Sei sulla pagina 1di 37

CHAPTER 8

FIRE PUMP

8.1 Evaluation of Existing Installation

8.1.1 Fire Pump System Overview


JGSPCs fire-fighting system consist of one (1) electric
driven pump, two (2) diesel driven pumps and a jockey pump as
shown in Figure 8.1. This system is protecting JGSPCs critical
process equipment such as vessels, tanks, pumps, compressors,
reactors and auxiliary process equipment. The system is
maintaining the water pressure of the fire water header at 13 bars
via the combination of pressure control valve and the jockey pump.
In case of fire, header pressure will drop in which case the three
main fire pumps will automatically run based on pre-assigned
pressure cut-in values for each pump. If the header pressure falls
below 9 bars, the electric-driven pump will automatically start, if it
continues to drop to 5 bars, the first diesel engine pump will
automatically run and lastly if the pressure drops below 3 bars, the
last diesel-driven engine pump will automatically start. All these
start sequence is trigger by pressure sensing device installed on
each pump. Status of the pump condition is monitored remotely via
plant Distributed Control System by the panel Operator as shown on
Figure 8.2.

Chapter 8-Fire Pump Page 359


Figure 8.1 P&ID of Fire Water System of JGSPC

Figure 8.2 DCS Schematic of Fire Water System of JGSPC

Chapter 8-Fire Pump Page 360


8.1.2 Electric Fire Pump Motor Data (GM9900)
The electric driver G9900 is a 600hp 6.9kV 3 phase medium-voltage
motor with the complete electrical specification shown in table 8.1.

Table 8.1 Electrical Specification for G9900 Fire Water Pump


Horsepower 600hp Service factor 1.15
Full load current 47.7A Enclosure TEFC
Voltage 6900V Insulation F
Phase 3 Frame 5810
Locked rotor current 320A Ambient 40oC
Full load RPM 1786 Frequency 60Hz

8.1.3 Fire Pump Controller


Existing fire pump controller is a METRON MV600 UL listed medium-
voltage fire pump controller. This controller is already on its end-of-
life state with several components failing and corroded panel.

Figure 8.3 Existing Fire Pump Controller Panel

Chapter 8-Fire Pump Page 361


8.1.4 Power Source
Power to the electric-driven fire pump comes from the
6.9kV feeder of TRM. The 3C-25mm2 XLPE cable routed into the
cable trays which traverse the process area and into the fire pump
controller. This process area is a fire hazard zone and has a very
high risk of fire pump cable damaged in case of fire within this
process area.

8.1.5 Reliability of Existing Source


Based on the power plant interruption record from January
2012 up to May 2017, there were four (4) power plant trips one
with more than 4 hours as summarized in Table 8.2 below.
According to NFPA 20 Annex A.9.3.2, a reliable power source has
not experienced any shutdowns longer than 4 continuous hours.
This means that our power plant can be considered as a reliable
source. Moreover, the plant has two diesel-driven fire pumps and
with that condition, NEC 695.3 B 2 exception allows a single source
of reliable power.

Table 8.2 Power Plant Power Interruption Record (from Jan


2013 up to May 2017)
Date and Time Duration Cause
11/30/2014 10:20:48 2hrs Diesel Generator trip
PM (controller issue)
5/22/2016 7:49:07 PM 8hrs Lightning Strikes
10/10/2016 7:54:44 PM 2hrs Diesel generator issue trip
(controller issue)
3/5/2017 8:5:04 AM 2hrs Diesel generator issue
(controller issue)

