offer minimal assistance.
means of escape provisions should reflect
This would include being sufficiently
the measures necessary for the evacuation
able to negotiate stairs unaided or
of higher dependency occupants.
with minimal assistance, as well as
being able to comprehend the
emergency wayfinding signage
around the facility.

8
2. Principles of fire safety in healthcare premises

Dependent patients adequate period of time is provided to enable a


2.23 The guidance in this document provides fire to be detected and extinguished before it
additional guidance above that of Approved threatens occupants.
Document B, which is necessary to meet the
2.28 The HVAC systems provided to intensive
increased dependency of patients who fall
care areas are designed so that the pressure
within this category (and those within the very
within the department is maintained at slightly
high dependency category).
above that of the adjacent areas. In a fire
emergency, the continuing operation of these
Very high dependency patients systems will assist in preventing smoke and
2.24 In operating theatres and areas that other products of combustion entering the
provide intensive care, any movement or intensive care area.
evacuation of patients may be life-threatening;
consequently, additional precautions are 2.29 Although it is accepted that some
required to address the implications of: occupants, because of their condition or
treatment, should not be moved, provision must
a. fire and smoke in a compartment either still be made for external evacuation. The need
adjacent or below; for a vertical movement strategy for such
occupants must be recognised, and
b. fire and smoke within the department appropriate measures must be installed to
itself. reduce the risk associated with such an action.
2.25 The enclosing of departments with fire- 2.30 Protected lobbies are provided to those
resisting construction and the strategic planning areas of the premises that require additional
of adjacent compartments goes some way means to protect against the movement
to mitigating the risk. The time required for of smoke. Where risk assessment has
evacuation is longer, as it is often necessary demonstrated a need, very high dependency
to move the patient, ventilators, monitoring treatment areas should be provided with a
equipment and support staff as one unit, and lobby, which should be sized appropriately to
the design should seek to maximise the fully accommodate a bed, the associated
protection to the occupants allowing for ancillary equipment and nursing staff, and
extended start-up times. should include sufficient additional floor space
to allow for any manoeuvring as necessary.
2.26 Some of the equipment, such as
the ventilator, are integral parts of the 2.31 Where smoke movement into an area
anaesthesiologists equipment and so are accommodating very high dependency patients
provided with an electrical back-up supply. has been identified as a potential risk (that is,
However, this type of equipment is often large where no hospital streets have been provided),
and unwieldy, and the evacuation must be every door opening in the compartment wall
pre-planned, as double doorsets are required should be provided with a protected lobby,
to facilitate the efficient movement of ancillary each door of which will provide a minimum
equipment. period of fire resistance of 30 minutes.
2.27 The aim of any design should be to 2.32 Any future change in dependency is likely
prevent a fire in an adjacent compartment to result in a significant change to the fire
either on the same storey or on a storey above precautions applicable. This applies equally to
or below, requiring the evacuation of a intensive premises designed for independent patients.
care area. The compartmentation and HVAC
(heating, ventilation and air-conditioning)
systems should be designed so that an

9
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

Healthcare premises in Purpose Facilities providing in-patient mental


Group 5 Assembly and health services and in-patient
Recreation accommodation for people with
2.33 It is becoming more common for health learning disabilities
centres, clinics and GP surgeries to provide 2.37 In this context, an in-patient service is
facilities for minor invasive investigations or defined as a unit with hospital beds that
procedures that require the use of a local provides 24-hour nursing care. Such a unit
anaesthetic. These will be DTS and DSS may be in a hospital campus or a community
services regulated by the Care Quality setting, and may be provided by the NHS or by
Commission see Appendix H. Generally the independent sector providers.
procedures will be undertaken in a minor
procedure room, or treatment room possibly 2.38 In-patient beds should be distinguished
with an adjacent recovery area where patients from placements registered for the provision of
may remain under observation until the effects care, which are provided by local authorities
of the anaesthetic have worn off. and independent sector providers and
registered by the CQC. These provide
2.34 In many cases the use of an anaesthetic accommodation, usually in a room in a multiple
will restrict mobility so that patients will require occupancy facility, and a care/support package
assistance to escape in the event of a fire. funded by health and social services.
Therefore in DTS and DSS premises the means
of escape from relevant areas should be 2.39 The guidance in HTM 05-02 applies only
designed so that it is always possible, in the to in-patient services and not placements.
first instance, to escape:
2.40 In-patient mental health services cover the
a. horizontally to a place of relative safety
following range of services:
from where further horizontal or vertical
evacuation is possible; or Acute in-patient bed acute in-patient
wards for working age adults (1865)
b. directly to a place of safety at ground
providing intensive medical and nursing
level.
support for patients in periods of acute
2.35 The place of relative safety should either psychiatric illness.
be a separate 30 minute sub-compartment, or Psychiatric intensive care unit
a refuge in an escape stairway that is enclosed a type of psychiatric ward. These wards
in 30 minute fire-resisting construction, either of are secure, meaning they are locked and
which should be large enough to accommodate entry and exit of patients is controlled.
the number of patients who at any one time Staffing levels are higher, sometimes with
could reasonably be expected to be receiving 1:1 nursing staffing ratios. They usually
or recovering from minor invasive investigations receive patients who cannot be managed
or procedures. in an acute ward due to the level of risk
the patient poses to themselves or
2.36 It is also strongly recommended that these others. In some cases patients may also
premises are provided with a fire detection and be referred from prisons or rehabilitation
alarm system that complies with the relevant wards. Patients will usually be detained
guidance in the HTM 05-03 series. under the Mental Health Act.
Forensic services this covers high,
medium and low secure units, of which

10
2. Principles of fire safety in healthcare premises

only the last two are covered by


Further information on all of the above
HTM 05-02.
is provided in Defining mental health
services, published in 2012 by the Mental
Low secure services are provided for Health Network of the NHS Confederation.
those patients who have long-standing
and complex problems who cannot be In-patient facilities for people with
safely or successfully cared for in an learning disabilities a learning
acute ward. Patients will be detained disability affects the way a person
under the Mental Health Act. understands information and how they
communicate; it is not the same as a
Medium secure services are learning difficulty or mental illness. In-
specially designed to meet the needs of patient assessment and treatment beds
adults with a serious mental illness, who are required for people with learning
require care and treatment in a secure disabilities with complex mental health
setting to ensure they are safely problems and/or challenging behaviours
managed. In most cases patients in that cannot be managed in the
medium security will have committed an community. The number of units across
offence and present a serious risk to the NHS is small.
themselves and others, combined with a
potential to escape.
Specific fire safety information relating to
Recovery and rehabilitation services the above premises
rehabilitation units are provided for
2.41 Although the range of services provided
adults with severe and enduring mental
varies considerably, there are common issues
health problems who have ongoing
that must be considered to enable appropriate
symptoms and functional impairments
levels of fire safety to be achieved. The ultimate
and cannot manage independent living,
aim is to provide a safe and secure environment
even with support.
where patients can receive care and treatment;
Child and Adolescent Mental Health however, safety from the effects of fire and
Services (CAMHS) Tier 4 in-patient maintaining the required levels of security
services these are defined as highly are equally important, and the design of fire
specialised provision that may be precautions and evacuation strategies should
required for children and young people up not compromise security.
to the age of 18, who may or may not be
detained under the Mental Health Act. 2.42 Highly trained specialised nursing and
clinical staff are always present when the
Dementia assessment the term premises are occupied and they will be trained
dementia is used to describe a syndrome to take the lead role in the evacuation of
that may be caused by a number of patients.
illnesses with progressive decline in
multiple areas of function, including 2.43 Should a fire start, it will be necessary to
impairment of memory, reasoning, evacuate the sub-compartment of fire origin
communication skills and the ability to and the number of staff available will influence
carry out daily activities. As well as the speed of evacuation. Such evacuation may
memory impairment, dementia might also be progressive horizontal evacuation to other
include behavioural and psychological compartments or sub-compartments as
symptoms such as depression, described in Chapter 3.
psychosis, aggression and wandering.
2.44 Patients may exhibit behavioural problems
that could impact on the fire and security

11
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

measures installed. Acute mental patients have should be considered, with the additional
a history of generating unwanted fire signals. caveat of any security measures required to
Tampering with fire doors is commonplace, and ensure patient safety.
special attention must be paid to final exits.
Specific design requirements for the above
2.45 The implications of this tampering are an
premises
increase in the number of false alarms and the
potential for complacency amongst staff to the 2.52 Sleeping accommodation should be in a
emergency signal. A security issue may also be separate compartment from day facilities.
created with regard to the control of patients
and the possibility of unrestricted egress. 2.53 Accommodation in compartments
providing sleeping accommodation should be
2.46 The potential to configure the alarm and limited to:
detection system such that in the first instance
a. bedrooms;
only staff receive the alarm, can reduce adverse
reactions from patients. A general alarm b. bathrooms, WCs etc;
confined to the compartment or zone would
only be activated as the evacuation strategy c. cleaners room;
was implemented. Further guidance is provided d. a small office for staff on overnight duty
in HTM 05-03 Part B. (this may be an office or a recess off a
circulation route);
2.47 Integration of the alarm and detection
system with staff and patient monitoring and e. linen stores.
location systems can improve response times
to alarm situations. 2.54 Where sleeping accommodation is
segregated by sex, male and female bedrooms
2.48 For security purposes, it is important should be in separate sub-compartments.
that final exits do not release immediately on
actuation of the alarm. The release mechanism 2.55 The maximum number of beds in any
should form part of the overall strategy for sub-compartment, including swing beds,
managing the evacuation. This gives control should be no more than 10.
to the staff and increases the security of the
facility. Some means of control should be 2.56 Where swing beds are provided it should
provided such that these doors can be opened be possible to include the swing beds in either
by staff, on confirmation of the fire signal, when sub-compartment.
it becomes necessary to evacuate to a
2.57 Depending on the patients it may be
designated (secure) assembly point.
necessary to maintain segregation during
2.49 Should it become necessary to evacuate evacuation; where this is the case, the design
an entire facility or part thereof, adequate safe of evacuation routes should ensure that this is
and secure external assembly points should be always possible. This will also extend to secure
available. places of safety away from the effects of fire,
outside the building.
2.50 Due to the intended occupancy,
evacuation to an external assembly point would 2.58 Bedrooms:
be a last resort only. a. All bedrooms should be classed as fire
hazard rooms.
2.51 When designing external escape routes
that are intended for use by mental health b. It may be necessary to provide the
patients, similar considerations to those above potential for bedroom doors to be

12
2. Principles of fire safety in healthcare premises

locked from the inside. However, if this is access areas affecting the patient-access areas
required, they should be easy to open of healthcare premises.
from the inside without recourse to a
key. In addition, any locking device 2.61 Non-patient-access areas, for the
used should be easy to open from the purposes of this document only, are divided
outside of the room by means of a into the following:
standard key issued to all staff.
a. Hazard departments: departments/
c. Where patients have restricted mobility, management units that contain high fire
are elderly or are suffering from loads and/or significant ignition sources.
dementia, moving the patients on Hazard departments should be
their beds is likely to the most effective separated by distance from any patient-
method of evacuation. Where this is the access areas and should not adjoin
case, the design of evacuation routes them, either horizontally or vertically,
should allow for bed evacuation and unless additional precautions are
should be designed either: provided.

(i) to comply with Figure 1 below; or b. Non-hazard departments: departments/


management units that do not contain
(ii) the architect or designer should high fire load and/or significant ignition
provide evidence to the client, fire sources. Non-hazard departments may
officer and building control officer, adjoin patient-access areas, either
that their design will permit bed horizontally or vertically, provided
evacuation; or they are separated from them by
(iii) an alternative method of evacuation compartment walls and floors.
should be agreed that fully
2.62 Patient-access areas should always be in
recognises the restricted mobility
different compartments from non-patient-
of the patients, the limitations of
access areas.
the proposed design and the
availability of trained staff to safely 2.63 Areas and departments/management
manage the evacuation. units should be located in accordance with
Table 1 below.
2.59 Where communal bathrooms2 are
provided, these should be designed as fire
hazard rooms. Staffing levels
2.64 The provision of an adequate number of
Separation of patient-access areas staff who have received effective fire safety
from other parts of healthcare training is the best first line of defence against
fire. This is particularly important when levels
premises of activity in the building are reduced. The
2.60 In addition to the general requirement for presence of trained staff who can respond
progressive horizontal evacuation, healthcare quickly and effectively to any fire emergency is
premises should also be designed to minimise a vital factor in limiting the consequences of a
the possibility of fires from the non-patient- fire, particularly where dependent patients are
involved.
2 Communalbathroomsallowunsupervisedaccessandare
distinctfrombathrooms,whicharenormallykeptlocked,with
patientsonlyhavingaccesswhensupervisedbystaff.The 2.65 Article 15 of the Fire Safety Order requires
formeraregenerallyprovidedinolderpremiseswherepatient the responsible person to:
bedroomsarenotprovidedwithfullen-suitefacilities;thelatter
aregenerallyprovidedinpremiseswherepatientbedrooms a. produce an evacuation procedure;
havefullen-suitefacilities(WC,washbasinandshower).

13
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

nominaldoorsetused
substantiallybeyond
Door 1550ecwrequiredwithclearcorridor Doornibmustallow

90degreesif1700
doorleaftoopen
(650)

widthsbetween2150and2400.
1700nominaldoorsetdrawn
ecw=1550

(1700)
150

nib

150(100) (2150) 150(100)


Zonefor Zonefor
handrail/ handrail/
2450(2350)
wall wall
protection protection

Figure 1 Widths of doors and corridors to permit bed evacuation

Note: Further guidance is provided in Chapter 3 and Health Building Note 00-04 Circulation and
communication spaces.

14
2. Principles of fire safety in healthcare premises

Separation from patient-access area


Hazard area or department/ Normal dependency Very high dependency
management unit
Atrium RefertoHTM05-03PartM RefertoHTM05-03PartM
Boilerhouse(main)1 60+autosuppression Notallowed
Carpark 60+autosuppression Notallowed
Centralstaffchange 60 60+autosuppression
Commercialenterprises 60+autosuppression Notallowed
Flammablestore 60+autosuppression Notallowed
Laundry 60+autosuppression Notallowed
Localmedicalgasstores2 60+ventilation Notallowed
Mainelectricalswitchgear3 60+autosuppression Notallowed
Mainkitchens 60+autosuppression Notallowed
Mainstores 60+autosuppression Notallowed
Medicalrecords 60 60+autosuppression
Pathology 60 60+autosuppression
Pharmaceutical(manufacturing) 60 60+autosuppression
Refusecollection/incineration 60+autosuppression Notallowed
Sterileservicesdepartment 60 60+autosuppression
Works 60+autosuppression Notallowed
Key:

60Maybeadjacentbutshouldalwaysbeseparatedby60-minutefire-resistingconstruction.60minutesfireresistancemaybe
reducedundercertaincircumstances(forexampleifsprinklersarefitted(seeparagraphs5.125.13)).
60+auto-suppressionPreferablyseparate;however,ifadjacent,itshouldbeseparatedby60-minuteimperforateconstruction
togetherwithauto-suppressioninthehazarddepartment.

Notallowedshouldnotbelocatedadjacenttoveryhighdependencydepartments.

Notes:

1Notapplicabletosmallboilers/switchgearinplantroomsservingpartofabuilding.

2Mainmedicalgasstoresshouldalwaysbelocatedinseparatebuildings.HealthTechnicalMemorandum02-01Medicalgas
pipelinesystemsgivesguidance.Localmedicalgasstoresshouldonlycontainsufficientquantityfordailyuse.
3Amediumorhighvoltagetransformer,orswitchgearroom,orbatteryroomservingawholebuildingorsite.

Table 1 Requirements for the location and fire separation of fire hazard departments from patient-access areas

b. have sufficient staff to implement it; and assumptions relating to patient evacuation can
be realised by the available trained staff.
c. ensure that staff are adequately trained.
2.67 It is the responsibility of management to
2.66 The emergency plan (see paragraphs ensure that adequate numbers of staff will
1.131.19) should detail the fire safety provisions always be available and to devise suitable
to each patient area and the dependency of arrangements to provide for the safe evacuation
the patients within the area being considered. of all relevant persons in accordance with the
This information will enable the fire safety emergency evacuation plan. When requested
management procedures to detail the they should be able to demonstrate that staffing
appropriate staffing levels required to undertake levels are adequate to ensure the effective
the evacuation of the area in the event of a fire; implementation of the emergency plan.
this information should be prepared as the
design is being developed to ensure design

15
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

2.68 Staff should receive training in the


methods of patient evacuation appropriate to
the dependency of the patients and be familiar
with the evacuation procedures at their place of
work, and when requested, health service
managers should be able to demonstrate that
staffing levels are adequate at all times to
ensure the safe evacuation of patients.

16
3. Means of warning and escape

Requirement 3.3 Health Technical Memorandum 05-03


Part B Fire detection and alarm systems
Chapter 3 provides guidance to comply with provides general principles and technical
the following Requirement from Part B of guidance on the design, specification,
Schedule 1 of the Building Regulations 2010. installation, commissioning, testing, operation
and maintenance of fire alarm systems in
Requirement healthcare premises. It should be read in
conjunction with BS 5839-1 and the relevant
Means of warning and escape parts of BS EN 54.

B1 The building shall be designed and


constructed so that there are appropriate Principles of means of escape
provisions for early warning of fire, and 3.4 The design and construction of the building
appropriate means of escape in case of fire should ensure that at all times, patients, visitors
from the building to a place of safety outside and staff can move away from a fire to: a place
the building capable of being safely and of temporary safety inside the building on the
effectively used at all material times. same level, from where further escape is
possible, ultimately to a place of safety outside
the building; or lead directly to the outside.
Fire detection and alarm
3.1 The design and construction of the building 3.5 This chapter provides guidance on means
should ensure that fires are detected at the of escape by reference to:
earliest possible opportunity and that suitable a. the potential for horizontal evacuation,
warning is then given to the occupants and the which is achieved by dividing the storey
emergency services. into compartments and sub-
compartments;
3.2 The provision of adequate means for
detecting a fire and raising the alarm is of vital b. the height above ground of the treatment
importance. Early detection permits time for area;
orderly evacuation and allows the fire to be
c. travel distances and escape routes;
tackled at an earlier stage, thus minimising the
damage caused. Detection is dependent on d. the provision of an adequate number of
both staff observation and the automatic stairways to facilitate vertical escape;
detection and alarm systems.
e. emergency and escape lighting.

17
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

Progressive horizontal evacuation which contains patient-access areas should be


divided into a minimum of three compartments.
3.6 The need for progressive horizontal One of these compartments may be a hospital
evacuation is discussed in Chapter 2. This street (see paragraphs 3.373.40).
principle will be met if the requirements in
paragraphs 3.73.43 and Figure 2 below are 3.12 Where sprinklers are installed, the fire-
achieved. resistance of the compartment walls may be
reduced to 30 minutes (integrity and insulation),
3.7 In a fire emergency, each compartment see paragraph 5.12.
should be capable of accommodating, as
well as its normal occupants, the designed
occupancy of the most highly occupied Floors over 12 m above ground level
adjoining compartment. This should include 3.13 Every level over 12 m above ground that
space to accommodate beds and medical contains patient-access areas should be
equipment required to ensure continuity of divided into a minimum of four compartments.
care. Where no hospital street is provided, each
compartment should have a minimum floor
Note area of 500 m2; where one of the
compartments is a hospital street, the area of
For a definition of ground level, see Height of the hospital street may be less than 500 m2.
a building in the Glossary.
3.14 Where sprinklers are installed, the
minimum floor area of each compartment
Floors up to 12 m above ground level with required by paragraph 3.13 above may be
an area of less than 1000 m2 reduced to 350 m2.

