Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
FIRE PUMP
G
Power Plant
Cable (new)
TRFP
Transformer BGENFP
13.8kV-6.9kV Backup
(new) G Generator
(new)
Cable (new)
TSFP
(new)
Fire Pump
Controller
FPC (new)
Cable (new)
Fire Pump
GM9900
(existing)
FLC 47.7A
Transformer 1.25 x 3 x IFLC x V
Transformer (1.25)(1.732)(47.7)(6900)
Transformer 712.6kVA
Primary CT size:
(transformersize) 2,000,000
IFL / Pr imary 83.67A
3(Pr imaryVoltage) 3(13800)
(150% x 83.67A)=125.5A, CT Ratio= 100:5
25VA (burden designation B-1)
Relaying ANSI 10C100 (class C), BIL rating 95kV
LRC 320A
6.9 5
P.U. Current setting (1.15)(320)( )( ) 9.2 In
13.8 100
P.U Current (9.2)(100 / 5) 184A
t 0.1 0.2
TD 1.28
3.922 3.922
0.0982 0.0982
2 2
I 1004
1 1
IP Pump 184
Chapter 8-Fire Page 368
8.2.5 Standby Generator Protection Settings Calculation
(Generatorsize) 3,500,000
IFL 292.85A
3(Pr imaryVoltage) 3(6900)
Primary CT size:
(150% x 292.85A)=440A, CT Ratio= 500:5
25VA (burden designation B-1)
Relaying ANSI 10C100 (class C), BIL rating 95kV
The highest fault at 13.8kV bus is 23,360A and with this worst case
fault current, the tripping time of the protective relay is
3.922
t 2
0.0982 2 0.126 second
23360 1
184
A
ISC t
23360 0.326
93.271mm2
143 143
IAmpacityRe q 1.25(IFLSecTrans)
IAmpacityRe q 1.25 x (83.67)x(13800/6900) 209.175A
IAmpacityRe q 1.25(IFLGen)
IAmpacityRe q 1.25 x (292.85) 366.07A/2 183A
For Motor Branch Circuit from Transfer Switch (ATS to Fire pump
panel and Fire pump panel to motor) (CABLE No.4):
IAmpacityRe q 1.25(IFLMotor)
IAmpacityRe q 1.25 x (47.7) 59.63A
From Table 8.4,
use 35m 3 x 1C-50mm2 copper XLPE 12/20kV aluminum shielded
PE (Fire resistant with 3-hour circuit integrity according to IEC
60331) using EMT conduit.
Z 0.1792 j0.1215419
Zcable1 0.00940978 j0.0063821 pu
Zbase 19.0440
Z0 Z0perkm Dis tan ce 0.8291 j0.6850 / km0.8km
0.66328 j0.548
0.66328 j0.548
Z0pu 0.034828 j0.028775 pu
19.044
Transformer Impedance
%IZ=6% at 2MVA base, X/R=6.8
S 10
Z Z2MVAbase BASE 0.06 0.3 pu
S Trans 2
X
R Z x cos tan-1 0.3 cos (tan-1(6.8)) 0.04364 p.u
R
X
X Z x sin tan- 1 0.3 sin (tan- 1(6.8)) 0.2968 p.u
R
ZTrans(1,2,0) 0.04364 j0.2968 pu
Generator Impedance
Typical values for a 4MVA synchronous generator are
X1=0.15 pu, X/R=27.8207
X2=0.15 pu, X/R=27.8207
X0=0.15 pu, X/R=27.8207
At 4MVA base
10
@ 10MVAbase X2 @ 10MVAbase X0 @ 10MVAbase0.15
" " "
X1 0.357 pu
4
0.357
R 0.012832 pu
27.8207
~ 1 pu
Power Plant
Equivalent Fault ZPP (0.000739 j0.017982) p u
Impedance
Cable 1
ZCable1 (0.00940978 j0.0063821) p u
Cable 2+Cable 4
ZCable 2 4 (0.004234 j0.001873) p u
Starting-Voltage Drop
1
VDFirePumpMotor 1 ZMotor
Z TOTAL
VDFirePumpMotor 1
1
0.387907 j2.586048
0.445929 j2.909085
I x1.15
VDFirePumpMotor FL ZCable1 ZTrans ZCable 2 4
IBase
VDFirePumpMotor
47.7x1.15 Z
Cable 1 Z Trans ZCable 2 4
836.73552
VDFirePumpMotor
47.7x1.15 0.310386 0.020348pu
836.73552
%VDFirePumpMotor 2.0348%
Gen
Cable 2+Cable4
Starting-Voltage Drop
At 3.5MVA, the voltage drop during starting is calcualted below.
