Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
INSTALACIONES ELECTRICAS I
CURSO:
TEMA : URBANIZACIN
ALUMNO :
I. INTRODUCCIN................................................................................................................1
2.1. Lote....................................................................................................................................2
2.2. Urbanizar............................................................................................................................3
III. Normas:...........................................................................................................................4
4.1. Generalidades.....................................................................................................................5
V. MEMORIA DE CLCULO....................................................................................................8
1
2. MARCO TERICO
Lote
2
De acuerdo a la L.G.U.C para urbanizar un terreno es obligacin del propietario del
predio, a su entero costo proyectar y construir pavimentos de calles y pasajes, las
plantaciones y obras de ornato, las instalaciones sanitarias y energticas con sus
obras de alimentacin y desages de aguas servidas y de aguas lluvias y las obras de
defensas y servicios del terreno, cumpliendo con los mecanismos de planificacin
territorial correspondientes.
Urbanizar
3
3. NORMAS
El desarrollo del proyecto se efectuar de acuerdo a los requisitos de las siguientes normas
peruanas:
4
socioculturales de la poblacin de las diferentes regiones del pas, fiscalizando y
supervisando su cumplimiento. REGLAMENTO NACIONAL DE EDIFICACIONES.
4. MEMORIA DESCRIPTIVA
Generalidades.
El presente proyecto comprende las Instalaciones Elctricas de una urbanizacin tanto de
alumbrado pblico como la distribucin de la energa para cada uno de los lotes. La
urbanizacin consta de 14 manzanas con 312 lotes.
Alcance del Proyecto.
El proyecto comprende: El diseo de las Redes Elctricas Subterrneas del Subsistema de
Distribucin Primaria en 22.4 kV, con cables del tipo N2XSY, para suministrar energa
elctrica.
Tambin abarca el diseo de las Redes Elctricas Subterrneas del Subsistema de
Distribucin Secundaria de 380 V con cable tipo NYY de diferentes dimetros, adems del
subsistema de alumbrado pblico con cable tipo NYY, con estructuras de postes de
concreto.
5
Descripcin del proyecto
Red del Subsistema de Distribucin Primaria (SDP)
Caractersticas de la Red:
Tensin : 22.4 KV
Sistema : Trifsico con neutro aislado
Frecuencia : 60 Hz
Distribucin : Subterrnea con cables N2XSY
Tensin : 380 V
Sistema : Trifsico con neutro.
Frecuencia : 60 Hz
Distribucin : Subterrnea con cables NYY
Las lneas de baja tensin estarn operando a 380 V con el fin de minimizar prdidas de
energa, por tratarse de un proyecto de urbanizacin dentro de una provincia rural de Lima.
Subestaciones de distribucin:
Cada predio contar con un factor de simultaneidad de 0,4 y un factor de demanda de 0.8
para realizar los clculos de mxima demanda y seccin de los conductores.
6
La acometida de cada lote la conformarn 5 conductores, las fases (R, S, T), el neutro y
tierra, de esta manera se conseguir que cada predio cuente con un suministro de 380 V,
usando las tres fases y el neutro, se obtendr 220 V.
Caractersticas de la Red
Tensin : 380 V
Sistema : Trifsico con neutro.
Frecuencia : 60 Hz
Distribucin : Subterrnea con cables NYY
Las lneas de baja tensin estarn operando a 380 V con el fin de minimizar prdidas de
energa.
Se hallado de los diferentes lotes que tenemos tomando como base de potencia 3kW x lote
7
MAXIMA DEMANDA TOTAL KW 1162.75 kW
RESERVA 10% 116.28
POTENCIA TOTAL KW DE LA MAXIMA DEMANDA 1279.03
POTENCIA TOTAL INSTALADA KW (642 lotes) 2895.25
FACTOR DE CARGA 0.5
POTENCIA TOTAL CONTRATADA KW 1448.1
FACTOR DE POTENCIA 0.85
POTENCIA TOTAL KW 1279.03
POTENCIA DEL TRANSFORMADOR CALCULADO KVA 1504.74
POTENCIA DEL TRANSFORMADOR COMERCIAL KVA 1600
5. MEMORIA DE CLCULO
Dnde:
8
* Para el clculo de la corriente del alimentador principal al T.G. se considerar
como la potencia, la mxima demanda de potencia en vatios.