3.8 Every level with a floor area of less than


General
1000 m2 and which contains patient-access
areas should: 3.15 In a fire emergency each compartment
should be capable of accommodating, in
a. contain no more than 30 patients; and addition to its normal occupants, the designed
b. be divided into a minimum of two
occupancy (including all relevant life support
compartments.
systems) of the most highly occupied adjoining
compartment.
3.9 Where a compartment provides sleeping
accommodation, the maximum number of Exits from compartments
beds in the compartment should be no more
than 20. 3.16 Exits from compartments should be by
way of a circulation space and provided in
3.10 On floors above ground-floor level where accordance with the guidance in Figure 2.
sprinklers are installed, the fire-resistance of
the compartment walls may be reduced to 3.17 While it is permissible to locate clinical and
30 minutes (integrity and insulation), see some non-clinical departments adjacent to
paragraph 5.12. each other, the means of escape through the
non-clinical area must be designed to safely
accommodate the evacuation of patients (that
Floors up to 12 m above ground level with is, escape routes should be sufficiently wide
an area of more than 1000 m2 enough to accommodate beds/trolleys).
3.11 Every level up to 12 m above ground level
that has a floor area of more than 1000 m2 and 3.18 It is not permissible to evacuate any non-
clinical area through a clinical area unless the

18
3. Means of warning and escape

1.Storeysupto12metresabovegroundwith
afloorareaoflessthan1000maminimum
oftwoexitsrequiredasshownbelow
Maximumof30patientson
Compartment Compartment eachstorey
one two

Wherecompartmentprovidessleeping
A A accommodationmaximumof20beds
B ineachcompartment

ExitAbywayofacirculationspaceto:
(i)astairway;or

(ii)afinalexit.

ExitBtoanadjoiningcompartment

(seealsoparagraphs3.163.20)

2.Storeysupto12metresabovegroundwitha

floorareaofmorethan1000maminimum

ofthreeexitsrequiredasshownbelow

Compartment Compartment
Compartment Compartment

one two
one two

B
B

A A

B B C C

D Hospitalstreet D

ExitBtoanadjoiningcompartment
(seealsoparagraphs3.163.20)
ExitCbywayofacirculationspaceto
Compartment A thehospitalstreet
three ExitDbywayofthehospitalstreetonly
toastairwayorfinalexit
ExitAbywayofacirculationspaceto:
(i)astairway;or

(ii)afinalexit.

ExitBtoanadjoiningcompartment

(seealsoparagraphs3.163.20)

3.Storeysover12metresaboveground

aminimumofthreeexitsrequiredasshown

below

Compartment Compartment
Compartment Compartment Compartment

one two
one two three

B
B B

A A

B B C C C

D D
Hospitalstreet

ExitBtoanadjoiningcompartment
A A (seealsoparagraphs3.163.20)
B ExitCbywayofacirculationspaceto
thehospitalstreet
ExitDbywayofthehospitalstreetonly
toastairwayorfinalexit
ExitAbywayofacirculationspaceto:
(i)astairway;or

(ii)afinalexit.

ExitBtoanadjoiningcompartment

(seealsoparagraphs3.163.20)

Figure 2 Requirements for progressive horizontal evacuation (paragraphs 3.63.15)

19
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

route through the clinical area is via a circulation b. a circulation space in an adjoining
route only. compartment or sub-compartment (see
Figure 3).
3.19 From ward bedrooms only, it is acceptable
to directly escape to: 3.20 Where a storey is divided into three or
more compartments, the exits from each
a. an adjacent ward bedroom in an
compartment should be located so that there
adjoining compartment or sub-
are at least two alternative exits that provide
compartment; or
horizontal escape to adjoining but separate
compartments.

Compartment1 Compartment2

Notes:

i. theescapedoorinthe
compartmentwallshouldbeavailable
foruseatalltimesandshouldneverbe
locked;

ii. thebedroomdoorandtheescape
doorshouldbeoppositeeachotherand
wardbedroom wardbedroom theroutebetweenthemkeptclear;

iii. escapeshouldbefromcirculation
spacethroughonewardbedroomonly,
throughthecompartmentwallthen
throughonewardbedroomonlytothe
circulationspace.

Compartment1 Compartment2

ward bedroom Note:

i. inthisinstanceescapefromthe
circulationspaceincompartment2
shouldnotbeviathewardbedroom
intocompartment1

Key..................................
circulationspace

Figure 3 Escape from ward bedrooms

20
3. Means of warning and escape

the management and operational arrangements


Note by making the boundaries of compartments
coterminous with departmental boundaries.
It is not possible to give precise
recommendations on the location of 3.23 Additional requirements for
alternative exits; the aim should be to locate compartmentation are provided in Chapter 5.
these as far apart as practical and if possible
in opposite walls. In the event of a fire, at
least one exit should always be available. Sub-compartmentation
3.24 The maximum size of a compartment
permitted by this document although
Escape routes over flat roofs appropriate for fire containment (see paragraph
3.21 If more than one escape route is available 5.11) is nevertheless considered too large if
from a storey, or part of a building, one of those the area contains patient-access areas. In the
routes may be by way of a flat roof, provided event of a fire, a large number of patients could
that: be overcome by the spread of fire, smoke and
toxic gases. Therefore, compartments
a. the route is for staff only; containing patient-access areas should be
b. the roof should be part of the same divided into smaller sub-compartments to limit
building from which escape is being the number of patients who may be affected by
made; a fire. Wherever possible, there should be a
balance of patients between sub-
c. the route across the roof should lead to compartments.
a storey exit or external escape route;
3.25 A compartment should be sub-
d. the part of the roof forming the escape
compartmented if:
route and its supporting structure,
together with any opening within 3 m of a. it has a floor area greater than 750 m2;
the escape route, should be fire-resisting or
(to a minimum period of 30 minutes if
the roof is used solely as an escape b. it contains departments to which more
route, or to a period provided in Table 5 than 30 patients will have access at the
if the roof is also used as a floor); and same time; or

e. the route should be adequately defined c. it contains sleeping accommodation for


and guarded by walls and/or protective more than 30 patients.
barriers which meet the provisions in
Approved Document K. Note

For out-patient departments in hospitals, the


Compartment/department relationships floor area may be increased to 1000 m2
3.22 The provision of compartments to facilitate before sub-compartmentation becomes
progressive horizontal evacuation should not be necessary.
looked upon only in terms of means of escape.
The management responsibilities, such as the 3.26 Sub-compartments should be enclosed
extent of the area under their control, the day- by walls having a minimum period of fire
to-day management, fire drills, the management resistance of 30 minutes, which should
of evacuation etc, will have a significant impact terminate at the underside of:
on the design, integrity, size and configuration
of compartments. For these reasons it is a. a compartment floor; or
strongly recommended that the design of a
compartment should recognise and integrate b. a roof.

21
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

Exits from sub-compartments c. 18 m for all other parts of healthcare


3.27 Each sub-compartment should be buildings.
provided with a minimum of two exits to
adjoining but separate compartments or Note
sub-compartments.
There will be exceptions to these distances in
3.28 In healthcare buildings, the left-hand certain parts of healthcare premises buildings
arrangement illustrated in Figure 4 is not (for example aseptic preparation units,
acceptable. operating departments, linac rooms). Where
these distances are exceeded, it must be
justified in the fire strategy document.
Travel distances
3.29 The distance to adjacent compartments, 3.31 Any part of an enclosed escape route
sub-compartments, hospital streets, stairways that has single direction of escape only, and
and final exits should be limited to ensure that exceeds 4.5 m, should be protected by
the occupants can escape from the effects of a 30-minute fire-resisting construction (integrity
fire within a reasonable period of time. and insulation). This does not include travel
within a room, but applies to stub corridors or
Single direction of escape a small corridor recess.
3.30 The maximum travel distance before there
3.32 Only glazing that provides a minimum
is a choice of escape routes should be no more
period of fire resistance of 30 minutes (integrity
than:
and insulation) may be provided on circulation
a. 15 m for in-patient accommodation; or spaces that give a single direction of escape.
Where a sprinkler system is installed, there is
b. as specified in paragraphs 3.853.87; or no requirement for insulation provided that the

A B

SC1 SC3 SC1 SC3

SC2 SC2

ThesubcompartmentationinexampleAisunacceptable ThesubcompartmentationinexampleBisacceptable
sinceafireinSC3wouldblocktheexitfromSC1 sinceafireinanyonesubcompartmentwouldnotblock
andSC2. thesafeexitfromothers.

Figure 4 Exits from sub-compartments

22
3. Means of warning and escape

glazing is not the type referred to as modified b. an adjoining compartment and to a


toughened. stairway or final exit (see Figure 5).

3.33 Escape from an inner room via an access 3.35 The maximum travel distance from any
room is permitted provided the access room is point within a sub-compartment should be no
not a fire hazard room. more than 30 m to:
a. an adjoining compartment or sub-
Total travel distance compartment; or
3.34 The maximum travel distance from any
b. a stairway or final exit (see Figure 6).
point within a compartment should be no more
than 60 m to: 3.36 Single-direction-of-escape travel distance
a. each of two adjoining compartments; or is an element of maximum travel distance.

Compartment1 Compartment2 Compartment3


60mmaximum
60mmaximum

i.Maximumtraveldistancenomorethan
60mtoeachoftwoadjoiningcompartments

OR

Compartment1 Compartment2
60mmaximum
60mmaximum

ii.Maximumtraveldistancenomorethan
60mtoanadjoiningcompartmentand
toastairway

Figure 5 Travel distances within a compartment

23
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

i. Maximumtraveldistancenomore
than30mtoanadjoiningcompartment
Subcompartment Compartmentor
orsubcompartment
subcompartment
30mmaximum

OR

ii. Maximumtraveldistancenomorethan30m
toastairwayorfinalexit Subcompartment

Stairwayorfinalexit
30mmaximum

Figure 6 Travel distances within a sub-compartment

Hospital streets (iii) so that the maximum distance from


a compartment exit to a final exit is
3.37 A hospital street should: no more than 90 m;
a. be constructed to the same fire-resisting e. at upper levels have access to a
standards as a fire compartment; minimum of two stairways each in
b. have a minimum clear width of 3 m; separate sub-compartments, which are
located so that:
c. be divided into a minimum of three sub-
compartments, each with a maximum (i) the maximum distance between
length of 30 m; stairways does not exceed 60 m;

d. at ground floor have a minimum of two (ii) the maximum single direction of
final exits located: travel within the street does not
exceed 15 m;
(i) at every extremity of the hospital
street; (iii) the distance from a compartment
exit to a stairway is no more than
(ii) so that the maximum travel 30 m; and
distance between final exits is no
more than 180 m measured along f. contain no other accommodation except
the length of hospital street; sanitary accommodation (see Figures 7
and 8).

24
3. Means of warning and escape

i.Basicdesign

Minimumwidthofstreet3000mm
Finalexitateveryextremity

Hospitalaccommodation Hospital
accommodation

Finalexit
minimumwidthof
street3000mm

Hospitalaccommodation Hospital
accommodation

Finalexit
60minutefireresisting
compartmentwalls

ii.Basicsubdivision

Maximumdistance

90mtoafinalexit
Hospitalaccommodation Hospital
accommodation
Lifts Lifts

Hospital
accommodation

Maximumdistance
60mtoafinalexit
Hospitalaccommodation Hospitalaccommodation

60minutefireresisting Maximumtraveldistance

compartmentwalls betweenfinalexits180m

Streetsubdivisions

30minutefireresisting

subcompartmentwalls

Figure 7 Hospital streets at ground level

25
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

Key...............................
Hospitalstreet

i.Basicdesign

Hospitalaccommodation

Hospitalaccommodation Hospital
accommodation
15m
maximum
singledirection 30mmaximumtravel
ofescapetravel distancetonearest
distance stairway

15m
maximum
singledirection
ofescapetravel Stairwayenclosuresmaximum
distance 60mapart Stairwayenclosuresmaximum60mapart

Hospitalaccommodation Hospitalaccommodation

60minutefireresisting
compartmentwalls
ii.Basicsubdivision Hospitalaccommodation

Hospitalaccommodation Hospital
Lifts
accommodation

Lifts

Hospitalaccommodation Hospitalaccommodation

60minutefireresisting
compartmentwalls Thearrangementindicatedbelowisnotacceptable,asa
Streetsubdivision30minutefire fireaffectingthehatchedareaofthehospitalstreet
resistingsubcompartmentwalls wouldpreventescapefromcompartments1and2

Hospitalstreet

Compartment3 Compartment1 Compartment2

Figure 8 Hospital streets on upper floors

26
3. Means of warning and escape

3.38 Entrances from the hospital street to 3.42 In departments and areas where beds or
adjoining compartments should: patient trolleys will not be used, the minimum
clear width of escape routes should be:
a. not be located in the same street sub-
compartment as entrances to stairways a. for up to 200 people 1200 mm;
and lift enclosures;
b. for over 200 people an additional
b. be located so that an alternative means 275 mm for every additional 50 people.
of escape from each compartment is
always possible (see Figure 8).
Vertical escape
3.39 Stairways should be located so that the 3.43 In the majority of healthcare premises
maximum travel distance from the exit of the the practice of designating certain stairways
stairway enclosure to a final exit from the as escape stairways and others as
hospital street is no more than 60 m. However, accommodation stairways only is not
it should be noted that there are additional acceptable, since in an emergency any stairway
requirements for fire-and-rescue service access will be used if necessary. Therefore all stairways
into hospital streets, see paragraphs 7.187.20. should be protected stairways designed to
permit vertical escape by the most appropriate
Additional requirements for hospital streets method, see paragraphs 3.533.55.
with only three sub-compartments
3.44 Most healthcare premises will normally
3.40 On upper storeys, stairways should contain an adequate number of stairways
be provided in two of the three sub- due to functional requirements; however, the
compartments, and the third sub-compartment minimum number of stairways should always
should be capable of accommodating all the meet the provisions in Table 2 below.
occupants with the associated beds and
medical equipment of the largest adjoining Number of patient beds on Number of stairways
compartment. any one upper storey
1100 2
101200 3
Width of escape routes 201300 4
3.41 Generally, within departments where beds 301400 5
and patient trolleys are being moved, the width
Table 2 Provision of stairways
of the circulation spaces required for these
activities should be adequate for escape 3.45 Every building providing healthcare should
purposes. However, elsewhere, the width of be provided with a minimum of two stairways.
escape routes should be determined by the Where hospitals are provided with hospital
number of people who would normally be streets, the stairways should be located within
expected to use them in an emergency. In the hospital street. In hospitals not provided
addition, the use of steps should be avoided on with hospital streets, each compartment should
circulation routes. Changes in level should be have access to a stairway by way of a
overcome using ramps. circulation space see Figure 2.

Note 3.46 In all healthcare premises, stairways


should be located so that alternative means
Guidance on suitable widths of circulation of escape is always available from every
routes within hospital departments, for compartment and sub-compartment.
operational purposes, is available in Health
Building Note 00-04 Circulation and 3.47 External stairways should not be provided
communication spaces. for escape purposes from patient-access
areas.
27
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

3.48 Stairways should always be remote from Assisted patient evacuation


each other so that in the event of fire at least
one is available for evacuation purposes. 3.53 All stairways to areas that provide sleeping
accommodation or contain dependent or very
high dependency patients should be designed
Escape lifts to permit the evacuation of patients on
3.49 Where departments providing care and mattresses (mattress evacuation) or other
treatment for very high dependency patients or similar methods. The stair width is not
bariatric patients are accommodated on upper determined by the number of people expected
floors, at least two escape lifts should be to use the flight in a fire emergency, but by the
provided. These should be sufficiently remote requirements of mattress manoeuvrability, and
from each other to ensure that at least one is therefore the guidance in Approved Document
always available in the event of a fire. K Protection from falling, collision and
impact in relation to landing depths need not
Note be applied.

It is unrealistic to believe that the total 3.54 Table 3 and Figure 10 below provide
evacuation of occupants from upper floors of guidance on dimensions to facilitate assisted
multi-storey buildings can be achieved solely patient evacuation.
by the use of lifts. Therefore escape
stairways will always be required. Width of stairways not intended for assisted
patient evacuation
3.50 The dimensions of escape lifts and lobbies 3.55 Where stairways provide escape from
should comply with Figure 9 below. areas used only by dependent patients, the
width of the stairway should be determined
3.51 In large buildings or extensive hospital from the guidance in paragraph 3.42.
complexes it may be appropriate to utilise
non-escape lifts as part of the evacuation All stairways
strategy. In such instances the lifts should be in
a separate fire compartment and separated by 3.56 All stairways should terminate at final exit
distance from the fire-affected part of the or escape level and:
building. An assessment will be required to a. provide access to the outside; or
support the use of non-escape lifts in an
evacuation; this should consider the guidance b. discharge to a route from the base of
of BD 2466 Guidance on emergency use of the stairway to the outside, which
lifts or escalators and fire and rescue service provides the same period of fire
operation. resistance as the protected shaft and
which contains no accommodation
3.52 All escape lifts should be designed to except that permitted for a protected
comply with the guidance in Health Technical shaft; or
Memorandum 05-03: Part E Escape lifts
c. discharge to a hospital street.
and BS 5588-8 Fire precautions in the
design, construction and use of buildings:
Code of practice for means of escape for Additional requirements for stairways
disabled people and Health Technical 3.57 Escape stairs should not discharge to an
Memorandum 08-02 Lifts. atrium.

28
3. Means of warning and escape

carsize
(1800)

handrail

approx2440withpumpattachedtoendofbed
450 10001080
clearcarsize
(2700)

trolley/

2370
equipment

450
600(500)

(1370)

widthofspaceforattendantstoturnbed180degrees
(3370)
CL

4310(3980)
lengthofspaceforattendantstoturnbed180degrees

Figure 9 Dimensions of escape lifts and lobbies

29
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

A B C
Minimum clear landing width Minimum clear stair width Minimum clear landing depth
(mm) (mm) (mm)
2800 1100 1950 allowsassistedpatient
2800 1200 1925 evacuationonly

2800 1300 1850


allowsassistedpatient
3000 1400 1750 evacuationandrestricted
ambulantpassing
3200 1500 1550
3400 1600 1600* allowsassistedpatient
evacuationplusambulant
3800 1800 1800* passing
*Stairwidthisnotdeterminedbythenumberofpeopleexpectedtousethestairsinafireemergency,butprincipallybythe
requirementsofassistedpatientevacuation.

Theevacuationstrategyandthenotesbelowwilldeterminetheoptimumrequirementsforstairwidthsandlandingdepths.

Foraclearlandingwidthof3400mm,theminimumclearlandingdepthforassistedpatientevacuationis1450mm.1600mmisthe
recommendeddepthtoenableambulantpassingandtoequalthestairclearwidth.SeeBS8300.

Foraclearlandingwidthof3800mm,theminimumclearlandingdepthforassistedpatientevacuationis1350mm.1800mmis
recommendedtoequalthestairwidth.SeeBS8300.

