Sei sulla pagina 1di 64

APPLICATION AND INSTALLATION GUIDE

GENERATOR SYSTEMS
Contents

Generator Systems................................................................. 1
Generation System Basics................................................... 2
Main Generator Components ........................................... 2
Magnetic Field and Voltage ............................................. 4
Phase and Voltage ......................................................... 5
Generator Design ............................................................... 6
Rotor ............................................................................ 6
Amortisseur Windings................................................. 6
Salient Pole Rotor....................................................... 6
Non-Salient Pole Rotor ................................................ 6
Permanent Magnet Rotor ............................................ 7
Stator ........................................................................... 7
Windings ................................................................... 9
Insulation Systems ....................................................... 11
Rotor Insulation........................................................ 12
Stator Insulation Combinations .................................. 12
Insulation Life .......................................................... 14
Coil Connections .......................................................... 17
Generator Features and Attachments ............................. 19
Bearings .................................................................. 19
Space Heaters ......................................................... 20
Ingress Protection (IP)............................................... 20
Physical Data............................................................... 21
Nameplate ............................................................... 22
NEMA & IEC Design Considerations ............................... 23
Temperature Rise ..................................................... 23
Maximum Momentary Overloads................................ 24
Maximum Deviation Factor........................................ 25
Telephone Influence Factor (TIF) ................................ 25
Single Frequency Weighting Short Circuit
Requirements........................................................... 26
Overspeed ............................................................... 26
Generator Performance Characteristics ............................... 27
Rated and Per Unit ....................................................... 27
Efficiency ................................................................ 27
Fault Current/Short Circuits ........................................... 28
Reactance ............................................................... 31
Transient Reactance (Xd).......................................... 32
Sub-Transient Reactance (Xd)................................... 34
Synchronous Reactance (Xd) ..................................... 36
Negative Sequence Reactance (X2) ............................ 37
Zero Sequence Reactance (Xo) .................................. 37
Harmonics & Distortion..................................................... 39
Miscellaneous Terms ........................................................ 43
Overspeed Capability ................................................ 43
Heat Dissipation ....................................................... 43
Derating .................................................................. 43
Generator Limits .............................................................. 44
Exciter & Regulator Characteristics and Performance ........... 45
Excitation System ........................................................ 45
Self-Excitation ......................................................... 46
Permanent Magnet Excitation .................................... 46
Voltage Regulation ....................................................... 46
Performance ............................................................ 49
Generator Voltage Specifications ............................... 50
Frequency Sensing ................................................... 51
Type ....................................................................... 52
Foreword
This section of the Application and Installation Guide generally describes
Generator Systems for Caterpillar engines listed on the cover of this
section. Additional engine systems, components and dynamics are addressed
in other sections of this Application and Installation Guide.
Engine-specific information and data is available from a variety of sources.
Refer to the Introduction section of this guide for additional references.
Systems and components described in this guide may not be available or
applicable for every engine.

Information contained in this publication may be considered confidential.


Discretion is recommended when distributing. Materials and specifications
are subject to change without notice.

CAT, CATERPILLAR, their respective logos, Caterpillar Yellow and the


POWER EDGE trade dress, as well as corporate and product identity used
herein, are trademarks of Caterpillar and may not be used without
permission.

2008 Caterpillar
All rights reserved.
Generator Systems Application and Installation Guide

Generator Systems
Electricity is a useful source of energy because it is versatile; much more
versatile than mechanical energy. It can be used for a variety of tasks, such
as lighting, heating and rotating electrical machinery and it can be used in a
variety of locations, such as offshore oilrigs, natural gas fields, remote areas
and urban confines.
Caterpillar generators convert the mechanical energy of an engine, or
prime mover, to electricity. The well-proven, innovative designs of Caterpillar
generators have lead to several highly reliable lines of generators used in
electric power generation applications worldwide. All Caterpillar electric
sets use AC generators. The AC generator, also called an alternator,
converts mechanical energy to electrical energy and acts as a voltage
source for the load.
This module describes basic concepts involved in the various Caterpillar
generator designs. It addresses basic electrical generation concepts,
generator design and performance as well as voltage regulation.
It is important to note that the information in this section applies, primarily,
to synchronous generators. The term synchronous describes the relationship
between the engine rpm and the generator output frequency; they are
exactly proportional.

SECTION CONTENTS

Generator System Basics ...... 2 Generator Performance


Main Generator Components Characteristics................... 28
Magnetic Field & Voltage Rated & Per Unit
Phase & Voltage Fault Current / Short Circuits
Generator Design ................ 6 Harmonics & Distortion ....... 40
Rotor Miscellaneous Terms .......... 44
Overspeed Capability
Stator
Heat Dissipation
Insulation Systems
Derating
Coil Connections
Generator Limits ................ 45
Generator Features &
Rated & Per Unit
Attachments
Fault Current / Short Circuits
Physical Data
Exciter & Regulator
NEMA & IEC Design Characteristics................... 46
Considerations Excitation System
Voltage Regulation

2008 Caterpillar
All rights reserved. Page 1
Application and Installation Guide Generator Systems

Generation System Basics


There are three basic requirements Essentially the process of
for the generation of voltage. They generating voltage goes in the
are magnetism, motion and following order. The exciter provides
conductors. DC current to the rotor windings. DC
When a coil moves relative to current through these wires creates
a magnetic field, a voltage is magnetic flux. Magnetic flux
produced; generation systems are generates an AC voltage in the
based on this concept. When a nearby stator windings when there
conductor cuts through a magnetic is relative motion between the two.
field, a current is produced in that The regulator then senses this
conductor. These two concepts are output and controls the exciter
very closely connected. Keep in current.
mind that it makes no difference if In Caterpillar generators, the rotor
the magnetic field is stationary and (the source of the magnetic field)
the conductor moves or whether rotates inside a stationary armature
the conductor is stationary and the called a stator. One reason for using
magnetic field moves. The important a stationary armature and a rotating
aspect is that there is relative magnetic field is the difficulty of
motion. taking 3-phase current from a
The simplest generator consists rotating armature. The rotor is
of a loop of wire rotating between rotated by a prime mover. In the
two permanent magnet poles. case of Caterpillar generator sets,
the prime mover is usually an
Note: In any generator set
engine.
installation, the frame of the
generator must be positively The rotor contains magnetic poles
connected to an earth ground with windings wrapped around them
or to the hull of the vessel. to form coils. These coils are called
field coils or field windings because
Main Generator Components they create a magnetic field when
An AC synchronous generator excited with a DC current. Typically,
is significantly more complex than the generator field windings contain
the simple generator of a wire loop many turns.
rotating between two permanent A magnetic field radiates out from
magnets. An AC synchronous the rotor as lines of magnetic flux.
generator consists of four main As the rotor rotates, so does the
components and/or systems: magnetic field. When this moving
Field (rotor) magnetic field comes across a stator
Armature (stator) winding, an AC voltage is produced.
The magnetic field is strongest at
Exciter the center of the north and south
Automatic Voltage Regulator poles where the lines of magnetic

2008 Caterpillar
Page 2 All rights reserved.
Generator Systems Application and Installation Guide

flux are concentrated. Therefore, synchronous or no-load speed in


the closer a pole is to a stator revolutions per minute (rpm).
winding, the higher the voltage 120 x f
produced in that stator winding. rpm =
Number of poles
It is important to note voltage is
a function of flux change per time,
not only the proximity to the field. If 50 Hz is desired from a four-pole
generator, the generator must be
The symmetrical design of the driven at 1500 rpm. A six-pole
generator ensures that the rotor generator is driven at 1000 rpm.
poles extend over equal arcs and
that the magnetic flux density The generated frequency of 50 Hz
is entirely a function of the driven
distribution is similar across all
stator windings. speed.

Magnetic poles refer to the 120 x f


1000 rpm =
magnetic north and south and are 6
the points where the magnetic field f = 50
is strongest on the rotor. The relationship between
the number of poles and the
synchronous speed is shown in
Table 1. These calculations are
figured by taking the fundamental
frequency of 50 or 60 Hz and
dividing it by the number of pole
pairs. It is then multiplied by 2
to get the synchronous speed
into rad/s, that is then converted
into rpm.
Synchronous Speeds
60 Hz 50 Hz
Poles rpm Poles rpm
Figure 1 2 3600 2 3000
4 1800 4 1500
A pole relates to the number of 6 1200 6 1000
magnetic poles developed in the 8 900 8 750
rotating field. Magnetic poles in 12 600 12 500
a four-pole generator are arranged Table 1
north-south-north-south around the
circumference of the rotor, as Regardless of the number of
shown in Figure 1. The number of pole pairs, the rotor moves 360
poles (north-south-north-south) and mechanical degrees in one
the desired frequency (cycles per revolution. In electrical degrees,
second or hertz) determine the however, each pole pair rotates
360 mechanical degrees. In other

2008 Caterpillar
All rights reserved. Page 3
Application and Installation Guide Generator Systems

words, electrical degrees are the as high as 250V is often used in


mechanical degrees times the larger generators, while smaller and
number of pole pairs: medium sized generators seldom use
Mechanical Degrees x Number of Pole Pairs voltages higher than 125V.
In a four-pole generator (two pole Because it is so difficult to extract
pairs), each pole pair moves 360 high voltage from a rotating
mechanical degrees, so the total armature, the magnetic field of the
electrical degrees moved is: main generator is rotated rather than
the armature. A rotating armature
360 x 2 = 720
generator will be used as an exciter
The following illustrates electrical in Caterpillar generators.
degrees in terms of number of poles:
Generator output voltage depends
2-poles = 360 electrical on the following:
4-pole = 720 electrical Speed of relative motion
6-pole = 1080 electrical between magnetic field and
8-pole = 1440 electrical stator conductors
The main armature, or the stator, Strength of magnetic field
remains stationary. The stator Number of series turns in the
consists of the stator core, and stator windings
its own windings called stator The strength of the magnetic field
windings, or armature windings. The is proportional to the current flowing
stator may also include exciter field through the field coils. As the
coils when used with a self-excited current rises, the magnetic field
field arrangement. The stator grows stronger.
windings are placed in slots along
The speed of relative motion
the inside of the stator. The stator
between the magnetic field and the
usually contains a large number of
stator windings depends on the
slots. The rotor magnetic field cuts
rotational speed of the rotor (engine
across the stator windings as it
rpm). As the rpm rises, so does the
rotates inside the stator. As a result,
speed (V) of relative motion. The
voltage is produced in these
higher the speed of relative motion,
windings.
the greater the generators output
The stator voltage is the generator capabilities.
output that is supplied to the load.
Voltage can be adjusted by
Magnetic Field and Voltage arranging the stator windings in
The magnetic field is induced in coils and varying the number of
the main generator by a DC current turns, or times the windings are
from the exciter through low voltage wound around the stator. More
field or rotor windings. These voltage can be induced by increasing
windings are low voltage compared the number of turns and less voltage
to the stator windings. DC voltage is induced by using fewer turns.
Consequently, stator windings can

2008 Caterpillar
Page 4 All rights reserved.
Generator Systems Application and Installation Guide

be arranged with the optimum Three-Phase Generator


number of coil turns to produce
the required output voltage.

Phase and Voltage


Phase, voltage and the stator
core are all inter-dependent. The
calculated design of the stator core
and winding distribution enables a
generator to provide the appropriate Figure 3
output voltage.
In three-phase generation, three
The phase voltage of a generator
phases of voltage are produced
is directly linked to the voltage
120 apart. However, to make the
output of that generator. The
connection a symmetrical 3-phase
type of voltage induced is partially
connection, a phase coil must have
dependent on the number of phases
an equal and opposite winding 180
in a generator.
away. Figure 4 illustrates this
A single-phase generator will relationship; Phase coil B has an
generate a voltage sine wave when equal and opposite winding at phase
the rotor completes one cycle (one coil B. The result is that the three
360 revolution). Refer to Figure 2. phases and their opposing windings
are actually 60 apart.
Single Phase Generator

Figure 2

A three-phase generator consists


of three coils equally spaced around
the stator and connected in a wye
Figure 4
(Y) or Delta () configuration.
Therefore, three voltages can be
produced consecutively with a 120
phase difference. Refer to Figure 3.

