Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
This write-up studies the system protection of the Nigerian Power System. In
this study, the various types of faults that often occur within the Nations power
system were discussed along with the protective measures and devices for guarding
against and/or curbing them. The study was particularly narrowed down to Nsukka
town, and the various faults peculiar to the town studied with a view to finding the
major causes of fault within the locality. Fault records which include the daily fault
undertaking and the yearly fault summary of the same utility company were analysed
and conclusions drawn to the major causes of fault in the locality. The economic
aspect of the various protection measures against the fault types were considered as
well; this was found to be very insignificant when compared to life and property.
1
INTRODUTION
The inordinate increase in the demand for electrical energy is instrumental to the
incessant power outage often witnessed within the nations power system. Hence is
the need for good power system protection which can be described as the automatic
of the system as well as limiting/ avoiding any possible damage to the elements due to
Power system protection being concerned with the total protection of a system
from fault(s), therefore curtails the use of sensitive devices such as relays, fuses,
switchgears etc. to bring about system protection. For adequate system protection
against fault, a good knowledge of the causes of the various faults as well as the
currents resulting from them is needed, for a steady and uninterrupted power supply.
The system protection of an area depends to a large extent on the faults peculiar to
the area. In other words, whatever protection measures that must be taken will
definitely depend on the predictable and most frequently occurring faults of the area.
For instance, Nsukka town located in Enugu State of Nigeria, lies within the rain
forest zone of the country were a reasonably high degree of rain fall is experienced for
the greater part of the year. This then implies that the majority of faults which occur
2
General Consideration for Protection
Fault occurrence in a system often have expensive cost implication on the side
of both the utility company and the consumer; hence the maintenance of an
without a good knowledge of the causes of the various fault that occur within the
system.
the lots of illegal connections they make. Most often these illegal connection causes
which results to total breakdown of the power machine. Another issue to consider is
the effect of climatic changes on the locality being supplied as well as the generating
and the transmission environment. Climatic factors such as lighting and thunderstorm
can cause serious flash-over and mechanical damages, thus resulting in dangerous
fault currents which can endanger the consumer and his apparatus/gadgets. Tropical
the dams and reservoirs used in power generation; in addition to this, periods of high
and low tide also affect the power generated and transmitted. [2]
can be achieved if the protection scheme operates in such a way as to prevent some
3
iii Total damage/condemnation of any machine/plant in the fault path
isolate as fast as possible, any part of the power system where a fault has occurred so
that protective devices do not operate unnecessarily. Though not enough, alternative
power supply outlets from power sources to load centers are also indispensable in
METHODS OF PROTECTION
should be able to pick out and cause only the faulty element to be disconnected. By
this reasoning, the protection methods applied to a system can indirectly be referred to
as methods of discrimination.
others are relatively protected. Absolute protection applies to unit systems in which
case system protection applies to only the zone or element intended to be protected,
while relative protection applies to non-unit systems where several relays and/or
associated equipment are used to provide protection covering more than one zone. [ ]
Details of these two are deibrately omitted since they can be found elsewhere in
published literature. [ ]
Power system fault is any condition which interferes with the normal flow of
current and hence brings about the electrical failure of the primary equipment of the
4
power system. Primary equipment can be described as the system equipment which
FAULT CLASSIFICATION.
balance is not lost irrespective of their occurrence in the system while the
unsymmetrical faults are those conditions which result to total system imbalance. [ ]
Power system faults can as well be categorized into two main types depending
Details of these two are deibrately omitted since they can be found elsewhere in
published literature. [ ]
Protection measures are the protection practices carried out in a power system
to forestall the severity of a fault on the system; whereas fault severity is a measure of
the degree of the disturbance as well as damage caused on the system by the fault
consideration the magnitude of the fault current as well as its duration. In other to
make a good assessment of the magnitude of the fault current, the following need be
considered seriously: Power system configuration, Fault type and The earthing system
employed.
5
given period of time. Due to changes in the magnitude and distribution of fault
current, system configuration is liable to change during the course of the fault. Hence
much as possible intimes of fault; by setting the system tripping relays to a high
degree of accuracy such that faults can be cleared without altering the healthy state of
Fault Type: System fault magnitude and its distribution is greatly determined by the
type of fault and its position on the power system; for example short-circuit faults are
often much more severe than open-circuit faults. The position of a fault determines its
has a greater distribution than one occurring along a single distribution line (e.g.
single phase-to-earth fault). The simultaneous occurrence of one or more fault types
Earthing System Employed: The power system earthing arrangement has great
influence on the system faults which involve the flow of earth currents e.g. the single
or two-phase-to-earth faults. Power system may be single- or multi- point earthed and
such systems may be earthed solidly or through an impedance which is used to limit
The wide range of possible system fault conditions as well as the relevant
protection practices pertinent to each condition, gives rise to the range of protection
system protection of an area depends to a large extent on the faults peculiar to the
6
area. In other words, whatever protection measures that must be taken will definitely
depend on the predictable and most frequently occurring faults of the area.