Chapter 8-Fire Pump Page 362


8.1.6 Design Considerations and Recommendations
1. Since the fire pump motor cable traversed the process area
where fire hazard exists, it is recommended to re-route the
cable outside the process area to minimize the fire hazard.
The cable used is not fire resistant cable so it is also
recommended to replace the cable with fire resistant cable
with 2 hours fire rating. Cable tray shall be used on the entire
length and will serve the required mechanical protection.
2. Existing normal power is not tapped ahead of supply and its
circuit is part of normal loads from a common transformer
serving other utilization equipment. It is recommended to
connect the supply from 13.8kV power plant generator bus
utilizing the spare feeder and 630A SF6 Circuit breaker as well
as a dedicated 13.8kV to 6.9kV step down transformer.
3. The plant has two diesel engine driven fire pumps therefore
no alternative power is required as permitted by NEC 695.3 B
2 exception. However, for the last five (5) years, there were
several incident of diesel engine failure during a scheduled fire
pump test run and these engines are not reliable. On the
other hand, the power plant is deemed not reliable as there
was at least one (1) incident of total power failure of more
than four (4) hours. Moreover, the power plant itself is being
protected by the fire protection system and a fire event within
the power plant area can impaired the normal power supply to
the fire pump. It is therefore recommended to install a
standby generator located within the fire pump area.
4. The step-down transformer 13.8kV-6.9kV shall be located
within the fire pump area. Oil-immersed/sealed type shall be
used.
5. Existing fire pump controller is already on its end-of-life phase
and shall be replaced with a new UL listed DOL fire pump
controller with NEMA 4X IP rating.
Chapter 8-Fire Pump Page 363
8.2 Design Calculations
Based on the recommendations from 8.1.6, the proposed design of
electric fire pump system is shown below in figure 8.3.

G
Power Plant

Dedicated Feeder (from


Spare 630A SF6 CB)
(existing)

Cable (new)

Transformer
13.8kV-6.9kV Backup
(new) G Generator
(new)
Cable (new)

Fire Pump
Controller
(new)

Cable (new)

Fire Pump
GM9900
(existing)

Figure 8.4 Single Line Drawing for Fire pump

8.2.1 Generator Load Calculation (power plant)


The load required by the fire pump motor to supply
indefinitely its locked-rotor current is calculated.

Re quired Locked Rotor MVA 3 x ILRC x V


Re quired Locked Rotor MVA (1.732)(320)(6900)
Re quired Locked Rotor MVA 3.824MVA

Chapter 8-Fire Pump Page 364


Each generator has 8.375MVA so at least one generator is
required to successfully start, run and supply the locked-rotor MVA
of the fire pump should there be a fire within the plant.

8.2.2 Standby Generator Sizing (alternative power)


With the consideration of normal starting, running and
locked rotor condition, the size of the standby generator is
approximately

Re quired Locked Rotor MVA 3 x ILRC x V


Re quired Locked Rotor MVA (1.732)(320)(6900)
Re quired Locked Rotor MVA 3.824MVA

Consider 3.824MVA or 4MVA diesel generator set with


3phase 6900kV 60Hz output wye solidly grounded. However,
voltage drop during motor starting will be calculated later in this
chapter and will determine the minimum generator size required to
satisfy the starting and running voltage drop using typical values of
reactance and X/R ratio as shown on Table 8.3.

Table 8.3 Typical Reactance and X/R ratio for Wye-Grounded


Synchronous Generator
Generator Capacity (MVA) X X/R

1.00 0.15 22.8176


1.50 0.15 24.6035
2.00 0.15 25.5712
2.50 0.15 26.2547
3.00 0.15 26.8206
3.50 0.15 27.3333
4.00 0.15 27.8207
Source: SKM Power Tools

Chapter 8-Fire Pump Page 365


8.2.3 Transformer Sizing
Transformer is sized at a minimum of 125% of the FLC of
the fire pump motor.

FLC 47.7A
Transformer 1.25 x 3 x IFLC x V
Transformer (1.25)(1.732)(47.7)(6900)
Transformer 712.6kVA

Say 1MVA but for future expansion consideration where


there is a possibility of adding another fire pump of the same size,
2MVA is selected. Transformer specification will be as follows:

Table 8.3 Transformer Specification


Capacity 2MVA
Voltage(Primary-Secondary) 13.8kV-6.9kV
Connection Delta/Wye resistance
(primary/Secondary) grounded
% Impedance 6
Cooling ONAN

8.2.4 Normal Power Protection Settings Calculation


The fire pump will utilize the spare 630A ABB SF6 Circuit
Breaker since its capacity is more than enough to handle the locked
rotor condition of the fire pump. Only the Time-overcurrent
protection function will be used and will be set at 115% of the
locked-rotor current of the fire pump motor.

