Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Conrad St.Pierre
Dupont Nameplate
Requirements of 2003 NEC
• Article 110.16 states ‘Flash protection is required when
examining, adjusting, servicing, or maintaining
energized equipment. The equipment shall be field
marked to warn qualified persons of potential electric
arc flash hazards’ ‘Flash protection is required when
examining, adjusting, servicing, or maintaining
energized equipment. The equipment shall be field
marked to warn qualified persons of potential electric
arc flash hazards’
• NEC is generally not retro-active, but for safety
reasons should apply to all to all electrically equipment.
The flash hazard analysis shall determine the 3 8+ to 25 cal/cm2 25 cal/cm2 Cotton underclothing plus
FR shirt, pants, overalls or equivalent
flash protection boundary and the personal
Cotton underclothing plus FR shirt, pants,
protective equipment that people within the arc 4 25+ to 40 cal/cm2 40 cal/cm2
plus double layer switching coat and pants
flash boundary must use.” Cotton underclothing plus FR shirt, pants,
5 40+ to 100 cal/cm2 100 cal/cm2
plus multi-layer switching suit or equivalent
1
Reality of Arc Flash Hazard
An arc flash can be Expensive
Arc current creates:
Recovery and rehabilitation costs can be – A brilliant flash of light
staggering – A loud noise
– Intense heat
• Cost for an incident involving one fatality – Fast moving pressure wave
and two injured employees has exceeded
$12 million. Products of arcing fault are:
• Another company’s expenses for three – Ionized gases
– Metal vapors
serious incidents in a three year period
– Molten metal droplets
have exceeded $875,000.
– Shrapnel
2
Results of Experiments
Video 2 • Best fit for arcing current: equations with terms of
• bolted fault current
• voltage
• gap between conductors
• open air or box
Arc Current
Getting from Incident Energy to PPE
LV Ia = 10 [K + 0.662 log(Ib) + 0.0966 V
+ 0.000526 G + 0.5588 log(Ib) V
• Utilizing PPE with Cal/cm2 values of – 0.00304 log(Ib) G]
1.2, 4, 8, 25, 40 the IEEE Equations MV Ia = 10 [0.00402 +0.983 log (Ibf)]
resulted in adequate levels of PPE in where:
95% of the arc-flash tests Ia = arcing current (kA)
K = – 0.153 for open configuration
• In 5% of the tests, the PPE chosen was or – 0.097 for box configuration
one level too low log(Ib) = log10 of sym RMS bolted fault current (kA)
Voltage = system voltage (kV)
G = distance between buses (mm)
3
Human
Man Conductor
without Causing
PPE Arc
Protection
12.0 175
Spreadsheet
Incident Energy (Cal/cm^2)
13.8-kV
150
Incident Energy (Cal/cm^2)
10.0
Ungded, Res Gnding, Other Imp gnded K2 = 0 4.16-kV
2.4-kV 125
34.5-kV
Low Imp -0.113 0.0 Bolt Fault Current in kA Bolted Fault Current in kA
Solid -0.113 -0.113 Time = 0.1 sec, Working distance = 24 inches, Arc gap per IEEE 1584 for switchgea, Grounded
4
Incident Energy verses Voltage and Test Data Incident Energy verses Voltage and Test Data
60 300
50 250
IEEE Lee's Method
IEEE Lee's Method
40 200
Cal/cm2
Cal/cm 2
0 0
0 10 20 30 40 50 60 70 80 0 10 20 30 40 50 60
Bolted kA Bolted kA
Comparison of IEEE Equations to 600 Volt Open Air Arc Test Data Comparison of IEEE Equations to 4160 Volt Open Air Arc Test Data
IEEE 1584 Eq, based on 24 inch to subject, 1.25 Inch Arc Gap, 1.0 sec IEEE 1584 Eq, based on 24 inch to subject, 4.0 Inch Arc Gap, 1.0 sec
300
200
IEEE 1584 Equations
Arc Pressure
Video 3
• In 1987 Ralph Lee presented an IEEE paper
on Arc Pressure
5
Limiting Flash Hazard Limiting Flash Hazard
1. Low voltage remote trip and close 5. On double ended load centers with normally
2. Use a remote or longer operating arms when closed tie, open an incoming breaker or th
racking in or opening/closing breakers tie breaker
3. Place a shield between the technician and the 6. Determine if smaller fuses can be used
device being placed in service or racked in
7. Change relay settings when working on
4. Review protective devices to see if they can equipment
be lowered in time and pick-up.
500 250E
500 100% Fault
300 1000 kVA 300
Location kA Time Cal/
1600A
Arc Heat 100
480V
100 (sec) Cm^2
600A
.05 .05
.03 .03
.01 .01
1 3 5 10 3 5 100 3 5 1000 3 5
6
Slide the tab to
run Short
Circuit.
W A R N IN G
B u s E le c tr ic a l S h o c k a n d F la s h H a z a rd
A p p r o p r ia t e P P E R e q u ir e d
W h e n L iv e P a r t s a r e E x p o s e d (R e s t r ic te d S h o c k H a z a r d D i s t a n c e = 2 6 i n c h )
V o lt s 480 0 M a x S h o rt C i r c u it k A 5 .0
P P E B a s e d o n 1 7 .9 in c h W o r k in g D i s t a n c e
A r c F la s h b o u n d a r y , P P E re q u i re d w i th in 1 3 . 2 i n c h e s )
C lo t h in g F ace
Level
0 X
S h ie ld
G lo v e Eye
C la s s
0 X
P r o te c ti o n
In s u l a te d H a ir /B e a rd N e t
T o o ls X N o t A llo w e d X
R eq u ire d X A r c F la s h b o u n d a r y a t e n e r g y < 1 . 2 c a l/ c m ^ 2
N o t R e q u ir e d
P r o je c t: T 1 2 3 E q u ip m e n t N a m e : 0 1