Table 3 Alternative stair and landing dimensions to facilitate assisted patient evacuation

Examplelandingdepthfor1500
clearstairwidth.Alternative
dimensionsseeTable3
C(1550)
Examplestairwidth,seetable

ExamplelandingwidthtofacilitateUturndraggingmattress,
for1500clearstairwidth.AlternativedimensionsseeTable1
B(1500)

A(3220)

DOWN
120(100)

Figure 10 Assisted patient evacuation down a stairway

30
3. Means of warning and escape

c. the provision of adequate paved


Note footpaths and dropped kerbs to the
assembly points;
Additional requirements for the enclosure and
ventilation of stairways are provided in d. the gradients of external escape routes;
paragraphs 5.265.33.
e. the proximity of external escape routes
to the external wall of the building; and
f. the need to maintain segregation of
Final exits patients if required by the emergency
3.58 The design of all exits should recognise evacuation strategy see Chapter 2.
the need to maintain the delicate balance
between the requirements of means of escape
and those of security. It is not possible to Departments providing intensive
provide definitive guidance on this issue; care
however, any solution should be agreed
3.63 In these departments, any movement or
between the enforcing authorities, the
evacuation of patients may be life-threatening;
trust management and its local security
consequently, additional precautions are
management specialist.
required to address the implications of:
3.59 Automatic final exit doors should be a. fire and smoke in an adjacent
freely openable by hand under any condition, compartment outside the intensive care
including power failure; otherwise, adjacent area;
non-automatic outward-opening doors must be
provided. b. fire and smoke within the department
itself.
3.60 Final exit doors should not be provided
with a step and should open onto an area 3.64 The aim of any design should be to
which is level for a distance of at least 1 metre. prevent a fire in an adjacent compartment
either on the same storey or on a storey above
or below requiring the evacuation of a intensive
External escape routes care area. The compartmentation and HVAC
3.61 Should it become necessary to evacuate should be designed so that an adequate period
an entire building or part of a building, adequate of time is provided to enable a fire to be
external assembly positions should be available. detected and extinguished before it threatens
Suitable positions may be roadways, hard the occupants.
standings or suitably designed parts of the
landscaping. 3.65 With the exception of doors from a
hospital street, every door opening in the
3.62 The following points should be considered compartment wall should be provided with a
when designing external escape routes: protected lobby, each door of which will provide
a minimum period of fire resistance of
a. the location of assembly positions to 30 minutes (integrity). This arrangement will
permit access for ambulances, while reduce the possibility of smoke ingress from a
maintaining adequate circulation space fire outside the department.
for other emergency vehicles;
b. the provision of adequate artificial

lighting;

31
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

Sub-compartmentation in departments Operating departments


providing intensive care
3.69 Operating departments, by their very
3.66 All departments providing intensive nature, are considered to be very high
care should be divided into at least two sub- dependency areas. Evacuation of patients from
compartments in order to separate the nursing these departments may be life-threatening;
area from the utility area. The following therefore, additional measures should be
provides an example: provided to allow sufficient time to prepare
Sub-compartment one staff base: patients for evacuation.

bed areas; 3.70 Consideration should be given to


subdividing the operating department to enable
clean utility; local transfer of patients from the immediate
dirty utility; threat to a temporary place of safety; this could
be achieved by:
linen store;
a. sub-compartmenting the operating
status laboratory; department with 30 minutes fire
resistance; or
Sub-compartment two entrance area:
b. installing life safety sprinklers (see
staff changing;
paragraphs 5.755.96) and dividing the
staff rest rooms; operating department with smoke-
retarding construction.
seminar rooms;
cleaners store; Note
main equipment store; The extent of the sub-division within the
bulk store;
operating departments should be risk-
assessed, taking into account its size and the
on-call area.
number of operating rooms, and operational
criticality of the department (that is, business
Heating and ventilation systems continuity).
3.67 The HVAC systems provided to intensive
care areas are designed so that the pressure 3.71 The design of the sub-compartmentation,
within the department is maintained at a level the location of smoke-retarding construction
slightly above that of the adjacent areas. In a fire and the operation of fire and smoke dampers
emergency, the continuing operation of these should not impede the clean air-flow paths
systems will assist in preventing smoke and and room-air dilution rates, as this may lead to
other products of combustion entering the an increased risk of healthcare-associated
intensive care area. infections. It is therefore essential that experts in
theatre ventilation systems are fully involved in
3.68 In departments providing intensive care, the design of all fire safety measures in
the HVAC systems should be designed so that operating theatres.
they continue to operate in a fire emergency.
The shutdown of these systems should be 3.72 Further guidance on the design of
controlled from remote panels located either at specialised ventilation for operating theatres is
the department entrance or adjacent to the contained in HTM 03-01 Part A.
main fire-alarm indicator panel.

32
3. Means of warning and escape

3.73 If practical, plantrooms should be sub- 3.78 Guidance on emergency escape lighting
compartmented to separate essential services is contained within BS 5266. For healthcare
(for example power and ventilation) serving premises buildings, this is supplemented by
very high dependency areas from other plant Health Technical Memorandum 06-01
equipment and machinery (for example lift Electrical services: supply and distribution and
motors, maintenance areas etc). the CIBSE guide Lighting guide LG2:
hospitals and healthcare buildings, which
provide additional guidance on hospital
Emergency and escape lighting emergency lighting and details of the electrical
3.74 In hospitals, electrical distribution is supply required.
generally provided by essential and non-
essential electrical circuits. To enable services 3.79 Emergency escape lighting should be
to be maintained, the essential circuits are provided to all areas in accordance with
provided with standby generators that operate BS 5266. Emergency escape lighting includes
when there is a failure of mains electricity escape route lighting, open area lighting and
serving the site or building. These are designed high-risk task area lighting, each of which has
to provide an emergency electrical back-up specific recommendations in terms of location
supply within 15 seconds of a mains failure. and luminance.

3.75 In terms of supporting resilience, additional 3.80 All emergency escape lighting should have
precautions are necessary; for example, the a minimum duration time of three hours and
distribution boards for the essential and non- should incorporate fully automatic network
essential circuits may be in the same location testing facilities.
but should be in separate metal cabinets.
Likewise, essential and non-essential circuits 3.81 Where possible, central battery or self-
are normally segregated; however, where this is contained emergency escape lighting fittings
not possible, essential services cables should must derive power from essential circuits.
be wired in fire-resistant cable. (Note: electrical
distribution systems serving life safety and Plant areas
fire-fighting applications as detailed in BS 8519
must always be wired in fire-resistant cable.) 3.82 The means of escape from plantrooms
should be designed to take account of the
3.76 In addition to the above, within each fire hazard presented by the equipment or
hospital department separate circuits are contents of the room and any hindrance to the
generally provided for circulation spaces. movement of the occupants (for example low
Therefore, failure of a lighting circuit supplying a headroom).
circulation space should not affect the lighting
circuits in the adjacent rooms, and vice-versa. 3.83 The escape route should be clear of
obstructions and have a clear height of at least
3.77 While these features provide a degree of 2 m throughout its length.
resilience, they do not fully address potential
failure modes such as final circuit, distribution 3.84 Where a minimum of two exits are
board or phase failure. Furthermore, HTM provided, the maximum travel distance from
06-01 recommends that emergency escape any point within a plantroom should not exceed
lighting in all areas can be operational within 25 m to the nearest exit from where alternative
0.5 seconds of interruption to the normal means of escape are provided. Of this 25 m,
supply, which is not achievable solely through the maximum single direction of escape should
the use of standby generators. not exceed 12 m.

33
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

3.85 Where only one exit is provided, the b. patients would be able to disperse,
maximum travel distance should not exceed not necessarily following the safest
12 m. evacuation route or abscond, possibly
placing themselves or others at risk; and
3.86 Where only one exit is provided, or where
there is a danger of people being trapped, c. it would also be more difficult to
alternative means of escape such as ceiling establish that everyone had safely
hatches and fixed ladders should be provided. escaped from the evacuated area of the
building.
3.87 Where the plantroom can be shown to be
of very low risk (for example only containing 3.90 In areas where security or maintaining
air-handling plant), the distances above may be patient segregation is important, the staffing
extended to 25 m and 35 m respectively. levels should be sufficient to allow the operation
of a key-operated, or other staff-controlled,
means of escape.
Security
3.91 Any slight delay in opening doors
3.88 In certain situations it may be essential
(compared with an automatic system) should
to maintain a high level of supervision and
be compensated for by the ability of sufficient
segregation during an evacuation.
numbers of well-trained staff team to undertake
3.89 In these situations, secure doors that are a controlled evacuation quickly.
released automatically on the activation of the
fire alarm system may not be acceptable, since:
a. it would be very difficult for staff to
maintain segregation of patients;

34
4. Internal fire spread (linings)

Requirement

Chapter 4 provides guidance to comply with the following Requirement from Part B of

Schedule 1 of the Building Regulations 2010.

Requirement

Internal fire spread (linings)

B2

(1) To inhibit the spread of fire within the building, the internal linings shall:
a. adequately resist the spread of flame over their surfaces; and
b. have, if ignited, a rate of heat release of a rate of fire growth which is reasonable in the
circumstances.

(2) In this paragraph internal linings means the materials or products used in lining any

partition, wall, ceiling or other internal surface.

4.1 The surface finish applied to walls and 4.3 Wall and ceiling finishes should meet the
ceilings can contribute to the spread of a fire. classifications in Table 4.
Some finishes will rapidly propagate the
development of fire by surface spread of
flame. This not only makes the fire difficult to Roof lights
control, but also provides additional fuel, which 4.4 Roof lights should also meet the
will increase the severity of the fire. requirements of Table 4.

4.2 Surface finishes that can be effectively 4.5 However, plastic roof lights with a Class 3
tested for surface spread of flame are rated rating for surface spread of flame may be used,
for performance by reference to the method provided that the limitations imposed by
specified in Table 4 below. paragraph 4.9 are observed.

35
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

Location National classification European class


Small rooms (not more than 4 m2 ) 1 C-s3,d2
Circulation spaces 0 B-s3,d2
Other rooms 0 B-s3,d2
Notes:

Thelimitationsonsurfacefinishesdonotapplyto:

a.demountablesanitarybackpanelscommonlyusedinhealthpremisestoprovideaccessformaintenancebehindwashbasins,
toilets,showersetc;and

b.roomsprovidingaspecialistfunction(forexampleaudiologybooths)whereotherfunctionalcriteriadictatethesurfacefinish.

ThenationalclassificationsdonotautomaticallyequatewiththeequivalentclassificationsintheEuropeancolumn;therefore,products
cannottypicallyassumeaEuropeanclassunlesstheyhavebeentestedaccordingly.

Whenaclassificationincludess3,d2,thismeansthatthereisnolimitsetforsmokeproductionand/orflamingdroplets/particles.

Table 4 Classification of linings

Thermoplastic materials a. the maximum area of each diffuser or


roof light;
4.6 Thermoplastic materials (see Appendix C)
that cannot meet the performance b. the maximum total area of diffusers and
requirements given in Table 4 may be used in roof lights;
roof lights and lighting diffusers in suspended
c. the minimum separation between
ceilings if they comply with the requirements in
diffusers and roof lights.
paragraphs 4.10 and 4.12.
4.9 Thermoplastic roof lights and lighting
4.7 The guidance on the use of thermoplastic
diffusers with a classification of lower surface
lighting diffusers applies irrespective of whether
TP(b) (see Appendix C) and roof lights with a
the lighting diffuser forms part of the ceiling or
Class 3 rating may be used in all areas, with the
is attached to the soffit of, or suspended
following restrictions:
beneath, a ceiling (see Figure 11).
a. the maximum area of each diffuser or
a.Diffuserformingpartofceiling roof light should be no more than 5m2;
b. the maximum total area of diffusers and
roof lights, as a percentage of the floor
Ceiling area of the space in which they are
located, should be no more than 15%;
b.Diffuserinfittingbelow,andnotforming
partof,ceiling c. the minimum distance between roof
lights should be not less than 3 m (see
Ceiling Figure 12).

Figure 11 Lighting diffuser in relation to ceiling 4.10 Thermoplastic roof lights with a
classification of upper surface TP(b) should not
be used.
4.8 Thermoplastic roof lights and lighting
diffusers with a classification of lower surface 4.11 Thermoplastic lighting diffusers should not
of TP(a) (see Appendix C) may be used in all be used in a fire-resisting ceiling unless they
locations, except stairways, with no restrictions have been satisfactorily tested as part of a
on: ceiling assembly that provides the appropriate
fire protection.

36
4. Internal fire spread (linings)

4.12 The minimum distance from a relevant


boundary of thermoplastic roof lights with a
classification of upper surface of TP(a) should
be not less than 6 m.

5mmaximumdimension
ofgroupofpanels 5mmax.
3mminimum

5mismaximumarea
ofdiffuserorrooflightinany
5mmax. one5m5mgroup

3mminimumdimension Key
betweengroupsofpanels Panelofdiffuser
orrooflight

Separatedgroupsof
panelsorrooflights

Notes:
a. Upperandlowersurfaceofsuspendedceiling,betweenplasticpanels,tocomplywithparagraph6.1inApprovedDocumentB.
b. NorestrictiononClass3rooflightsinsmallrooms.

Figure 12 Layout restrictions on Class 3 rooflights, TP(b) rooflights and TP(b) lighting diffusers

37
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

5. Internal fire spread (structure)

Requirement

Chapter 5 provides guidance to comply with the following Requirement from Part B of

Schedule 1 of the Building Regulations 2010.

Requirement

Internal fire spread (structure)

B3

(1) The building shall be designed and constructed so that, in the event of fire, its stability will

be maintained for a reasonable period.

(2) A wall common to two or more buildings shall be designed and constructed so that it

adequately resists the spread of fire between those buildings. For the purposes of this

sub-paragraph a house in a terrace and a semi-detached house are each to be treated as

a separate building.

(3) Where reasonably necessary to inhibit the spread of fire within a building, measures shall

be taken, to an extent appropriate to the size and intended use of the building, comprising

either or both of the following:

a. sub-division of the building with fire-resisting construction;


b. installation of suitable automatic fire suppression systems.

(4) The building shall be designed and constructed so that unseen spread of fire and smoke

within concealed spaces in its structure and fabric is inhibited.

Elements of structure a. resistance to collapse; that is, the ability


to maintain load-bearing capacity (which
5.1 The fire resistance of an element of applies to load-bearing elements only);
construction is a measure of its ability to
withstand the effects of fire in one or more b. resistance to fire penetration; that is, an
ways, as follows: ability to maintain the integrity of the
element; and

38
5. Internal fire spread (structure)

c. resistance to the transfer of excessive 5.4 Roof structure and structure that only
heat; that is, an ability to provide supports a roof may not require fire-resistance
insulation from high temperatures. for life safety purposes unless:

5.2 To prevent the premature failure of the a. the stability of the building depends on
structure, the load-bearing elements of the the roof; or
building are required to have a minimum period b. the roof serves as a floor, for example a
of fire resistance in terms of resistance to rooftop car park or plantroom; or
collapse or failure of load-bearing capacity.
The purpose of providing the structure with fire c. the roof is used as an escape route.
resistance is to:
5.5 The minimum period of fire resistance
a. minimise the risk to the occupants, provided by the elements of structure should be
many of whom may still be in a as in Table 5.
temporary place of safety within the
building awaiting evacuation; 5.6 Reductions in periods of fire resistance are
permitted only where sprinklers are installed
b. reduce the risk to fire-fighters; and
throughout the building. Partial sprinkler
c. reduce the danger to people in the coverage will not provide the same extent of
vicinity of the building. protection for structural elements.

5.3 For the purposes of this document, 5.7 Partial sprinkler protection can help mitigate
elements of structure are: localised fire risks in a building and therefore
may offer other benefits for the design. A fire
a. a column, beam, or other member engineer should be consulted on a solution
forming part of a structural frame; that provides enhancements based on partial
b. a load-bearing wall; sprinkler coverage which should be supported
by fire engineering evidence.
c. a floor.

Minimum period of fire resistance provided by elements


of structure
Unsprinklered Sprinklered
Single-storey healthcare buildings 30minutes 30minutes
Healthcare buildings with storeys up to 12 m above ground or 60minutes 30minutes*
basements no more than 10 m deep (60minutesinrespectofbasements*)
Healthcare buildings with storeys over 12 m above ground or 90minutes 60minutes*
basements more than 10 m deep
Healthcare buildings with storeys over 30 m Notpermitted 90minutes*
Notes:

*ThereductioninfireresistanceisconditionaluponalifesafetysprinklersysteminstalledandmaintainedinlinewithBSEN12845.

Elementsofstructureinrelationtobasementsincludetheground-floorslab.

Whereonesideofabasementis(duetotheslopeoftheground)openatgroundlevel,givinganopportunityforsmokeventingand
accessforfire-fighting,itmaybeappropriatetoadoptthestandardoffireresistanceapplicabletoabove-groundstructuresfor
elementsofstructureinthatstorey.

Inordertoreducethefireresistancetoelementsofstructure,thewholebuildingmustbeprotectedbyasprinklerinstallationdesign.

Table 5 Fire resistance of elements of structure

39
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

Compartmentation Materials used to meet this provision can be


found in the Glossary (Appendix A) under
5.8 The requirement for compartmentation is Material of limited combustibility.
discussed in Chapters 2 and 3. Within patient-
access areas, compartmentation is used to 5.15 Where sprinklers are installed throughout
divide a storey into places of temporary safety the whole building, the requirement for
which may be used for refuge. In addition, elements of structure and compartment walls
compartmentation prevents rapid fire spread to be constructed of materials of limited
throughout the building and reduces the combustibility does not apply.
likelihood of large fires.

5.9 For buildings more than one storey in Openings in compartment walls and floors
height, all floors should be compartment floors. 5.16 All openings in floors and compartment
walls should be protected to provide at least
5.10 In healthcare premises, the maximum size the same period of fire resistance as the
of a compartment is generally determined by its compartment structure.
use; it is strongly recommended that the size of
the management department determines the 5.17 To maintain the integrity of
size of a compartment (see paragraph 3.22). compartmentation, openings should be
limited to:
5.11 The maximum area of a compartment
should not exceed: a. doors which have a period of fire
resistance not less than that of the
2000 m2 in a multi-storey building; compartment structure (that is, integrity
3000 m2 in a single-storey building. performance);
b. openings for pipes of not more than
5.12 The minimum period of fire resistance 160 mm diameter which, if exposed to a
(integrity and insulation) provided by temperature of 800C, will not soften or
compartment walls should be: fracture to the extent that flames or hot
a. for single-storey healthcare buildings gases will pass through the wall of the
30 minutes (except where this conflicts pipe;
with the requirements of Table 5); or c. pipes of materials other than those in (b)
b. for all sprinklered healthcare buildings above of not more than 40 mm
30 minutes; or diameter;

c. for all other healthcare buildings d. pipes of any diameter that are provided
60 minutes, including those with with a proprietary seal which has been
basements more than 10 m deep and shown by test (for the diameter of pipe
those four storeys or more above proposed) to maintain the fire resistance
ground level. of the compartment structure;
e. ventilation ducts that comply with the
5.13 All compartment floors are considered as
requirements of BS 5588-9 (see
elements of structure and should satisfy the
Figure 16);
requirements of Table 5.
f. refuse and laundry chutes of non-
combustible construction that are
Elements of structure and accessed through fire-resisting doors;
compartment walls and
5.14 Elements of structure and compartment g. protected shafts.
walls are required to meet the above provisions.

40
5. Internal fire spread (structure)

Junction of compartment walls with roofs Glazing in sub-compartment walls


5.18 Compartment walls should be taken up to 5.23 Uninsulated fire-resisting glazed screens
the underside of the roof covering or deck, and may only be provided in sub-compartment
fire-stopped to maintain the fire resistance. The walls provided they satisfy the following
compartment wall should also be continued requirements:
across any eaves cavity.
a. the glazing should provide a minimum
5.19 A zone of the roof 1.5 m wide on either period of 30 minutes fire resistance
side of the wall should have a covering of (integrity only);
designation AA, AB or AC (see Approved b. the area of integrity-only glazing should
Document B, Appendix B, paragraph 6) on be limited to a maximum of 1 m2 in any
a substrate or deck of a material of limited room.
combustibility.
5.24 There is no limit on the use of glazed
Note screens that provide a minimum period of fire
resistance of 30 minutes (integrity and
Double-skinned insulated roof sheeting, with
insulation).
a thermoplastic core, should incorporate a

band of material of limited combustibility at


5.25 Where sprinklers are fitted, there is no limit
least 300 mm wide centred over the wall.
on the use of glazed screens that provide a
minimum period of fire resistance of 30 minutes
(integrity only), provided the glass is not of the
5.20 As an alternative to paragraphs 5.18 and type referred to as modified toughened.
5.19 the compartment wall may be extended up
through the roof for a height of at least 375 mm
above the top surface of the adjoining roof Protected shafts
covering. 5.26 Openings in floors for stairways, lifts,
escalators, and pipes and ducts not complying
Glazing in a compartment wall with paragraph 5.17 should be enclosed in a
5.21 Any glazing provided in a compartment protected shaft that has the same period of fire
wall should have the same period of fire resistance (integrity, insulation and, where
resistance (integrity and insulation) as the applicable, load-bearing capacity) as the
compartment wall. Glazing should have a compartment floor (see Figure 13).
permanent, legible mark giving the
5.27 The protected shaft should form a
manufacturer, product name, fire-resistance
complete barrier to fire between different
rating and any requirement for impact safety
compartments to which the shaft connects and
performance according to BS 6206 or BS EN
should be constructed from materials of limited
12600.
combustibility. Where services (pipes, cables,
ducts etc) are required to pass through the
Sub-compartment walls enclosing structure they should be adequately
fire-stopped to maintain the fire resistance of
Openings in sub-compartment walls the protected shaft. Where pipes are required
5.22 All openings in sub-compartment walls to pass through the enclosing structure, they
should be protected to provide a minimum should be designed in accordance with
period of fire resistance of 30 minutes. Figure 14.