Primary CT size:

(transformersize) 2,000,000
IFL / Pr imary 83.67A
3(Pr imaryVoltage) 3(13800)
(150% x 83.67A)=125.5A, CT Ratio= 100:5
25VA (burden designation B-1)

Chapter 8-Fire Pump Page 366


Relaying ANSI 10C100 (class C), BIL rating 95kV

Protection Settings Calculation (Primary Overcurrent protection 51):


51 pickup (I>)
Set at 115% of LRC

LRC 320A
6.9 5
P.U. Current setting (1.15)(320)( )( ) 9.2 In
13.8 100
P.U Current (9.2)(100 / 5) 184A

The circuit breaker size of 630A is enough for the locked-


rotor requirement of 184A. Moreover, the setting is less than 300%
of transformer FLA or 252A which complies with PEC 1 table
4.50.1.3(a) for supervised location and primary protection only.
Time dial setting is set such that the protection curve is 200ms
above the TR-FR inrush point 1004A, 0.1sec.

t 0.1 0.2
TD 1.28
3.922 3.922
0.0982 0.0982
2 2
I 1004
1 1
IP 184

8.2.5 Standby Generator Protection Settings Calculation

Generator Full load current

(Generatorsize) 3,500,000
IFL 292.85A
3(Pr imaryVoltage) 3(6900)

Circuit Breaker Sizing:


(125% x 292.85)=366A, use 630A, 15kV class, 3pole, 60Hz
Vacuum Circuit breaker, 95kV BIL, Indoor type, calculated from
short circuit calculation from 8.2.7 is 1.953kA with a worst case

Chapter 8-Fire Pump Page 367


adjustment factor of 1.3 from chapter 4.3.5 or 2.53kA, so a 25kAIC
available in the market is sufficient.

Primary CT size:
(150% x 292.85A)=440A, CT Ratio= 500:5
25VA (burden designation B-1)
Relaying ANSI 10C100 (class C), BIL rating 95kV

Phase time overcurrent protection will be set at 115% of


fire pump motor LRC.

LRC 320A and Reference Voltage 6900V


5
P.U. Current setting (1.15)(320)( ) 3.68 In
500
P.U Current (3.6)(500 / 5) 360A

This setting is less than 125% of generator full load


current. Time dial will be set such that the protection curve is above
the knee point of the generator decrement curve. By adjusting the
excel plot, the suitable time dial setting is found at 2.5.

8.2.6 Cable Sizing

The highest fault at 13.8kV bus is 23,360A and with this worst case
fault current, the tripping time of the protective relay is



3.922
t 2
0.0982 2 0.126 second
23360 1
184

Adding a margin to this time


t= 0.2 + 0.126 =0.326s
For an XLPE cable at 13.8kV, the minimum cable size is

Chapter 8-Fire Pump Page 368


A
ISC t

23360 0.326
93.271mm2
143 143

For primary cable (CABLE No.1):

IAmpacityRe q 1.25 x 83.67 104.59A

From Table 8.4 and considering the minimum cable size of


93.271mm2, use 800m 3 x 1C-95mm2 XLPE 12/20kV aluminum
shielded PE (Fire resistant with 3-hour circuit integrity according to
IEC 60331) using trefoil cable formation.

For Transformer Secondary Cable to Transfer Switch (CABLE No.2):

IAmpacityRe q 1.25(IFLSecTrans)
IAmpacityRe q 1.25 x (83.67)x(13800/6900) 209.175A

From Table 8.4, use 20m 3 x 1C-95mm2 copper XLPE


12/20kV aluminum shielded PE (Fire resistant with 3-hour circuit
integrity according to IEC 60331) using EMT conduit.

For Generator Cable to the Transfer Switch (CABLE No.3):

IAmpacityRe q 1.25(IFLGen)
IAmpacityRe q 1.25 x (292.85) 366.07A/2 183A

From Table 8.4, use 20m 2 sets 3 x 1C-95mm2 copper XLPE


12/20kV aluminum shielded PE (Fire resistant with 3-hour circuit
integrity according to IEC 60331) using EMT conduit.