2008 Caterpillar
All rights reserved. Page 5
Application and Installation Guide Generator Systems

Generator Design
Generators are constructed in Amortisseur Windings
various ways to satisfy different Amortisseur windings, also known
load and customer requirements. as damper windings, are special
At Prime power ratings, SR4B conducting bars laid into a squirrel
generators are limited to 105C cage configuration. They are set in
(221F) temperature rise over an the notches in the rotor and then
assumed 40C (104F) ambient and are shorted on the end by either a
may be used on a continuous duty shorting ring or shorting laminations.
(24 hours per day) basis. They are used to increase machine
stability. This is due to the windings
SR5 generators are limited to a
and rotors relationship to the
125C (257F) temperature rise
synchronous speed. If the rotor is
over the same conditions.
at synchronous speed, there is no
At Standby power ratings, SR4B induced voltage through the
generators are limited to 130C amortisseur bars, hence there is no
(266F) temperature rise over an interaction. Conversely, if there is
assumed 40C (104F) ambient a differential between the rotor and
and are used many times for back-up synchronous speed, a voltage will
power needs, and are rated on a be induced in the windings. This
temporary use basis. voltage produces a current flow and
SR5 generators are limited to a in turn creates a magnetic field.
150C (302F) temperature rise The interaction of the two magnetic
over the same conditions. fields in turn cause a torque that will
The rating is expressed in kilowatts correct this speed difference
(kW) at 0.8 power factor. A resulting in speed and torque
common ratio, kW divided by stability.
0.8 permits calculation of kilovolt- Salient Pole Rotor
amperes (kVA) on all generators. A rotor configured with the
individual rotor poles protruding from
Rotor the center of the rotor is known as a
The rotor is defined as any rotating salient pole rotor.
winding or element of a generator.
It can be described as an assembly The rotating salient pole field
of thin magnetic steel laminations, arrangement is affected by
tightly compressed and then riveted, reluctance torque and is used for
bolted or welded together to form a engine-driven generators on most
magnetic path. It is around this core machines in the 20 kVA (16 kW)
that the field windings, or coils of and larger sizes.
conducting material, are wound Non-Salient Pole Rotor
around or inserted. A non-salient pole rotor, or
cylindrical rotor, is typically made
from solid cylindrical material and

2008 Caterpillar
Page 6 All rights reserved.
Generator Systems Application and Installation Guide

usually has grooves cut into the pole thick steel stampings/ laminations
faces to place the windings. stacked together. Stacking machines
A rotating non-salient pole field, use automatic welding to assure
or cylindrical rotor, isnt affected correct stator skew, stack pressure,
by reluctance torque and it is mainly and slot alignment. Stator stampings
used for large, steam turbine-driven are usually stamped from special
generators. The non-salient silicone steel.
configuration usually has grooves The stator core is subjected to
cut into the pole faces to place the an alternating magnetic flux which
windings. induces currents, called eddy
currents, in the core that create
Permanent Magnet Rotor
losses. Creating the core from
A permanent magnet (PM) field
stacked stampings rather than from
eliminates the need for an exciter
one solid piece of steel inhibits eddy
and therefore is very cost effective
currents, reducing losses. The
in smaller size generators. The
silicone added to the steel stampings
disadvantage to this is that its flux
and an oxide coating help to inhibit
density (field strength) is constant
eddy currents.
and voltage regulation is poor.
However, if it is to be used in an In addition to eddy current losses
application with a steady load and in the stator core, there are
minor fluctuations, a PM field can hysteresis losses. One definition of
be very effective. hysteresis is the failure of a property
that has been altered by an external
A rotating armature, stationary
agent to return to its original value
field generator is used mainly in
when the cause of the alteration is
small, low-voltage machines. A
removed. Figure 5 illustrates
common use for this generator is as
hysteresis.
an exciter for brushless generators.
For additional discussion of PM The B-H curve in Figure 5 shows
used in larger generator excitation that unmagnetized iron starts at zero
systems, refer to Exciter & Regulator and proceeds to saturation as the
Characteristics and Performance- magnetomotive force (MMF)
Permanent Magnet. increases. In simpler terms, the
unmagnetized iron becomes
Stator magnetized. As MMF is reduced to
The stator is defined as any zero again (or as the iron loses its
stationary winding or element of a magnetism), a residual B results.
generator. The stator core is where The residual B means that the iron
the usable electricity is generated. does not entirely lose its magnetism
The windings carrying the usable when MMF returns to zero. The
electricity are placed in the stator same curve loops around as MMF
core slots. becomes negative then positive
The stator core is made up of again from an AC exciting current.
hundreds of 0.0185 in. to 0.025 in. Since the hysteresis loop results in

2008 Caterpillar
All rights reserved. Page 7
Application and Installation Guide Generator Systems

internal domain realignment, energy of attributes, one of which is the


is expended. Losses are proportional physical size of the stator core. The
to the area of the loop created due inside diameter (called the air gap
to the work expended in following diameter) and the inside core length
through the cycle of magnetization are among a number of attributes
and demagnetization. related to the kVA output
The inside stator diameter and core
length are used to calculate the
D2L value (which determines the
kVA output of the generator).
The air gap is the space between
the pole face and stator lamination
teeth. The air gap area is the ID of
the stator minus the OD over the
pole face divided by 2 multiply by
the length of the stator. The flux
density of the air gap (Bg) is then
the total flux (ft) divided by the
Figure 5 inside core area.
The magnetic flux in the air gap is
Figure 6 illustrates the core loss created by the field windings on the
curve for M-43, 24 gauge, hot rolled rotor. The rotor laminations are not
steel shows how core loss increases necessarily made of the same
with increasing induction at 50 Hz material as stator laminations
and 60 Hz. The core losses because the flux in rotor laminations
measured in this curve include both is unidirectional, always flowing out
eddy currents and hysteresis. of the north and into the south
magnetic poles.
Core Loss Curve Different loads require different
types of voltage. Generators are
designed with various combinations
of slot, conductor, and winding
types to provide the specific kind of
voltage required by the generators
loads.
Stator stampings contain one of
two kinds of winding slots. The
semi-closed slot accepts only a
random winding, meaning one wire
Figure 6 at a time is fed into the slot. The
open slot accepts a random winding
The output capability of a or a form-wound winding. The entire
generator is measured by a number coil is placed into the slot, rather

2008 Caterpillar
Page 8 All rights reserved.
Generator Systems Application and Installation Guide

than being inserted wire by wire. called a phase sheet, which


Double-layer winding consists of increases the creepage distance,
two coil sides per slot, resulting in separates each coil group.
the same number of coils as slots.
Shown in Figure 7 are both a Lap Routed Winding
random wound, semi-closed slot
cross-section and a random wound,
open slot cross-section.

Stator Windings

Figure 8

Lap winding is a double-layer


winding. There are two coil sides per
Figure 7 slot, resulting in the same number of
coils as slots. Surge rope and tape
Windings are added to end turns to hold the
Stator winding processes can be end turns stationary during surges,
divided into two categories; the motor starting, and transients. The
routing of the coils and the type of surge rope, which is made with a
winding. The routing of the coils strong fiberglass and epoxy, also
refers to the pattern in which the reduces deformation of the end
windings are applied to the coil. turns when they are stressed. The
The type of winding refers to the tape additionally serves to protect
shape of the winding material. the coil end turns from abrasion
between coils. Figure 8 shows a
Routing Styles schematic of a lap wound coil.
There are three coil routing styles.
They are lap, wave, and concentric. Concentric windings are wound
The most common styles are lap into loops within larger loops. This
and concentric. All SR4B and SR5 results in the simplest mechanical
generators are lap wound. assembly and the least amount of
copper. This configuration however,
Lap routed windings are loops experiences slightly higher levels of
routed across one another and harmonics. This winding style is the
wound into a double diamond shape. most economical and allows an
An entire coil group can be wound entire coil group to be wound at
at one time, so connections are once and machine inserted. Like lap
made only at the coil group, not winding, connections are made at
at each coil. An insulation material the coil groups, not at each coil.

2008 Caterpillar
All rights reserved. Page 9
Application and Installation Guide Generator Systems

Concentric winding is a single-layer rectangular wires which can be


winding. There is one coil side per placed very close to one another,
slot, resulting in twice as many slots resulting in the maximum amount of
as coils. Phase sheets are placed copper, least amount of spaces, and,
between the phases to provide extra therefore, superior efficiency and
insulation between coil groups. durability. While concentric windings
Figure 9 shows a schematic of a and lap windings may be either
concentric wound coil. random or form wound, form
windings are usually impractical for
Concentric Winding lower power rated generators
because of inadequate spacing.
The two winding types are shown
in Figure 10 and Figure 11.

Random Winding

Figure 9

Coil Pitch
When a coil is wound 180
electrical degrees, the voltages on Figure 10
the conductors on either side are
equal in magnitude and opposite in Random wound coils are wound
direction and are said to be a full with round copper magnet wire that
pitch coil. Sometimes a coil is is insulated with a moisture resistant
wound less than 180 and is said to heavy polyester film and amide-imide
be a fractional pitch coil. The reason overcoat. Containing multiple
for this is to reduce certain harmonic conductors per turn, the coils
factors that will be discussed later consist of one or many turns each
in this guide. SR5 generators are and are wound in a double diamond
2/3-pitch. shape. Random wound coils are cost
Winding Types effective and are suited for low
Winding types can be random or power ratings, standby applications,
formed. Random windings utilize clean environments, and low
coils of round wire. Material costs operating hours.
are lower, but this method leaves
spaces between the individual wires.
Formed windings utilize square or

2008 Caterpillar
Page 10 All rights reserved.
Generator Systems Application and Installation Guide

Formed Winding Because form wound coils are pre-


formed, air space exists between
each coil in the coil head, allowing
better cooling. Each coil head is also
braced with double surge ropes and
other blocking between coils to
prevent coil movement during surges
and other transients such as sudden
load changes and switching.
Manufacturing costs for
concentric/random windings are
Figure 11
lowest, but the more expensive
Form wound coils are pre-formed lapped/formed windings provide
with rectangular copper magnet wire increased durability and electricity
and taped with multiple layers of quality. Caterpillar generators have
fused double daglass over heavy been designed in accordance with
film polyester with an amide-imide the expected application; Lower
overcoat. Daglass is a polyester power rated generators use
and glass insulation material. The lapped/random. Higher power rated
coils are taped to add mechanical generators use lapped/formed
strength. The number of tape layers windings.
varies depending on the voltage Insulation Systems
applied to the coil and the dielectric
The insulation system is a complex
strength (ground insulation) needed.
combination of insulation materials
Additional protection can be added
that are carefully selected by the
if required because of environmental
generator designer to prevent
factors. Mica tape is used for ground
undesirable electrical flow.
insulation because of its insulating
properties, such as: high dielectric Generators consist of three types
strength, high breakdown voltage, of material; copper wire, iron, and
high insulation resistance, and insulation. To function properly,
excellent protection against the individual copper conductors in
moisture, chemicals, and other stator windings must be completely
environmental factors. insulated from neighboring
conductors in the same coil and
Open stator slots allow the coils
from the surrounding iron (referred
to be placed in the slots without
to as ground).
separation of the wires within the
coils. Coils are connected either by Insulation must prevent electrical
groups or by individual coils with breakdown between components,
both crimp connections and but it must also be used as sparingly
soldering. Connections are taped as possible. Less insulation means
and sleeved to assure a good seal more space available for copper and
against environmental factors. better heat dissipation. More copper

