1 RECOMMENDED SUPPLIER and MANUFACTURERS, PLACES OF

MANUFACTURE & TESTING

PLACE OF
PLACE OF
ITEM MANUFACTURER TESTING &
MANUFACTURE
INSPECTION
11kV Circuit Breakers ABB India
11kV Copper Busbar Metal gems India
11kV Current Transformers Excel Power Switchgear India
11kV Voltage Transformers Excel Power Switchgear India
11kV Switch Panels Excel Power Switchgear India
Protection Relays SEL
Meters SHARK 200
Anti-Condensation heaters
OPTOLINK Schneider VAMP
SENSOR Schneider VAMP
Arc flash protection Schneider VAMP 321
MCBs Schneider
Control and selector switches KRAUS & NAIMER
Interlock relay Sprecher+Schuh
Indication lamps Schneider ZB5AV
Push buttons Schneider XB5
Measuring disconnect terminal Weidmuller WTL 6/1/STB
Terminals of type Phoenix Contact UK2.5B
Cable trunking Critchley Betaduct
DIN Rail Weidmuller TS35
240/120VAC, 250VA Control
Legrand 442 65
transformer
Transformer lockout relay SEL
Bus zone lockout relay SEL
Test blocks SEL
37
2 TECHNICAL PARTICULARS AND GUARANTEES

2.1 BUSBARS
Required
Item Units
12 kV
1. Rated Normal Current A 2000
2. Rated current at Max. ambient temperature A 2000
3. Conductor Material Cu
4. Standard Applicable IS 1897
5. Single conductor Cross section mm2 1260
6. Insulation material
7. Fire Certification (IEC 60466, etc)
Section 5 Forms of Proposals and Appendices 1
2.2 CIRCUIT BREAKERS
Required Tendered
Item Units
12 kV 12 kV
1. ABB
INDIA
2. Country of Manufacture
3. Place of Testing INDIA
IEC 62271
4. Applicable Standards IEC62271,IEC60694, etc
5. number VD4 12.31
6. Type tested Yes/No Yes Yes
7. Type test Report, Ref No.
8. Rated Voltage kV 12 12
9. Rated Frequency Hz 50 50
o
Rated Normal Current at 20 C
- Line feeder circuit breaker A 1250 1250
10.
- Transformer circuit breaker A 1250 1250
- Bus section circuit breaker A 2000 2000
Rated Current at Max. ambient temperature
- Line feeder circuit breaker A 1250
11.
- Transformer circuit breaker A 1250
- Bus section circuit breaker A 2000
12. Rated Lightning Impulse Withstand kA 95 75
12. Rated 1 min Power Frequency Withstand kV 35 28
Rated short circuit breaking current (symmetrical,
14. kA 31 31.5
r.m.s)
Rated short circuit breaking current (asymmetrical,
15. kA 28 31.5
r.m.s)
16. Rated making current (peak) kA 75 80
17. Rated Duration of Short Circuit Current s 3 3
18. Rated cable charging breaking current A 25
19. Rated line charging breaking current A
20. Rated small inductive breaking current A 20
Voltage drop across terminals of one pole at rated 375
21. mV
current
22. Amplitude factor 1.5
23. First pole-to-clear fault 1.5 1.5
O-0.3 sec-CO-3 O-0.3s-CO-3
24. Rated operating sequence
min-CO min-CO
Min. time t" between two successful three phase auto
reclosures at full rated breaking current
25. min
(sequence O-0.3-C-t"-O-0.3-C)

Closing time Ms 45 to 80
26.
- tolerances ms
Dead time (max) ms
27.
- tolerances ms
Break time (max.) at full rated breaking current ms 50 to 75
28.
- tolerances ms
29. Make time (max.) ms
Section 5 Forms of Proposals and Appendices 2
- tolerances ms
Arcing time (max.) at full short circuit duty ms 15
30.
- tolerances ms
Life duration of main contacts (no load mechanical 10000
31. Operations
operations)
Number of switching operations at rated breaking
32. capacity before contact maintenance becomes No. Min 100 50
necessary
Auxiliary contacts:
- number NO/NC 6NO + 6NC
33.
- voltage rating V DC 110 110
- current rating A DC 10
Making coil
- Rated voltage V DC 110 110
34.
- min. operating voltage V 88 77
- Rated power each W 200
Trip coil
- Rated voltage V DC 110 110
35.
- min. operating voltage V 55 77
- Rated power each W 200
36. Motor Voltage V DC 110 110
37. Motor Power W 200
Max. temperature rise of contacts at rated normal 65
38. K
Current
39. Arc quenching medium Vacuum/GIS/SF6 Vacuum
40. Material of main contacts copper
Maximum Shock load imposed on floor or foundation
41. when opening under fault conditions (compression or N
tension)
Minimum Clearances in air
(a) Between phases mm 120 80
42. 120
(b) Phase to earth mm 120
(c) Across CB poles mm 120 80
43. Material of filter employed for the
absorption of the products of combustion
44. Method of controlling voltage
distribution between breaks
(capacitor, resistor etc.)
45. Weight of complete 3 pole breaker kg 110
46. Weight of heaviest part for shipment kg
Period the equipment has been in commercial
47. years >5
operation
Section 5 Forms of Proposals and Appendices 3
2.3 CURRENT TRANSFORMER
Required Tendered
Item Units
15 kV 15 kV
1. Manufacturer Excel