5.28 Any internal glazing provided to a


protected shaft should have the same period of

41
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

Compartmentwall

Door Door
Externalwall Door Door

ProtectedshaftA ProtectedshaftC
boundedonthreesides aservicesductbounded
bycompartmentwalls onfoursidesby
andonfourthsideby ProtectedshaftB compartmentwalls
anexternalwall boundedonfoursides

bycompartmentwalls

Note:Theprotectedshaftshouldmeettherelevantprovisionsforcompartmentwalls
Figure 13 Protected shafts

Structure

Notlessthan Notlessthan
1000mm 1000mm

Pipespecification(b) Sleeve(orpipe)
ofspecification(a)
tobeincontact
withpipe

Pipematerialandmaximumnominalinternaldiameter(mm)
(a)Non (b)Lead,aluminium, (c)Anyothermaterial
combustible aluminiumalloy,
material1 uPVC2,fibrecement

Structure
enclosinga 160 110 40
protectedshaft
whichisnota
stairwayorlift
shaft

Anyothersituation 160 40 40

Notes:
1. Anynoncombustiblematerial(suchascastiron,copperorsteel)which,ifexposedtoa
temperatureof800C,willnotsoftenorfracture totheextentthatflameorhotgaswill
passthroughthewallofthepipe.
2.uPVCpipescomplyingwithBS4514anduPVCpipescomplyingwithBS5255.
Figure 14 Pipes penetrating fire-resisting structure

42
5. Internal fire spread (structure)

fire resistance (integrity and insulation) as the pipes conveying oil as part of the operating
protected shaft. mechanism of a hydraulic lift and ventilation
ductwork provided for the purposes of
5.29 The use of roof lights over protected shafts pressurising the stairway.
used for stairways should be limited to those
that provide a Class 1 surface spread of flame 5.33 Protected shafts containing a stairway
on both upper and lower surfaces. should be provided with an opening window, or
similar, providing a clear ventilation area of 1 m2.
5.30 The use of protected shafts should be
limited to:
Protected lobbies
a. stairways;
5.34 Protected shafts for stairways and lifts
b. lifts; should be provided with protected lobbies
except where they are accessed from a hospital
c. escalators; street.
d. chutes;
5.35 Protected lobbies should not be located
e. ducts; so that they form part of a through route; that
is, they should not be located across a corridor
f. pipes.
if the corridor continues beyond the protected
5.31 No accommodation should be included lobby (see Figure 15).
within protected shafts.
5.36 Guidance on the recommended
5.32 Pipes conveying oil or gas and ventilation dimensions for internal lobbies is provided in
ductwork should not be located in the same Health Building Note 00-04 Circulation and
protected shaft as a stairway or lift except communication spaces. This recommends that
where swing doors are used, a minimum clear

i.stairwayaccessedfromacirculationspace ii.stairwayaccessedfromahospitalstreet

(protectedlobbyrequired) (protectedlobbynotrequired)

FD30S

Protected
lobby

FD30S

FD30S

Hospitalstreet

Circulationspace

Figure 15 Protected lobbies to stairways

43
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

length (that is clear of the furthest point that to identify and segregate fire hazard rooms by
door(s) will swing into) is provided of: at least 30 minutes fire-resisting construction.
a. 1.570 m for general traffic access; and 5.41 Table 6 gives examples of fire hazard
b. 4.100 m for bed/trolley access. rooms. The list is not exhaustive, and the onus
rests with the designer to assess the fire risk
5.37 Protected lobbies should: associated with all rooms to determine the
need to enclose in fire-resisting construction.
a. be constructed from materials of limited
combustibility and have the same fire Chemicalstores Relativesovernightstayroom
resistance as the protected shaft; and Cleanersroom Wardkitchens
Clothesstorage Patientbedroomsprovidedspecificallyfor
b. contain no other accommodation except thosesufferingfrommentalillness
Disposalrooms
that allowed for protected shafts. peoplewithlearningdisabilities
Hubrooms
Liftmotorrooms Communalbathroomsinmentalhealth
Fire stopping premises(seeparagraph2.52)
Mainstaffchanging Linenstores
5.38 In addition to any other provisions in this andlockerrooms
document for fire-stopping, joints between Storerooms Staffon-callrooms
fire-separating elements should be fire-stopped Key
and all openings for pipes, ducts, conduits or Doorstotheseroomstobekeptlocked
cables to pass through any part of fire- shut

separating elements should be: Doortobefittedwithappropriately


designedfree-swingself-closingdevices
a. kept as few in number as possible; Doorstobefittedwithself-closing
devices
b. kept as small as practicable; and
Table 6 Examples of fire hazard rooms
c. fire-stopped (which in the case of a pipe
5.42 Fire hazard rooms and areas should
or duct, should allow thermal
be enclosed in 30 minutes fire-resisting
movement).
construction (integrity and insulation). Walls
5.39 Guidance on the process of design, may be terminated at ceiling level provided that:
installation and maintenance of passive fire a. the ceiling is non-demountable and has
protection is available in Ensuring best practice a minimum period of fire resistance of
for passive fire protection in buildings (ISBN: 30 minutes when tested (complete
1 87040 919 1) produced by the Association for with any lighting units) from below in
Specialist Fire Protection (ASFP). accordance with BS 476 (Parts 20 and
22);
Fire hazard rooms and areas b. ducts perforating the ceiling are fitted
5.40 For most building types, it is normally with fire dampers;
required to protect escape routes with fire- c. conduits, pipes etc perforating the
resisting walls, ceilings and doors (protected ceiling are fire-stopped and comply with
corridors). In healthcare premises this is not the requirements of paragraph 5.27.
considered acceptable, since the excessive
number of fire-resisting doors, all fitted with 5.43 Where sprinklers are installed, the need
self-closing devices, would be a hindrance to to enclose fire hazard rooms in fire-resisting
staff and patients during the everyday running construction should be risk-assessed.
of a healthcare building. For this reason, the
technique advocated for healthcare buildings is

44
5. Internal fire spread (structure)

Glazed screens Location and operation of fire and smoke


5.44 Uninsulated glazed screens should not be dampers and fire dampers
provided to fire hazard rooms; however, there 5.49 Ventilation ducts should maintain the
is no limit on the use of glazed screens that period of fire resistance of the construction
provide a minimum period of fire resistance of through which they pass; this includes but
30 minutes when tested to the relevant parts is not limited to fire hazard rooms, sub-
of BS 476 (integrity and insulation) or BS EN compartments, compartments, cavity barriers
12600. and protected shafts.

5.50 The type of dampers permitted in each


Ventilation systems form of construction is indicated in Table 7.
5.45 Mechanical ventilation is used extensively
in healthcare premises, including specialist 5.51 All dampers should be installed in
systems for primary patient treatment in accordance with the manufacturers tested
operating departments, critical care areas and details so that they maintain their integrity
isolation rooms. It is also installed to ensure against the passage of fire for the required
compliance with quality assurance of period of fire resistance. They should be
manufactured items in pharmacy and sterile adequately fixed into, or to, the construction
services departments and to protect staff from they are protecting. A damper that is supported
harmful organisms and toxic substances (for only by the ductwork in which it is located, or
example in laboratories). by timber battens, frames or other methods
that do not provide the fire resistance required,
5.46 In the event of a fire, large quantities of is not acceptable.
smoke and toxic gases can be given off, which
potentially could be transferred through the 5.52 Dampers provided in 30-minute fire-
ductwork to rooms and areas remote from the resisting ceilings should be adequately
fire. Therefore, measures are required to: supported either by the ceiling or from the
structural soffit. In the ceiling situation, it is also
a. limit the spread of fire, smoke and other essential to ensure that the integrity of the
products of combustion within the fire-resisting ceiling is maintained. It is not
ductwork between protected areas; acceptable to form an opening, install a diffuser
or grille and fit a damper above if the gap
b. prevent a breach in the integrity of an
between the ceiling opening and the damper
enclosing fire-resisting element of
does not achieve 30 minutes fire resistance.
construction where penetrated by
ductwork. 5.53 Where, due to the specialist nature of the
ventilation system, the inclusion of dampers is
5.47 Ventilation systems should be designed
not recommended, fire rated ductwork will be
and installed to comply with Health Technical
required. This would typically occur with the
Memorandum 03-01 Specialised ventilation
provision of fume cupboards, isolation rooms
for healthcare premises and BS 5588-9.
and kitchen extract systems, for example. The
5.48 Ventilation systems should not be fire rated ductwork should meet the same
common to both patient areas and hazard performance requirements of the elements
departments. Fresh-air intakes should be through which it passes and should be installed
positioned to avoid the possibility of the intake in accordance with the manufacturers tested
of smoke and toxic gases. detail.

45
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

Fire and smoke damper Fire damper (Thermal Air transfer grille cold Air transfer grille
activated by AFD activation) smoke (activated by (thermal activation)
AFD)

Compartmentfloor X X X

Compartmentwall X X X

Protectedshaft X X X

Sub-compartmentwall X X X

Cavitybarrier N/A N/A

Firehazardroom X

Doortofirehazard
rooms
N/A N/A X

Doorsinsub-
compartmentwalls
N/A N/A X

Doorsincompartment
N/A N/A X X
walls
Doorstoprotected
N/A N/A X X
shafts
Notes:

Firesmokedampersandairtransfergrillesactivatedbythefirealarmprovidemoreresponsivecontainmentthanthermallyactivated
devicesandareconsideredpreferable.

Airtransfergrillesshouldnotbefittedinfiredoorsunlessaccompaniedbyatestcertificateprovidedbythedoormanufacturer.

Table 7 Permissible locations of transfer grilles, fire dampers, and fire and smoke dampers

Fireresistingwall

Fire
stopping

Ductwork

Fire
damper

Actuationofdampers:
i) inaccordancewithBS5588:Part9;
ii) bytheoperationofthedetectionandalarmsystemeithersideofthecompartmentorsubcompartmentwall;or
iii) byoperationoffusiblelinkinwallstofirehazardrooms

Figure 16 Fire and smoke damper in compartment, sub-compartment wall or wall to fire hazard room

46
5. Internal fire spread (structure)

5.54 Ductwork passing through, or over,


hazard rooms should be provided with fire
dampers in accordance with Figure 17.
i.ductworkpassingthroughbutnot
servingfirehazardroom

30minutefire 30minutefire
resistingwall resistingwall

Ductwork

Fire Fire
stopping stopping

Firehazard
room

i.firedampersnotrequired;

ii.ductworkinthehazardroomtohave30minutesfireresistance
(integrityandinsulation)whentestedtotherelevantpartsofBS476.

ii.ductworkpassingoverfirehazardroomfitted
withfireresistingceiling

Ductwork

Fireresistingceiling

30minutefire 30minutefire
resistingwall resistingwall

Firehazard
room

i.firedampersnotrequired;

ii.ceilingtobenondemountableandhaveaminimumperiodoffireresistance
of30minutes,whentested(completewithanylightingunits)frombelow
inaccordancewithBS476Parts20and22.

iii.ductworkservingfirehazardrooms

i.ductsshouldnotpassthroughthe
Supplyductwork hazardroomiftheductservesthefire
hazardroomandotherroomsbeyond
Firedamper thefirehazardroom;

Firehazard Otherroom ii.thefirehazardroomshouldbe


room servedbyspursfittedwithfiredampers
operatedbyfusiblelinks;

iii.whereflexibleconnectionsareused,
Firedamper theyshouldcomplywithBS55889
andnotpassthroughthefire
Extractductwork
resistingwalls

Figure 17 Options for the design of ductwork passing through or serving a fire hazard room

47
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

5.55 Where ventilation systems utilise air 5.61 Guidance on the construction and fixing of
transfer grilles, Table 7 indicates the types of air cavity barriers is provided in Appendix E.
transfer grille permitted in the different forms of
construction. 5.62 With the exception of the ceiling void
above operating departments (see paragraph
5.56 The fire resistance may be achieved by 6.48), 30-minute fire-resisting barriers should
the ductwork material itself, or through the be provided to subdivide concealed roof or
application of a protective material. ceiling voids, so that the maximum dimension
of uninterrupted roof or ceiling void should
Operation of ventilation plant not exceed 20 m. Wherever possible, cavity
barriers should be positioned to coincide with
5.57 The ventilation plant should not fire-resisting walls.
necessarily automatically shut down on the
operation of the automatic fire detection and 5.63 Thirty-minute fire-resisting cavity barriers
alarm system. For example, in areas where the should also be provided:
automatic shutdown of ventilation plant will
impede the clean air-flow paths and room-air a. to prevent the interconnection of vertical
dilution rates, this may lead to an increased risk and horizontal cavities;
of healthcare-associated infections. Where, due b. at the intersection of fire-resisting
to operational reasons, the ventilation plant construction and elements containing a
continues to run, override facilities will be concealed space;
required and the shutdown of the system
should be controlled from panels located either c. within the void behind the external face
at department entrances or adjacent to the of rain-screen cladding, at every floor
main fire alarm indicator panels. level and on the line of compartment
walls abutting the external wall.
Cavity barriers 5.64 Cavity barriers should not be provided:
5.58 Concealed spaces or cavities in the a. in cavity walls, as illustrated in Figure 18;
construction of a building may permit the rapid or
spread of fire and smoke. It is possible for fire
and smoke to be transferred to areas remote b. in double-skinned insulated roof
from the seat of the fire by way of uninterrupted sheeting, as illustrated in Figure 19; or
concealed spaces. For this reason, it is
c. below a floor next to the ground or
essential that fire-resisting barriers are provided
oversite concrete providing:
to restrict the size of these concealed spaces.
(i) the cavity is less than 1000 mm in
5.59 In healthcare premises, the subdivision height; or
provided through the requirements for hazard
protection, sub-compartmentation and (ii) it is not accessible by persons; and
compartmentation is such that generally the
(iii) there are no openings in the floor
additional subdivision of ceiling voids for cavity
such that it is possible for
barriers is not required. The exception to this is
combustibles to accumulate in the
where sub-compartment walls and walls to fire
cavity.
hazard rooms are terminated at 30-minute
fire-resisting ceilings. 5.65 Openings in barriers should be limited to
those for:
5.60 Irrespective of the above, there is a
requirement to prevent the interconnection of a. doors which have at least 30 minutes
horizontal and vertical cavities. fire resistance;

48
5. Internal fire spread (structure)

Sectionthroughcavitywall

Close cavityat
topofwall(unless
cavityistotally
filledwith
insulation)

Opening Close cavity


aroundopening

Twoleavesof
brickorconcr ete
each atleast
75mmthick

Note:

Combustiblematerialsshouldnotbeplacedinorexposedtothecavity,exceptfor:

a. timberlintels,windowordoorframes,ortheendsoftimberjoists;
b. pipes,conduitorcable;
c. DPC,flashingcavitycloserorwalltie;
d. thermalinsulatingmaterial(twoleavesofbrick,blockorconcreteeachatleast75mmthick,100mmmaximumcavitywidth)

Figure 18 Cavity wall not requiring a cavity barrier

i.acceptablewithoutcavitybarriers

Theinsulationshouldmakecontactwithbothskinsofsheeting

ii.cavitybarriersrequired

Figure 19 Cavity barriers in double-skinned insulated roof sheeting

49
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

b. pipes (see paragraph 5.32); e. be beneficial in terms of business

continuity.

c. cables or conduits;
d. openings fitted with a suitably mounted 5.70 The control of a fire at an early stage
automatic fire and smoke damper; extends the time available to evacuate and
enhances the protection provided to adjoining
e. ducts which, unless they are fire- places of temporary safety.
resisting, are fitted with a suitably
mounted automatic fire damper where 5.71 An extended evacuation time will help
they pass through the cavity barrier. where staff numbers are limited or where the
attendance of additional responding staff may
Cavity barriers above operating be delayed.
departments
5.72 The control of a fire can reduce the need
5.66 The complexities of ventilation ductwork for onward phases of evacuation. This will
systems above operating departments mean benefit very high dependency patients and help
that the provision of cavity barriers may maintain continuity of care.
seriously compromise service access and
means of escape for maintenance staff. 5.73 For premises providing care only for
Therefore cavity barriers should not be provided independent patients, the inclusion of sprinklers
over operating departments. may support the use of smoke-retarding
construction as an alternative to 30 minutes
5.67 Additionally, operating departments have fire-resisting construction. Any solution
restricted access and are well supervised when adopting this approach should be fully
in use, and hazard areas are enclosed within supported by fire engineering evidence to
fire-resisting construction. demonstrate that an equivalent level of safety
will be maintained as with a standard HTM-
compliant design solution.
Sprinklers
5.68 With the exception of buildings over 30 m 5.74 To avoid conflict, the AFD zoning
in height, the guidance in this document does arrangements should take precedence over the
not require the installation of sprinklers in sprinkler system, including in the cause and
patient care areas of healthcare buildings. effect.
However, the design team is expected to
consider the advantages that might be gained 5.75 Life-safety systems are defined in BS EN
by installing life-safety sprinklers throughout the 12845 as sprinkler systems forming an integral
building or to specific areas. Where specific part of measures required for the protection of
hazards are identified in the building, it may be life.
more appropriate to consider the application of
an alternative fire suppression system, such as 5.76 The performance of life-safety sprinklers
high pressure water mist technologies. can be enhanced by the specification and
installation of quick-response sprinkler heads
5.69 Life-safety sprinklers will: that enable the activation of the system quickly
after the heads have reached their operating
a. limit the size of a fire; temperature. This response is quicker than
conventional heads that have been developed
b. control fire spread;
for property protection.
c. provide additional time to evacuate;
5.77 Where a sprinkler system is specifically
d. limit fire damage; and recommended within this document, it should

50
5. Internal fire spread (structure)

be provided in the building or separated part (ii) any pump arrangements should
and designed and installed in accordance with comply with BS 5306-2, clause
either: 17.4.1.5; and
a. the requirements of BS 5306-2, (iii) the capacity of each tank should
including the relevant hazard be equivalent to at least half the
classification together with the additional specified minimum water volume
requirements for life safety; or of a single full capacity tank, as
appropriate to the hazard; or
b. the requirements of BS EN 12845,
including the relevant hazard (iv) one tank should be equivalent to
classification together with the special half the specified water volume of a
requirements for life safety systems. single full capacity tank and the
other should not be less than half
Note the minimum volume of a reduced
capacity tank (see BS 5306-2,
Any sprinkler system installed to satisfy Table 25), as appropriate to the
the requirements of this Health Technical hazard.
Memorandum or Part B of the Building
Regulations should be regarded as a life- Note
safety system. However, there may be some
circumstances where a particular life-safety The requirement for inflow should be met.
requirement specified in BS 5306-2 or BS EN Whichever water storage arrangement is
12845 is inappropriate or unnecessary. used at (iii) or (iv) above, the total design
capacity of the water supply, including any
inflow for a reduced capacity tank, should be
5.78 Water supplies for non-residential sprinkler
at least equivalent to a single full capacity
systems should consist of either:
tank complying with Tables 2124 of BS
a. systems designed and installed to 5306-2, as appropriate to the hazard and
BS 5306-2; or pipework design.
b. systems designed and installed to
BS EN 12845; Systems designed and installed to BS EN
c. Systems designed and installed to 12845
BS 5306-2. 5.80 These systems consist of either:
5.79 These systems consist of either: a. two single water supplies complying
with BS EN 12845, clause 9.6.1, where
a. two single water supplies complying each is independent of the other; or
with BS 5306-2, clause 13.1.2, where
each is independent of the other; or b. two stored water supplies, where:
b. two stored water supplies, where: (i) gravity or suction tanks should
satisfy the all requirements of BS
(i) gravity or suction tanks should EN 12845, clause 9.6.2 b) other
be either Type A, Type D or their than capacity; and
equivalent (see BS 5306-2, clause
17.4.11.6); and (ii) any pump arrangements should
comply with BS EN 12845, clause
10.2; and

51
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

(iii) the capacity of each tank is 5.84 Areas of the building not provided with
equivalent to half the specified sprinkler protection should be separated from
minimum water volume of a single those areas that are protected, by the provision
full capacity tank, as appropriate to of 60-minute fire-resisting structure (integrity
the hazard; or and insulation).
(iv) one tank should be at least
equivalent to half the specified Effect on other fire precautions
water volume of a single full 5.85 In those parts of healthcare buildings
capacity tank and the other should where sprinkler systems are provided, the
not be less than the minimum effect of sprinklers on the overall package of fire
volume of a reduced capacity tank precautions has to be considered to ensure
(see BS EN 12845, clause 9.3.40), that a cost-effective fire safety strategy is
as appropriate to the hazard. provided. Where sprinklers are installed in
healthcare premises in accordance with the
Note above guidance, some of the requirements of
this document may be modified to take account
The requirements for inflow should be met. of the effect of sprinkler operation at an early
Whichever water storage arrangement is stage of fire development.
used at (iii) or (iv) above, the total capacity of
the water supply, including any inflow for a 5.86 Where sprinklers are installed, the
reduced capacity tank, should be at least guidance may be modified subject to a
equivalent to a single full capacity tank suitable and sufficient risk assessment being
complying with BS EN 12845, Tables 9 and undertaken and the information being recorded
10 or clause 9.3.2.3, as appropriate to the in the fire safety manual. Examples include:
hazard and pipework design.
a. progressive horizontal evacuation

(paragraphs 3.63.15);

5.81 Where pumps are used to draw water b. glazing in sub-compartment walls

from two tanks, each pump should be (paragraphs 5.235.25);

arranged to draw water from either tank and so


that any one pump or either tank could be c. elements of structure (paragraphs 5.1
isolated. 5.7 and 5.145.15);

5.82 The sprinkler water supplies should d. compartmentation (paragraphs 5.8


generally not be used as connections for other 5.13);
services or other fixed fire-fighting systems. e. fire hazard rooms and areas

(paragraphs 5.405.44);

5.83 In patient-access areas of healthcare


premises, the sprinkler system should be a f. external fire spread (paragraphs 6.5
life-safety system, fitted with quick-response 6.15);
heads as defined in the Fire Protection
g. number and location of fire-fighting
Associations LPC rules for automatic sprinkler
shafts (paragraphs 7.11 and 7.13).
installations.