2008 Caterpillar
All rights reserved. Page 11
Application and Installation Guide Generator Systems

and better heat dissipation improves operation where generators carrying


maximum output from the generator. uneven loads can result in voltage
Due to the added stress put on the and operational instability which
material in higher voltage machines, translates to added stress on the
higher quality insulation or more insulation. Damper windings will
insulation must be used. minimize these oscillations. Damper
windings also dampen oscillations
Rotor Insulation
occurring from short-circuit and
Each Caterpillar rotor is precision
engine pulses.
layer wet wound. This means the
conductors are hand-placed precisely Tests are performed on the rotor
in rows, layering one row on top of to assure that there is no material
the other. Each layer of conductors movement in the rotor. A prototype
is brushed with high bond strength spin test runs at 125% rated speed
epoxy before the next layer is added for two hours at 170C (338F).
to assure a good seal between Stator Insulation Combinations
conductors. Stator insulation is categorized into
Since the field coils employ a low classes based on their ability to
voltage, field coil insulation problems withstand heat for a specified period
are mostly mechanical. As the rotor of time. Class H is temperature rated
rotates, centrifugal force is applied at 180C (356F) and Class F at
to the field coils causing the coils to 155C (311F).
bow out. When centrifugal force is Windings are coated with various
broken down into its components, layers of insulation. Insulation
there is a vertical force (FV) and a materials can be used individually
side force (FS). The side force or in combinations and may be
causes the coils to bow out. comprised of acrylics, asphalts,
To prevent field coils from bowing epoxies, melamines, phenolics,
out due to centrifugal force, wedges polyamides, polyimides, polyesters,
are placed in-between the poles with polyethylenes and silicones. Possible
their two sides holding the coils insulation systems include:
tightly against the poles. Extra Magnet wire with a polyester
wedges and bracing are sometimes and amide-imide overcoat.
added for extra assurance that rotor
Nomex-mylar-nomex
materials do not move.
ground insulation. (Mylar
The purpose of the Amortisseur or is a DuPont polyester film.)
damper windings (discussed earlier) Depending on the manufacturing strategy,
is to prevent rotational oscillations insulation coating is applied to stator windings
in the rotor. These windings provide for random wound generators by either a
a motoring effect and produce a double dip and bake process or a vacuum
pressure impregnation (VPI) process, while
torque in the rotor working against form wound generators utilize the VPI
such oscillations, thereby providing process, exclusively.
superior voltage stability. This is
particularly important during parallel

2008 Caterpillar
Page 12 All rights reserved.
Generator Systems Application and Installation Guide

Random Wound Stators that are treated However, the list is by no means
using the dip and bake process are initially
complete. In the US, system
submerged into a polyester
resin. Polyester resin is used for its superior voltages are based on 120V with
heat dissipation, flexibility, voltage breakdown multiples of that voltage.
strength, and moisture resistance. The resin
Nominal System Identical System
penetrates the spaces between the
conductors and leaves a uniform resin build. Voltages* Voltage
The resin is then cured by a bake cycle. By 120 110, 115, 125
holding the conductors together, the resin
120/240 110/220, 115/230
prevents vibration and premature failure. Once
the polyester resin is cured, the stator is 208Y/120 199Y/115
dipped and baked using an epoxy resin. The 240 220, 230
epoxy adds extra protection against moisture,
chemicals, and other environmental factors. If 400, 480 440, 460
requested and/or necessary, additional dips 600 550, 575
and bakes maximize resin buildup and
environmental protection. As many as 2 to 4 2400 2200, 2300, 2500
dips and bakes are possible. To further protect 4160Y/2400 3810, 4000
against abrasion and moisture, asphalt epoxy
is also applied to the lead end. Also, end Table 2
windings are sprayed with red sealer to help
retard voltage tracking and to seal all parts
from rust and corrosion. Tracking is caused by
Caterpillar system voltages
contaminants like salt water, which can get are divided into three classes to
trapped on the coil end turns. Surface currents differentiate between types of
then develop and carbonize or track the resin generators. The classes are Low
surface.
Random Wound and Form Wound stators Voltage, Medium Voltage and High
that are treated using the Vacuum Pressure Voltage.
Impregnated (VPI) process are placed in a
sealed tank in which all air is drawn out and
Low Voltage A class of
then filled with polyester or epoxy resin. This nominal system voltages of
process maximizes the ability for the resin to 1 KV or less
penetrate and adhere to the windings. To
further protect against abrasion and moisture, Medium Voltage A class
asphalt epoxy is also applied to the lead end. of nominal system voltages
Adding coastal insulation protection, an greater than 1 KV, but less
optional epoxy based coating, can further
strengthen the insulation coating. This optional
than 100 KV
coating is required to prevent premature High Voltage A class of
standard insulation deterioration in harsh nominal system voltages equal
environments that contain high levels of
abrasive (sand, salt or dust) or corrosive (salt to or greater than 100 KV and
or other chemicals) air borne contaminants. equal to or less than 230 KV
Note: The integrity of all types of generator Caterpillar may supply generators
winding insulation systems is distinctly
improved when moisture is restrained from
up to 15 KV in some applications.
collecting on winding insulation. During Applications above 15 KV are used
generator nonuse periods, it is highly for transmission voltages and are
recommended to use space heaters to prevent used in vary large power plant
moisture collection.
generators or they are specifically
Table 2 shows examples of system developed for step up transformers.
voltages that may be encountered.

2008 Caterpillar
All rights reserved. Page 13
Application and Installation Guide Generator Systems

Generator armature windings 30 to 50C (86 to 122F) if the


must withstand a test voltage overheating does not last too long.
of 1000 volts plus two times the
rated voltage of the machine. Typical Damage Curve
The field windings must withstand
1500 volts rms.
A Megger test is used to measure
insulation resistance with respect
to ground. A measurement of
100 meg-ohms is common at the
time of manufacture. Megger
readings of one meg-ohm per
1000 volts of generator rating
minimum acceptable insulation level.
Larger generators are sometimes Figure 12
required to pass tests associated
with insulation coordination for Insulation Life
lightening and voltage surges. The more current the stator
This requirement falls under Basic windings can accommodate, the
Impulse Insulation Levels (BIL) and greater the generator output. Q
represents ampere conductors per
the generator must be tested under
surge conditions. inch of armature circumference.
There are, however, limitations
Figure 12 shows a typical damage to ampere conductors per inch of
curve. Any generator operation with armature circumference, temperature
currents above this curve should be rise being the most important.
avoided. Although a generator may
not suddenly fail when currents Temperature rise is the limitation of
exceed the damage curve (like a the insulation to withstand the heat
fuse), currents above the damage produced when current runs through
the stator windings. The thermal
curve will cause insulation to
become brittle, carbonized, and expansion of the wires from this heat
cracked. Another threat is the plays a part in this limitation.
differential expansion of materials. Since the late 1950s, plastics
Copper expands significantly and have been used as the primary
iron expands, relatively, little with insulation for generators. As
high current. These materials, late as 1960, British standards
expanding at different rates, cause specifications referred to insulation
stress and stress cracking in the classes by material. Since the
insulation. Conductors may also 1960s, however, insulation
lose strength, fracture, and/or melt. classes have been referred to by
However, insulation can safely the maximum temperature limit of
exceed its rated temperature by the materials in each class. Refer
to Table 3.

2008 Caterpillar
Page 14 All rights reserved.
Generator Systems Application and Installation Guide

The bar graphs in Figure 13 show


Maximum insulation class temperature limits
Class Operating Material
Temperature
measured by resistance or
Cotton, Silk, Paper, thermometer and by embedded
A 105C (221F)
Suitably Impregnated detector. Notice the inclusion of
Glass, Asbestos,
B 130C (266F) Mica. Suitably the hot spot as a separate factor
Bonded in the resistance graphs.
Glass, Asbestos,
Mica. Suitably
F 155C (311F) Bonded with materials
that permit 155C
operation.
Silicone Elastomer,
Mica, Glass,
H 180C (356F)
Asbestos. Bonded
with silicone resins

Table 3

Figure 13

Ambient temperature and method location in stator windings with the


of measurement further subdivide highest temperature. A hot-spot is
the maximum temperature limits located approximately in the center
shown in the table. Ambient of each stator slot and
temperature is usually considered approximately in the center of each
40C (104F), although marine and field winding.
some others prefer between 45C An embedded detector measures
(113F) and 50C (122F). the temperature limit of the stator
When measuring stator windings windings. Because the embedded
by resistance, a hot-spot allowance detector is located at the hot spot,
is added. The hot-spot is the the measured temperature already

2008 Caterpillar
All rights reserved. Page 15
Application and Installation Guide Generator Systems

includes the hot spot. Note that an representative. Note that this type of
embedded detector can measure the graph is used to compare insulation
temperature limit of the stator systems. These curve bands do not
windings and is usually a standard predict actual design life of a
factory test. Because the rotor is machine. For example, one CANNOT
rotated, however, an embedded assume that the design life of a
detector cannot test the field machine is any given number of
windings; they must be tested by hours because the insulation life is
resistance. a given number of hours. The curve
There are two basic types of bands only COMPARE insulation
embedded detectors; Resistive systems.
Temperature Devices (RTD) and Note: For every 10C (18F)
thermocouples. increase in temperature, insulation
An RTD is an electronic sensing life is halved.
device that varies resistance with a
change in temperature. This change Sample Thermal Endurance
in resistance is then measured and Curve Band
converted into a temperature
reading. The RTD delivers more
of an average reading than the
thermocouple.
The thermocouple is another type
of temperature sensing device. It is
typically used in random wound
machines due to its sturdier design.
The thermocouple delivers a reading
at a precise point, usually the hot- Figure 14
spot. Both devices can be placed in
windings and the machines There are several indications that
bearings. They can show increases thermal deterioration is occurring in
in winding insulation temperature winding insulation.
and prevent excess bearing heat Loss in weight and thickness
effects. Increase in stiffness or
Thermal endurance is the ability brittleness
of the insulation to withstand heat. Increase in density
Figure 14 shows typical thermal
Non-uniform shrinkage with
endurance curve bands for the
cracks penetrating from the
different insulation classes. The
surface
curve bands predict insulation life in
hours versus the temperature of the Reduced tensile strength
windings. There are many test Less resistance to moisture
points outside these bands; the penetration
points shown are merely

2008 Caterpillar
Page 16 All rights reserved.
Generator Systems Application and Installation Guide

Reduced dielectric strength Figure 15 shows different types


Serious decrease in resistance of connections for one phase of a
4-pole, three-phase winding. The
Insulation tends to breakdown at phase consists of four pole-phase
higher voltages due to the added groups; one for each pole in the
electromagnetic field force. Silicon phase. Each coil could have any
Controlled Rectifier (SCR) loads that number of turns, limited only by
of high harmonic content can also
the space within the slot. The
seriously affect insulation.
pole-phase groups can be connected
Heat is not the only cause of in series, 4-parallel, or 2-series, 2-
winding insulation deterioration. parallel.
Damage to insulation can occur
during winding due to improper
handling, careless winding,
insufficient resin coverage, or
insufficient cure time. Therefore,
tests are conducted after every
winding process is completed.
Additional causes of insulation
failure include the following. Figure 15
Conducting contaminants;
like dirt and chemicals Different types of connections
induce different voltages. Therefore,
Mechanical damage from
the type of connections used in a
shock, vibration, foreign
generator depends on the voltage
objects and stress
required by the load. Series
Surge voltages generated in connections produce high voltage
the load or in the line and parallel connections produce
Operation at abnormal low voltage. The series and series-
voltage, current or power parallel connections are often
factor combined into the same generator
Loosened coils and wedges so the generator can be connected
to produce high or low voltage. This
Moisture on creepage surfaces dual voltage capability is usually
Blocked ventilation passages identified; for example, a generator
Abrasives in the cooling air labeled 120/240-277/480V can
be connected for either 120/240V
Coil Connections or 277/480V. 120V and 277V
The design of the coil connections are line-to-neutral voltages (single-
in a generator and the way a load is phase), while 240V and 480V are
connected to a generator determine line-to-line voltages (single-phase
the level and type of output voltage or three-phase).
from that generator.

2008 Caterpillar
All rights reserved. Page 17
Application and Installation Guide Generator Systems

Caterpillar generators have 4, 6,


10, or 12 line leads or outputs.
These can be connected into a low
voltage wye configuration (coils
parallel) or into a high voltage
wye configuration (coils in series).
Generators with 12 leads can be
connected in delta configuration.
Larger generators use more than one
wire per line lead. This feature eases
the problem of forming very heavy
conductors inside a limited space
for terminal connections.
All leads are identified. If more
than one wire is used per line lead, Figure 16
a line lead number identifies each
In a wye connection, the terminal
of these wires. Thus, on smaller
voltage is 1.73 times the terminal-
generators, there would be only one
to-neutral voltage (represented by
wire marked T1. However, on larger
the letter V in Figure 16). In the
generators, there will be two or
same generator, a delta connection
more wires marked T1. These are
would have the same terminal-to-
to be connected together to form
neutral voltage as the wye
one lead.
connection for its terminal voltage.
The first voltage listed in a rating However, the delta line current (I)
like 220/440 volts is the line-to-line would now be 1.73 times the wye
voltage at the specified frequency line current (I).
when the generator leads are
A wye connection can be
connected for the low voltage.
structured in the two ways shown in
The second voltage listed is the
Figure 17; a fixed neutral connection
line-to-line voltage at the specified
or a broken neutral connection.
frequency when the re-connectable
The broken neutral allows you to
line leads are series connected for
reconfigure from a wye to delta
high voltage.
and vice-versa. It also provides
Some applications demand a differential protection by allowing
wye connection rather than a delta the machine to monitor the currents
connection and vice-versa. For into and out of individual phases.
example, the delta connection is
sometimes used to obtain single-
phase 120-240 volts, 3-wire, along
with three-phase, 3-wire on the
same generator. Figure 16 shows
an example of a wye and a delta
connection.