For Motor Branch Circuit from Transfer Switch (ATS to Fire pump
panel and Fire pump panel to motor) (CABLE No.4):

IAmpacityRe q 1.25(IFLMotor)
IAmpacityRe q 1.25 x (47.7) 59.63A

Chapter 8-Fire Pump Page 369


From Table 8.4, use 35m 3 x 1C-50mm2 copper XLPE
12/20kV aluminum shielded PE (Fire resistant with 3-hour circuit
integrity according to IEC 60331) using EMT conduit.

Table 8.4 Cable Specification Sheet for LION Cable

Chapter 8-Fire Pump Page 370


Figure 8.5 Cable Specification Sheet

Chapter 8-Fire Pump Page 371


8.2.6 Voltage Drop Calculation
According to article 6.95.1.7 of PEC 1 2009, voltage drop at
controller line terminals shall not drop more than 15% under motor
starting condition and shall not drop below 5% for under running
condition where the motor is operating at 115% of full load current
rating. Using per-unit calculation, the impedances of cables
transformer and motor are calculated below.

Power plant available fault


From Chapter 4 Table 4.3, the Thevenins equivalent impedance at
power plant bus at base 10MVA is
ZPP (0.000739 j0.017982) p u

Cable no. 1 Impedance


For the 800m cable from power plant to transformer, the impedance
is

R Rperkm Dis tan ce 0.224 / km0.8km 0.1792

XL 2f LperkmDis tan ce 260 0.403x103H / km 0.8km 0.1215419
Z 0.1792 j0.1215419

Z 0.1792 j0.1215419
Zcable1 0.00940978 j0.0063821 pu
Zbase 19.0440


Z0 Z0perkm Dis tan ce 0.8291 j0.6850 / km0.8km
0.66328 j0.548
0.66328 j0.548
Z0pu 0.034828 j0.028775 pu
19.044

Transformer Impedance
%IZ=6% at 2MVA base, X/R=6.8
S 10
Z Z2MVAbase BASE 0.06 0.3 pu
S Trans 2

Chapter 8-Fire Pump Page 372


X
R Z x cos tan-1 0.3 cos (tan-1(6.8)) 0.04364 p.u
R

X
X Z x sin tan- 1 0.3 sin (tan- 1(6.8)) 0.2968 p.u
R
ZTrans(1,2,0) 0.04364 j0.2968 pu

Cable no. 2 Impedance


20m cable

R Rperkm Dis tan ce 0.224 / km0.02km 0.00448

XL 2f Lperkm Dis tan ce 260 0.403x103H / km 0.02km 0.003038
Z 0.00448 j0.003038
Z 0.00448 j0.003038
Zcable 2 0.000941 j0.000638 pu
Zbase 4.761

Z0 Z0perkm Dis tan ce 0.8291 j0.6850 / km0.02km
0.016582 j0.0137
0.016582 j0.0137
Z0pu 0.0008707 j0.000719 pu
19.044

Cable no. 3 Impedance


20m cable

R Rperkm Dis tan ce 0.224 / km0.02km / 2 0.00224

XL 2f L perkm Dis tan ce 260 0.403x10 3 H / km 0.02km / 2 0.001519
Z 0.00224 j0.001519
Z 0.00224 j0.001519
Zcable 2 0.0004705 j0.000319 pu
Zbase 4.761

Z0 Z0perkm Dis tan ce 0.8291 j0.6850 / km0.02km / 2
0.0041455 j0.003425
0.0041455 j0.003425
Z0pu 0.000217 j0.000179 pu
19.044

Chapter 8-Fire Pump Page 373


Cable no. 4 Impedance
35m cable

R Rperkm Dis tan ce 0.448 / km0.035km 0.01568

XL 2f Lperkm Dis tan ce 260 0.446x103H / km 0.035km 0.005884
Z 0.01568 j0.005884
Z 0.01568 j0.005884
Zcable 2 0.003293 j0.001235 pu
Zbase 4.761

Z0 Z0perkm Dis tan ce 0.9370 j0.7011 / km0.035km
0.032795 j0.024538
0.032795 j0.024538
Z0pu 0.001722 j0.001288 pu
19.044