52
6. External fire spread

Requirement a portion of the roof should provide some fire


resistance to prevent the fire spreading through
Chapter 6 provides guidance to comply with the roof to other parts of the same building in
the following Requirement from Part B of different compartments (see also paragraphs
Schedule 1 of the Building Regulations 2010. 6.12 and 6.13).

Requirement 6.4 With the exception of unprotected areas,


the minimum period of fire resistance provided
External fire spread by external walls should be as in Table 8.

B4 Height to the top floor Minimum period of fire


resistance

(1) The external walls of the building shall Notmorethan5m 30minutes

adequately resist the spread of fire Over5m 60minutes

over the walls and from one building to Notes:

another, having regard to the height, use 1.Theminimumperiodoffireresistancerelatestointegrityand


load-bearingcapacity.Theminimumprovisionforinsulation
and position of the building. is15minutesunlesstheexternalwallislessthan1000mm
fromaboundaryoradjacentbuilding,whentherequirement
(2) The roof of the building shall adequately forinsulationshouldbethesameasthatforintegrityandload-
bearingcapacity.
resist the spread of fire over the roof and
from one building to another, having 2.Anexternalwallthatisalsoanelementofstructureshould
complywithTable5.
regard to the use and position of the
building. Table 8 Minimum period of fire resistance of external walls

6.1 In certain circumstances it may be Space separation


necessary for the external walls or roofs of a 6.5 In healthcare buildings up to 12 m in height,
healthcare building to provide a period of fire the maximum percentage of unprotected area
resistance to prevent fire spreading to adjacent in an external wall, in relation to the distance
buildings or parts of the same building in to adjacent compartments, buildings or
different compartments. boundaries, should be determined from the
graph in Figure 20 (Figure 21 provides guidance
6.2 For walls, this requirement is determined by on how to establish the relevant boundary, and
a combination of space separation between Figure 22 provides guidance on establishing the
buildings and the amount of unprotected area notional boundary).
within the walls.
6.6 In healthcare buildings over 12 m in height,
6.3 Generally, roofs are the topmost element the maximum percentage of unprotected area
of the building and as a consequence are not in an external wall, in relation to the distance
required to provide a period of fire resistance to adjacent compartments, buildings or
from below. However, where a low-level roof boundaries, should be determined from the
abuts an external wall of a patient-access area,

53
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

Distancebetweenface
ofbuildingandrelevant Notes:
boundary(m) i.Figure22providesguidanceonhowto
establishtherelevantboundary

ii.arelevantboundarymayalsobeanotional
12.5
boundarybetweentwobuildingsonthesamesite;
Figure23providesguidanceonestablishingthe
notionalboundary;
10
iii.wherethebuildingisfittedwithsprinklers
throughout,thedistancetotherelevant
boundarymaybehalvedsubjecttoaminimum
7.5
distanceof1000mmbeingmaintained.

2.5

100 90 80 70 60 50 40 30 20 10 0

Percentageofunprotectedarea

Figure 20 Permitted unprotected area method of determining the amount of unprotected area in an external wall

thisboundaryislessthan
Foraboundarytoberelevantitshould:
80o tosideCandis
a. coincidewith;or thereforerelevant
tosideC
b. beparallelto;or
c. beatanangleofnotmorethan

80o to

thesideofthebuilding.

C
thisboundaryis
paralleltoand
thereforerelevant
tosideD
B D

thisboundary
coincideswithandis
thereforerelevant A
tosideB
thisboundaryis
paralleltosideA

butthecentrelineofaroad,
river,canalorrailwaymay
bearelevantboundary

Figure 21 Relevant boundary area

54
6. External fire spread

Siteboundary Notionalboundary

BuildingA BuildingB

Compliancewiththeprovisions Compliancewiththeprovisions
forspaceseparationinrespect forspaceseparationinrespect
ofbuildingA ofbuildingB

Thenotionalboundaryshouldbesetintheareabetweenthetwobuildingsusingthefollowingrules:
1.Thenotionalboundaryisassumedtoexistinthespacebetweenthebuildingsandispositionedsothatoneofthe
buildingswouldcomplywiththeprovisionsforspaceseparationhavingregardtotheamountofitsunprotectedarea.
Inpractice,ifoneofthebuildingsisexisting,thepositionoftheboundarywillbesetbythespaceseparationfactors
forthatbuilding.
2.Thesitingofthenewbuilding,orthesecondbuildingifbotharenew,canthenbecheckedtoseethatitalso
complies,usingthenotionalboundaryastherelevantboundaryforthesecondbuilding.
Forfurtherinformationaboutnotionalboundaries,seeparagraph13.6inApprovedDocumentB.

Figure 22 Notional boundary

methods set out in the BRE Report 187


External fire spread: building separation and Note
boundary distances.
The national classifications do not

6.7 When calculating the amount of automatically equate with the equivalent

unprotected area: European classifications; therefore, products

cannot typically assume a European class

a. small unprotected areas as indicated in unless they have been tested accordingly.

Figure 23 may be disregarded;


b. an external surface of combustible 6.10 When a classification includes s3,d2,
material more than 1 mm thick should this means that there is no limit set for smoke
be counted as an unprotected area production and/or flaming droplets/particles.
amounting to half the actual area of the
combustible material.
Surfaces of roofs
Canopies 6.11 All healthcare buildings providing in-patient
6.8 Provided a canopy is more than 1 m from facilities or invasive procedures should have
a relevant boundary, the provision for space roof coverings complying with the Approved
separation may be disregarded. Document B.

Surfaces of external walls Junction of walls and low-level roofs


6.9 The surfaces of external walls of healthcare 6.12 Where a roof abuts an external wall, the
premises should provide a surface spread of roof should provide a minimum period of fire
flame classification of Class 0 (European Class: resistance of 60 minutes (integrity and
B-s3,d2). insulation) for a distance of 3 m from the wall
(see Figure 24).

55
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

Theunprotectedareaofthe
externalwallofastairway
formingaprotectedshaft
maybedisregardedfor
separationdistancepurposes

Compartment
floor

Compartmentwall

Unprotectedareaswhichmaybe
disregardedforseparationdistancepurposes

Representsanunprotectedareaofnot Dimensionalrestrictions
morethan1mwhichmayconsistof
twoormoresmallerareaswithinan 4mminimumdistance
areaof1000mm1000mm
1500mmminimumdistance
Representsanareaofnot
morethan0.1m Dimensionunrestricted

Figure 23 Unprotected areas which may be disregarded

3m

Shadedareaoflowlevelroof
(includinganyrooflights)to
provideaminimumperiodoffire
resistanceof60minutes
(integrityandinsulation)

Externalwall
nofireresistance

Lowlevelroof
(flatorpitched)
withnofireresistance

Figure 24 Fire-resistance at junction of external walls and low-level roof

56
6. External fire spread

6.13 Where sprinklers are installed throughout merit some departure from the usual measures
the area below the low-level roof, paragraph to restrict the fire spread within buildings,
6.12 above does not apply. specifically:
the fire load is well defined; and
Junction of compartment and sub- where the car park is well ventilated,
compartment walls and external there is a low probability of fire spread
walls from one storey to another. Ventilation is
the important factor and, as heat and
6.14 Where: smoke cannot be dissipated so readily
a. a compartment wall (or sub- from a car park that is not open-sided,
compartment wall) meets an external fewer concessions are made. The
wall; or guidance in paragraphs 6.19 to 6.24
below is concerned with three ventilation
b. a protected shaft meets an external wall, methods open-sided (high level of
natural ventilation), natural ventilation and
a 1 m wide storey-height strip of external wall mechanical ventilation.
that has a similar period of fire resistance
should be provided to prevent lateral fire spread 6.17 Not withstanding the recommendations of
(see Figure 25). Table 1, where it is proposed to include car
parking under any part of the healthcare
6.15 Where sprinklers are installed on both premises, the following additional requirements
sides of the compartment (or sub-compartment should be provided.
wall), paragraph 6.14 does not apply.
All car parks
Additional requirements for car 6.18 Access from the car park to a healthcare
parks building should be through a protected lobby.
6.16 Buildings or parts of buildings used as In addition, vertical access from the car park
parking for cars and other light vehicles are to the building should be via a stairway or
unlike other buildings in certain respects which stairways, provided with protected lobbies,

compartmentor
subcompartmentwall
Externalwall
minimum1000mm
inlength

Plan

Minimumdistancebetween
openings1000mmmeasured
onthediagonal
compartmentor
subcompartmentwall

Plan
Figure 25 Junction of compartment or sub-compartment wall and external wall

57
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

serving the car-park storeys and providing park, if the finish meets all
access to one storey only of the building. relevant aspects of the guidance
requirements of Chapters 4 and 5
Open-sided car parks of this guidance.
6.19 If the building, or separated part containing (ii) any fire door;
the car park, complies with the following
(iii) any attendants kiosk not
provisions, it may be regarded as an open-
exceeding 15 m2 in area; and
sided car park for the purposes of fire
resistance assessment in Table A2 of Approved (iv) any shop mobility facility.
Document B Fire safety. The provisions are
that: Car parks that are not open-sided
a. there should not be any basement 6.20 Where car parks do not have the standard
storeys; of ventilation set out in paragraph 6.19, they are
b. each storey should be naturally not regarded as open-sided and a different
ventilated by permanent openings standard of fire resistance is necessary (the
at each car parking level, having an relevant provisions are given in Table A2 of
aggregate vent area not less than 1/20th Approved Document B). Such car parks still
of the floor area at that level, of which at require some ventilation, which may be by
least half (1/40th) should be equally natural or mechanical means, as described in
provided between two opposing walls paragraphs 6.21 or 6.22. The provisions of
(where one element of structure paragraph 6.19 apply to all car-park buildings,
supports or carries or gives stability whatever standard of ventilation is provided.
to another, the fire resistance of the
supporting element should be no less Natural ventilation to car parks
than the minimum period of fire 6.21 Where car parks that are not open-sided
resistance for the other element, are provided with some, more limited, natural
whether that other element is load- ventilation, each storey should be ventilated by
bearing or not); permanent openings (which can be at ceiling
c. if the building is also used for any other level) at each car-parking level. These should
purpose, the part forming the car park is have an aggregate free-vent area of not less
a separated part and the fire resistance than 1/40th of the floor area at that level, of
of any element of structure that supports which at least half should be split equally
or carries or gives stability to another (1/160th on each side) and provided between
element in the other part of the building two opposing walls (see Approved Document F
should be no less than the minimum Ventilation for additional guidance on normal
period of fire resistance for the elements ventilation of car parks).
it supports;
Mechanical ventilation to car parks
d. all materials used in the construction of
the building, compartment or separated 6.22 In most basement car parks, and in
part should be non-combustible, except enclosed car parks, it may not be possible
for: to obtain the minimum standard of natural
ventilation openings set out in paragraph 6.21.
(i) any surface finish applied to a In such cases a system of mechanical
floor or roof of the car park, or ventilation should be provided as follows:
within any adjoining building,
compartment or separated part of a. the system should be independent of
the structure enclosing the car any other ventilating system (other than

58
6. External fire spread

any system providing normal ventilation e. the fans should be rated to run at 300C
to the car park) and be designed to for a minimum of 60 minutes, and the
operate at 10 air changes per hour in a ductwork and fixings should be
fire condition (see Approved Document constructed of materials having a
F Ventilation for guidance on normal melting point not less than 800C.
ventilation of car parks);
6.23 For further information on equipment for
b. the system should be designed to removing hot smoke, refer to BS EN 12101-3:
run in two parts, each part capable of 2002.
extracting 50% of the rates set out in (a)
above, and designed so that each part 6.24 An alternative method of providing smoke
may operate singly or simultaneously; ventilation from enclosed car parks is given in
the BRE Report 368: Design methodologies
c. each part of the system should have an
for smoke and heat exhaust ventilation and
independent power supply that would
BS 7376-7:2006.
operate in the event of failure of the main
supply;
d. extract points should be arranged so
that 50% of the outlets are at high level
and 50% at low level;

59
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

7. Access and facilities for the fire-and-rescue

service

Requirement d. the provision of fire mains within the


building;
Chapter 7 provides guidance to comply with e. private fire hydrants;
the following Requirement from Part B of
Schedule 1 of the Building Regulations 2010. f. venting for heat and smoke from

basement areas.

Requirement

Access and facilities for the fire service Site access


7.2 When considering site access for the fire-
B5
and-rescue service, the following should be
(1) The building shall be designed and considered:
constructed so as to provide reasonable a. the location and number of site access
facilities to assist firefighters in the points;
protection of life.
b. the design of the internal roadways
(2) Reasonable provision shall be made with respect to width, radii of bends,
within the site of the building to enable gradients, clearance between and under
fire appliances to gain access to the buildings;
buildings.
c. the weight and turning circle of the fire
appliances.
7.1 The fire-and-rescue service, once alerted,
will attend quickly and, once there, should be 7.3 A minimum of two access points to the site,
provided with adequate facilities to ensure the suitable for use by the fire-and-rescue service,
protection of life and property. Particular should be provided for fire appliances. Their
matters which require consideration are: location should be agreed with all relevant
authorities.
a. site access;
7.4 New hospital roads that may be used by fire
b. vehicular access around the buildings appliances should comply with Table 7 of this
for fire appliances; Health Technical Memorandum. One access
c. access into the building for the fire- point for the fire-and-rescue service may be an
fighting personnel; emergency access point dedicated solely for
the use of the fire service.

60
7. Access and facilities for the fire-and-rescue service

Access around the building 7.6 Where access is provided to an elevation in


accordance with Table 9, overhead
7.5 Access around a healthcare building is obstructions should be avoided in the zone
required to enable high-reach appliances to be indicated in Figure 26.
used where necessary, and to enable pumping
appliances to supply water and equipment for 7.7 Turning facilities should be provided in any
fire-fighting and rescue activities. dead-end route that is more than 20 m long.

overheadobstructionstobeavoidedinthiszone

faceofbuildingatgroundlevelor
verticalplaneofprojectingupperstorey

C D

A B

hardstandingoraccessroad obstruction

Typeofappliance

Turntableladder Hydraulicplatform
Dimension(m) Dimension(m)

A.Maximumdistanceofnearedgeof 4.9 2.0


hardstandingfrombuilding

B.Minimumwidthofhardstanding 5.0 5.5

C.Minimumdistanceoffurtheredgeof 10.0 7.5


hardstandingfrombuilding

D.Minimumwidthofunobstructedspace N/A 2.2


(forswingofapplianceplatform)

Note:
1.Hardstandingforhighreachappliancesshouldbeaslevelaspossibleandshouldnotexceedagradientof1in12.

2.Fireappliancesarenotstandardised.Somefireserviceshaveapplianceswithagreaterweightordifferentsize.Inconsultationwiththefireandrescue
authority,thebuildingcontrolbodyshouldadopttherelevantdimensionsandgroundloadingcapacity.

Figure 26 Relationship between building and access roads or hard standings for high-reach appliances

61
Firecode fire safety in the NHS: HTM 05-02: Guidance in support of functional provisions for healthcare premises

This can be by hammerhead or turning circle, 7.8 Access for fire appliances to healthcare
designed on the basis of Table 10 and Figure buildings not fitted with internal fire mains
27. should comply with the guidance in Table 9.
Total floor area (m) Height above ground of top storey (m) Provide vehicle access to: Type of appliance
Upto2000 Upto9 Within45m Pump

Over9 15%ofperimeter High-reach


2000to8000 Upto9 15%ofperimeter Pump

Over9 50%ofperimeter High-reach


8000to16,000 Upto9 50%ofperimeter Pump

Over9 50%ofperimeter High-reach


16,000to24,000 Upto9 75%ofperimeter Pump

Over9 75%ofperimeter High-reach


Over24,000 Upto9 100%ofperimeter Pump

Over9 100%ofperimeter High-reach


Note: Thetotalfloorareaistheaggregateofallfloorswithinthebuilding.

Table 9 Fire-and-rescue-service access around hospitals not fitted with fire mains

Appliance type Minimum width Minimum width Minimum Minimum Minimum Minimum
of road between of gateways (m) turning circle turning circle clearance carrying
kerbs (m) between kerbs between walls height (m) capacity
(m) (m) (tonnes)
Pump 3.7 3.1 16.8 19.2 3.7 12.5
High-reach 3.7 3.1 26.0 29.0 4.0 17.0
Notes

1.Fireappliancesarenotstandardised.Somefireserviceshaveappliancesofgreaterweightordifferentsize.Inconsultationwiththe
fire-and-rescueauthority,thebuildingcontrolbodymayadoptotherdimensionsinsuchcircumstances.

2.Becausetheweightofhigh-reachappliancesisdistributedoveranumberofaxles,itisconsideredthattheirinfrequentuseofa
carriagewayorroutedesignedto12.5tonnesshouldnotcausedamage.Itwouldthereforebereasonabletodesigntheroadbaseto
12.5tonnes,althoughstructuressuchasbridgesshouldhavethefull17-tonnecapacity.

Table 10 Typical vehicle access route specification

Fireandrescueservicevehiclesshouldnothavetoreversemorethan20mfromtheendofanaccessroad

Fireservice
Exit
vehicle

20mmax.