2008 Caterpillar
Page 18 All rights reserved.
Generator Systems Application and Installation Guide

Open Delta

Figure 17

The zigzag connection is


sometimes used to get an
alternative voltage from a generator.
For example, the connection Figure 19
shown in Figure 18 can provide
The lead terminal numbering
120-208V from a generator wound
for 120-240V. system follows the pattern shown
in Figure 20. This system is used
Zigzag Connection for both three-phase generators and
motors.

Figure 18 Figure 20
Several single-phase connections
are possible for 2-wire or 3-wire
Generator Features and
loads. These connections are Attachments
normally used only on smaller Several attachments and features
generators at or below 250 kW. can also be configured to assist
An open delta, as shown in in meeting generator requirements.
Figure 19 is reconfigured from an These include bearings,
original delta from three-phase to environmental protection devices
single-phase use; this type of and space heaters.
connection, however, will only Bearings
provide approximately 57% of the Bearings are devices that permit
original three smooth movement between

2008 Caterpillar
All rights reserved. Page 19
Application and Installation Guide Generator Systems

surfaces. In a generator, they are protection from water. Table 4 lists


used to hold the rotor in place and the levels of protection for solid
allow that smooth rotation. objects coming in contact with the
A single bearing system is used in machine. Table 5 lists the levels of
the smaller generators with lighter protection from water. These tables
weight rotors. It is necessary to only offer brief descriptions; each
have a two bearing system when level of each category has specific
the weight of the rotor exceeds definitions and qualifications.
the limits of the engine rear main A standard Caterpillar SR5
bearing. In a traditional two bearing generator is rated for IP23. The first
system, the generator is not digit, 2, indicates the machine is
attached directly to the engines protected against solid objects
flywheel housing. This brings about greater than 12 mm. The second
alignment difficulty due to the digit, 3, indicates protection from
separation of the two machines. spraying water.
A close coupled two bearing system
alleviates these original alignment
Solid Object Ingress Protection
problems by attaching the generator (first digit of IP designation)
to the flywheel housing. First
Description
Digit
Space Heaters
0 Non-Protected Machine
Space heaters are electrical
Machine protected against
resistance heaters that are often solid objects greater than
used to help prevent condensation 1
50 mm (approximately the size
collection and moisture absorption of a hand)
on generator windings during nonuse Machine protected against
periods. The integrity of all types of solid objects greater than
2
12mm (approximately the size
generator winding insulation systems
of a finger)
is distinctly improved when moisture is Machine protected against
restrained from collecting on winding solid objects greater than
insulation. 3
2.5 mm (approximately the
size of a hand tool)
Ingress Protection (IP)
Machine protected against
Ingress Protection (IP) refers to solid objects greater than
the degree of protection an 4
1 mm (approximately the size
enclosure provides for a machine. of wires)
This is protection both for persons Machine protected against
5
in contact with moving parts and dust
for the protection of machines Table 4
against the harmful effects due to
the collection of water and dust.
An IP designation is typically two
digits, where the first digit is the
level of protection from solid objects
and the second digit is the level of

2008 Caterpillar
Page 20 All rights reserved.
Generator Systems Application and Installation Guide

Inertia
Water Ingress Protection Inertia data is essential to studies
(second digit of IP designation) of transient response, such as the
Second
Description effect of a larger generator with
Digit more rotor weight and greater mass
0 Non-Protected Machine moment of inertia. When the
Machine protected against
1 information is given to an engineer,
dripping water
Machine protected against
it must be correctly identified.
2 dripping water when machine These figures list the mass
is tilted up to 15 moment of inertia in System
Machine protected against
3 International (SI) units and English
spraying water
Machine protected against
units. Other symbols used to
4 designate inertia of rotating
splashing water
Machine protected against machinery are WK2, WR2, and GD2.
5
water jets The standard inertia presentation
Machine protected against below is globally recognized and can
6
heavy seas
be readily converted to other inertia
Machine protected against
7 designations.
effects of immersion
Table 5 Force x Distance x Time2
Nm sec2 = Newton x meter x Second2
Two types of IP protection are lbin. sec2 = lb x in. x Second2
totally enclosed water cooled
(TEWAC) and totally enclosed air To convert to moment of inertia
cooled (TEAC). (WK2) in SI units:
Multiply Nm sec2 by 9.803
Physical Data m/sec2.
Rotor Weight Multiply lbin. sec2 by 2.683 to get
Rotor weight indicates the total inertia (WK2) in lbft2, the common
weight of the generator rotor. When English unit designation.
used with the formula for inertia, the
Center of Gravity
flywheel effect of the generator can Center of gravity is information
be found. Engineers may use these that gives the location of the
figures when generator loads are generator center of weight in three
sudden or cyclic. planes. With the total generator
Stator Weight weight, the information can be used
Stator weight is given in kilograms to determine the center of gravity
and pounds and gives an indication of an assembly consisting of engine,
of the capacity of a generator. generator, radiator, and base.
Engineers generally assume that a Combined calculations require
heavier stator contains more reducing all values to moments
working copper and iron and (lbin. or kgmm). These are
therefore has greater capabilities. summed algebraically in each plane
of reference.

2008 Caterpillar
All rights reserved. Page 21
Application and Installation Guide Generator Systems

Nameplate Maximum ambient


The nameplate is an engraved temperature for which the
metal plate or printed film on the generator is designed
side of a motor/generator. The plate Insulation system designation
contains the minimum required (if the armature and field use
information needed to identify its different classes of insulation
functionality. systems, both shall be given,
National Electrical Manufacturers that for the armature being
Association (NEMA) Requirement given first)
The following is required ** Applies to the exciter in the
nameplate information as set by case of a brush-less machine.
National Electrical Manufacturers
Association (NEMA). International Standards Organization
(ISO) 8528 Requirement
a. Manufacturers type and Generating sets shall bear the
frame designation following rating plates as set by the
b. Kilovolt-ampere output International Standards Organization
c. Power factor (ISO) 8528. The nameplate for the
set must provide the following
d. Time rating
information.
e. Temperature rise*
a. The words Generating set
f. Rated speed in rpm ISO 8528
g. Voltage b. The manufacturers name or
h. Rated current in amperes mark
per terminal c. the serial number of the set
i. Number of phases d. the year of manufacture of
j. Frequency The set
k. Rated field current** e. The rated power, in kilowatts,
l. Rated excitation voltage with the prefixes COP, PRP or
LTP, in accordance with ISO
Additional information may be 8528-1:1993, clause 13
included such as:
f. The performance class in
m. Enclosure or IP code accordance with ISO 8528-
n. Manufacturers name, mark, 1:1993, clause 7
or logo g. The rated power factor
o. Manufacturers plant location h. The maximum site altitude
p. Serial number or date of above sea-level, in meters
manufacture. i. The maximum ambient
* As an alternate marking, temperature, in degrees
Temperature Rise can be replaced Celsius
by the following information. j. The rated frequency, in hertz

2008 Caterpillar
Page 22 All rights reserved.
Generator Systems Application and Installation Guide

k. The rated voltage, in volts


NEMA & IEC Design
l. The rated current, in amperes Considerations
m. The mass, in kilograms. The following are design
The rating and class of output of considerations as set in the NEMA
the generator shall be combined as code book.
follows. Temperature Rise
a. Where a continuous rating The observable temperature rise
based on duty type S1 is under rated load conditions of each
stated, the rated output shall of the various parts of the
be followed by the marking synchronous generator, above the
BR (basic continuous temperature of the cooling air, shall
rating), e.g. Si=22 kVA BR; not exceed the values in the table
b. Where a rating with discrete below.
constant loads based on duty The temperature of the cooling air
type S10 is stated, the basic is the temperature of the external air
continuous rating based on S1 as it enters the ventilating openings
shall be marked as mentioned of the machine, and the temperature
immediately above. In addition rises given in the Table 6 are based
the peak rated output shall be on a maximum temperature of 40C
shown followed by the (104F) for this external air.
marking PR (peak
continuous rating), the
maximum running time of
500 h per year and the factor
TL, e.g. Si=24 kVA PR 500 h
per year, TL=0,9.

2008 Caterpillar
All rights reserved. Page 23
Application and Installation Guide Generator Systems

Temperature Rise
Method of Temperature Rise, Degrees C
Item Machine Part Temperature Class of Insulation System
Determination A B F H
a. Armature Windings
1. All kVA ratings Resistance 60 80 105 125
2. 1563 kVA and Embedded
70 90 115 140
less detector**
3. Over 1563 kVA
a) 7000 volts and Embedded
65 85 110 135
less detector**
Embedded
b) Over 7000 volts 60 80 105 125
detector**
b. Field Winding Resistance 60 80 105 125
c. The temperature attained by cores, amortisseur windings, collector rings, and
miscellaneous parts (such as brushholders, brushes, pole tips, etc.) shall not
injure the insulation or the machine in any respect.
* For machines which operate under prevailing barometric pressure and which are designed not to exceed the specified
temperature rise at altitudes from 3300 feet (1000 meters) to 13000 feet (4000 meters), the temperature rises, as
checked by tests at low altitudes, shall be less than those listed in the foregoing table by 1 percent of the specified
temperature rise for each 330 feet (100 meters) of altitude in excess of 3300 feet (1000 meters).
** Embedded detectors are located within the slot of the machine and can be either resistance elements or
thermocouples. For machines equipped with embedded detectors, this method shall be used to demonstrate conformity with
the standard (see 20.63).
NOTES:
1Temperature rises in the above table are based upon generators rated on a continuous duty basis. Synchronous
generators may be rated on a stand-by duty basis (see 22.85). In such cases, it is recommended that temperature rises not
exceed those in the foregoing table by more than 25C under continuous operation at a stand-by rating.
2Diesel engine specifications often call for machines which are suitable for 10-percent overload for 2 hours out of any
24 consecutive hours of operation. Generators having a corresponding overload capability are sometimes required. In such
cases, it is recommended that the generators and their excitation systems be designed to deliver 110 percent of kVA at
rated power factor, frequency, and voltage with temperature rises under rated load conditions not exceeding those given in
the above table.
3Temperature rises in the foregoing table are based upon a reference ambient temperature of 40C. However, it is
recognized that synchronous generators may be required to operate at an ambient temperature higher than 40C. The
temperature rises of the generators given in the foregoing table shall be reduced by the number of degrees that the ambient
temperature exceeds 40C. (Exceptionfor totally enclosed water-air-cooled machines, the temperature of the cooling air
is the temperature of the air leaving the coolers. Totally enclosed water-air-cooled machines are normally designed for the
maximum cooling water temperature encountered at the location where each machine is to be installed. With a cooling
water temperature not exceeding that for which the machine is designed.
a. On machines designed for cooling water temperatures from 5C to 30C the temperature of the air leaving the
coolers shall not exceed 40C.
b. On machines designed for higher cooling water temperatures the temperature of the air leaving the coolers shall be
permitted to exceed 40C provided the temperature rises of the machine parts are then limited to values less than those
given in the table by the number of degrees that the temperature of the air leaving the coolers exceeds 40C.)
Table 6

Maximum Momentary Overloads overload with the field set for normal
Synchronous Generators shall be rated load excitation in accordance
capable of carrying a 1-minute with Table 7.