Motor Impedance
From chapter 2 equation 2.7, motor sub-transient impedance is
2
" SBASE V
ZM PU x M
3 ILR VM VBASE
2
" 10,000 6900
ZM PU x 2.614811 pu
3 320 6,900 6900
For medium-voltage motors with power per pair poles less than 1
MW,
RM " "
0.15 with XM 0.989 ZM
"
XM
"
XM "
0.989 ZM 0.9892.614811 2.586048 pu
"
R M 0.15XM 0.152.686048 0.387907 pu

ZMotor 0.387907 j 2.586048 pu

Chapter 8-Fire Pump Page 374


Generator Impedance
Typical values for a 4MVA synchronous generator are
X1=0.15 pu, X/R=27.8207
X2=0.15 pu, X/R=27.8207
X0=0.15 pu, X/R=27.8207
At 4MVA base
10
@ 10MVAbase X2 @ 10MVAbase X0 @ 10MVAbase0.15
" " "
X1 0.357 pu
4

0.357
R 0.012832 pu
27.8207

Z4MVAGen 0.012832 j0.357 pu

For 3.5 MVA generator


X1=0.15 pu, X/R=27.333
X2=0.15 pu, X/R=27.333
X0=0.15 pu, X/R=27.333
10
@ 10MVAbase X2 @ 10MVAbase X0 @ 10MVAbase0.15
" " "
X1 0.428 pu
3.5
0.428
R 0.015679 pu
27.333

Z3.5MVAGen 0.015679 j0.428 pu

Chapter 8-Fire Pump Page 375


Starting Voltage Drop for Normal Power

~ 1 pu

Power Plant
Equivalent Fault ZPP (0.000739 j0.017982) p u
Impedance

Cable 1
ZCable1 (0.00940978 j0.0063821) p u

Transformer ZTrans 0.04364 j0.2968 pu

Cable 2+Cable 4
ZCable 2 4 (0.004234 j0.001873) p u

Fire Pump
Motor ZMotor (0.387907 j2.586048) p u

ZTOTAL 0.445929 j2.909085 p.u

Figure 8.6 Impedance for Normal Power Voltage Drop

Starting-Voltage Drop

1
VDFirePumpMotor 1 ZMotor
Z TOTAL

VDFirePumpMotor 1
1
0.387907 j2.586048
0.445929 j2.909085

VDFirePumpMotor 0.111518pu 11.1518%

Calculation shows that the voltage drop during motor starting is


below 15% and is acceptable.

Chapter 8-Fire Pump Page 376


Running-Voltage Drop for Normal Power

I x1.15
VDFirePumpMotor FL ZCable1 ZTrans ZCable 2 4
IBase

VDFirePumpMotor
47.7x1.15 Z
Cable 1 Z Trans ZCable 2 4
836.73552

VDFirePumpMotor
47.7x1.15 0.310386 0.020348pu
836.73552

%VDFirePumpMotor 2.0348%

Calculation shows that the maximum voltage-drop when


the motor running is below 5% and is acceptable.

Chapter 8-Fire Pump Page 377


Starting Voltage Drop for Backup Power

~ 1 pu

ZGen@ 3.5MVA 0.015679 j0.428 pu

Gen

ZCable 2 4 (0.02016 j0.008914) p u

Cable 2+Cable4
ZMotor (0.387907 j2.586048) p u

Fire Pump
Motor
ZTOTAL 0.40782 j3.015921 p.u

Figure 8.7 Impedance for Backup Power Voltage Drop

Starting-Voltage Drop
At 3.5MVA, the voltage drop during starting is calcualted below.

1
VDFirePumpMotor 1 ZMotor
Z TOTAL

VDFirePumpMotor 1
1
0.387907 j2.586048
0.40782 j3.015921

VDFirePumpMotor 0.1414pu 14.14%

Calculation shows that the voltage drop during motor


starting is below 15% and is acceptable.

Chapter 8-Fire Pump Page 378


Running-Voltage Drop for Backup Power

I x1.15
VDFirePumpMotor FL ZCable 2 4
IBase
47.7x1.15 Z
VDFirePumpMotor Cable 2 4
836.73552

VDFirePumpMotor
47.7x1.15 0.004629 0.000303pu
836.73552

%VDFirePumpMotor 0.03%

Calculation shows that the maximum voltage-drop when the motor


running is below 5% and is acceptable.