Turningcircle,hammerhead
orotherpointatwhich
vehiclecanturn

Figure 27 Turning circles

62
7. Access and facilities for the Fire and Rescue Service

Access and facilities for the fire b. the depth of basements;


service c. floor area; and
7.9 In low-rise buildings without deep d. the provision of hospital streets.
basements, the needs of the fire service will be
met by a combination of the normal means of
Number and location of fire-fighting shafts
escape and the measures required for vehicular
health buildings not provided with a hospital
access around the building.
street
7.10 The requirements for additional facilities 7.11 For health buildings not provided with
(fire-fighting shafts, fire mains and fire hydrants) hospital streets, fire-fighting shafts should be
for the fire-and-rescue service are determined provided in accordance with the requirements
by: of Table 11.
a. the height of the building;

Area of largest floor


No sprinklers Sprinklers
Lessthan Between Between Over Lessthan Between Between Over
900m2 900m2and 1800m2and 3300m2 900m2 900m2and 1800m2and 3300m2
1800m2 3300m2 1800m2 3300m2
Belowground
Two Notrequired 1 2 3plus1 Notrequired 1 2 3plus1
basement forevery forevery
storeys additional additional
1500m2 1500m2
Morethan 1+lift 1+lift 2+lift 3+liftplus 1+lift 1+lift 2+lift 3+liftplus
10m 1forevery 1forevery
(seenote2) additional additional
1500m2 1500m2
Aboveground
Upto12m Notrequired Notrequired Notrequired Notrequired Notrequired Notrequired Notrequired Notrequired
Between 1 1 2 3plus1 Notrequired Notrequired Notrequired Notrequired
12mand forevery
18m additional
900m2
Over18m 1+lift 2+lift 2+lift 3+liftplus 1+lift 2+lift 2+lift 3+liftplus
(seenote2) 1forevery 1forevery
additional additional
900m2 1500m2
Hoselaying 45malongaroutesuitableforlayinghose 60malongaroutesuitableforlayinghose
distance
(seenote3)
Notes:

1.Depthofbasementsandheightsofstoreyabovegroundareallmeasuredfromfireservicevehicleaccesslevel.

2.Onefire-fightingshaftshouldalsoincludeafire-fightinglift.

3.Fire-fightingshafts,irrespectiveofbuildingheight,shouldbelocatedtomeetthemaximumhoselayingdistances.Inordertomeet
thehoselayingcriterionitmaybenecessarytoprovideadditionalfiremainsinescapestairways.Thisdoesnotimplythatthese
stairsshouldbeotherwisedesignedasfire-fightingshafts.

4.Forfurtherguidanceonmeasuringtheheightofabuilding,referenceshouldbemadetoAppendixCofApprovedDocumentB(Fire
safety).Tocountthenumberofstoreysinabuilding,countonlyatthepositionwhichgivesthegreatestnumber.

Table 11 The number of fire-fighting shafts

63
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

7.12 If a fire-fighting shaft is required to serve should be provided within 15 m of a final exit,
a basement it need not also serve the upper which itself is within 18 m of a suitable fire
floors unless they also qualify because of the service access point.
height or size of building. Similarly, a shaft
serving upper storeys need not serve a 7.19 All hospital streets should have fire main
basement that is not large or deep enough to outlets located at department entrances so that
qualify in its own right; however, a fire-fighting every part of every storey is no more than 45 m
stair and any fire-fighting lift should service all from a fire outlet connection, measured along a
intermediate storeys between the highest and route that is suitable for laying hose. Fire hoses
lowest storeys that they serve. may wedge open cross-corridor fire doors
designed to prevent the passage of smoke
7.13 Fire-fighting shafts should serve all floors along the corridor; to prevent this it is
through which they pass. recommended that sections of the hospital
street that provide access to a department
should be provided with a fire main outlet within
Design and construction of fire- that section of a hospital street.
fighting shafts
7.20 Where healthcare buildings with a hospital
7.14 Fire-fighting stairways and lifts should be
street have upper storeys over 18 m above fire
approached from inside the building through a
service vehicle access level, or a basement at
fire-fighting lobby.
more than 10 m below ground or fire service
7.15 Fire-fighting shafts should be equipped vehicle access level, lifts for use by the fire-
with fire mains having outlet connections and and-rescue service are required; these
valves in every fire-fighting lobby except at should be:
access level. a. located within the hospital street
immediately adjacent to a stairway;
7.16 Where fire-fighting shafts include fire-
fighting lifts, a fire-fighting lift installation b. accessed directly off the hospital street;
includes:
c. within 18 m of an entrance suitable for
a. the lift car itself; use by the fire-and-rescue service.
b. the lift well; and
Note
c. the lift machinery space together with
the lift control system and the lift The fire-and-rescue service should be
communications system. consulted on any additional requirements
they may have for the lift to be suitable for
7.17 The shaft should be constructed generally their use.
in accordance with clauses 7 and 8 of BS
5588-5. Fire-fighting lift installations should
conform to BS EN 81-72 and to BS EN 81-1 or Fire mains
BS EN 81-2 as appropriate for the particular
type of lift. 7.21 A fire main should be located in every
fire-fighting shaft (see Table 11) or as required
by paragraphs 7.187.20.
Health buildings provided with a hospital
street 7.22 In healthcare premises with a floor over
7.18 Fire-fighting shafts are not required in 50 m above ground or access level, wet rising
health buildings provided with hospital streets. mains should be provided. Where fire mains are
In these buildings a minimum of two stairways

64
7. Access and facilities for the fire-and-rescue service

provided in healthcare premises that are lower Note


than this, either wet or dry mains are suitable.
The above guidance ensures that adequate
7.23 Wet or dry fire mains should be water supplies are provided for those
designed and installed in accordance with buildings which are not constructed within
BS 9990:2006. easy access of public hydrants.

Provision of fire hydrants


7.24 Where a building that has any Venting of basements
compartment of 280 m2 or more is being
7.27 In addition to the measures above, there
erected more than 100 m from an existing
may be a need in case of fire to remove heat
fire hydrant, additional hydrants should be
and smoke from basements. In a fire involving a
provided:
basement, the products of combustion tend to
a. buildings provided with fire mains escape via stairways, making access difficult
hydrants should be provided within for the fire-and-rescue service. Venting can
90 m of dry fire main inlets; reduce this problem, improve visibility and
lower temperatures, making access for the
b. buildings not provided with fire mains fire service less difficult.
hydrants should be provided within
90 m of an entry point of the building 7.28 Smoke outlets provide a route for heat
and not more than 90 m apart. and smoke to escape to the open air from the
basement level(s). They can also be used by
7.25 Each fire hydrant should be clearly the fire service to let cooler air into the
indicated by a plate, affixed nearby in a basement.
conspicuous position, in accordance with
BS 3251. 7.29 Smoke outlets connected directly to
the open air should be provided from every
7.26 Where no piped water supply is available basement storey, except for any basement
or there is insufficient pressure and flow in the storey that:
water main, or an alternative arrangement is
proposed, the alternative source of supply a. has a floor area of less than 200 m2;
should be provided in accordance with the
b. is not more than 3 m below the adjacent
following recommendations:
ground level.
a. a charged static water tank of at least
45,000 L capacity; or 7.30 Smoke outlets should:

b. a spring, river, canal or pond capable of a. be positioned at high level in the space
providing or storing at least 45,000 L of they serve;
water at all times of the year, to which b. be evenly distributed around the
access, space and a hard standing are perimeter of the building;
available for a pumping appliance; or
c. discharge into the open air outside the
c. any other means of providing a water building.
supply for fire-fighting operations
considered appropriate by the fire-and- 7.31 In each basement compartment/sub-
rescue authority. compartment, the combined cross-sectional
area of all smoke outlets should be not less
than 2.5% of the compartment/sub-
compartment floor area.

65
Firecode fire safety in the NHS: HTM 05-02: Guidance in support of functional provisions for healthcare premises

7.32 If the outlet terminates at a point that capable of handling gas temperatures of
is not readily accessible, it should be kept up to 300C for not less than one hour. It
unobstructed and covered with a metal grille or should come into operation automatically on
louvre. the activation of:

7.33 If the outlet terminates at a point which a. the sprinkler system; and/or
is readily accessible, it may be covered by a b. the fire detection and alarm system.
suitably indicated panel or pavement light which
can be broken out or opened.
Construction of outlet ducts and shafts
7.34 Outlets should not prejudice the use of 7.37 Outlet ducts and shafts, including any
escape routes. bulkheads over them, should be enclosed in
non-combustible fire-resisting construction.
Mechanical smoke extract
7.38 Where there are natural smoke outlet
7.35 As an alternative to natural venting, shafts from different basement compartments
providing the basement is fitted with a sprinkler of the same basement storey, or from different
system to BS EN 12845, a mechanical extract basement storeys, they should be separated
system may be provided. from each other by non-combustible fire-
resisting construction.
7.36 The air extraction system should provide
at least 10 air changes per hour and be

66
Appendix A: Glossary of terms

For the purposes of this document the following Cavity barrier: a construction, other than a
terms are defined: smoke curtain, provided to close a concealed
space against penetration of smoke or flame, or
Air transfer grille (fire and cold smoke): provided to restrict the movement of smoke or
a device that will allow the passage of air in flame within such a space.
normal use, but when activated will contain
both cold smoke and hot gases usually Circulation space: a space (including a
activated by heat and an electrical interface protected stairway) mainly used as a means of
with the detection and alarm system. access between a room and an exit from the
building or compartment.
Assisted patient evacuation: the assisted
evacuation of patients by staff, which may Class 0 surface spread of flame: the
include the use of support equipment (for classification achieved by a material or
example ski sheets, evacuation chairs, composite product which is either:
mattresses).
a. composed throughout of materials of
Atrium (plural atria): a space, or system of limited combustibility; or
conjoined spaces, within the building that
adjoins more than one storey. b. a Class 1 material (when tested in
accordance with BS 476-7:1971 or 1987)
Note which, when tested in accordance with
BS 476-6:1981 or 1989, has a fire
Shafts used solely for stairs, escalators, lifts propagation index (I) of not more than 12
or services are not classified as atria. and a sub-index (i1) of not more than 6.

Class 0 is not a classification identified in any


Auto-suppression: mechanical methods British Standard test.
of fire suppression that are activated
automatically such systems may include Compartment (fire): a building or part of
water sprinklers and CO2 flooding systems. a building, comprising one or more rooms,
spaces or storeys, constructed to prevent the
Basement storey: a storey with a floor which spread of fire to or from another part of the
at some point is more than 1200 mm below the same building, or an adjoining building. (A roof
highest level of ground adjacent to the outside space above the top storey of a compartment
wall. is included in that compartment.)

67
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

Compartment floor: a fire-resisting floor used performance criteria to those ends. (It may have
to separate one fire compartment from another one or more leaves, and the term includes a
and having a minimum period of resistance of cover or other form of protection to an opening
60 minutes. in a fire-resisting wall or floor, or in a structure
surrounding a protected shaft.)
Compartment wall: a fire-resisting wall used
to separate one fire compartment from another Fire engineering: the application of scientific
and having a minimum period of resistance of and engineering principles to the protection of
60 minutes (or 30 minutes in single-storey people, property and the environment from fire.
buildings).
Fire hazard: a set of conditions in the
Emergency lighting: lighting provided for use operation of a product or system with the
when the power supply to the normal lighting potential for initiating a fire.
fails.
Fire hazard room: a room or other area
Escape lighting: that part of the emergency which, because of its function and/or contents,
lighting which is provided to ensure that the presents a greater hazard of fire occurring and
escape routes are illuminated at all material developing than elsewhere.
times.
Fire resistance: the ability of an element
Final exit: the termination of an escape route of building construction, a component or a
from a building giving direct access to a place structure to fulfil, for a stated period of time,
of safety outside the building. the required load-bearing capacity, fire integrity
and/or thermal insulation and/or other expected
Fire-and-smoke damper: fire-and-smoke duty in a standard fire resistance test.
damper, triggered by AFD, which, when tested
in accordance with BS EN 1366-2, meets the Fire stop: a seal provided to close an
ES classification requirements defined in BS EN imperfection of fit or design tolerance between
13501-3:2005 and achieves the same fire elements or components, to restrict the
resistance in relation to integrity as the element passage of fire and smoke.
of the building construction through which the
duct passes. Healthcare building: a hospital, treatment
centre, health centre, clinic, surgery, walk-in
Note centre or other building where patients are
provided with medical care by a clinician.
Intumescent fire-and-smoke dampers may
be tested to ISO 10294-5. Height of a building (or storey): the distance
from ground level at the lowest side of the
building measured to the finished floor level of
Fire containment air transfer grille: a the top storey.
device that will allow the passage of air in
normal use, but when activated will contain the Hospital street: a special type of
passage of fire and hot smoke. compartment that connects final exits, stairway
enclosures and department entrances, and
Fire door: a door or shutter provided for serves as a fire-fighting bridgehead and a safe
the passage of persons, air or objects, which, evacuation route for occupants to parts of the
together with its frame and furniture as installed building unaffected by fire.
in a building, is intended when closed to resist
the passage of fire and/or gaseous products of Material of limited combustibility: either:
combustion and is capable of meeting specified
a non-combustible material; or

68
Appendix A: Glossary of terms

any material of density 300 kg/m3 (including any exit route between the foot of the
or more which, when tested in stairway and the final exit) that is adequately
accordance with BS 476-11, does not enclosed in fire-resisting construction.
flame, and whose rise in temperature
on the furnace thermocouple is not Refuge: a place of temporary safety
more than 20C; or within a building. This may be an adjoining
compartment or sub-compartment capable
any material with a non-combustible of holding all those threatened, without a
core of 8 mm thickness or more, significant change in level and from which there
having combustible facings (on one or is potential for further escape should that
both sides) not more than 0.5 mm become necessary.
thick; or
Relevant boundary:
any material of density less than
300 kg/m3 which, when tested in a. the actual boundary of the premises; or
accordance with BS 476-11, does not
flame for more than 10 seconds and b. the boundary of the site which the side of
whose rise in temperature is not more the building faces, and which is parallel, or
than 35C on the centre (specimen) at an angle of not more than 80, to the
thermocouple and not more than 25C side of the building; or
on the furnace thermocouple.
c. the centre line of a road, railway, river or
Non-combustible: any material which canal that adjoins the actual boundary; or
is capable of satisfying the performance
requirements specified in BS 476-4, or any d. a notional boundary established between
material which when tested in accordance with buildings, if two or more buildings share
BS 476-11 does not flame or cause any rise in the same site.
temperature on either the centre (specimen) or
Swing beds: Single-bed rooms located in
furnace thermocouple.
such a manner that they can be part of either
Patient-access areas: those areas of the the male wing or the female wing. Swing
healthcare building to which patients have beds are generally provided where sleeping
reasonable access either with or without accommodation is segregated by sex, and
supervision. then only in facilities providing in-patient mental
health services or accommodation for people
Place of safety: a place where persons are in with learning disabilities.
no danger from fire.
Smoke-retarding construction:
Progressive horizontal evacuation: construction intended to retard the passage
evacuation of patients away from a fire into a of smoke.
fire-free compartment or sub-compartment on
the same level. In the absence of an appropriate method of test
and performance criteria, such construction
Protected shaft: a shaft that enables should not contain unsealed joints and
persons, air or objects to pass from one permanently open or openable areas. Joints
compartment to another, and which is enclosed between such construction and any abutting
with fire-resisting construction. element should be tight and preferably sealed
with a filler conforming to BS EN 1366-3 or BS
Protected stairway: a stairway discharging EN 1366-4 (for example plaster), a mastic, or a
through a final exit to a place of safety flexible strip (for example neoprene), as
appropriate.

69
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

Any doors located within smoke-retarding Unprotected area: in relation to a side or


construction, when tested in accordance with external wall of building, this means:
BS 476-31.1 with the threshold taped, and
subjected to a pressure of 25 Pa, should have a window, door or other opening; and
leakage rate not exceeding 3 m3/h per metre.
any part of an external wall which has a
Sub-compartments: areas into which the period of fire resistance less than that
building can be divided to reduce travel required for the elements of structure
distance and which provide 30 minutes (integrity and load-bearing capacity
resistance to fire. only), and which provides less than
15 minutes fire resistance (insulation);
Sub-compartment wall: a fire-resisting wall and
used to separate one sub-compartment from
another and having a minimum period of fire any part of the external wall which has
resistance of 30 minutes. combustible material more than 1 mm
thick attached or applied to its external
Travel distance: the horizontal distance to face, whether for cladding or any other
be travelled by a person from any point within purpose. (Combustible material in this
the floor area to the nearest adjoining context is a material which is neither
compartment, sub-compartment, escape non-combustible nor a material of
stairway or external exit, having regard to the limited combustibility.)
layout of walls, partitions, fittings and furniture.

70
Appendix B: Periods of fire resistance

The performance of those elements of the resistance to the transfer of excessive


building which are required to achieve a heat (insulation), which applies to
specified period of fire resistance is determined fire-separating elements.
by reference to BS 476-2024:1987.
Performance is assessed against one or Table B1 summarises the specific requirements
more of the following criteria: for each element in terms of the three
performance requirements above.
resistance to collapse (load-bearing
capacity), which applies to load- A suspended ceiling should not be relied upon
bearing elements; to contribute to the fire resistance of a
compartment floor.
resistance to fire penetration (integrity),
which applies to fire-separating
elements;

71
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

Table B1 Periods of fire-resistance


Part of building Minimum provisions when tested to the relevant part of Minimum Method of
BS 4761 (minutes) provisions when exposure
tested to the
Load-bearing Integrity Insulation
relevant European
capacity 2
standard 3
Structuralframe, SeeTable5 Notapplicable Notapplicable R(seeTable5) Exposedfaces
beamorcolumn
Load-bearingwall SeeTable5 Notapplicable Notapplicable R(seeTable5) Eachsideseparately
Compartment 60 60 60 REI60 Fromtheunderside
floor4,5
Compartmentwall6 Notapplicable 607 607 EI60 Eachsideseparately
Single-storey
buildings 30 30 EI30
Sub-compartment Notapplicable 30 30 EI30 Eachsideseparately
wall6
Walltoafirehazard Notapplicable 30 30 EI30 Eachsideseparately
room
Protectedshaft 60 60 60 REI60 Eachsideseparately
Fire-fightingshafts 120 120 120 REI120 Fromsideremote
fromshaft
1.construction 60 60 60 REI60 Fromshaftside
separatingthe
shaftfromthe
building
2.construction 60 60 60 REI60 Eachsideseparately
separatingfire-
fightingstairway
fromthefire-
fightingliftshaft
andfire-fighting
liftlobby
Cavitybarrier8 Notapplicable 30 15 E30andEI15 Eachsideseparately
Fire-resistingceiling Notapplicable 30 30 EI30 Fromtheunderside
(asdescribedin
paragraph5.42)
Notes:

1.BS476-21forload-bearingelements;BS476-22fornon-load-bearingelements;BS476-23forfire-protectingsuspendedceilings;
andBS476-24forventilationducts.
BS476-8resultsareacceptableforitemstestedorassessedbefore1January1988.

2.Appliestoload-bearingelementsonly(seeB3.iiandAppendixEofApprovedDocumentB).

3.ThenationalclassificationsdonotautomaticallyequatewiththeequivalentclassificationsintheEuropeancolumn;therefore,
productscannottypicallyassumeaEuropeanclassunlesstheyhavebeentestedaccordingly.

RistheEuropeanclassificationoftheresistancetofireperformanceinrespectofload-bearingcapacity;

EistheEuropeanclassificationoftheresistancetofireperformanceinrespectofintegrity;and

IistheEuropeanclassificationoftheresistancetofireperformanceinrespectofinsulation.

4.SeeTable5forfloorsthatareover12mand30mabovegroundlevel.

5.GuidanceonincreasingthefireresistanceofexistingtimberfloorsisgiveninBREDigest208Increasingthefireresistanceof
existingtimberfloors.

6.Exceptforanylimitationsonglazedelements.

7.Maybereducedifsprinklersareinstalled.

8.ForthepurposesofmeetingtheBuildingRegulations,cavitybarrierswillbedeemedtohavesatisfiedtheprovisionsabove,provided
thattheyachieveanintegrityrequirementofatleast30minutesandaninsulationrequirementofatleast15minutes.