2008 Caterpillar
Page 24 All rights reserved.
Generator Systems Application and Installation Guide

Armature Current, % of
Synchronous Speed rpm
Normal Rated Current TIF According to the 1960 Single
1801 and Over 130 Frequency Weighting
1800 and Below 150 Frequency TIF Frequency TIF
Table 7 60 0.5 1860 7820
180 30 1980 8330
It is recognized that the voltage 300 225 2100 8830
and power factor will differ from the 360 400 2160 9080
420 650 2220 9330
rated load values when generators
540 1320 2340 9840
are subjected to this overload
660 2260 2460 10340
condition. Also, since the heating
720 2760 2580 10600
affect in machine winding varies 780 3360 2820 10210
approximately as the product of the 900 4350 2940 9820
square of the current and the time 1000 5000 3000 9670
for which this current is being 1020 5100 3180 8740
carried, the overload condition will 1080 5400 3300 8090
result in increased temperatures and 1140 5630 3540 6730
a reduction in insulation life. The 1260 6050 3660 6130
generator shall therefore not be 1380 6370 3900 4400
subjected to this extreme condition 1440 6650 4020 3700
for more than a few times in its life. 1500 6680 4260 2750
It is assumed that this excess 1620 6970 4380 2190
1740 7320 5000 840
capacity is required only to
1800 7570
coordinate the generator with the
control and protective devices. Table 8
Maximum Deviation Factor Shall not exceed the values in
The deviation factor of the open Table 7.
circuit line-to-line terminal voltage
kVA Rating of Generator TIF
of synchronous generators shall
125 to 4999 150
not exceed 0.1.
5000 to 19999 75
Telephone Influence Factor (TIF) 2000 and Above 70
Telephone Influence Factor (TIF) Table 9
shall be measured at the generator
terminals on open circuit at rated When specified, the residual
voltage and frequency. When component TIF based on the
specified, the balance TIF is based weighting factors given shall not
on the weighting factors in Table 8. exceed the values in Table 10.
These residual components apply to
those voltage ratings 2000 volts or
higher.

2008 Caterpillar
All rights reserved. Page 25
Application and Installation Guide Generator Systems

values which give an


kVA Rating of Generator TIF (residual) integrated product, equal or
125 to 4999 150 less than 40 for salient pole
5000 to 19999 75 machines and 30 for air
2000 and above 70 cooled cylindrical rotor
Table 10 machines.
b. The maximum phase current
Single Frequency Weighting Short is limited by external means
Circuit Requirements to a value which does not
A synchronous generator shall be exceed the maximum phase
capable of withstanding, without current obtained from the
damage, a 30-second, three-phase three-phase fault.
short circuit when operating at rated
Overspeed
kVA and power factor, at five
Synchronous generator shall be so
percent over voltage, with fixed
constructed that, in an emergency
excitation. The generator shall also
not to exceed two minutes, they will
be capable of withstanding, without
withstand without mechanical injury
damage, any other short circuit at its
overspeeds above synchronous
terminals of 30 seconds or less
speed in accordance with the values
provided:
in Table 11.
a. The machine phase currents Overspeed, Percent of
under fault conditions are Synchronous Speed rpm
Synchronous Speed
such that the negative phase 1801 and Over 20
sequence current (I2), 1800 and Below 25
expressed in per unit of stator Table 11
current at rated kVA, and the
duration of the fault in
seconds (t) are limited to

2008 Caterpillar
Page 26 All rights reserved.
Generator Systems Application and Installation Guide

Generator Performance Characteristics


220
Vpu = = 0.917
Rated and Per Unit 240
Per unit values are expressed as
a decimal fraction of some whole 100
Spu = = 0.833
value. Twenty percent, 20% or 120
0.20 indicates part of some whole
value. Per unit is a pure number. It And from these base numbers you
has no label such as volts, amperes can calculate current and impedance
or ohms. Per unit is often bases.
abbreviated as P.U. or p.u. Sbase (240 V)2
Ibase = = = 50A Zbase =
The per unit system eliminates the Vbase 240 V
use of cube roots that are inherent
to three-phase calculations. The Vbase (240 V)2
Vbase = = = 4.8 12kVa
per unit basis also provides a Ibase Sbase
comparable value system for all
generators, transmission lines, Efficiency
motors and related measures so Efficiency is the percentage of
they look, more or less, alike. engine flywheel horsepower that
kVA, volts, amps, power factor, is converted into electrical output,
resistance and reactance are all or in other words, power out of the
figures converted to per-unit values. generator divided by power in.
Per-unit calculations are defined as 100% efficiency is a theoretical level
the actual value of the figure divided that assumes no losses in heat,
by the base value. It is customary to windage or friction.
select voltage and apparent power
base values; once these are done, all output power
other base values can be calculated. Efficiency =
input power
Refer to Reactance for more per
unit calculations. output
Efficiency =
To convert a circuit quantity to output + losses
a per unit value, divide by the base
value, which is usually the rated input - losses
Efficiency =
value. For example, the following input
equations show the per unit values
for a 240/120-V, 120 kVA generator Generator efficiencies are
that is operated at 100 kVA with published at 100% of rated.
220 volts. Percent generator efficiency is
shown in the following formula.
% Gen. kVA x PF x 100
=
Efficiency (kVA x PF) + gen. losses + exciter losses

2008 Caterpillar
All rights reserved. Page 27
Application and Installation Guide Generator Systems

In discussion of generator generator to provide adequate fault


efficiency, generator losses must current to the short in order to give
be considered. These include the a protective device, such as breakers
following. and fuses, enough time to react.
Armature Winding The loss Permanent Magnet (PM) generators
based upon phase currents are able to sustain fault current due
and phase resistances. to their excitation characteristics
while self excited (SE) generator
Field The loss due to field
may have trouble providing this
current and field resistance. current for enough cycles. Refer to
Core Loss Iron losses, the section entitled NEMA Design
hysteresis, and eddy currents Considerations for official standards
due to the flux variation in the on short circuits.
armature core. Caterpillar IE system (Independent
Stray Load Losses Iron Excitation) also has short circuit
losses and eddy current losses current capabilities. It is designed
in the copper due to fluxes such that the short circuit current
varying with load and capabilities can be disabled during
saturation. parallel operation with the utility and
Friction and Windage Loss fully implemented during stand alone
Loss of the power used to operation for maximum performance.
overcome bearing friction and The IE excitation system relies on
windage. There is a power residual magnetism for voltage build-
used against the friction up. The immunity to non linear
between the bearings and the loads, excellent motor starting and
rotor that creates a friction the short circuit capabilities, are
loss. The power necessary to standard IE features not available on
move the rotor poles through Self Excited generators.
the air and to drive cooling air When a generator experiences a
through the generator creates sudden load increase, such as a
windage loss. starting a motor, output voltage and
Exciter Loss All losses speed of the genset dip for a short
similar to those experienced time. This is called a transient dip
by the main generator. These and is illustrated in Figure 21. When
include field, core, stray load, the load is thrown off, an overshoot
friction and windage losses. occurs. Without proper generator
design, this overshoot could
Fault Current/Short Circuits potentially cause a short-circuit.
Short circuits generally occur when
electric current is diverted from its
intended path to ground or another
line of the generator. When short
circuits occur, it is necessary for a

2008 Caterpillar
Page 28 All rights reserved.
Generator Systems Application and Installation Guide

offset the short circuit current for a


Transient Dip very short time.

Figure 21

Each phase of a generator has


the following impedances: Figure 22
Equivalent Armature A three-phase fault is a short
Reactance between all three phases of the
Armature Leakage Reactance output. A line-to-line fault is a short
Armature Resistance between two of the three phases,
and the same concept goes for line-
Synchronous Reactance
to-neutral and line-to-ground faults.
Synchronous Impedance A more detailed explanation of faults
Voltage Proportional to is covered under Power Systems.
Excitation Requirements Figure 23 illustrates a short circuit;
Line Current Variable definitions can be found on
Page 32 of this section.
Phase Voltage
The vectors shown in Figure 22
demonstrate that to maintain
constant voltage at the terminals,
the excitation requirements will
vary according to the power factor.
Therefore, excitation requirements
are greatest at lagging power factors
and less at leading power factors.
There may also be a direct current
component to short circuits. In most
Figure 23
short circuits, the ratio of reactance
to resistance is high. If a fault Stator Resistance
occurs at zero voltage on the sine Stator resistance refers to the
wave in such a circuit, the current internal resistance of the generator
will not be symmetrical. It will that is developed by the stator
contain a DC component that will copper and winding configuration.

2008 Caterpillar
All rights reserved. Page 29
Application and Installation Guide Generator Systems

Assume each coil in Figure 24 and For resistance of 1-2, 2-3, 3-1
Figure 25 represents an equal (line-to-line), multiply the coil
resistance value in ohms. The resistance by 4.
numbers shown represent the line For resistance of 1-4, 2-5, 3-
and neutral in the stator windings. 6, 7-0, 8-0, 9-0 (individual
The figures show the points at coil resistance), single coil
which the listed resistance value resistance applies.
or a multiple of it applies.
For resistance of 1-0, 2-0,
In Figure 24, the generator coils and 3-0, multiply the coil
are connected in parallel for low resistance by 2.
voltage.
Resistance measurements will be
valid only if made with instruments
capable of measuring very low
resistance. Do not attempt to use
an Ohmmeter. The inaccuracy is
too great to have any value.
Resistance values vary with
temperature. Given resistance values
apply only at 25C (77F).
Correction must be applied at other
Figure 24
temperatures. For temperatures
For resistance of 1-2, 2-3, or other than 25C, multiply the listed
3-1 (line-to-line), single coil value by 0.00393 and then by the
resistance value applies. total temperature difference
between 25C and the existing
For resistance of 1-0, 2-0, or temperature. Add the result to the
3-0 (line-to-neutral), divide the listed value if the temperature is
coil resistance by 2. higher. Subtract the result if the
In Figure 25, the generator coils temperature is lower.
are connected in series for high A reverse process can find internal
voltage. temperature of generator coils. The
generator stator resistance must be
accurately measured.
Open Circuit Time Constant
The open circuit time constant is
determined from a test performed as
follows:
The generator is operating at
normal rated voltage with no
Figure 25 load.

2008 Caterpillar
Page 30 All rights reserved.
Generator Systems Application and Installation Guide

The main rotating field is Short Circuit Ratio


supplied from a separate The short circuit ratio gives an
source, usually a battery. indication of generator response to
The rotating field input is a suddenly applied load. It is the
short-circuited and the voltage ratio of the field current required for
across the generator output the rated voltage at open circuit to
terminals will reduce. the field current required for the
rated armature current at short
Time, in seconds, for the circuit. It can also be found as the
generator terminal voltage to reciprocal of the synchronous
reach 36.8% of its original reactance. This number is usually
value is recorded as the open on the order of 0.3-0.6. Refer to
circuit time constant. Figure 26.
The open circuit time constant
figure is primarily used in the design
of voltage regulators. Some
engineers use the open circuit time
constant along with another factor
called generator time constant,
which can be supplied upon request.
Individually and together, these two
time constants provide switchgear
and distribution designers with
information needed to study the
possible voltage changes resulting Figure 26
from severe load changes.
Reactance
Generator Time Constant The impedance, or combined
The generator time constant is a reactance and resistance, control
measure of the magnetic inertia in the flow of current in an alternating
a generator and gives an indication current circuit. In generator sets, the
of machine performance under short generator reactance is such a large
circuit conditions. The factor is part of the total impedance that the
determined by actual running tests resistance can be disregarded. The
where the generator output is short- amount of current that will flow as
circuited and the reaction is a result of a ground or short circuit
recorded. The time elapsed between is therefore determined by the
short circuit application and voltage various generator reactances
decline to 36.8% of normal is the (assuming a constant field current).
generator time constant. The symbol The five major reactances are
is TD and it has a value in seconds shown in Table 12.
approximately equal to 10% of the
open circuit time constant.