Based on the above results, the minimum generator size


based on the percent voltage drop during motor starting is 3.5MVA.

8.2.6 Short Circuit Calculation


Short circuit calculation shall be performed to verify the
short circuit duties of the protection devices for backup generator
and power plant bus. The result shall also be used for verifying the
protection coordination for both sources.

Chapter 8-Fire Pump Page 379


~ 1 pu
~ 1 pu

Power Plant
0.000739+j0.017982
Equivalent Fault
Impedance

Cable 1 0.009409+j0.006382

Transformer
0.04364+j0.2968

Cable 2 + Cable 4
0.004234+j0.001873

Fire Pump
Motor
0.387907+j2.58604

Figure 8.8 Positive Sequence Diagram for Normal Power


Mode

ZGEN EQ,ZERO =0.000555+ J0.017761

BUS1
0.000739+j0.017982
Reference

ZCable1,ZERO=0.034828+j0.028775
0.009409+j0.006382

Z TR,ZERO=0.04364+j0.2968
0.04364+j0.2968

Reference

0.004234+j0.001873

ZCable2,ZERO=0.0008707+j0.000719

0.387907+j2.58604

Figure 8.9 Negative (left) and Zero (right) Sequence


Diagram for Normal Power Mode

Chapter 8-Fire Pump Page 380


Fault at primary terminals of transformer (Normal Power
Mode)
Z1=Z2= 0.010148+j0.024364 and Z0=0.035383+j0.046536i

For three-phase fault:

Vfault 1
I3faultpu 37.888 pu
Z1 0.010148 j0.024364

I3faultactual IBase x I3faultpu 418.36976x37.888 15,851 A

Tripping Time at 15,851A



3.922
t 0.0982 1.28 0.126 second
15851 2
1
184

For single-line-to-ground fault:

3Vfault 3
I3faultpu 27.187933 pu
Z0 Z1 Z2 0.05568056 j0.0952642

I3faultactual IBase x I3faultpu 418.3697x27.187933 11,374A

Tripping Time at 11,374 A



3.922
t 0.0982 1.28 0.127 second
2
11374

184 1

Chapter 8-Fire Pump Page 381


Fault at secondary terminals of transformer (Normal Power
Mode)

Z1=Z2=0.05378878+j0.3211641 and Z0= 0.04364+j0.2968

For three-phase fault:

V 1
I3faultpu fault 3.0709 pu
Z1 0.05378878 + j0.3211641

I3faultactual IBase x I3faultpu 836.739x3.0709 2,569 A

Tripping Time at 2,569(6900/13800) or 1284.77A



3.922
t 0.0982 1.28 0.23 second
2
1284.77
1
184

For single-line-to-ground fault:

3Vfault 3
I3faultpu 3.1538 pu
Z0 Z1 Z2 0.15121756 j0.9391282

I3faultactual IBase x I3faultpu 836.739x3.1538 2,638.93 A

Tripping Time at 2,638.93(0.577) or 1522.66A



3.922
t 0.09821.28 0.2 second
2
1524

184 1

Chapter 8-Fire Pump Page 382


Fault at ATS (Normal Power Mode)

Z1=Z2= 0.05472978+j0.321802 and Z0= 0.0445107+j0.297519

For three-phase fault:

Vfault 1
I3faultpu 3.0635 pu
Z1 0.05472978 j0.3218021

I3faultactual IBase x I3faultpu 836.739x3.0635 2,563.4 A

Tripping Time at 2,563.4(6900/13800) or 1281.7A



3.922
t 0.0982 1.28 0.231 second
1284.77 2
1
184

For single-line-to-ground fault:

3Vfault 3
I3faultpu 3.1458 pu
Z0 Z1 Z2 0.15397026 j0.9411232

I3faultactual IBase x I3faultpu 836.739x3.1458 2,632.2618 A

Tripping Time at 2,632.2618(0.577) or 1518.815A



3.922
t 0.0982 1.28 0.2 second
1518.815 2
1
184

Chapter 8-Fire Pump Page 383


Fault at terminals of Motor (Normal Power Mode)

