Concrete Tunnel Design Based on AASHTO-17th & ACI 318-14
INPUT DATA & DESIGN SUMMARY
CONCRETE STRENGTH fc' = 5 ksi
REBAR YIELD STRESS fy = 60 ksi

TUNNEL DIMENSIONS L= 32 ft, (AASHTO Fig 2.5)


H= 16 ft, (AASHTO Fig 2.5)
C= 9.9 ft
S= 16 in
D= 60 in
t= 20 in
REINFORCING (As)
2 layers # 9 @ 8 in o.c. (curvered)
Concrete Cover = 3 in, (AASHTO 8.22.1)
FACTORED SOIL PRESSURE (SD level, including surcharge & seismic ground shaking)
Pt = 1760 psf Pb = Pt + Wt = 2671 psf [THE DESIGN IS ADEQUATE.]
P1 = 720 ft-pcf, (psf) P2 = 1820 ft-pcf, (psf)

ANALYSIS
DETERMINE TUNNEL FORCES BY FINITE ELEMENT METHOD
Point X (ft) Y (ft) Pu (k) Mu (ft-k) Vu (k)
0 0.00 0.00 24.97 124.44 0.00
1 3.40 0.22 25.83 116.28 7.17
2 6.73 0.87 27.51 91.87 11.67
3 9.96 1.94 29.95 52.18 15.69
4 13.03 3.41 33.08 -1.21 19.07
5 15.89 5.26 40.68 -66.10 5.66
6 17.29 7.98 41.81 -83.43 3.82
7 18.23 10.89 42.16 -95.13 1.40
8 18.68 13.92 41.52 -99.43 -1.32
9 18.63 16.98 40.02 -95.39 -4.02
10 18.09 20.00 37.82 -83.08 -6.46
11 17.06 22.88 34.98 -63.29 -8.41
12 15.57 25.56 31.65 -37.55 -9.61
13 13.67 27.96 28.09 -8.14 -9.87
14 11.40 30.01 24.62 22.10 -9.12 Rt = 18.72
15 8.83 31.68 21.60 50.02 -7.37 Rb = 26.62
16 6.02 32.89 19.37 72.60 -4.79 qt = 121.95
17 3.05 33.64 18.18 87.28 -1.66 qb = 36.63
18 0.00 33.89 18.18 92.37 0.00

CHECK AXIAL & FLEXURE CAPACITY


rProvD = 0.0076053 < rMAX = 0.0400 (tension face only, ACI 318-14 7.3.3 or R21.2.2)
> rMIN = 0.0008 (tension face only, ACI 318-14 9.6.1.2, 9.6.1.3 or Table 11.6.1)
[Satisfactory]

700.0

600.0

500.0

400.0
500.0
AT AXIAL LOAD ONLY
400.0
AT MAXIMUM LOAD
f Pn (k) 300.0 AT MIDDLE
AT e t = 0.002
200.0 AT BALANCED
AT e t = 0.005
100.0
AT FLEXURE ONLY
0.0 (Note: For middle reforcing the max fMn is at c
0.0 50.0 100.0 150.0 200.0 250.0 equal to 0.5 t /

f Mn (ft-k) [Satisfactory]

CHECK SHEAR CAPACITY (ACI 318-14 9.6.3.1)

fV n 2f bd '
fc = 20.92 kips / ft > Vu, max = 19.07 kips / ft [Satisfactory]
PAGE :
DESIGN BY :
REVIEW BY :

THE DESIGN IS ADEQUATE.]

ft, (top circle radius)


ft, (bottom circle radius)
deg, (between 5 & 18)
deg, (between 0 & 5)

f Pn f Mn
617.4 0.0
617.4 17.2
377.3 126.1
137.2 184.6
130.2 186.6
54.6 221.6
0.0 105.0
ddle reforcing the max fMn is at c
equal to 0.5 t / b1, not at balanced condition.)