2008 Caterpillar
All rights reserved. Page 31
Application and Installation Guide Generator Systems

Negative phase sequence


Table of Generator Reactances reactance is used in
Approx. calculating line-to-line faults.
Name Symbol Range Importance Time
Effective The factors involved in a short
Sub-transient
Determines
1 to 6 circuit are defined in the list below:
Xd .08 to .26 max. inst.
Reactance cycles X = Transient Reactance
current
Determines X d = Sub-Transient Reactance
Transient 6 cycles to id = Transient Current
Xd .16 to .45 current when
Reactance 5 sec. I d = Sub-Transient Current
breaker opens
erated = Generator Rated Voltage
Determines
Synchronous continuous T d2 = Short Circuit Sub-Transient Time Constant
Xd 2.0 to 3.9 steady state
Reactance after 5 sec. Td = Short Circuit Transient Time Constant
current
Td2 Field Inductance
To determine = Open Circuit Time Constant;
fault current in Field Resistance in Seconds
Zero Sequence
Xo .02 to .25 grounded
Reactance
neutral Transient Reactance (Xd)
machines The term transient reactance is
Negative Phase To determine usually expressed by the symbol Xd.
Sequence X2 .1 to .4 current in line-
Reactance to-line faults
It is one of the five reactance figures
frequently used by engineers when
Table 12 comparing generator capability with
load requirement, or when
Synchronous reactance determines comparing one generator with
steady-state current. However, another. Reactance figures are
when a sudden change from steady always used with the following:
state occurs, such as short circuit,
Related kVA rating, called
other reactances come into play.
Base kVA
This happens because the flux in the
machine cannot change immediately. The refuted ampere rating,
called Base Amperes
Sub-transient reactance
determines maximum Related voltage, called Base
instantaneous current. It lasts Voltage
up to about 6 cycles. The listed figures are per unit
Transient reactance is a values. Reactance are also
longer lasting reactance expressed in percent (100% x
determining current up to per unit).
as much as 5 seconds. Transient Reactance Note: This
Other reactances not subject to expression will be used to explain
time limitations: reactance values in general and to
show some of the related arithmetic
Zero sequence reactance
and uses of the five listed reactance
determines neutral currents in
values in Table 12.
grounding studies. It is also a
factor in determining neutral The transient reactance is similar
currents when third harmonics to sub-transient reactance, except
are encountered. that transient reactance determines
the amount of current for

2008 Caterpillar
Page 32 All rights reserved.
Generator Systems Application and Installation Guide

approximately six cycles to five Most engineers prefer a


seconds. presentation in the following order.
The five listed reactance per unit Line-to-line voltage
values describe the line-to-neutral Prime power kVA
value at the kVA and ampere
Line amperes (at the listed
condition, or volt condition, listed in
line-to-line voltage)
the same price list reference number
and rating. These line-to-neutral Line-to-neutral reactance in
reactance per unit values can be the per unit value
directly converted to a line-to-neutral Various ratings on a specific
ohmic value by use of Ohms law generator do not change the
and the per unit value. First, divide reactance. However, the per unit
the line-to-neutral rated voltage by value reactance do change directly
the rated line amperes. The result with the rating.
will be Ohms. Next, multiply the
Example:
result by the per unit value. The
Determine the per unit value of
result is Ohms reactance.
transient reactance of a generator
Example: at a 180 base kVA at 480 volts. At
Transient reactance = 0.2490 per 219 kVA, 480 volts, the reactance
unit. The base voltage is 480, base is 0.2490 P.U. Per unit values
ampere is 263. Generator voltage change directly with the base kVA.
listed is line-to-line. This must be
180
converted to line-to-neutral voltage. x 0.2490 = 0.2046 P.U.
219
Divide 480 by the square root of 3.
480
= 277 The reactance in ohms has not
3
changed because at 180 kVA, the
277 is the base voltage. line ampere rating would be 216
amperes. The calculation shows:
Transient 277 277 volts
Reactance, = X 0.2490 x 0.2046 = 0.262 Ohms
216 amperes
ohms 263
Per unit reactance changes
= 0.262 Ohms inversely (volts down, reactance up)
with the square of the voltage ratio
if the kVA rating remains the same.

2008 Caterpillar
All rights reserved. Page 33
Application and Installation Guide Generator Systems

Example: Transient reactance (per unit)


At 480 volts, the listed transient figures are used to approximate the
reactance is 0.2490. The base current at the time a circuit breaker
voltage is to be decreased from opens under three-phase, short-
480 volts to 416 volts. The kVA circuit conditions. A circuit breaker
is to remain the same. The per unit will probably open at 7 cycles
transient reactance at the lower (0.13 seconds at 60 Hz), which is
voltage is: within the time transient reactance
(480/416)2 x 0.2490 = 0.3310 per unit values apply (about 6 cycles to
5 seconds). The calculation requires
The ohmic line-to-neutral transient two values; base amperes and the
reactance has not changed. Line-to- transient reactance. For a generator
neutral voltage is now: at 60 Hz, 480 volts, divide the base
416 amperes by the transient reactance
= 240 volts
3 per unit value.
Example:
Since the kVA rating is to remain Generator base amps = 263
at 219 kVA, the line ampere rating
Transient reactance = 0.2490
is:
263 amperes
219 kVA x 1000 = 1056 amperes
= 303 0.2490
3 x 416

Transient reactance in ohms is: Sub-Transient Reactance (Xd)


If a generator is operating at
240 volts x 0.3310 normal voltage and a short circuit
= 0.262 Ohms
303 amperes occurs, a large amount of current
will flow. The initial value (for
Two other terms are used relating approximately the first six cycles),
to reactance; they are direct and in terms of full load current, is
saturated. expressed by voltage divided by
Direct All of the figures sub-transient reactance.
quoted in the Caterpillar This term is usually expressed as
TMI system are direct axis Xd and for Caterpillar generators
reactance per unit values. has a per unit value of 0.1 to 0.3.
This data can also be shown Engineers frequently request the
in quadrature axis figures. percent sub-transient reactance. Per
Saturated Where unit values are directly convertible
applicable, figures are to percent; 0.1 becomes 10% and
calculated at magnetic 0.3 becomes 30%. Engineers also
saturation. Occasionally request the sub-transient impedance.
an unsaturated value of a This implies the Ohmic line-to-
reactance may be required. neutral reactance since the stator
resistance is less than 2% of the

2008 Caterpillar
Page 34 All rights reserved.
Generator Systems Application and Installation Guide

line-to-neutral impedance. Calculate


the sub-transient line-to-neutral Symmetric Current
reactance as:
Volts, line neutral
x Xd
Base amperes

For a generator at 60 Hz, 219 Figure 27


kVA, with Xd equal to 0.120 and
base amperes of 263: Asymmetrical, or offset, refers to
a current that is not centered to a
480 volts fixed reference axis as shown in
= 277 volts, line neutral
3 Figure 28. Asymmetrical current is
also known as the Direct Current
277 (DC) component.
x 0.1201 = 0.1265 Ohm
263 amperes
Asymmetric Current
The sub-transient reactance applies
to a time period ranging from one to
six cycles. The per unit value is
often used to determine the
maximum current in event of a short
circuit.
Note: Root-Mean-Square (RMS) is
used by ammeters, voltmeters and Figure 28
the more common measuring
devices to indicate current. The point in time at which the
short circuit occurs determines if
The RMS symmetrical current
the resultant current is initially
will be the rated amperes divided
symmetrical or asymmetrical or a
by the sub-transient reactance per
combination of each. If the fault
unit value. Under three-phase short
occurred the instant the voltage is
circuit, this generator can produce:
crossing the zero line, the current
263 will be asymmetrical. The resulting
= 2190 amperes RMS
0.1201 value is known as maximum
Symmetrical & Asymmetrical asymmetrical current. If the fault
Symmetrical refers to a occurred when the voltage is at
current that is symmetric to a a positive or negative peak, the
fixed reference axis as shown resultant current will be
in Figure 27. symmetrical. A fault occurring at
any point in time between zero
crossing, and the positive or
negative peak will produce a lesser
value of asymmetrical current.

2008 Caterpillar
All rights reserved. Page 35
Application and Installation Guide Generator Systems

In time, within one to five cycles, are about one-half the transient
the asymmetrical current declines reactance per unit value.
to a very low value. From that time Some engineers also use sub-
forward, the symmetrical current is transient reactance to determine
the only significant current. the approximate voltage dip on
The maximum asymmetrical short a generator when starting large
circuit RMS current can be found by motors.
multiplying the RMS symmetrical
Synchronous Reactance (Xd)
value by square root of 3. In the After transient conditions have
above example, the generator will occurred, current flow is determined
produce 2190 x 3 = 3793 RMS by the synchronous reactance.
amperes, asymmetrical. This is a steady state value and
Calculations involving circuit is effective after approximately
breakers normally require peak five seconds.
currents. Symmetrical and
asymmetrical currents from a
Caterpillar generator can be
converted to peak values by
multiplying either value by the
square root of 2. In the above
example, the generator will
produce: 2190 x 2 = 3096
peak symmetrical amperes or
3793 x 2 = 5363 peak
asymmetrical amperes. Figure 29
Note that a smaller sub-transient
Synchronous reactance is
reactance per unit value results in
identified by the symbol Xd and
higher available short-circuit current.
has a per unit value of 2.0 to 4 in
Available short-circuit current is Caterpillar generators. This factor
sometimes expressed as a multiplier is used to determine the steady-
(called available current ratio), which state fault current capability of a
is the reciprocal of the per unit sub- separately excited generator. This is
transient reactance. For this the short circuit current which would
generator: be produced after five seconds. Self-
1 excited generators, such as the SR4,
= 8.326
0.1201 lose excitation before five seconds.
Therefore, the synchronous
Rated current times that multiplier reactance factor cannot be used to
equals RMS symmetrical current: determine the actual steady-state
fault current. The factor does,
263 Amperes x 8.326 = 2190 however, give a comparison with
Per unit sub-transient reactance other generators by considering the
values of Caterpillar generators

2008 Caterpillar
Page 36 All rights reserved.
Generator Systems Application and Installation Guide

probable performance if excited from The peak asymmetrical value is the


a separate source. RMS asymmetrical value multiplied
The diagram in Figure 29 indicates by 2:
the current available at various 2875 x 1.414 = 4065 amperes
periods of time. Zero Sequence Reactance (Xo)
Negative Sequence Reactance (X2) The zero sequence reactance is the
The negative sequence reactance major factor determining the ground
is an important factor in determining current in case of a grounded neutral
the fault current on a line-to-line unit having a phase-to-ground fault.
short circuit in a three-phase unit. This reactance factor has the
This factor has a symbol X2 and a symbol X0 and a per unit value of
per unit value that approximates the 0.03 to 0.13 or approximately one-
value of the sub-transient per unit third the value of the sub-transient
reactance value. Engineers use this per unit reactance figure. The factor
figure when calculating probable is used to determine probable value
fault currents in event of a line-to- of line-to-neutral, short-circuit
line short circuit from a particular currents and possible line-to-ground
generator. currents in the event the neutral is
Calculation is very similar to that grounded and a line-to-ground fault
used for sub-transient short circuits. occurs. Fault current calculation is
For a generator at 60 Hz, 219 kVA, similar to those of line-to-line
263 amperes, and X2 of 0.1543: calculation:
Rated amperes x 3 rated amperes x 3
amperes, RMSSC = amperes, RMS =
Xd + X2 Xd + X2+ X0

236 x 3 263 x 3 For a generator at 60 Hz,


= 219 kVA, 263 amperes and X0
0.1201 + 0.1543 0.2744
of 0.0450:
1660 amperes. RMS, symmetrical 236 x 3 263 x 3
= =
0.1201 + 0.1543 + 0.0450 0.3194

1660 amperes is the RMS = 2470 amperes. RMS, symmetrical


effective symmetrical current. The
peak symmetrical value is found by
multiplying the RMS value by 2: 2470 is the RMS effective
1660 x 1.414 = 2347 amperes symmetrical current. The peak
symmetrical value can be found by
RMS asymmetrical value is
multiplying the RMS value by 2:
determined from:
2470 x 1.414 = 3493 amperes
RMS x 3 = 1660 x 1.732 = 2875

2008 Caterpillar
All rights reserved. Page 37
Application and Installation Guide Generator Systems

RMS asymmetrical value can different. The line-to-neutral short


be found by multiplying the RMS circuit is often the highest value and
symmetrical value by 3. the most likely to occur.
Note: Available currents resulting
from different type of faults are