1
VDFirePumpMotor 1 ZMotor
Z TOTAL
VDFirePumpMotor 1
1
0.387907 j2.586048
0.40782 j3.015921
I x1.15
VDFirePumpMotor FL ZCable 2 4
IBase
47.7x1.15 Z
VDFirePumpMotor Cable 2 4
836.73552
VDFirePumpMotor
47.7x1.15 0.004629 0.000303pu
836.73552
%VDFirePumpMotor 0.03%
~ 1 pu
~ 1 pu
Power Plant
0.000739+j0.017982
Equivalent Fault
Impedance
Cable 1
0.009409+j0.006382
Fault Point 1
Transformer
Fault Point 2 0.04364+j0.2968
Cable 2
Fault Point 3
0.004234+j0.001873
Chapter 8-Fire
Cable 4 Pump Page 381
Fault Point 4
0.387907+j2.58604
Fire Pump
Motor
Figure 8.8 Positive Sequence Diagram for Normal Power
Mode
BUS1
0.000739+j0.017982
Reference
ZCable1,ZERO=0.034828+j0.028775
0.009409+j0.006382
Z TR,ZERO=0.04364+j0.2968
0.04364+j0.2968
Reference
0.004234+j0.001873
ZCable2,ZERO=0.0008707+j0.000719
0.387907+j2.58604
Vfault 1
I3faultpu 37.888 pu
Z1 0.010148 j0.024364
3Vfault 3
I3faultpu 27.187933 pu
Z0 Z1 Z2 0.05568056 j0.0952642
3.922
t 0.0982 1.28 0.127 second
2
11374
184 1
V 1
I3faultpu fault 3.0709 pu
Z1 0.05378878 + j0.3211641
3.922
t 0.0982 1.28 0.23 second
2
1284.77
184 1
3Vfault 3
I3faultpu 3.1538 pu
Z0 Z1 Z2 0.15121756 j0.9391282
3.922
t 0.09821.28 0.2 second
2
1524
184 1
Vfault 1
I3faultpu 3.0635 pu
Z1 0.05472978 j0.3218021
3.922
t 0.0982 1.28 0.231 second
1284.77 2
1
184
3Vfault 3
I3faultpu 3.1458 pu
Z0 Z1 Z2 0.15397026 j0.9411232
3.922
t 0.0982 1.28 0.2 second
1518.815 2
1
184
V 1
I3faultpu fault 3.046807 pu
Z1 0.05802278 j0.3230371
3.922
t 0.0982 1.28 0.232 second
2
1274.713
184 1
3Vfault 3
I3faultpu 3.1291 pu
Z0 Z1 Z2 0.16227826 j0.9448812
3.922
t 0.0982 1.28 0.201 second
2
1510.767
1
184
~ ~ 1 pu
1 pu
Fault Point 5
0.0004705+j0.000319
Cable 3
Fault Point 6
Cable 4
0.003293+j0.001235
Fault Point 7
Fire Pump
Motor
0.387907+j2.58604
BUS1
Reference
0.015679+j0.428
ZCable3,ZERO=0.000217+j0.000179
0.0004705+j0.000319
ZCable4,ZERO=0.001722+j0.001288
0.003293+j0.001235
ZCable4,ZERO=0.387907+j2.586048
0.387907+j2.58604
Z1=Z2=Z0= 0.015679+j0.428
Vfault 1
I3faultpu 2.334 pu
Z1 0.015679 + j0.428
3.922
t 0.0982 2.5 0.59 second
1953.687 2
1
360
3Vfault 3
I3faultpu 2.334 pu
Z0 Z1 Z2 0.047037 j1.284
3.922
t 0.0982 2.5 0.59 second
1953.687 2
1
360
V 1
I3faultpu fault 2.333 pu
Z1 0.0161495 j0.428319
3.922
t 0.0982 2.5 0.59 second
2
1952.1545
1
360
3Vfault 3
I3faultpu 2.333 pu
Z0 Z1 Z2 0.048195 j1.284817
3.922
t 0.0982 2.5 0.59 second
2
1952.3814
1
360
3Vfault 3
I3faultpu 2.3259 pu
Z0 Z1 Z2 0.056503 j1.288575
3.922
t 0.0982 2.5 0.592 second
2
1946.186
1
360
Transformer
G9900
Damage Curve
Motor
100 Running
Curve
IFLA=47.7A Cable Damage
Curve
G9900
Motor
Starting
Curve
ILRC=320A
10
TIME (s)
R1
1 51V
CT 100:5
Pickup=9.2In
Pickup I=184A
ANSI VI
TD=1.28
0.1
Inrush point
1004A @0.1s
0.01
1 10 100 1000 10000 100000
CURRENT (A) AT 13.8kV BASE
G9900
100 Motor
Running Generator
Curve Overload
IFLA=47.7A Curve
R2
51V
10 CT 400:5
Pickup=3.68In
Pickup I=360A
TIME (S)
ANSI VI
TD=2.5
Generator
Decrement
Curve
@ 3PU Field
1 Current
Cable Damage
Curve
0.1
0.01
1 10 100 1000 10000 100000
CURRENT (A) AT 6.9kV BASE
Table 8.8
100% 80%
Isc Iarc
Location En En
(kA) (kA)
(j/cm2) (j/cm2)
Power Plant 23.25 22.24 9.05 7.59
ATS (Normal) 2.56 2.55 0.87 0.73
ATS (Backup) 1.95 1.95 0.65 0.55
Back up Generator Breaker 1.95 1.95 0.65 0.55
Panel
! WARNING
Arc-Flash and Shock Hazard
Appropriate PPE Required
Equipment ID: 52FP
Arc-Flash Protection Shock Protection
! WARNING
Arc-Flash and Shock Hazard
Appropriate PPE Required
Equipment ID: BGENFP
Arc-Flash Protection Shock Protection
Cable Schedule
Length Size Insulation/Volt/ Raceway
Tag From To 2
(m) (mm ) Sheathing
Cable 52FP TRFP 2400 95 XLPE/12/20kV 6x12 Cable
aluminum tray
1
Shielded/Polyolefin-
Copolymer
Cable TRFP TSFR 60 95 XLPE/12/20kV 65mm-Conduit
aluminum
2
Shielded/Polyolefin-
Copolymer
Cable BGEN TSFR 60 95 XLPE/12/20kV 65mm-Conduit
aluminum