Clculo de cables para las cargas: consideramos una tolerancia del 25%
9
SAB-1
MANZANA A
C
NUMERO DE In Scu Scu ajuste DV I diseo cable
LOTE LONG cap
LOTES
m A mm2 mm2 % A A NYY
6 400.4 1 9.27 17.73 25 1.77 11.59 163 3-1x25mm2
5 380.4 2 18.55 33.69 35 2.41 23.18 195 3-1x35mm2
4 344.4 3 27.82 45.75 50 2.29 34.77 230 3-1x50mm2
3 328.3 4 37.09 58.15 70 2.08 46.37 282 3-1x70mm2
2 315.4 5 46.37 69.84 70 2.49 57.96 282 3-1x70mm2
1 269.8 6 55.64 71.69 95 1.89 69.55 336 3-1x95mm2
7 365.5 1 9.27 16.19 25 1.62 11.59 163 3-1x25mm2
8 357.9 2 18.55 31.70 35 2.26 23.18 195 3-1x35mm2
9 350.3 3 27.82 46.54 50 2.33 34.77 230 3-1x50mm2
10 342.7 4 37.09 60.70 70 2.17 46.37 282 3-1x70mm2
11 335.1 5 46.37 74.20 95 1.95 57.96 336 3-1x95mm2
12 327.5 6 55.64 87.02 95 2.29 69.55 336 3-1x95mm2
13 319.9 7 64.91 99.17 120 2.07 81.14 382 3-1x120mm2
14 312.3 8 74.19 110.64 120 2.30 92.73 382 3-1x120mm3
15 304.7 9 83.46 121.44 150 2.02 104.32 428 3-1x150mm2
16 297.1 10 92.73 131.57 150 2.19 115.92 428 3-1x150mm3
17 289.5 11 102.01 141.02 150 2.35 127.51 428 3-1x150mm4
18 281.9 12 111.28 149.80 150 2.50 139.10 428 3-1x150mm5
10
SAB-1
MANZANA F
LONG NUMERO In Scu Scu ajuste DV I diseo C cap cable
LOTE
M DE LOTES A mm2 mm2 % A A NYY
22 411.5 1 9.27 18.22 25 1.82 11.59 127 3-1x25mm2
21 403.2 2 18.55 35.71 35 2.55 23.18 195 3-1x35mm2
20 394.9 3 27.82 52.46 70 1.87 34.77 230 3-1x70mm2
19 386.6 4 37.09 68.48 70 2.45 46.37 230 3-1x70mm2
18 378.3 5 46.37 83.76 95 2.20 57.96 282 3-1x95mm2
17 370 6 55.64 98.31 120 2.05 69.55 127 3-1x120mm2
16 361.7 7 64.91 112.12 120 2.34 81.14 195 3-1x120mm2
15 353.4 8 74.19 125.20 150 2.09 92.73 230 3-1x150mm2
14 345.1 9 83.46 137.54 150 2.29 104.32 230 3-1x150mm2
13 336.8 10 92.73 149.15 150 2.49 115.92 282 3-1x150mm2
12 328.5 11 102.01 160.02 185 2.16 127.51 336 3-1x185mm2
11 320.2 12 111.28 170.16 185 2.30 139.10 336 3-1x185mm3
10 311.9 13 120.55 179.56 185 2.43 150.69 336 3-1x185mm4
9 303.6 14 129.83 188.23 240 1.96 162.28 336 3-1x240mm2
8 295.3 15 139.10 196.16 240 2.04 173.87 336 3-1x240mm3
7 287 16 148.37 203.35 240 2.12 185.47 382 3-1x240mm4
6 278.7 17 157.65 209.81 240 2.19 197.06 382 3-1x240mm5
5 270.4 18 166.92 215.54 240 2.25 208.65 382 3-1x240mm6
4 262.1 19 176.19 220.53 240 2.30 220.24 382 3-1x240mm7
3 244.6 38 352.38 411.61 400 2.57 440.48 428 3-1x400mm2
2 213.3 39 361.66 368.39 400 2.30 452.07 428 3-1x400mm3
1 201 40 370.93 356.04 400 2.23 463.66 428 3-1x400mm4
23 410.8 1 9.27 18.19 25 1.82 11.59 282 3-1x25mm2