Z1=Z2=0.05802278+j0.3230371 and Z0=0.0462327+j0.298807

For three-phase fault:

V 1
I3faultpu fault 3.046807 pu
Z1 0.05802278 j0.3230371

I3faultactual IBase x I3faultpu 836.739x3.046807 2549.427 A

Tripping Time at 2549.427(6900/13800) or 1274.713A



3.922
t 0.0982 1.28 0.232 second
2
1274.713
184 1

For single-line-to-ground fault:

3Vfault 3
I3faultpu 3.1291 pu
Z0 Z1 Z2 0.16227826 j0.9448812

I3faultactual IBase x I3faultpu 836.739x3.1291 2618.313A

Tripping Time at 2618.313(0.577) or 1510.767A



3.922
t 0.0982 1.28 0.201 second
2
1510.767
1
184

Chapter 8-Fire Pump Page 384


~ 1 pu ~ 1 pu

Backup Gen

0.015679+j0.428

Cable 2

0.028733+j0.0024807
Fire Pump
Motor

Figure 8.10 Positive Sequence Diagram for Backup Power


Mode

ZGEN EQ,ZERO =0.015679+ J0.428


0.015679+j0.428
BUS1

Reference

ZCable2,ZERO=0.029598+j0.028775
0.028733+j0.0024807

Figure 8.11 Negative (left) and Zero (right) Sequence


Diagram for Backup power Mode

Chapter 8-Fire Pump Page 385


Fault at Backup Generator Breaker Switchgear (Back Power
Mode)

Z1=Z2=Z0= 0.015679+j0.428

For three-phase fault:

Vfault 1
I3faultpu 2.334 pu
Z1 0.015679 + j0.428

I3faultactual IBase x I3faultpu 836.739x2.334 1,953.687 A

Tripping Time at 1,953.687A



3.922
t 0.0982 2.5 0.59 second
1953.687 2
1
360

For single-line-to-ground fault:

3Vfault 3
I3faultpu 2.334 pu
Z0 Z1 Z2 0.047037 j1.284

I3faultactual IBase x I3faultpu 836.739x2.334 1,953.687 A

Tripping Time at 1953.687A



3.922
t 0.0982 2.5 0.59 second
1953.687 2
1
360

Chapter 8-Fire Pump Page 386


Fault at ATS Panel (Back Power Mode)

Z1=Z2=0.0161495+j0.428319 and Z0=0.015896+j0.428179

For three-phase fault:

V 1
I3faultpu fault 2.333 pu
Z1 0.0161495 j0.428319

I3faultactual IBase x I3faultpu 836.739x2.333 1,952.1545 A

Tripping Time at 1,952.1545A



3.922
t 0.0982 2.5 0.59 second
2
1952.1545
1
360

For single-line-to-ground fault:

3Vfault 3
I3faultpu 2.333 pu
Z0 Z1 Z2 0.048195 j1.284817

I3faultactual IBase x I3faultpu 836.739x2.333 1,952.3814 A

Tripping Time at 1952.3814



3.922
t 0.0982 2.5 0.59 second
2
1952.3814
1
360

Chapter 8-Fire Pump Page 387


Fault at Motor Terminals (Back Power Mode)

Z1=Z2=0.0194425+j0.429554 and Z0=0.017618+j0.429467

For three-phase fault:


V 1
I3faultpu fault 2.3256 pu
Z1 0.0194425 j0.429554

I3faultactual IBase x I3faultpu 836.739x2.3256 1,945.9328 A


Tripping Time at 1,945.9328A



3.922
t 0.0982 2.5 0.592 second
2
1945.9328
1
360

For single-line-to-ground fault:

3Vfault 3
I3faultpu 2.3259 pu
Z0 Z1 Z2 0.056503 j1.288575

I3faultactual IBase x I3faultpu 836.739x2.3259 1,946.1864A

Tripping Time at 1946.186



3.922
t 0.0982 2.5 0.592 second
2
1946.186
1
360

Chapter 8-Fire Pump Page 388


Fault Point Three Phase Fault Single Line to
Ground

Chapter 8-Fire Pump Page 389


TCC for Phase OC Protection for Fire Pump G9900 on Normal
1000 Power
Transformer
FL=83A