72
Appendix C: Doors and doorsets

Fire doors should have the appropriate techniques complying with BS EN 12101-6:
performance as indicated in Table C1. In 2005 are used, doors with the suffix S
the table the doors are identified by their should also have a leakage rate not exceeding
performance under BS 476-22 in terms of 3 m3/m/hour (head and jambs only) when
integrity for a period of minutes (for example tested at 25 Pa under BS 476-31.1. The method
FD30). A suffix (S) is added for doors of test exposure is from each side of the doors
where restricted smoke leakage at ambient separately, except in the case of lift doors,
temperatures is needed. Unless pressurisation which are tested from the landing side only.

Table C1 Location of fire doors


Location of door Minimum period of fire resistance in Minimum period of fire resistance in
terms of integrity (minutes) when tested terms of integrity (minutes) when tested
to BS 476 -221 to European standards2
Sub-compartment wall FD30S E30Sa
Fire hazard rooms FD30S E30Sa
In a compartment wall FD30SSingle-storeyhealthcarebuildings E30Sa
FD30SStoreysabovegroundin E30Sa
healthcarebuildingsfittedwithsprinklers
FD60Selsewhere E60Sa
To a protected shaft containing a lift, or
stairway or escalator:
a. accessed from a hospital street FD30S E30Sa
b. elsewhere FD30Stoeachofthetwosetsofdoorsto E30Sa
thelobby
To a protected shaft containing chutes, FD60S E60Sa
ducts and pipes
Within a cavity barrier FD30* E30S
Notes:

1.ToBS476-22(orBS476-8subjecttoparagraph5inAppendixAofApprovedDocumentB).

2.ThenationalclassificationsdonotautomaticallyequatewiththeequivalentclassificationsintheEuropeancolumn;therefore,
productscannottypicallyassumeaEuropeanclassunlesstheyhavebeentestedaccordingly.

UnlesspressurisationtechniquescomplyingwithBSEN12101-6:2005areused,allthesedoors(exceptthosemarked*)shouldalso
either:

(a)havealeakageratenotexceeding3m3 /m/hour(headandjambsonly)whentestedat25PaunderBS476-31.1;or

(b)meettheadditionalclassificationrequirementofSawhentestedtoBSEN1634-3.

73
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

Door closers automatic door releases must be


provided with a ready means of manual
Fire doors should be fitted with an automatic operation from a position at the door;
self-closing device complying with BS EN 1154
or BS EN 1634-1, with the exception of: each door fitted with an automatic
door release should be closed at a
fire doors to patients bedrooms predetermined time each night and
in mental health facilities and remain closed throughout sleeping
accommodation for people with hours. If for reasons of management
learning disabilities; this is impracticable, it should be the
specific responsibility of the fire warden
doors which are kept locked shut; and
(or other nominated member of staff) to
with the exception of doors to stairways, it may operate the release mechanism at least
be acceptable for fire doors to be held open on once a week to ensure that:
electrically operated door-release mechanisms
the mechanism is working

provided that all of the following criteria can be


effectively;

satisfied:
the doors close effectively onto their

the door-release mechanism should


frames.

conform to BS 5839-3:1988 and BS


7273-4:2007 and be fail-safe (that is, in
the event of a fault or loss of power, the Identification
release mechanism should be triggered
All fire doors, including each leaf of double
automatically);
doors, should be provided with an identification
all doors fitted with automatic door disc (except in mental health accommodation).
releases should be linked to the fire The disc should be a minimum of 45 mm in
detection and alarm system; diameter, clearly indicating the fire-resisting
standard of the door (for example FD30s,
all automatic door releases within a FD60s etc).
compartment/sub-compartment
should be triggered by any of the
following:
Doors on escape routes
Fire doors on escape routes should be side-
the actuation of any automatic fire
hung or pivoted. Revolving doors should be
detector within the compartment/
avoided, but where they are used, they must
sub-compartment;
easily convert to outward-opening doors;
or there should be outward-opening doors
the actuation of any manual
adjacent to the revolving door, capable of
fire-alarm call point within the
allowing safe egress for the numbers of
compartment/sub-compartment;
persons likely to use them. Turnstiles and
shutters are not acceptable on escape routes
any fault in the fire warning system
and should not be used.
within the compartment/sub-
compartment;
Sliding doors are acceptable on escape routes
provided they convert to outward-opening
any loss of power to the fire warning
doors when subjected to reasonable pressure
system;
from any direction. In the case of powered
sliding doors, they should in addition be
provided with a monitoring system to ensure

74
Appendix C: Doors and doorsets

that they fail-safe to the fully open position in providing single direction of escape should
the event of a power failure. open in the direction of escape.

Door swings should not obstruct the circulation Fire-exit doors to rooms containing more than
space or the designed width of the escape 60 people should open outwards from the
route. However, doors to cupboards etc that room. Door swing direction for escape routes
are normally locked may open onto circulation within mental health facilities should be
routes, but it is recommended that such doors reviewed on a risk assessment basis.
should open through 180 to avoid obstruction.
Fire doors across circulation routes should be
Fire doors across escape routes providing fitted with glazed observation panels to a height
alternative means of escape must be double- of 500 mm above the threshold of the door.
swing, and those across escape routes

75
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

Appendix D: Thermoplastic materials

A thermoplastic material means any synthetic (ii) solid (as distinct from double- or
polymeric material which has a softening point multi-skinned) polycarbonate sheet
below 200C if tested to BS EN ISO 306:2004. at least 3 mm thick;
Specimens for this test may be fabricated from
the original polymer where the thickness of (iii) multi-skinned rigid sheet made from
material of the end product is less than 2.5 mm. unplasticised pvc or polycarbonate
which has Class 1 rating when
A thermoplastic material in isolation cannot be tested to BS 476-7:1971, 1987 or
assumed to protect a substrate when used as 1997; or
a lining to a wall or ceiling. The surface rating of (iv) any other rigid thermoplastic
both products must therefore meet the required product, a specimen of which when
classification. If, however, the thermoplastic tested to BS 2782-0:2004 Method
material is fully bonded to a non-thermoplastic 508 performs so that the test flame
substrate, only the surface rating of the extinguishes before the first mark,
composite will need to comply. and the duration of flaming or
afterglow does not exceed five
Concessions are made for thermoplastic
seconds following removal of the
materials used for windows, roof lights and
burner.
lighting diffusers. They are described in
paragraphs 4.64.12. TP(a) flexible
For the purposes of paragraphs 4.14.12, either: (i) These are flexible products not
more than 1 mm thick which
thermoplastic materials should be used comply with the Type C
according to their classification 03 under requirements of BS 5867-2 when
the tests in BS 476-6 and BS 476-7 (if they tested to BS 5438, Test 2, 1989,
have such a rating); or with the flame applied to the
surface of the specimens for 5, 15,
they may be classified TP(a) rigid, TP(a) 20 and 30 seconds respectively,
flexible, or TP(b) according to the following but excluding the cleansing
methods. procedure.
TP(a) rigid TP(b)
(i) rigid solid pvc sheet; (i) rigid solid polycarbonate sheet
products less than 3 mm thick, or
multi-skinned polycarbonate sheet

76
Appendix D: Thermoplastic materials

products which do not qualify as that does not exceed 50 mm/


TP(a) by test; or minute. (If it is not possible to cut or
machine a 3 mm thick specimen
(ii) other products which, when a from the product, a 3 mm test
specimen of the material between specimen can be moulded from the
1.5 and 3 mm thick is tested in same material as that used for the
accordance with BS EN ISO manufacture of the product.)
306:2004, have a rate of burning

77
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

Appendix E: Construction and fixing of cavity


barriers

Every cavity barrier should be constructed to Cavity barriers should also be fixed so that their
provide at least 30 minutes fire resistance performance is unlikely to be made ineffective
except for a cavity barrier in a stud wall or by:
partition, which may be formed of:
a. movement of the building due to
a. steel at least 0.5 mm thick; or subsidence, shrinkage or temperature
change, and movement of the external
b. timber at least 38 mm thick; or envelope due to wind;
c. polythene-sleeved mineral wool or b. collapse in a fire of any services

mineral wool slab in either case under penetrating them;

compression when installed in the


cavity; or c. failure in a fire of their fixings; or
d. calcium silicate (cement-based or d. failure in a fire of any material or
gypsum-based boards at least 12.5 mm construction which they abut. For
thick). example, if a suspended ceiling is
continued over the top of a fire-resisting
A cavity barrier may be formed by any wall or partition, and direct connection is
construction provided for another purpose if it made between the ceiling and the cavity
meets the provisions for cavity barriers. barrier above the line of the wall or
partition, premature failure of the cavity
Cavity barriers should be tightly fitted to rigid barrier can occur when the ceiling
construction and mechanically fixed in position collapses. However, this does not arise if
wherever possible. Where this is not possible the ceiling is designed to provide fire
(for example in the case of a junction with protection of 30 minutes or more.
slates, tiles, corrugated sheeting or similar
materials), the junction should be fire-stopped.

78
Appendix F: Fire behaviour of insulating core

panels

Introduction Unlike other buildings, healthcare premises (in


particular hospitals) often utilise progressive
Insulating core panel systems are used horizontal evacuation rather than total building
for external cladding as well as for internal evacuation. Selecting the appropriate insulated
structures. However, while both types of core products for internal walls or partitions, or
panel system have unique fire behaviour for external cladding material, is vital for patient
characteristics, both can present particular and building occupant safety.
problems with regard to fire spread.

Panels typically consist of an inner core Fire behaviour of the core materials
sandwiched between, and bonded to, a
membrane such as facing sheets of galvanised
and fixing systems
steel. The panels are then formed into a The use of cladding panels for both internal
structure by jointing systems, usually designed and external walls can produce a significant
to provide an insulating and/or hygienic risk to the occupants of healthcare buildings,
performance. The panel structure can be in particular in-patients who may be dependent
free-standing, but is usually attached to the on staff for evacuation. In considering the use
building structure by lightweight fixings and of such cladding, reference should be made to
hangers. the requirements of Approved Document B.
The panel in-fill material, when involved in a fire,
The most common forms of insulation in should not compromise the safety of occupants
present use are: remaining in the building either through fire or
through smoke spread.
expanded polystyrene;
When compared with other types of
extruded polystyrene; construction technique, these panel systems
therefore provide a unique combination of
polyurethane; and problems for firefighters, including:
mineral fibre. hidden fire spread within panels with
thermoplastic cores;
However, panels with the following core
materials are also in use: production of large quantities of black toxic
smoke;
polyisocyanurate; and
rapid fire spread leading to flashover; and
modified phenolic.

79
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

they are hidden fire behind lining systems. (ii) hot areas;

Wherever possible, cladding with a non- (iii) fire breaks in combustible panels;
combustible core should be used. (iv) fire-stop panels;
(v) general fire protection;
Design recommendations
(vi) external cladding.
To identify the appropriate solution, a risk
assessment approach should be adopted. This All cores
would involve identifying the potential fire risk
within the enclosures formed by the panel (i) chill stores;
systems and then adopting one or more of the
(ii) cold stores;
following at the design stage:
(iii) clean rooms.
removing the risk;

separating the risk from the panels by an General


appropriate distance;
Generally, panels or panel systems should
providing a fire suppression system for the not be used to support machinery or other
risk; permanent loads. Any cavity created by the
arrangement of panels, their supporting
providing a fire suppression system for the structure or other building elements should be
enclosure; provided with suitable cavity barriers.

providing fire-resisting panels; Examples of possible solutions and general


guidance on insulating core panel construction
specifying appropriate materials/fixing and can be found in the International Association
jointing systems. for Cold Storage Construction (European
Division)s Design, construction, specification
In summary, the performance of the building and fire management of insulated envelopes for
structure, including the insulating envelope, the temperature controlled environments. While this
superstructure, the substructure etc, must be document is primarily intended for use in
considered in relation to their performance in relation to cold storage environments, the
the event of a fire. guidance, particularly in Chapter 8, is
considered to be appropriate for most
insulating core panel applications.
Specifying panel core materials
Where at all possible, the specification of Note
panels with core materials appropriate to the
application will help to ensure an acceptable Core materials may be used in other
level of performance for panel systems when circumstances where a risk assessment
involved in fire conditions. has been made and other appropriate fire
precautions have been put in place.
The following are examples of core materials
that may be appropriate to the application
concerned.

Mineral fibre cores


(i) cooking areas;

80
Appendix G: Fire drawings

Provision of drawings f. any smoke-control system(s) (or


ventilation system with a smoke-control
The following information should be provided function), including mode of operation,
as drawings to assist the responsible persons control systems and inlet air routes, and
to operate, maintain and use the building in fire-and-smoke damper locations and
reasonable safety and to assist the eventual HVAC routing;
owner, occupier and/or employer to meet their
statutory duties under the Regulatory Reform g. any high-risk areas (for example heating
(Fire Safety) Order. This is considered best machinery);
practice to comply with regulation 38 of the
h. specifications of any fire safety
Building Regulations.
equipment provided, in particular any
An as-built plan of the building should be routine maintenance schedules; and
provided showing: i. any assumptions in the design of the fire
a. escape routes; safety arrangements regarding the
management of the building.
b. compartmentation and separation (that
is, location of fire-separating elements
including cavity barriers in walk-in Fire drawings
spaces); To adequately assess the fire precautions at
design stage, a set of fire drawings should be
c. fire doors, self-closing fire doors and
prepared using symbols based on BS 1635.
other doors equipped with relevant
hardware (for example panic locks); In order to adequately assess compliance with
d. locations of fire and/or smoke detector the requirements of this guidance, the drawings
heads, alarm call-points, detection/ should show in sufficient detail the detection
alarm control boxes, alarm sounders, and alarm systems, the means of escape, the
alarm zones and Cause and Effect, fire structural fire precautions, the portable and
safety signage, emergency lighting, fire fixed fire-fighting equipment, smoke control/
extinguishers, dry or wet risers and ventilation arrangements, and access and
other fire-fighting equipment, and facilities for the fire-and-rescue service.
location of hydrants outside the building;
A typical set of fire drawings would comprise:
e. any sprinkler system(s), including
isolating valves and control equipment; a. a location plan;
b. a site plan;

81
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

c. a floor plan of each storey, prepared at a completion, an as-built set of drawings can be
scale of not less than 1:200; prepared.
d. a floor plan of each department, The as-built drawings should be held by the
prepared at a scale of not less than trust so that any proposed future alterations
1:100 and preferably at a scale of 1:50; can be checked against the fire drawings to
and ensure that the integrity of fire safety is
e. a set of elevations. maintained in accordance with the
recommendations in this document.
During the construction of a project, variations
to the structure and the layout frequently occur; This is an operational requirement and cannot
these variations should not subvert the integrity be enforced through the current Building
of the agreed fire precautions. The variations Regulations.
should be recorded on the fire plans so that on

82
Appendix H: Care Quality Commission types of
service

Healthcare services
Code Service type
ACS Acute services
Theseservicesarecomplexandvarygreatly.Generally,however,theyprovidemedicaland/orsurgicalinvestigations,
diagnosisandtreatmentforphysicalillnessorcondition,injuryordisease.Theycanprovideservicestoadults,childrenor
both.Theymayprovideservicestoabroadrangeofpeopleortoaparticulargroupofpeople.

Theycan:
admitpeopleonadaycasebasisorasin-patients;
admitpeopleatshortnoticeorinanemergency(whetherornottheyhaveadedicatedemergencydepartment);
seepeopleonanout-patientbasis.

Theymayalsoprovideservicessuchas:
Surgicaloperations
Specialistmedicaltreatments
Emergency
Consultations
Diagnostics
Maternityandneonatal
Pathology
Terminationofpregnancy
Complexdentalprocedures
Liaisonpsychiatry.

Peopleareusuallyadmittedtotheserviceunderthecareofamedicalorclinicalpractitioner.Theservicemayalsoemploya
broadrangeofhealthcareprofessionalstomeettheneedsofthepeopleusingtheservice.

Someservicesmaybesmallerthanothersandmaynotprovidethesamerangeofacuteservicesas,say,alocaldistrict
hospitalmayoffer(suchasanemergencydepartment).

Examples of services that fit under this category


AcuteNHShospitals
Acuteindependenthospitals
Terminationofpregnancyclinics
NHScommunityhospitals
Independentsectortreatmentcentres(ISTCs)
Communityhospitals
Cosmeticsurgeryclinics
Specialistorsinglespecialtyhospitals
Maternityhospitals
IVFclinicsprovidingsurgicaltreatmentorendoscopy
Haemodialysisunits
Minorinjuriesunits

83
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

Code Service type


HBC Hyperbaric chamber services
Theseservicesinvolvetheadministrationofoxygen(whetherornotcombinedwithoneormoreothergases)toaperson
inasealedchamberthatisgraduallypressurisedwithcompressedair.Theservicesarecarriedoutby,orunderthe
supervisionof,amedicalpractitioner.

Theserviceshelptotreatarangeofmedicalconditionsincluding:
airorgasembolism
decompressionillness
carbonmonoxidepoisoning
gasgangrene
necrotisingfasciitis
otherconditionsapprovedbytheUnderseaandHyperbaricMedicalSociety.

Examples of services that fit under this category


Type1hyperbaricchambers
Type2hyperbaricchambers
HPS Hospice services
Theseprovidearangeofservicesforconditionswherecurativetreatmentisnolongeranoption,andpeopleare
approachingtheendoftheirlife.Theyprovidecare,treatmentandsupportforpeopleandtheirfamiliesandcarers,
includingrespitecareforpeoplewholivewithfriendsorfamilyathome.

Care,treatmentandsupportcanbeprovidedinaccommodationorinthecommunity.Itcanbelong-orshort-termcare,on
anin-patientbasisorprovidedthroughdaycare,daytherapyoroutreachservices.

Theserviceswillgenerallyemployorworkwithabroadrangeofhealthandsocialcareprofessionalstomeettheneedsof
peopleusingtheservice.

Examples of services that fit under this category


Adulthospices
Childrenshospices
Dayhospices
End-of-lifecareteams
Hospiceathome
LTC Long-term conditions
Theseservicesprovidearangeofcare,treatmentandsupporttopeoplewithphysicalorneurologicalillnesses,cognitive
impairmentsorinjuriesthatareunlikelytoimprove.Theseconditionsmayhavebeeninheritedoracquired,andmaynot
necessarilybelife-limiting.Thiscare,treatmentandsupportisthesoleormainpurposeoftheservice.

Peoplemaybecaredforbytheseservicesformanyyearsatatime,andwillbeadmittedandstayatthefacilityovertime.
Peopleusingtheseservicesrequirethesupportofmedicalpractitionersandarangeofotherhealthcareprofessionals,and
theircare,treatmentandsupportmayinvolvehighlytechnicalinterventionssuchasventilation.
MLS Hospital services for people with mental health needs, and/or learning disabilities, and/or problems with substance
misuse
Theseservicesareforpeoplewithmentalhealthneedsorlearningdisabilities,whoareadmittedtohospital,involving
anovernightstay,forassessmentortreatmentwhenthereisaneedformoreintensivesupportthanwouldtypicallybe
providedinthecommunity,oraneedforaspecialistassessmentorintervention.

Thisusuallyoccursdueto:
anacuteepisodeofaseveritythatrequires24-hourcare;
aneedforahigherlevelofsecurity;
aneedforaspecialistassessment,treatmentand/orrehabilitation.

Thismightincludeprovidingcare,treatmentandsupportforpeopledetainedundertheMentalHealthAct1983.

Somepeoplewithmentalhealthneedsoralearningdisabilitymayrequirelonger-termaccommodationinhospital,while
othersmaybeadmittedforshortperiodsortreatedonadaycasebasis.

Theseservicesalsocoverin-patienttreatmentforpeoplewithproblems with substance misuse.Theyusuallyinvolve


shortperiodsofhospital-basedtreatment,including24-hourmedicalcovertoassessandstabilisetheperson,and
treatmentforwithdrawalfromdrugs(legal,illegalandsubstitutepreparations)ordetoxificationfromalcohol.

Allthehospitalservicesabovewillusuallycompriseoneormorewardsinwhichcare,treatmentandsupportareprovided.
Theremaybearangeofotherfacilitiesincludingoccupationalandartstherapies,psychologicaltherapies,psychosocial
interventions,recreationalactivitiesandservicestoaddressphysicalhealthneeds.