24 389 2 18.55 34.45 35 2.46 23.18 282 3-1x35mm2
25 368.5 3 27.82 48.96 50 2.45 34.77 282 3-1x50mm2
26 360.4 4 37.09 63.84 70 2.28 46.37 282 3-1x70mm2
27 352.3 5 46.37 78.01 95 2.05 57.96 336 3-1x95mm2
28 344.2 6 55.64 91.46 95 2.41 69.55 336 3-1x95mm2
29 336.1 7 64.91 104.19 120 2.17 81.14 336 3-1x120mm1
30 328 8 74.19 116.20 120 2.42 92.73 336 3-1x120mm2
31 319.9 9 83.46 127.50 150 2.12 104.32 336 3-1x150mm0
32 311.8 10 92.73 138.08 150 2.30 115.92 282 3-1x150mm1
33 303.7 11 102.01 147.94 150 2.47 127.51 282 3-1x150mm2
34 295.6 12 111.28 157.08 185 2.12 139.10 282 3-1x185mm1
35 287.5 13 120.55 165.51 185 2.24 150.69 282 3-1x185mm0
36 279.4 14 129.83 173.22 185 2.34 162.28 336 3-1x185mm1
37 271.3 15 139.10 180.21 185 2.44 173.87 336 3-1x185mm2
38 263.2 16 148.37 186.49 185 2.52 185.47 336 3-1x185mm3
39 255.1 17 157.65 192.05 240 2.00 197.06 336 3-1x240mm3
40 247 18 166.92 196.89 240 2.05 208.65 336 3-1x240mm4
41 238.9 19 176.19 201.01 240 2.09 220.24 230 3-1x240mm5
42 230.8 20 185.47 204.42 240 2.13 231.83 230 3-1x240mm6
43 222.7 21 194.74 207.10 240 2.16 243.42 230 3-1x240mm7
11
SBA-1
MANZANA N LOTES Ping(KW) FD MD(KW)
A 18 135 0.4 54
B 38 285 0.4 114
E 40 300 0.4 120
F 43 322.5 0.4 129
J 27 202.5 0.4 81
K 27 202.5 0.4 81
TOTAL 193 1447.5 0.4 579
SBA-1
CUADRO DE CARGAS GENERAL
ITEM DENOMINACION DE LAS CARGAS Ping(KW) FD MD(KW)
1 PREDIOS: 8 MZ, 204 LOTES, MD(por predio)=3KW 1447.5 0 579
2 ALUMBRADO PUBLICO 31 LUMIN-250W/C.U 7.75 1 7.75
MAXIMA DEMANDA TOTAL KW 1455.25 586.75
RESERVA 10% 58.68
POTENCIA TOTAL KW 645.43
POTENCIA TOTAL INSTALADA KW 1455.25
FACTOR DE CARGA 0.4
POTENCIA CONTRATADA KW 582.1
FACTOR DE POTENCIA 0.85
POTENCIA TOTAL KW 645.43
POTENCIA DEL TRANSFORMADOR CALCULADO KVA 759.32
POTENCIA DEL TRANSFORMADOR COMERCIAL KVA 800
12
SAB- 2
MANZANA G
C
NUMERO DE In Scu Scu ajuste DV I diseo cable
LOTE LONG cap
LOTES
m A mm2 mm2 % A A NYY
15 434.5 1 10.51 21.81 25 2.18 13.14 163 3-1x25mm2
14 403 2 21.02 40.45 50 2.02 26.27 230 3-1x50mm2
13 394 3 31.53 59.32 70 2.12 39.41 282 3-1x70mm2
12 385 4 42.04 77.29 95 2.03 52.55 336 3-1x95mm2
11 376 5 52.55 94.35 95 2.48 65.69 336 3-1x95mm3
10 367 6 63.06 110.52 120 2.30 78.82 382 3-1x120mm2
9 358 7 73.57 125.77 150 2.10 91.96 428 3-1x150mm2
8 349 8 84.08 140.13 150 2.34 105.10 428 3-1x150mm3
7 340 9 94.59 153.58 185 2.08 118.23 483 3-1x185mm2
6 331 10 105.10 166.12 185 2.24 131.37 483 3-1x185mm3
5 322 11 115.61 177.77 185 2.40 144.51 483 3-1x185mm4
4 313 12 126.12 188.51 240 1.96 157.65 561 3-1x240mm2