2008 Caterpillar
Page 38 All rights reserved.
Generator Systems Application and Installation Guide

Harmonics & Distortion


Quality of electrical performance
is a measure of how close the
electrical output of the generator
is to a true sine wave. The ideal
voltage waveform is a sine wave
pattern in which a voltage cycle
starts at zero, increases to a positive
peak, returns to zero, increases to a Figure 30
negative peak, and finally returns to
zero, completing the cycle. The waveform distortion discussed
above can cause problems in voltage
The actual voltage waveform from
regulation, generator and load
rotating machinery is never perfect.
overheating, and inaccurate
Internal generator and external load
instrument readings. Both voltage
characteristics cause distortions in
and current may have harmonic
the wave. These factors impair the
components. The current
consistency of the generator output,
components produce heat and are
and can result in voltage regulator
therefore derating factors for the
sensing errors and incorrect
generator as well as system motors.
instrument readings.
Occasionally, specifications
In brief, harmonics are energy
require a 2/3-pitch stator winding;
levels existing at multiples of the
this is a common competitive
fundamental waves frequency.
practice in reducing 3rd harmonics.
Harmonics may produce undesirable
Caterpillar generator design
effects in the generator and motor
minimizes 3rd harmonic voltage
performance may suffer from
without compromising 5th and 7th.
excessive harmonics. The remainder
It is, therefore, important for
of this discussion will be limited to
specifications to stress the actual
harmonics of lower orders, those
total harmonic levels produced by
with significant magnitudes, are the
the generator.
3rd, 5th, and 7th. Generators are
symmetrical machines that have One very important factor to
even numbers of north and south remember is that most harmonics
poles, resulting in cancellation of all are produced by the load itself.
even number harmonics. Only odd Examples are large battery chargers
number harmonics remain. In a for uninterruptible power supply
60 Hz set, the 3rd harmonic occurs (UPS) systems, fluorescent lamps
at 180 Hz, the 5th at 300 Hz, 7th at and variable speed motor drives.
420 Hz, and so on. The effects of Each of these harmonic voltages
3rd and 5th harmonics on the generated are in the windings, but
composite waveform are illustrated a 3rd harmonic current will not flow
in Figure 30. in a three-phase, wye connected

2008 Caterpillar
All rights reserved. Page 39
Application and Installation Guide Generator Systems

winding unless the neutral is than 180 electrical degrees apart).


connected. The 3rd harmonic Placing the two sides of a coil less
current will flow in a delta than 180 electrical degrees apart
connected generator winding as reduces the voltage induced by
shown in Figure 16. Both 5th and 7th the coil. However, it helps control
harmonics will flow in either winding harmonics, shortens end turns, and
since they are line harmonics. simplifies the physical construction
The major difficulty caused by of the generator.
harmonic currents is heat generated Table 13 shows the percent
in the winding, core, and rotor. reduction of 3rd, 5th, and 7th
Since generator ratings are limited harmonics at various pitch factors.
by allowable temperature rise, 3rd 5th 7th
harmonics act as derating factors. Harmonics Harmonics Harmonics
In derating, the magnitude of the 8/9
12% 32% 60%
current is of obvious importance, Pitch
7/8
because losses are proportional to Pitch
50% 82% 30%
the square of the current. Increased 2/3
100% 10% 12%
frequency causes increased core Pitch
losses and increased copper loss Table 13
from skin effect. 5th and 7th
harmonics are the offenders here Another common method of
because they are in the 600 Hz reducing slot harmonics is to
range. skew or angle the stator slots.
Another difficulty caused by Occasionally, the poles are skewed
harmonics is waveform distortion. instead. In either case, the voltage
The more harmonic content in a is somewhat reduced, but so are the
generated wave, the more distortion harmonics.
from a sine wave occurs. If the Adjustments are made in the pole
distortion is severe, it can cause flux waveform and the stator
voltage regulator sensing problems windings to achieve an adequate
and inaccurate instrument readings. waveform in the output voltage.
This section explains the various The factor K accounts for both
methods of minimizing harmonics. types of adjustments.
The following methods are used to The voltage output waveform
minimize harmonics: can also contain harmonics. It can
Pitch Factor contain odd harmonics, such as
3rd, 5th and 7th, but never even
Skew Factor
harmonics. A quality output voltage
Waveform Shaping waveform must be shaped as
Most generators are fractional sinusoidal as possible to reduce
pitch. In other words, the stator these harmonics. To create an
windings are less than a pole pitch output voltage waveform that is as
from one coil side to the other (less

2008 Caterpillar
Page 40 All rights reserved.
Generator Systems Application and Installation Guide

sinusoidal as possible, the shape of harmonics, but not all


the pole heads is adjusted. harmonics
A square pole head generates a Telephone Influence Factor (TIF)
square flux wave; a square flux and Telephone Harmonic Factor
wave generates many odd (THF) measure the possible effect
harmonics in the stator windings. of harmonics in a generator wave
To make the flux wave more shape on telephone circuits. TIF and
sinusoidal, the pole tips can be THF are measured at the generator
beveled. This increases the air-gap terminals on open circuit at rated
length at the pole tips, increasing voltage and frequency. TIF is used in
the reluctance, or resistance, of the US, while THF is used in the rest
the flux path. of the world.
However, to achieve the best flux TIF & THF Weighting Curves
waveform possible, the pole face is
rounded at a radius with a different
center than the stator core.
All generators have harmonic
waveform distortion and non-
sinusoidal rotor flux density.
Following is a list of generator
design factors for distortion
reduction.
Stator Slots more stator
slots give better winding Figure 31
distribution
Figure 31 shows a comparison
Winding Style symmetrical of TIF and THF weighting curves.
lap winding produces the best Weight refers to the sound
waveform wave/harmonic with the most
Skew one slot pitch skew emphasis on it. The higher the
eliminates ripple harmonics weight, the more emphasis placed.
Slot Opening wider the slot The calculating procedures are
openings increase harmonics different for TIF and THF, but similar
frequencies give almost equal
Pole Head Width wider pole weights.
heads increase flux
distribution Limits for generator harmonics
are based on these curves. The most
Tapered Pole Heads annoying frequencies in telephone
tapered pole heads distribute interference are usually 2500 to
more nearly sinusoidal flux 3000 Hz, and therefore have the
Stator Winding Pitch highest weighting.
reduces or eliminates certain

2008 Caterpillar
All rights reserved. Page 41
Application and Installation Guide Generator Systems

TIF is the summation of RMS manufacturers meet 5% deviation,


values of each harmonic in a percentages of 10% and below are
waveform multiplied by a weighting generally acceptable in the industry.
factor; like those in a weighting Caterpillar generators do not exceed
curve. The product is squared and 5% waveform deviation. Deviation
added together. TIF is then the ratio from a perfect sine wave, as shown
of the square root of this sum to the in Figure 32, is primarily the result of
RMS of the entire wave. harmonics, generated as a field pole
Balanced TIF is measured at passes a conductor. There are many
frequencies other than triples. design techniques available to make
Triples are harmonics divisible by the deviation factor very low. These
3; 3rd, 9th, 15th, etc. Generators of techniques may or may not have
higher voltage (above 2000V) are importance when the generator is
often required to have residual TIF under normal load.
values below 100. Residual TIF
measures triple frequencies only. Example of Deviation from Sine
Wave
Total Harmonic Distortion (THD)
is the ratio of the sum of the
interference from all harmonics to
the fundamental signal.
Waveform deviation factor, or
wave-shape deviation factor, is
an indication of the degree that a
generated voltage differs from a
perfect sine wave. It is common
practice that these factors not Figure 32
exceed 10% of the line-to-line
generated voltage at no load.
Although most generator

2008 Caterpillar
Page 42 All rights reserved.
Generator Systems Application and Installation Guide

Miscellaneous Terms
Overspeed Capability may be necessary. Refer to the
Overspeed capability is the ability altitude/temperature de-rating chart
of the generator to handle the in TMI or consult your Caterpillar
sudden increase over rated rpm due dealer.
to the removal of a large load. This Where the temperature of the
is usually on the order of 125 to ventilating air to the generator
150% of rated rpm. exceeds 40C (104F), de-rating of
Heat Dissipation the generator may be necessary. See
Heat dissipation occurs when a Figure 33 for general capabilities.
device is heated due to current flow. Non-Linear & Unbalanced Loads
Some electrical energy is then lost Non-linear loads & unbalanced
from the energy used in the heating loads generate harmonic currents
of this device. that cause waveform distortion of
Derating the generator. In this situation,
Generator de-rating refers to the excess heat can be created and
need to lower a generators rated a larger generator may be needed.
operating capabilities due to an Crest Factor
environmental reason or a load Crest factor is the peak voltage
affect. This situation requires the divided by the RMS voltage.
use of a larger generator than
Distortion Factor
would be necessary under normal
Distortion factor is the sum of
conditions. Several examples of
the harmonics divided by the RMS
these conditions are as follows:
voltage.
Altitude
For application over 3300 ft
elevation, derating of the generator

Figure 33

2008 Caterpillar
All rights reserved. Page 43
Application and Installation Guide Generator Systems

Generator Limits
Rating limits are occasionally thermal limits. Unfortunately, it is
illustrated as shown in Figure 34; typically not possible to monitor the
kVA and kW versus power factor. temperature directly because this is,
The fluctuations in the kVA line normally, a rotating device. In this
represent the generator operating right quadrant, the generator output
limits. It is important to note that is only limited by the generators
every generators limit tendency to become self-excited
characteristics are different and with a high leading power factor.
cannot be classified by size or type. While operating in the leading
For example, the limits for a standby power factor condition, there is
generator are less limiting than for a tendency for an overvoltage
an equivalent prime-continuous condition. An overvoltage condition
generator. In another example, field may affect the successful operation
heating limits may be the limiting of the automatic voltage regulator.
factor at 0.8 PF, or they may not If the generator operates in the
limit the generator at all. left quadrant of Figure 34, it has a
The engine is many times the lagging power factor. It is limited
limiting factor in a genset as shown here by both the rotor (field) and
by the engine kW limit line. stator (armature) heating. Many
If the generator operates in the times, the field temperature limit
leading power factor quadrant, it is lower than the armature limit,
operates on a capacitive load. In this especially at low power factor
condition, the rotor is subject to values.
heat generation and may reach

Figure 34

2008 Caterpillar
Page 44 All rights reserved.
Generator Systems Application and Installation Guide

Exciter & Regulator Characteristics and Performance


exciter system is unacceptable by
Excitation System
todays standards.
Generator voltage is controlled
entirely by the exciter-regulator In the shunt excitation system,
system. The function of the both voltage output sensing and AC
excitation system is to supply DC power output are taken from three-
current to the main generator field phase AC generator output lines;
windings, enabling them to produce this is represented in one line in
a magnetic field. In turn, this Figure 35. The static exciter
magnetic field enables the stator converts the AC power to DC power
windings to produce output voltage. (originally by magnetic amplifiers,
but presently by SCRs) and feeds
The main generator output voltage
the DC power to the main generator
should be kept at a constant value
field windings.
for whatever load conditions it may
be supporting. Note that there is a
drop in voltage at the load terminals
due to the impedance of the
armature windings and to the
reduction of the magnetic field flux.
The magnetic field flux is reduced
because of the opposing amp-turns
of the load current in the armature,
known as armature reaction. Figure 35

Until the 1960s, most engine- In a self-regulating system, the


driven exciters were DC generators voltage and current are taken from
with rotating armatures, stationary the AC generator output lines.
fields, commutators and brushes. The voltage and current are added
The excitation current was fed to together so at a power factor of 1.0,
the shaft-mounted main field they are 90 apart. When the power
through slip rings and brushes. factor lags, the angle changes to
Control of the exciter voltage was give an increased resultant. The
accomplished with a variable varying resultant is fed through the
resistance in the exciter field. rectifier to the field. The function of
DC exciters are seldom used rectifiers is to convert the AC
today. Adjusting these exciters for current from the exciter to a DC
close control of saturation, operating current that can be supplied to the
point on the curve, and brush and field windings. The rectifier circuits
commutator setting is too difficult. most commonly used are the 3-
Additionally, the short brush life and phase bridge and the 3-phase star.
commutator maintenance of this

2008 Caterpillar
All rights reserved. Page 45
Application and Installation Guide Generator Systems

Self-Excitation can only be fitted to the main stator


The generator can be deemed while it is being wound. The two
Self-Excited (SE) as well. An SE auxiliary windings are designed to
generator uses the output from the provide power to the voltage
main generator to supply its own regulator. The two coils are
exciter current. When assembled, connected in series to the three
a brushless generator contains the phase power input of the voltage
functional parts shown in Figure 36. regulator. One auxiliary winding
The engine drives the exciter produces a voltage proportional to
armature, rectifier, and main field, the output voltage of the unit. The
while the main armature, automatic other acts like a current transformer
voltage regulation, and exciter field and produces a voltage proportional
are stationary. to the output current of the unit.
The two windings combined to
provide a voltage regulator with
a constant voltage source.
The main generator output voltage
should be kept at a constant value
for whatever load conditions it may
be supporting. A voltage regulator
controls this function by controlling
the output of the exciter.
Figure 36
Voltage Regulation
Permanent Magnet Excitation Voltage regulation is achieved
The permanent magnet or pilot through the excitation control
exciter furnishes power to the main system. The term voltage
exciter, thus, eliminating the main regulation originates from the
exciters dependence on generator inherent regulation of a synchronous
output voltage. It is in essence a generator without an Automatic
very small generator attached at the Voltage Regulator (AVR). A better
end of the same shaft as the main term than voltage regulation might
generator. The permanent magnet be voltage accuracy, meaning a
eliminates the exciters dependence voltage that does not deviate from
on output from the main generator a given value for any reason other
making it a more stable device in than transient load changes. This is
load transients. considered ideal voltage regulation.
The IE excitation system consists The purpose of the voltage
of two special sets of coils that are regulator is to control generator
wound to fit in carefully selected output in order to maintain voltage
slots of the main stator. The special within prescribed limits with
wire selected for the IE coils provide changes in loads. There is a
total separation and isolation from misconception in the marketplace
the stator main winding. The coils that voltage regulation must be