2. Type wound primary

3. Applicable Standards - IEC 60044-1 60044-1


4. Rated secondary current A 1 1
5. Rated lightning impulse withstand voltage (primary) kV 75 75
6. Rated Power Frequency withstand voltage (primary) kV 28 28
7. Rated short-time current Protection

cores (Transformer Diff):


- Rated Primary Current A As per list As per list
8. - Accuracy class Class 0.1PL 0.1PL
- Resistance of secondary winding at 75oC Ohms <3
- Rated Burden VA 25 15
Protection cores(OC & EF for feeders):
- Rated Primary Current A As per list As per list
- Accuracy class
Class 5P10 5P10
9.
- Resistance of secondary winding protection cores at
Ohms <3 <3
75oC
- Rated Burden VA 25 15
Protection cores(Bus Section):
- Rated Primary Current A 2000/1200 2000/1200
- Accuracy class
Class 5P10 5P10
10
- Resistance of secondary winding protection cores at
Ohms <3 <3
75oC
- Rated Burden VA Min 25 15
See scope of
11. Number of Cores No. works and
Drawings
12. Knee point e.m.f. of protection cores V Min 450
13. Knee point e.m.f. of busbar protection cores V Min 415
14. Insulation material for windings
15. Limits on exciting current A
16. Partial discharge pC < 50
Section 5 Forms of Proposals and Appendices 4
2.4 VOTLAGE TRANSFORMER COMPLETE WITH FUSE AND RESISTOR
Required Tendered
Item Units
15 kV 15 kV
1. Manufacturer Excel

2. Type Fixed
3. Applicable Standards - IEC 60044-2 60044-2
4. Method of transformation Inductive Inductive
5. System Voltage kV 15 12kV
6. Type of supply 3 phase 3 phase
7. Frequency Hz 50 50
8. Basic Insulation Level kV 75 75
9. Creepage distances mm
10. Transformation ratio
11. Class of accuracy 0.1 0.1
12. Class of insulation
See scope of
13. Number of secondaries and accuracy class works &
drawings
14. Thermal capacity of ground-fault detection winding A/h
15. Rated burden (total on all secondaries) VA
Acc. IEC
16. Partial discharge
60044-4
17. Height mm
18. Weight of single pole unit kg
19 Burden VA 25 25
Section 5 Forms of Proposals and Appendices 5
2.5 SWITCH PANELS
Required Tendered
Item Units
15 kV 15 kV
1. Manufacturer Excel
2. Type
rated voltage kV 12 12
2. Applicable Standards - IEC IEC 60694 IEC 60694
Impulse withstand voltage kV peak kV 75 75
Power frequency withstand voltage kV 28 28
4. Thickness Mm 3
5. Short time rating, 3 sec kA 31.5 31.5
6. Integral earthing switch for feeder and busbar Yes/No Yes Yes
7. Short circuit rating of earth switch 31.5
8. Making capacity of earth switch
Transducer and Local Energy Meter (Transformer)
9. - Manufacturer and model NEMO NEMO
- protocol DNP3 DNP3
Transducer and Local Meter
10. - Manufacturer and model NEMO NEMO
- protocol DNP3 DNP3
Anti Condensation heater
- Manufacturer APT
11. - Heater voltage 230
- Heater Output W 80
Is heater switch provided Yes Yes
Material CRCA
Surface Finish Semiglossy
Dimensions
12.
Length mm
Width mm
Height mm
13. Total Net Weight kg
Section 5 Forms of Proposals and Appendices 6