3 304 13 136.63 198.35 240 2.07 170.78 561 3-1x240mm3
2 295 14 147.14 207.28 240 2.16 183.92 561 3-1x240mm4
1 286 15 157.65 215.31 240 2.24 197.06 561 3-1x240mm5
16 366.8 1 10.51 18.41 25 1.84 13.14 160 3-1x25mm2
17 357.8 2 21.02 35.92 35 2.57 26.27 195 3-1x35mm2
18 348.8 3 31.53 52.52 70 1.88 39.41 282 3-1x70mm2
19 339.8 4 42.04 68.22 70 2.44 52.55 282 3-1x70mm3
20 330.8 5 52.55 83.01 95 2.18 65.69 336 3-1x95mm3
21 321.8 6 63.06 96.90 120 2.02 78.82 382 3-1x120mm2
22 312.8 7 73.57 109.89 120 2.29 91.96 382 3-1x120mm3
23 303.8 8 84.08 121.98 150 2.03 105.10 428 3-1x150mm2
24 294.8 9 94.59 133.16 150 2.22 118.23 428 3-1x150mm3
25 285.8 10 105.10 143.44 150 2.39 131.37 428 3-1x150mm4
26 276.8 11 115.61 152.81 185 2.07 144.51 483 3-1x185mm3
27 267.8 12 126.12 161.29 185 2.18 157.65 483 3-1x185mm4
13
SAB 2
MANZANA H
C
NUMERO In Scu Scu ajuste DV I diseo cable
LOTE LONG cap
DE LOTES
M A mm2 mm2 % A A NYY
11 197.8 1 10.51 9.93 10 2.48 13.14 95 3-1x10mm2
10 185.3 2 21.02 18.60 25 1.86 26.27 163 3-1x25mm2
9 177.3 3 31.53 26.70 35 1.91 39.41 195 3-1x35mm2
8 169.3 4 42.04 33.99 35 2.43 52.55 195 3-1x35mm3
7 161.3 5 52.55 40.48 50 2.02 65.69 230 3-1x50mm3
6 153.3 6 63.06 46.16 50 2.31 78.82 230 3-1x50mm4
5 145.3 7 73.57 51.05 70 1.82 91.96 282 3-1x70mm3
4 137.3 8 84.08 55.13 70 1.97 105.10 282 3-1x70mm4
3 129.3 9 94.59 58.40 70 2.09 118.23 282 3-1x70mm5
2 106.4 10 105.10 53.40 70 1.91 131.37 282 3-1x70mm6
1 86.4 11 115.61 47.70 70 1.70 144.51 282 3-1x70mm7
12 176.5 1 10.51 8.86 10 2.21 13.14 95 3-1x10mm2
13 153.7 2 21.02 15.43 16 2.41 26.27 127 3-1x16mm2
14 133.3 3 31.53 20.07 25 2.01 39.41 163 3-1x25mm2
15 125.3 4 42.04 25.15 35 1.80 52.55 195 3-1x35mm2
16 117.3 5 52.55 29.44 35 2.10 65.69 195 3-1x35mm3
17 109.3 6 63.06 32.91 35 2.35 78.82 195 3-1x35mm4
18 101.3 7 73.57 35.59 50 1.78 91.96 230 3-1x50mm3
19 93.3 8 84.08 37.46 50 1.87 105.10 230 3-1x50mm4
14
SAB-2
MANZANA I
LONG NUMERO In Scu Scu ajuste DV I diseo C cap cable
LOTE
M DE LOTES A mm2 mm2 % A A NYY
10 270 1 10.51 13.55 16 2.12 13.14 127 3-1x16mm2
9 261 2 21.02 26.20 35 1.87 26.27 195 3-1x35mm2
8 252 3 31.53 37.94 50 1.90 39.41 230 3-1x50mm2
7 243 4 42.04 48.78 50 2.44 52.55 230 3-1x50mm3
6 234 5 52.55 58.72 70 2.10 65.69 282 3-1x70mm2
5 225 6 63.06 67.75 70 2.42 78.82 282 3-1x70mm3
4 216 7 73.57 75.89 95 2.00 91.96 336 3-1x95mm2
3 207 8 84.08 83.11 95 2.19 105.10 336 3-1x95mm3
2 198 9 94.59 89.44 95 2.35 118.23 336 3-1x95mm4
1 189 10 105.10 94.86 95 2.50 131.37 336 3-1x95mm5