Examples of services that fit under this category


NHSorindependentservicesthatprovidespecialisthospitalservicesforpeoplewithmentalhealthneeds,learning
disabilitiesandproblemswithsubstancemisuse
Childandadolescentmentalhealthservices(CAMHS)tier4

84
Appendix H: Care Quality Commission types of service

Code Service type


RHS Residential substance misuse treatment/rehabilitation services
Theseservicesprovide,astheirsoleormainpurpose,treatmenttopeoplefollowinganillnessorinjurythatimpairstheir
physical,mentalorcognitivewellbeing,butforwhichcontinuedrehabilitativecareislikelytobringaboutimprovement.
Theymayconsistofarangeofservicesthatpromotefasterrecoveryfromillness,preventunnecessaryadmissiontoacute
services,supporttimelydischargeandmaximiseindependentliving.

Theservicescanbeprovidedonashort-orlong-termbasis,inhospital,residential,daycareordomiciliarysettings.They
aremainlyprovidedwithinhealthcaresettingsbutcanalsobeprovidedinasocialcaresetting.

Examples of services that fit under this category


Intermediatecareschemes
Rehabilitationunits
RSM Residential substance misuse treatment/rehabilitation services
Theseservicesareprovidedtoadultsandchildrenwhohaveproblemswithmisusingdrugsand/oralcohol.Theyprovide
care,treatmentandsupport,bothpharmacologicalandpsychosocial,andhelppeopletoreintegrateintotheircommunities,
focusingonthecopingstrategiesandlifeskillstheyneedtodothis.Theyemployabroadrangeofhealthandsocialcare
professionalstomeettheneedsofpeoplewhousetheirservices.

Someoftheseservicesmayalsoprovideassessment,stabilisationandtreatmentforwithdrawalfromdrugs(legal,illegal
andsubstitutepreparations)ordetoxificationfromalcohol.

Examples of services that fit under this category


Residentialsubstancemisuserehabilitationservices
Crisisinterventionunits
Carehomesprovidingaccommodationforthetreatmentofsubstancemisuse
DTS Doctors treatment services
Theseservicesinvolvedoctorsworkinginpremises,oraroom,designatedforminormedicaltreatmentsaswellasmedical
consultation.Oftenthedoctorwillcompletemedicalconsultations,includingphysicalexaminationandsimplephysiological
measurement(suchasbloodpressuretests).Theywilldiscussdiagnosisandtreatmentoptionsandmayprescribe
medicinesforthepersontotakeathome.

Theywillalsoundertakeminorinvasiveinvestigationsorprocedures,suchasconsciousendoscopy,inatreatmentroom
designedforthispurpose.

Theremaybeotherhealthcareprofessionals,forexamplenurses,supportingtheworkofthedoctor.

Examples of services that fit under this category


Independentdoctorsconsultingrooms
NHSGPpractices
Earlymedicalabortionclinics
Travelvaccinationservices
Polyclinics

85
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

Code Service type


DSS Diagnostic and/or screening services
Theseservicesprovideindividualhealthassessmentand/orscreeningtopeople,using:

Diagnosticimaging,suchas:
X-rays

Computedtomography(CT)
Magneticresonanceimaging(MRI)
Ultrasoundscanning
Gamma
cameras
PETscanners
Pathology
Physiologicalmeasurement
Geneticandscreeningservices
Endoscopy.
Theyprovide,asthesoleormainpurpose,diagnosisorscreening.Theydonotusuallyprovideanyotherhealthorsocial
careservices.Whilelargeacutehospitalswillhavesimilarservices,thiscategoryrelatesonlytothesededicated,focused
services.

Theseservicesundertakeinvestigationsonbehalfofthepersonusingtheserviceoronbehalfofahealthcareprofessional
thatthepersonisconsulting(whoislegallypermittedtorequestsuchinvestigations).

Theywillinvolvearangeofhealthcareprofessionalsthatmayinclude:

Medicalpractitioners
Nurses
Radiographers
Physiologicalmeasurementtechnicians.
Examples of services that fit under this category

Healthscreeningcentres
MRIorCTscanningservices(fixedandmobile)
Babyscanningservices
Endoscopycentresandclinics
Stand-aloneormobileurodynamicservices
UCS Urgent care services
Theseservicesareprovidedinparallelwithanemergencydepartmentandvarygreatlyfromoneservicetoanother.They
generallycompriseatriageservice,runbydoctorsandnurses.

Theywillnotusuallyscreenpeoplewhosesymptomsrequireimmediate,veryurgentoremergencycare.Instead,they
screenstandardcaseswheretimeisnotoftheessence,andwherepossiblerefertheseforimmediateconsultationwithan
on-siteprimarycareprovider.

Theymayprovideservicessuchas:

consultationswithadoctor
physicalexaminationsandsimplephysiologicaltestingandmeasurement
diagnosisandtreatment
prescribingmedicines
referralstootherprimarycareservices.
Examples of services that fit under this category

Primarycaretrustemergencytriage
Urgentcaretriage
Primarycareaccesscentre
Walk-inclinic

86
Appendix J: Qualitative Design Review

Because of the complex and changing facilities managers and the fire safety
nature of healthcare and the often conflicting advisor;
requirements between fire safety and nursing
care etc, it is therefore essential that early c. design team architects and engineers;
consultation takes place between all relevant d. fire service representative; and
parties; ideally this consultation should form
a Qualitative Design Review, as detailed in e. building control or approved inspector.
PD 7974-0:2002, Application of fire safety
engineering principles to the design of buildings The QDR is a structured technique that allows
Part 0: Guide to design framework and fire the team to think of the possible ways in which
safety engineering procedures. The following a fire hazard might arise and establish a
information has been taken from the range of strategies to maintain the risk at an
aforementioned PD 7974:0: 2002. acceptable level. The fire safety design can
then be evaluated quantitatively or qualitatively
The QDR is essentially a qualitative process against the objectives and criteria set by the
that draws upon the experience and knowledge team. The QDR should be conducted in a
of the fire safety engineer and a team of others systematic way to reduce the chance of a
involved in the design and operation of the relevant item being missed.
building.
Whilst the QDR is essentially a qualitative
For very large and complex projects, it is process, it can often be useful to carry out
recommended that the QDR be carried out by quick calculations to resolve a difference of
a study team involving one or more fire safety opinion between team members or to establish
engineers, other members of the design team the most significant scenarios for detailed
and a member of operational management. quantification.
It might also be appropriate to include
representatives of approval bodies or the The main stages in the QDR are:
insurers to ensure that their views can be a. review architectural design and

accounted for. occupant characteristics;

The QDR team on a major project might b. establish fire safety objectives;
include the following:
c. identify fire hazards and possible

a. fire safety engineer (chair); consequences;

b. client user group generally involving d. establish trial fire safety designs;
clinicians, nurses, managers, estates or

87
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

e. identify acceptance criteria and methods electronic security locks), and fire-and-
of analysis; smoke dampers;
f. establish fire scenarios for analysis. automatic fire detection systems,
emergency communication systems,
All findings should be clearly recorded so that CCTV, fire safety signage, emergency
the underlying philosophy and assumptions lighting, fire extinguishers;
that underpin the FSE study are explicit and
can be readily checked by a third party. This dry or wet risers and other fire-fighting
information should be contained in the Fire equipment, other interior facilities for the
Safety Strategy for the premises. fire-and-rescue service, emergency
control rooms, location of hydrants
Information provided to support Regulation 38 outside the building, and other exterior
should include the following information. The facilities for the fire-and-rescue service;
reader should note that the information detailed
below is only intended as guidance; however, sprinkler system(s) design, including
the level of detail required will vary from building isolating valves and control equipment;
to building and should be considered on a and
case-by-case basis:
smoke-control system(s) (or HVAC
the fire safety strategy, including all system with a smoke-control function)
assumptions in the design of the fire safety design, including mode of operation
systems (such as fire load), and any risk and control systems;
assessments or risk analysis;
any high-risk areas (for example heating
all assumptions in the design of the fire machinery) and particular hazards;
safety arrangements regarding the
management of the building; as-built plans of the building showing the
locations of the above;
escape routes (including stairs and lifts),
escape strategy (for example simultaneous specifications of any fire safety equipment
or phased) and muster points; provided, including operational details,
operator manuals, software, system zoning,
details of all passive and active fire safety routine inspection, and testing and
measures, including (but not exhaustively): maintenance schedules. Records of any
acceptance or commissioning tests;
compartmentation (that is, location
of fire-separating elements), cavity any other details appropriate for the specific
barriers, fire doors, self-closing fire building;
doors and other doors equipped with
relevant hardware (for example findings of the QDR consultation.

88
Appendix K: References

Acts and Regulations COUNCIL of 9 March 2011 laying down


harmonised conditions for the marketing of
Building Regulations 2010. SI 2010 No 2214. construction products and repealing Council
HMSO, 2010. Directive 89/106/EEC. Published in the Official
Journal L88, 04 April 2011.
Building Regulations 2010: Approved
Document B: Fire Safety Volume 2.
Department for Communities and Local Firecode publications
Government, 2006 edition (incorporating 2007,
Health Technical Memorandum 05-01:
2010 and 2013 ammendments).
Managing healthcare fire safety. Second
Building Regulations 2000: Approved edition. Department of Health, 2013.
Document F: Ventilation. Department for
Health Technical Memorandum 05-03:
Communities and Local Government, 2010.
Part A. General fire safety. Department of
Building Regulations 2000: Approved Health, 2013.
Document K: Protection from falling,
Health Technical Memorandum 05-03:
collision and impact. Department for
Part B. Fire detection and alarm systems.
Communities and Local Government, 2013.
The Stationery Office, 2006.
Regulatory Reform (Fire Safety) Order
Health Technical Memorandum 05-03:
2005. SI 2005 No 541. HMSO, 2005.
Part D. Commercial enterprises on
http://www.opsi.gov.uk/si/si2005/20051541.htm
healthcare premises. Second edition.
Department of Health, 2013.
European legislation
Health Technical Memorandum 05-03:
Council Directive 89/106/EEC of 21 Part E. Escape bed lifts. The Stationery
December 1988 on the approximation Office, 2006.
of laws, regulations and administrative
provisions of the Member States relating Health Technical Memorandum 05-03:
to construction products. Official Journal of Part F. The prevention and control of
the European Communities. L 40, 11.02.1989, arson in NHS healthcare premises.
p 12. Department of Health, 2013.
Construction Products Regulations:
REGULATION (EU) No 305/2011 OF THE
EUROPEAN PARLIAMENT AND OF THE

89
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

Health Technical Memorandum 05-03: relevant requirements of these


Part G. Laboratories on healthcare recommendations.
premises. The Stationery Office, 2006.
BS 476-4:1970. Fire tests on building materials
Health Technical Memorandum 05-03: and structures. Non-combustibility test for
Part H. Reducing false alarms in materials. British Standards Institution, 1970.
healthcare premises. Department of Health,
2013. BS 476-6:1989+a1:2009. Fire tests on
building materials and structures. Method of
Health Technical Memorandum 05-03: test for fire propagation for products. British
Part J. Guidance on fire engineering of Standards Institution, 2009.
healthcare premises. The Stationery Office.
2008. BS 476-7:1997. Fire tests on building materials
and structures. Method of test to determine the
Health Technical Memorandum 05-03: classification of the surface spread of flame of
Part K. Guidance on fire risk assessments products. British Standards Institution, 1997.
in complex healthcare premises.
Department of Health, 2013. BS 476-11:1982. Fire tests on building
materials and structures. Method for assessing
Health Technical Memorandum 05-03: the heat emission from building materials.
Part L. NHS Fire statistics 1994/52004/5. British Standards Institution, 1982.
The Stationery Office. 2007.
BS 476-20:1987. Fire tests on building
materials and structures. Method for
Health Building Notes determination of the fire resistance of elements
Health Building Note 00-04: Circulation of construction (general principles). British
and communication spaces. Department of Standards Institution, 1987.
Health, 2013.
BS 476-21:1987. Fire tests on building
materials and structures. Methods for
Health Technical Memoranda determination of the fire resistance of
Health Technical Memorandum 02-01: loadbearing elements of construction. British
Medical gas pipeline systems. The Standards Institution, 1987.
Stationery Office, 2006.
BS 476-22:1987. Fire tests on building
Health Technical Memorandum 03-01: materials and structures. Methods for
Specialised ventilation for healthcare determination of the fire resistance of non-
premises. The Stationery Office, 2007. loadbearing elements of construction. British
Standards Institution, 1987.
Health Technical Memorandum
06-01: Electrical services: supply and BS 476-23:1987. Fire tests on building
distribution. The Stationery Office, 2007. materials and structures. Methods for
determination of the contribution of
Health Technical Memorandum 08-02: components to the fire resistance of a structure.
Lifts. Department of Health, 2010. British Standards Institution, 1987.

BS 476-24:1987, ISO 6944:1985. Fire tests


British and European Standards on building materials and structures. Method for
determination of the fire resistance of ventilation
The latest version of any standard should be
ducts. British Standards Institution, 1987.
used, provided that it continues to address the

90
Appendix K: References

BS 476-31.1:1983. Fire tests on building BS 5588-8:1999. Fire precautions in the


materials and structures. Methods for design, construction and use of buildings. Code
measuring smoke penetration through of practice for means of escape for disabled
doorsets and shutter assemblies. Method of people. British Standards Institution, 1999.
measurement under ambient temperature
conditions. British Standards Institution, 1983. BS 5588-9:1999. Fire precautions in the
design, construction and use of buildings. Code
BS 1635:1990. Recommendations for graphic of practice for ventilation and air conditioning
symbols and abbreviations for fire protection ductwork. British Standards Institution, 1999.
drawings. British Standards Institution, 1990.
BS 5588-12:2004. Fire precautions in the
BS 3251:1976. Specification. Indicator plates design, construction and use of buildings.
for fire hydrants and emergency water supplies. Managing fire safety. British Standards
British Standards Institution, 1976. Institution, 2004.

BS 5266-1:2011. Emergency lighting. Code of BS 5839-1:2002+A2:2008. Fire detection


practice for the emergency lighting of premises. and fire alarm systems for buildings. Code
British Standards Institution, 2011. of practice for system design, installation,
commissioning and maintenance. British
BS 5306-1:2006. Code of practice for fire Standards Institution, 2008.
extinguishing installations and equipment on
premises. Hose reels and foam inlets. British BS 5839-3:1988. Fire detection and alarm
Standards Institution, 2006. systems for buildings. Specification for
automatic release mechanisms for certain
BS EN 12845:2004+A2:2009. Fixed fire protection equipment. British Standards
firefighting systems. Automatic sprinkler Institution, 1988.
systems. Design, installation and maintenance.
British Standards Institution, 2009. BS 5867-2:2008. Fabrics for curtains, drapes
and window blinds. Flammabililty requirements.
BS 5306-3:2009. Fire extinguishing Specification. British Standards Institution,
installations and equipment on premises. 2008.
Commissioning and maintenance of portable
fire extinguishers. Code of practice. British BS EN 12600:2002. Glass in building.
Standards Institution, 2009. Pendulum test. Impact test method and
classification for flat glass. British Standards
BS 5306-8:2012. Fire extinguishing Institution, 2002.
installations and equipment on premises.
Selection and positioning of portable fire BS 7863:2009. Recommendations for colour
extinguishers. Code of practice. British coding to indicate the extinguishing media
Standards Institution, 2012. contained in portable fire extinguishers. British
Standards Institution, 2009.
BS 5588-5:2004. Fire precautions in the
design, construction and use of buildings. BS 9990:2006. Code of practice for non-
Access and facilities for fire-fighting. British automatic fire-fighting systems in buildings.
Standards Institution, 2004. British Standards Institution, 2006.

BS 5588-7:1997. Fire precautions in the BS EN 3-8:2006. Portable fire extinguishers.


design, construction and use of buildings. Additional requirements to EN 3-7 for the
Code of practice for the incorporation of atria in construction, resistance to pressure and
buildings. British Standards Institution, 1997. mechanical tests for extinguishers with a

91
HTM 05-02: Firecode Guidance in support of functional provisions (Fire safety in the design of healthcare premises)

maximum allowable pressure equal to or lower door and shutter assemblies and openable
than 30 bar. British Standards Institution, 2006. windows. British Standards Institution, 2014.

BS EN 3-9:2006. Portable fire extinguishers. BS EN 1634-3:2004. Fire resistance tests for


Additional requirements to EN 3-7 for pressure door and shutter assemblies. Smoke control
resistance of CO2 extinguishers. British doors and shutters. British Standards
Standards Institution, 2006. Institution, 2004.

BS EN 3-10:2009. Portable fire extinguishers. BS EN 12101-3:2002. Smoke and heat


Provisions for evaluating the conformity of a control systems. Specification for powered
portable fire extinguisher to EN 3-7. British smoke and heat exhaust ventilators. British
Standards Institution, 2009. Standards Institution, 2002.

BS EN 3-7:2004+A1:2007. Portable fire BS EN 12101-6:2005. Smoke and heat


extinguishers. Characteristics, performance control systems. Specification for pressure
requirements and test methods. British differential systems. Kits. British Standards
Standards Institution, 2007. Institution, 2005.

BS EN 54. Fire detection and fire alarm BS EN 12600:2002. Glass in building.


systems. (12 parts). British Standards Pendulum test. Impact test method and
Institution. classification for flat glass. British Standards
Institution, 2002.
BS EN 81-1:1998+A3:2009. Safety rules for
the construction and installation of lifts. Electric BS EN 12845:2004+A2:2009. Fixed
lifts. British Standards Institution, 2009. firefighting systems. Automatic sprinkler
systems. Design, installation and maintenance.
BS EN 81-2:1998+A3:2009. Safety rules British Standards Institution, 2009.
for the construction and installation of lifts.
Hydraulic lifts. British Standards Institution, BS EN 13501-3:2005+A1:2009. Fire
2009. classification of construction products and
building elements. Classification using data
BS EN 81-72:2003. Safety rules for the from fire resistance tests on products and
construction and installation of lifts. Particular elements used in building service installations:
applications for passenger and goods fire resisting ducts and fire dampers. British
passenger lifts. Firefighters lifts. British Standards Institution, 2009.
Standards Institution, 2003.
BS 2782-0:2011. Methods of testing plastic.
BS EN 1154:1997. Building hardware. Part 0: Introduction. British Standards
Controlled door closing devices. Requirements Institution, 2011.
and test methods. British Standards Institution,
1997. BS ISO 10294-5:2005. Fire-resistance tests.
Fire dampers for air distribution systems.
BS EN 1366-2:1999. Fire resistance tests for Intumescent fire dampers. British Standards
service installations. Fire dampers. British Institution, 2005.
Standards Institution, 1999.

BS EN 1634-1:2014. Fire resistance and Other publications


smoke control tests for door and shutter Building Research Establishment. BRE Report
assemblies, openable windows and elements 187: External fire spread: building
of building hardware. Fire resistance test for

92
Appendix K: References

separation and boundary distances. Fire Protection Association. LPC rules for
BREPress, 1991. automatic sprinkler installations. Fire
Protection Association, 2009 (includes technical
Building Research Establishment. BRE Digest bulletins).
208: Increasing the fire resistance of http://www.thefpa.co.uk
existing timber floors. BREPress, 1988.
Health & Safety Executive. Fire safety in
Building Research Establishment. BD 2466: construction. HSG168. HSE Books, 2010.
Guidance on emergency use of lifts or http://www.hse.gov.uk/pubns/books/hsg168.
escalators and fire and rescue service htm
operation. Department for Communities and
Local Government, 2009. International Association for Cold Storage
Construction (IACSC) (European Division).
Building Research Establishment. BRE Report Design, construction, specification and
368: Design methodologies for smoke and fire management of insulated envelopes
heat exhaust ventilation. BREPress, 1999. for temperature controlled environments.
IACSC, 1999).
Chartered Institution of Building Services
Engineers (CIBSE). Lighting Guide 02:
Hospitals and Health Care Buildings
(Society of Light and Lighting SLL LG2). CIBSE,
2008.

93

Potrebbero piacerti anche