PMA 600 H

Intumescent Waterborne Basecoat for structural steelwork.


Indoors.

Fire resistance rating: up to 90 minutes. Application instruction have been read


Optimised for 1 hour before starting of work.
Different basecoats are not applied on
Renitherm PMA 600 H is a white thin film waterborne

the same section of steel.
intumescent coating for the fire protection of internal Equipment is clean and free from
and semi exposed structural steelwork contaminants or dried material.
Wet film gauges are available for use.
Application
The following instructions are for on-site application Surface Preparation
only. Seek our advice for off-site application. Renitherm PMA 600 H should be applied onto a
clean, undamaged, dry and primed steel surface only.
Ensure that: Primer is compatible with Renitherm Following Primers are not compatible with Renitherm
PMA 600 H and has been applied PMA 600 H: Chlorinated rubbers, Bitumen, Thermo-
correctly. plastic Primers. Contact AUDAX for compatibility
Overcoating time for the Primer has not of Primer if you intend to use different Primer like
been exceeded. Renitherm Primers.
All damage to the Primer has been
repaired and re-primed.
Product Data Renitherm PMA 600 H
Site and weather conditions are within
the specification. Specific Gravity 1.35
Renitherm PMA 600 H is stored Colour white
correctly. Volume Solids 72 % 2 % (ISO 3233:1998)
Surface is dry, clean and free from
VOC 15 g/litre
contamination.
Theoretical coverage: 1.38 ltr/m2 at 1.0 mm DFT
Correct spray equipment is used.
Conditions during application Thickness Requirements
Renitherm PMA 600 H is recommended for use and During the application, measure the wet film thickness
application on dry protected structural steel only. If the frequently with the WFT gauge provided to ensure the
basecoat is allowed to get wet, it is likely to be dama- correct thickness is being applied. To use the gauge,
ged. Blistering and wrinkling may occur. Renitherm insert the teeth into the wet basecoat. The last tooth
PMA 600 H should only be applied when the air and to be coated indicates the wet film thickness achieved.
steel temperatures are above 5 C. Relative humidity In the event of over or under applications, adjustments
should be below 80 % for successful application. to the loading rates of subsequent coats will be
Steel surface temperature should be a minimum of required.
2 C above the dew point. Ensure the steel is dry and
free from contact with rain or condensation during the Drying Times
application and drying of Renitherm PMA 600 H. Drying of Renitherm PMA 600 H is depending upon a
number of factors like
Application Methods temperature
Renitherm PMA 600 H is supplied ready for use and air Movement
must not be thinned but should be thoroughly mechani- humidity
cally stirred prior to use. method of Application
thickness of coating
Airless: Renitherm PMA 600 H may be applied to
Spraying: a maximum wet film thickness (WFT) of High humidity and low air movement or low steel
1.2 mm in a single spray coat comprising temperatures can result in condensation on the steel-
of several passes. Achieving of maximum work causing prolonged drying times and possibly
loadings will depend on site conditions. poor basecoat adhesio.
Build up thickness to achieve loading
required in several quick passes. It may Overcoating Times in Hours
be possible to apply two coats of Reni- Indication of recoat or topsealing times taking into
therm PMA 600 H in one day particularly account loading areas and application methods are
if the atmospheric temperature is above given below:
20 C and relative humidity below 70 %.
However before doing this, ensure that Hours per application (0.3 mm WFT) thin coat.
previously applied coat is dry, particularly Hours per application (0.6 mm WFT) medium coat.
in the web/flange junctions. Hours per application (1.2 mm WFT) thick coat.

Airless spray equipment is recommended and should Brushing or rolling adds about 20 %
match these guidelines: to drying time, compared to spraying.
Drying are doubled at 5 C or at over
Data
75 % relative humidity.
Tip size 1925 Final drying time before topsealing is a
Fan width 2040 minimum of 16 hours.
These figures are based on constant
Operating Pressure 25003000 psi
conditions, fluctuations up or down will
Hose diameter 10 mm (3/8) internal diameter
give variations to the drying time. If
Hose length max. 60 metres overnight condensation causes wetting
a further full drying period should be
Brush/Roller For brush application use a laying on allowed.
Application: technique to avoid heavy brush marking.
Maximum wet film per coat when using
a brush or roller is 1.0 mm. A short piled
roller will produce a light textured finish.
10 C 20 C 30 C
RH Spray Still Air Air Flow Still Air Air Flow Still Air Air Flow
Hrs Hrs Hrs Hrs Hrs Hrs
Thin 4 1/2 2 1/4 3 3/4 1 1/2 2 1/4 1 1/2
30 % Medium 6 1/4 3 3/4 5 1/4 3 4 1/2 2 1/4
Thick 9 4 1/2 6 3 3/4 6 3
Thin 5 3 4 1/2 2 3 1 1/2
50 % Medium 9 4 1/2 6 1/4 4 6 3
Thick 12 6 9 5 1 1/2 3 1/2
Thin 11 6 9 5 6 3
70 % Medium 15 9 15 7 12 5
Thick 18 12 18 9 15 6

Final thickness check Storage


Take dry film thickness (DFT) readings as soon as Renitherm PMA 600 H should be stored between
coating is sufficiently hard to allow reading to be made +5 C and +30 C and protected from direct sunshine.
without indenting surface. DFTs may be taken using Do not store below +5 C. The shelf life is 12 months
equipment such as an electronic electromagnetic type from date of manufacture, subject to re-inspection
recorder. Ensure that the DFT of the primer is deduc- thereafter. Containers should remain unopened until
ted from the reading of the intumescent basecoat. Do needed. Shelf life may be reduced at higher storage
not apply topseal until the readings are in accordance temperatures.
with the specified thicknesses.

Application of topseal
Once DFTs have been achieved as specified,
Renitherm TC topseal can be applied. Make sure
that Renitherm PMA 600 H is completely dry before
applying topseal. AUDAX fully complies with the
requirements of EN ISO 9001
standard. This certification is
Maintenance one more proof for Renitherms
Damaged areas should be abraded back to a sound quality, reliability and safety.

surface. The surface should then be clean and dry


before re-applying. Renitherm Filler may be used for
repairing scratches and chips. Once repaired, topseal
should be re-applied.
November 2013, Rev. 1.1