As already mentioned, since the town lies in the rain forest zone of the
country, the majority of faults which occur in this area are consequences of weather
condition. Such faults often occur as a result of trees or branches of a tree falling on
power (HT or LT) lines, thereby causing either the short-circuited phase fault(s) or the
voltage/fault current on power lines (over head lines), thus resulting in flashovers to
the earth. Heavy rainfall at times causes an electric pole to fall; this may have a
the wind often cause short-circuited phase faults by jamming or marrying two or
three phases together. Bush turning, often during the dry season, can result to fault
when a wooden electric pole is consumed by fire. Other causes of fault experienced in
Nsukka town can be termed constructional causes, such are: Termites eating up
wooden poles, vehicles hitting (by accident) electric poles and the action of vandals
on the properties of the utility company. Snakes even cause LT lines to bridge. [12]
There are also in-station faults which occur in the switchyard. These faults,
though rare, are said to occur when power equipment, such as the transformer,
develops a fault. Such faults include: transformer differential fault, buchholz fault,
phases such that the normal input to output power ratio is altered; Buchholz fault
occurs when moisture develops within the transformer oil; this fault is taken care of
7
by an action known as bleeding the transformer. High winding temperature is said to
occur when the transformer oil becomes unusually heated up; this fault is taken care
of by reducing the loads on the transformer. Each of the station faults has a relay that
monitors it and sensitizes the switchgear for a trip-action when the need arises.
Of these, faults due to lightning strokes on overhead lines are more rampant in
Nsukka town. Faults due to lightning can be flashovers between a phase and the earth
(Earth fault) or between two or more phases (short-circuit phase fault). Earthfault is a
condition when the line potential is neutralized as a result of the line getting in contact
with the earth; this is the fault described by the laymen as phase failure [12]; while
short-circuit phase fault is condition where by two or more phases get in contact, thus
resulting to over-current flowing through one of the phases; this often has the effect of
melting the line and a resultant open circuiting when the line melts and opens. The
cut; this often happens when the fuse (HRC) in the distribution/feeder pillar fails to
open on the occurrence of an overcurrent. Up-riser is the cable carrying power form
Prevention they said is better than cure. This statement applies in virtually all
area of human endeavor including Nsukka power system. For this reason, a variety of
protection measures are carried out to avert the factors and possible conditions which
The possible causes of faults in Nsukka power system and the protection
measures often carried out to prevent them are shown in table 1.1.
8
Table 1.1: Some causes of faults in Nsukka power system and protection measures against
them.
Causes of fault Protection measures
In the Nsukka power system, the protective devices used are generally
classified into two viz: Outdoor and Indoor protection devices. The indoor protection
devices are those situated inside the control room and they include relays,
switchgears/breakers and fire extinguishers for use against any fire outbreak, as well
as sand for safely absorbing any oil spillage; while the outdoor protection devices
include all protection devices in the switchyard, outside the control room, as well as
residential houses.
Protection devices outside the control room but within the switchyard include:
protection devices of a substation include: the J and P (Johnson and Philip) fuse, HRC
9
(high rupture capacity) fuse, cross arm/separations, isolators, surge arresters and line
straps/stay wires, while that for residential distribution board is the cut-out fuse.
to the system engineer for predicting the system performance, and thus be able to
make adequate provision for effective protection measures. It is for this reason that
undertaking since there is no independent power station in the locality. Hence the
fault data collected and being used for this work is from the PHCN Nsukka
undertaking.
Appendix III shows a one month daily fault report to the PHCN Nsukka
undertaking station. Fault reports are made on a daily basis by the customers of the
utility company who can best be described as laymen in terms of language used in
making the report; while the actual description of the fault, 3rd column is made by the
The utility company also keeps a monthly record of the summary of faults
Surge arrester failure, Earth faults, Short Circuit faults, Open Circuit faults and
Unclassified faults.
functions to intercept any overcurrent due to lightning stroke on the HT lines, from
10
Earthfaults:
This results when the potential of a phase is neutralised as a result of the phase being
in contact, either physically or by induction (as flashover to earth), with the earth.
Short-circuit faults:
When two or more phases get in contact, a resultant overcurrent flows through one of
Open-circuit faults:
Open circuit fault occurs when a conduction path fails. It may be a single-phase, two-
phase, or three-phase path failure; but the most rampant is the single-phase open-
circuit fault.
Unclassified faults:
This is the name given to faults occuring as a result of a failure in the operation of any
Appendix IV shows the fault summary report for the year 2006.