Transformer
G9900
Damage Curve
Motor
100 Running
Curve
IFLA=47.7A Cable Damage
Curve

G9900
Motor
Starting
Curve
ILRC=320A
10
TIME (s)

R1
1 51V
CT 100:5
Pickup=9.2In
Pickup I=184A
ANSI VI
TD=1.28

0.1
Inrush point
1004A @0.1s

0.01
1 10 100 1000 10000 100000
CURRENT (A) AT 13.8kV BASE

Chapter 8-Fire Pump Page 390


TCC for Phase OC Protection for Fire Pump G9900 on Backup
Power (Standby Generator)
1000
Generator 51V
Full load Pickup I=360A
Curve

G9900
100 Motor
Running Generator
Curve Overload
IFLA=47.7A Curve

R2
51V
10 CT 400:5
Pickup=3.68In
Pickup I=360A
TIME (S)

ANSI VI
TD=2.5
Generator
Decrement
Curve
@ 3PU Field
1 Current

Cable Damage
Curve

0.1

0.01
1 10 100 1000 10000 100000
CURRENT (A) AT 6.9kV BASE

G9900
Motor
Starting
Curve
ILRC=320A

Chapter 8-Fire Pump Page 391


Generator
Decrement
Curve
@ 3PU Field
8.2.7 Equipment Grounding Conductor
Primary pickup current of 51FP is 184A, according to Table
2.50.6.13 of PEC I 2009, the minimum equipment grounding
conductor size is 14mm2 copper. However, since the full load
current of 2 MVA transformer is 84A and the maximum allowable
setting of the overcurrent protection device at the primary of the
transformer is 252A or 300% of the full load amps, a 22 mm2
equipment grounding conductor is recommended in order to serve
for future expansion of additional fire pumps.

Equipment Protection EGC Length


Size/ Size (m)
Setting (A) (mm2)

Normal source to power 252 22 820


transformer (Primary)
Power Transformer to ATS 252x2=504 38 22
Generator to ATS 360 30 22
ATS to Fire pump controller Highest of 38 20
panel the two
source (504)
Fire pump control panel to fire 504 38 15
pump motor

Chapter 8-Fire Pump Page 392


8.2.7 Arc-Flash Calculation

Chapter 8-Fire Pump Page 393


Table 8.4 Bill of Materials
No Description Qty. Total Cost
1 1C-150mm2 XLPE 12/20kV aluminum shielded PE 2400 m 8,400,000
(Fire resistant with 3-hour circuit integrity
according to IEC 60331) using trefoil cable
formation.

3C-14mm2 copper conductor EPR insulated 8kV 75m 300,000


MV-105 type in 1 x 65mm EMT conduit
1C-14mm2 copper conductor 820m 123,000
Transformer, 2MVA 13.8kV-6.9kV, Oil immersed, 1 set 1,617,083.00
Dyn11
Fire Controller Eaton LMR 100-3250hp 6900kV 1 set 450,300.00
DOL

3M Cold Shrink QT-III Silicone Rubber Indoor 7 sets


Tubular Termination Kits for single core cable.
7624T110 15kV (110kV BIL)
3M Cold Shrink QT-III Silicone Rubber Indoor 4 sets
Tubular Termination Kits for three core cable.
7624T110 15kV (110kV BIL)
Cable tray ladder type-straight section, HDG 225 pcs
Steel, 6 rung x12W x 12 L with solid flanged
cover
Heavy duty cover clamps HDG steel series 148 625 pcs
Universal splice plates HDG steel series 148 700 pcs
Trefoil Cable cleats 912pcs
Cable tray fittings HDG steel 90deg horizontal 10pcs
bend series 148, 12
Cable tray fittings HDG steel vertical bend inside 10 pcs
series 148, 12
Cable tray fittings HDG steel vertical bend 12 pcs
outside series 148, 12
Bonding jumper 2000A max, 99-1620 700 pcs

Chapter 8-Fire Pump Page 394


Power Transformer 2MVA ONAN 13.8kV-6.9kV 1 set
Dyn11

Chapter 8-Fire Pump Page 395

Potrebbero piacerti anche