LC12DAL Control For WALCD Series Load Banks
MC Manual Control Description
Dimensions
Description
The LC12DAL controller is a portable processor capable of controlling one or more resistive or reactive
load banks from a distance of up to 100m. Operating features include a four-line display with simple
step-by-step instructional prompts, display of load values such as kW, kVa, V, Hz, PF, Amps and load
time. Choice of operation includes manual and automatic load routines. The automatic loading feature has
loading routines with time duration and pause override function. Changes to a load routine such as load
size and time, is possible at any time during a load test from the pause function key. The controller
automatically tunes and corrects the load bank in the event of voltage or resistance fluctuation. The
controller also ensures that the load bank is fully protected against over voltage or frequency, preventing
the test to proceed. All functions are fully displayed, including warning messages, such as voltage
exceeded, frequency incorrectly set, emergency stop, load aborted and cooling failure.
The LC12DAL construction is made of solid aluminium extrusion with die cast corners, weatherproofed
and sealed to IP55. The handle can be rotated and locked in any position to suit the user. Connections
includes a 6 pin input connector, standard USB port for connection to a PC or Laptop, to obtain additional
on-line graphics of actual load tests. Additional features of the controller includes adjustment of all the
operational settings namely operating voltage, frequency, power factor, data capture printing intervals.
Test routines are held in memory for repeated use. Data captured includes all electrical values, such as
phase voltage, line to line voltage, phase currents, line currents, frequency, kW selected, kW achieved,
kVa, power factor and elapse time.
Safety features include load bank "System Diagnostics" to ensure that voltage and the operating current
do not exceed the load banks designed rating. The LC12DAL controller is also available in a panel
mounted version for test cell operations.
Operational Features
Technical Data
OPERATING VOLTAGE
15 Volts
INPUT CONNECTION
6 Pin Socket & Flexible Data Cable
OPERATING DISTANCE
Up To 100m
PC INTERFACE MONITORING
B Type USB
DISPLAY SCREEN
Backlit 75 x 25
OPERATING MODE SELECTION
Manual & Auto
POWER SELECTION
Input Voltage, Power Factor & Frequency
AUTO LOADING MEMORY
Store Up To Six Routines
LOAD STEPS IN AUTO
Up To 10 Per Routine
LOAD PROCESS TIME
Selectable from 1 To 600 Minutes Per Load Step
LOAD STEP RESOLUTION
1kW & 5kW Subject To Load Bank Model
FUNCTION DISPLAY
Number Of Load banks Connected
Fan Start
Fan Stop Activated
Cooling Fault
Emergency Stop
Manual Selection
Auto Selection
Load Menu Profile
Input Volts Exceeded
HZ Incorrectly Set
Load Bank Not Responding
Load Bank Diagnostics
DISPLAY AND PRINTOUT
Volts = Phase To Phase & Phase To Neutral
Amps Per Phase
HZ, kW, kVa, PF
DATA CAPTURE
Output To PC