2008 Caterpillar
Page 46 All rights reserved.
Generator Systems Application and Installation Guide

0.5%. While Caterpillar regulators overshoot. As a result, oscillations


meet this specification, it is occur. Therefore, the stability circuit
important to note that normal utility anticipates restoration of voltage, so
voltage fluctuates by 5% or more; over-correction is avoided.
this equates to at least 10 times as The excitation control system in a
much. synchronous generator is usually a
Voltage regulation is affected feedback control system consisting
mainly by loading and transients. of the exciter and the AVR. Open
Other factors that affect voltage loop systems are seldom used.
regulation include cold-to-hot drift, The system components involved
frequency effect, generator heating in meeting performance
effect, and ambient temperature specifications are the synchronous
change. Voltage regulation generator, the AVR, and the exciter.
encompasses all variables that must These three components and their
be controlled to keep generator interaction are responsible for the
voltage within a given percentage following performance
of a specified value. characteristics.
The AVR senses the voltage Synchronous Generator
level at the generator terminals by Total harmonic content,
comparing it to the reference. The maximum single harmonic,
reference in older mechanical AVR crest factor, form factor,
was often a spring or saturating deviation factor, and phase
reactor. Today, the AVR reference voltage balance.
is often a zener diode; a very stable
AVR Stable recovery
voltage device. The desired voltage
voltage, maximum voltage
level is set by the voltage adjust
modulation, frequency of
rheostat. This voltage level is
modulation, voltage drift with
compared to the terminal voltage.
ambient temperature, voltage
The reference in the error detector
drift with time, cold-to-hot
is fed through the amplifier to the
drift, and voltage regulation.
power section (usually triggering an
Maintaining voltage regulation
SCR) to feed the exciter field. The
means keeping the generator
power section provides the exciter
within the specified load
field with more or less current
range, power factor range, and
depending on the error signal
ambient temperature range.
requirement. For example, the AVR
may call for increased excitation Generator And Exciter
because of falling terminal voltage. Maximum voltage dip,
The increased excitation brings the maximum voltage overshoot,
voltage back up, but by the time the and recovery time.
AVR senses and responds to the The steady-state voltage variation
need to drop the excitation once is the percentage fluctuation allowed
more, the voltage may tend to by the voltage regulator under

2008 Caterpillar
All rights reserved. Page 47
Application and Installation Guide Generator Systems

constant load, temperature, and speed. Most modern generators,


engine speed. Generator sets therefore, utilize a regulator which
generally provide much less variation permits a brief voltage droop
than the normal utility; but in some proportional to speed droop
applications, especially paralleling, (volts/Hz) upon application of a load.
close regulation may be a sales With this volts-per-hertz relationship,
advantage. Caterpillar generators the regulator reduces the voltage in
have a steady state regulation of proportion to speed when a large
0.5% from nominal voltage block of load is applied causing a
(constant load, constant temperature drop in engine speed. This reduction
and constant frequency). in voltage reduces the kW load
No Load (N.L.) to Full Load (F.L.) allowing the engine to recover to
voltage regulation is the measure of rated speed and frequency. Figure
a generator sets ability to return to 37 and Figure 38 shows a
rated voltage after the application comparison between the response of
of a load. Low variation is desirable a constant voltage regulator system
because voltage drop causes and a volts-per-hertz type. Volts-per-
increased current flow and heating hertz regulators are standard on
in electric motors which can reduce Caterpillar generators and available
their life. Low voltage can also as an option on some competitive
cause breakers to trip unnecessarily. generators.
All Caterpillar generators have 1%
N.L. to F.L. regulation.
Caterpillar has led the industry in
regulators with three-phase voltage
sensing. Most Caterpillar generators
are equipped to sense three-phase
voltage. Three-phase sensing
averages all three-voltage phases,
resulting in better regulation;
especially when the load is
Figure 37
unbalanced. The most significant
benefit is the ability to handle the
three-phase silicone controlled
rectifier (SCR) drives used in
systems such as un-interruptible
power supplies (UPS).
A key requirement of a generator
set is its ability to recover from load
transients. With a constant voltage
regulator, it is possible to overload
an engine during load applications to Figure 38
the point that it cannot recover

2008 Caterpillar
Page 48 All rights reserved.
Generator Systems Application and Installation Guide

A two-volts-per-hertz system With a solid-state AVR, the recovery


regulates in the same fashion but is quite rapid.
the regulation is twice as aggressive. Note: Steady-state tolerance is the
One significant characteristic of the acceptable recovery range for
V/Hz curve is a double knee terminal voltage.
frequency. This refers to the allowed
Figure 40 shows the results of
variation in frequency (usually
faster and slower response times
around 2-3 hertz) from the rated
of excitation and regulation systems
frequency before regulation occurs.
to a transient load. The voltage dip
This difference allows for minor
is greater for the slow response
variations in frequency without
system than for the fast response
changing the voltage unnecessarily.
system. The voltage also continues
Performance to follow the inherent regulation
Figure 39 illustrates the characteristic and consequently
relationship between the AVR and drops to a lower value than the
load application. It demonstrates faster system voltage.
that a transient condition without
an AVR (therefore, with constant
excitation) causes the terminal
voltage of the generator to decrease
to a lower voltage until it reaches
a steady state. This lower voltage
depends upon the generator
regulation, sometimes called
inherent regulation. For most
applications, this inherent regulation Figure 40
is unsatisfactory.
An inductive coil, such as a field
winding, will not allow current to
build up immediately. The rate of
buildup is determined by what is
called a time constant. The coil time
constant is measured in seconds and
is inductance (Henrys) divided by
resistance (ohms). Thus, a coil with
an inductance of 2.0 Henrys and a
Figure 39 resistance of 2 ohms would have a
time constant of 2.0 divided by 2.0
equals 1.0 seconds. So, 1.0 second
With an AVR producing a high is required to reach 63% of the final
excitation, the terminal voltage will current value of voltage divided by
recover its initial value or a value resistance. The current will reach
within the steady-state tolerance. 100% value in five time constants.

2008 Caterpillar
All rights reserved. Page 49
Application and Installation Guide Generator Systems

To continue the example, 100% independent of the generator output


current will be reached in 5 x 1.0, voltage. Therefore, the pilot exciter
or 5.0 seconds. sustains high current transient
Since the excitation system and loading, as well.
the generator have several inductive Controlling excitation with the
coils within them, their associated reactive load is one way of sharing
time constants will have an effect the reactive load between paralleled
on how fast the magnetic fields generators.
respond to a change in voltage. A broad manual voltage
Even though the AVR may react to adjustment range is required for
a change in output voltage almost some applications, particularly when
instantaneously, the exciter field, the operating the same generator at
exciter armature, the main field and 120/208 volts or 240/480 volts.
the main generator time constants Broad voltage adjustment can go
will prevent a corresponding as high as 20%.
instantaneous change in generator
Protective features that can be
terminal voltage. These time
added to a generator excitation
constants must be taken into
system are:
account with any transient
response time. Over/Under Voltage
The excitation voltage for the Sensing Loss
exciter field of a brushless generator Over-Excitation
is provided by the generator output.
Over-Frequency
For steady-state loads and most
transient loads, this power is Loss of Excitation
sufficient. However, generator Some of the features listed are
output voltage drops under transient redundant. A generator will never
loading. Voltage to the AVR drops, need all these features in a single
as well. If the voltage drop is severe, application. A small generator will
the reduction in voltage to the use very few of these features.
exciter field will cause the main
Generator Voltage Specifications
generator voltage to collapse or Note: The numbers represented by
fold-up. To avoid this, a booster
n in the specifications below will
arrangement, also called a series-
vary depending on the generator set
boost, is used for generators that
and application.
might be subjected to extreme
loading (e.g. short circuits). The Voltage regulation specifications
series-boost employs a current are met when the following occur:
transformer, which supplies voltage 1. Generator voltage accuracy
to the exciter field during high must be within plus or minus
current loading transients. Also, the n percent with a frequency
permanent magnet pilot exciter change of no more than plus
supplies current to the exciter field or minus n percent when

2008 Caterpillar
Page 50 All rights reserved.
Generator Systems Application and Installation Guide

the load varies between no unloaded phases is equal and


load and rated load. is averaged around the true
2. With constant load, generator voltage.
voltage must remain within True RMS: For 1-phase and
n percent at an ambient 3-phase sensing, true RMS
temperature range of n sensing is not affected by
degrees Celsius to n irregular waveforms.
degrees Celsius. Waveform tolerance is the
3. A constant load and ambient amount of non-sinusoidal
temperature generator voltage waveform that can be handled
drift must not exceed n by AVR sensing without loss
percent for an n hour of accuracy. Radio frequency
period. interference suppression may
be added to aid waveform
4. When the generator is started
tolerance.
cold, voltage must not vary
more than plus or minus n Frequency Sensing
percent for the first n Soft Regulation
minutes at constant load and Voltage and frequency dip
ambient temperature. determines the generator sets ability
5. Transient Performance to pick up large block loads. As the
Upon application or rejection frequency decreases, reducing the
of n load, generator voltage voltage reduces the kW load by the
must not vary more than n square of the voltage (or P = V2/R),
percent from the initial voltage enabling the engine speed to recover
and must recover to and stay faster. Reducing voltage with
within n percent of the frequency also allows the machine
initial voltage within n to operate at a reduced speed
seconds. without damage to the exciter or
Response time is the time required generator field. Voltage reduction
for the AVR to respond to a specific can be programmed on some
change in sensed voltage. An AVR regulators to reduce voltage faster
uses the following voltage sensing or slower.
functions. Hard Regulation
Single-Phase: If the load is When using constant volts-per-
unbalanced and the loaded hertz, the engine is loaded more and
phase is sensed, the unloaded will require more time to recover.
phase voltages will be high. If Induction motor flux density remains
the unloaded phase is sensed, constant. It is, therefore, possible to
the loaded phase voltage will control motor speed through engine
be low. speed control, with certain
limitations.
Three-Phase: The voltage
spread between loaded and

2008 Caterpillar
All rights reserved. Page 51
Application and Installation Guide Generator Systems

Type The Caterpillar Digital Voltage


The automatic voltage regulator, Regulator (CDVR) is a
VR3, is the analog version. It is microprocessor based voltage
standard in many small to medium regulator. The main purpose of a
sized generator sets and is the more digital voltage regulator is to
cost effective of the two types. It regulate the output voltage of a
can sense in three-phase and in generator that is used with an
single-phase in a self-excited set-up. engine generator set. Control power
It can be configured in a volts-per- for the Digital Voltage Regulator is
hertz regulating configuration that supplied from an external 24 DCV
provides superior engine speed source. The power stage of the
control and stability. In a VR3F or Digital Voltage Regulator can be
flat-top design, the volts-per-hertz supplied from a multi-pole, high
slope is twice as steep allowing for frequency, permanent magnet
added stability and control of generator (PMG), from the generator
overshoot. output (shunt excitation), or from
The Digital Voltage Regulator auxiliary windings that are included
(DVR) is the digital version of the on some generators. Connections to
Caterpillar voltage regulator. RMS the Digital Voltage Regulator are
sensing is standard on this package made through three multi-pin, plug
and gives it better capabilities. It is type connectors. The communication
typically used in medium to larger between the Digital Voltage
sized generator sets. It can provide Regulator and a service tool is
superior volts-per-hertz regulation accomplished using a CANBUS
because it can be programmed to a protocol.
specific application.

2008 Caterpillar
Page 52 All rights reserved.
LEBW4993-02 2008 Caterpillar Printed in U.S.A.
All rights reserved.

Potrebbero piacerti anche