11 225.5 1 10.51 11.32 16 1.77 13.14 127 3-1x16mm2
12 216.5 2 21.02 21.73 25 2.17 26.27 163 3-1x25mm2
13 207.5 3 31.53 31.24 35 2.23 39.41 195 3-1x35mm2
14 198.5 4 42.04 39.85 50 1.99 52.55 230 3-1x50mm2
15 189.5 5 52.55 47.55 50 2.38 65.69 230 3-1x50mm2
16 180.5 6 63.06 54.35 70 1.94 78.82 282 3-1x70mm3
17 171.5 7 73.57 60.25 70 2.15 91.96 282 3-1x70mm4
18 162.5 8 84.08 65.25 70 2.33 105.10 282 3-1x70mm5
19 153.5 9 94.59 69.34 70 2.48 118.23 282 3-1x70mm6
SAB 2
15
MANZANA H
C
NUMERO In Scu Scu ajuste DV I diseo cable
LOTE LONG cap
DE LOTES
M A mm2 mm2 % A A NYY
11 197.8 1 10.51 9.93 10 2.48 13.14 95 3-1x10mm2
10 185.3 2 21.02 18.60 25 1.86 26.27 163 3-1x25mm2
9 177.3 3 31.53 26.70 35 1.91 39.41 195 3-1x35mm2
8 169.3 4 42.04 33.99 35 2.43 52.55 195 3-1x35mm3
7 161.3 5 52.55 40.48 50 2.02 65.69 230 3-1x50mm3
6 153.3 6 63.06 46.16 50 2.31 78.82 230 3-1x50mm4
5 145.3 7 73.57 51.05 70 1.82 91.96 282 3-1x70mm3
4 137.3 8 84.08 55.13 70 1.97 105.10 282 3-1x70mm4
3 129.3 9 94.59 58.40 70 2.09 118.23 282 3-1x70mm5
2 106.4 10 105.10 53.40 70 1.91 131.37 282 3-1x70mm6
1 86.4 11 115.61 47.70 70 1.70 144.51 282 3-1x70mm7
12 176.5 1 10.51 8.86 10 2.21 13.14 95 3-1x10mm2
13 153.7 2 21.02 15.43 16 2.41 26.27 127 3-1x16mm2
14 133.3 3 31.53 20.07 25 2.01 39.41 163 3-1x25mm2
15 125.3 4 42.04 25.15 35 1.80 52.55 195 3-1x35mm2
16 117.3 5 52.55 29.44 35 2.10 65.69 195 3-1x35mm3
17 109.3 6 63.06 32.91 35 2.35 78.82 195 3-1x35mm4
18 101.3 7 73.57 35.59 50 1.78 91.96 230 3-1x50mm3
19 93.3 8 84.08 37.46 50 1.87 105.10 230 3-1x50mm4
16
SBA-2
MANZANA N LOTES Ping(KW) FD MD(KW)
C 27 202.5 0.4 81
D 27 202.5 0.4 81
G 27 202.5 0.4 81
H 19 142.5 0.4 57
I 19 142.5 0.4 57
L 3 22.5 0.4 9
M 35 262.5 0.4 105
N 35 262.5 0.4 105
TOTAL 192 1440 0.4 576
SBA-2
CUADRO DE CARGAS GENERAL
ITEM DENOMINACION DE LAS CARGAS Ping(KW) FD MD(KW)
1 PREDIOS: 8 MZ, 204 LOTES, MD(por predio)=3KW 1440 0.4 576
2 ALUMBRADO PUBLICO 31 LUMIN-250W/C.U 7.75 1 7.75
MAXIMA DEMANDA TOTAL KW 1447.75 583.75
RESERVA 10% 58.38
POTENCIA TOTAL KW 642.13
POTENCIA TOTAL INSTALADA KW 1447.75
FACTOR DE CARGA 0.4
POTENCIA CONTRATADA KW 579.1
FACTOR DE POTENCIA 0.85
POTENCIA TOTAL KW 642.13
POTENCIA DEL TRANSFORMADOR CALCULADO KVA 755.44
POTENCIA DEL TRANSFORMADOR COMERCIAL KVA 800
17
6. INFORME RESUMEN DEL RSSTAE
Proteger a los usuarios y pblico en general contra los peligros de las instalaciones
elctricas y actividades inherentes a las actividades con la electricidad.
a) Alcance
b) Autoridades
18
7. CONCLUSIONES Y RECOMENDACIONES.
19