Methods of Analysis
Since a fault results to the interruption of power flow, which most often is
expensive and at times embarrasses the customer in terms of delay in his work or
business venture, such that he lodges a report with the utility company, it is the
assumption of the company that about 90% of the total faults that occur in an area of
There are several methods which can be used in the analysis of fault data, but
in this research work with Nsukka town as case study, the method of analysis
employed is the fault tree method. A detailed description of fault tree method is
11
Predicted Analysis
Oral discussion with some members of staff of the PHCN Nsukka undertaking
reveals that fault occurrence in Nsukka town is said to be seasonal, because the
greatest number of fault reports are always made during the rainy season. Hence one
can easily conclude that the most rampant faults peculiar to Nsukka town are
Analysis Proper
The fault tree method has a lot of basic concepts, some which are briefly
explained to aid in the easy understanding of the analysis. The entire analysis using
the fault tree method is aimed at finding out all the possible causes of an undesirable
event (fault) which can best be described as the top event of the analysis.
safety and availability, to the catastrophic events which can be very costly, in terms of
life and economy. In order to find the undesirable event, there is always the need to
make a preliminary risk analysis. This is so because if the event is too general, the
analysis tends to be unrealistic due to the complex nature of such an event, but if the
event is too specific, the analysis may as well fail to identify the important element(s)
of the system. Appendix V shows some of the most commonly used fault tree gate
Figure: 4.1 shows the fault tree diagram for Surge arrester failure,
Figure 4.3 shows the fault tree diagrams for Short Circuit faults,
Figure 4.4 shows the fault tree diagram for Open Circuit faults.
12
JP fuse
cut
13
Earthfault
Phase-to-earth
connection
Phase-to-ground
Solid
earthed
system
Lightning
flashover to
earth
Phase-to-neutral
Phase-to-Phase
Wet tree/ short-circuit and
branch on consequential
power line wire cut
Wind Tree/tree
jamming branch
phase and bridging phase
neutral and neutral
together together
14
HRC fuse/Upriser
cuts
Phase-to-
phase short-
circuit
Overloading a
phase Phase
imbalance within
the transformer
Tree/branch
bridging two Electromagnetic
or more lines attraction
15
Wire bridging/twisting
Phase-to-phase Phase-to-neutral
bridging bridging
Wind
Tree/branch
causing wire
Pole jamming two or
to jam/bridge
fall/collapse more phases
Snakes Electromagnetic together
attraction
Tree/branch
Wind causing jamming two or
wire to more phases
jam/bridge together
From the fault tree diagrams of the various fault classifications, it can easily be
deduced that the basic causes of faults in Nsukka town are rooted to the atmospheric
16
CONCLUSIONS
required. Simple back-up protections which are often inherent in the main protection
are required for high reliability. Fuses are often used more than switchgears which
operate are in general less serious than those of transmission and generation systems.
of supply to the individual consumers who are customers of the utility company;
hence is the need for discriminative protection, without which it will be impossible to
The Nsukka power system, a distribution system, has the primary function of
ensuring steady power supply to its customers (inhabitants of Nsukka locality). This
protection measures such as tree cutting/trimming, use of surge arresters, use of stay
From the fault analysis of chapter 4, it is seen that the greatest problem facing
the Nsukka power system is that of faults due to inclement weather conditions. These
faults can either be the severe short-circuited phase faults, open-circuited phase faults
or a combination of both.
Finally, the cost of protection can never be overestimated when one puts into
consideration the life of the working personnel; hence the security to life first, and
equipment, underscores the absolute need for the best protection ever possible.
17
REFERENCES:
1. D.O. Uke, A comprehensive study of power system communication, B.
Eng. Project research paper, UNN, 2001.
2. H. Ibrahim, The impact of global climate change on energy
development, keynote Address at the International workshop
organized by NEPA, 1994.
3. T.C. Madueme, Electric power principles, EE331 lecture notes, UNN,
1999.
4. The Electricity Council, Power System Protection. vol.1, London:
McDonald, 1969.
5. C.A. Gross, Power System Analysis. New York: John Wiley & Sons, 1979.
6. British Standard Specification for Electrical protective relays (B.S.
142:1966.)
7. A.R. Van and C. Warrington, Protective Relays, their theory and Practice.
Chapman and Hall.
8. Ryder and Rushton, et al, A Moving coil relay applied to modern systems
of protection, proc. I.E.E., 1950.
9. GEC Measurements publication, R-5404, St. Leonards work, Stafford
ST174LX, England.
10. B.M. Weedy, Electric Power Systems.2nd Edition, London: John Wiley and
Sons Ltd., 1972.
11. D.J. Cole, Use of LV and HV Communication Protection Relays on
offshore platforms, I.E.E., Power Engineering Journal, vol.13,
No.5, pp 241-250, Oct. 1999.
12. Oral Interview with some members of staff of PHCN Nsukka undertaking.
13. T.C. Madueme, Switchgear and High voltage Engineering, EE 533
lecture notes, UNN, 2001.
14. E.J. Hanley and H. Kumamoto, Reliability Engineering and Risk
Assessment. Prentice Hall co. 1981.
15. D.F. Haasl, Advanced concepts in fault tree Analysis, System safety
Symposium, Seattle.
16. A. Villemeur, Reliability, Availability, Maintainability, and Safety
assessment. vol.1, New York: John Wiley and Sons, 1992.
18
17. T.C. Madueme, Lightning Activity on power outage data in the Nsukka
area of Anambra state,
18. Jiyoda Electrical Associates, Fault Analysis and Solutions of the Enugu
district, 1995.
19. G.O. Onodu, NEPA in-service training lecture notes, 2004.
19