Permanent safe

Constructions
Interior air sealing provides protection against structural damage and mould

Roofs | Walls | Ceilings | Floors | New buildings and refurbishments


Interior air sealing with airtightness / Dampfbremsbahnen Interior
Luftdichtung innen mit air sealing with derived timber
Construction inside

vapour control membranes sheathing (e.g. OSB)

4 9
Interior air Air sealing with
sealing of external roof
masonry insulation
structures

12 13
Construction

Interior air sealing with


airtightness / vapour control Interior air sealing Interior air sealing Interior air sealing
membranes with wood-based panels for masonry structures with external roof insulation

Installation with vapour retarder Installation with vapour retarder Sealing 12 Installation of external roof insu-
and airtightness layers consisting and airtightness layers consisting Ground or ceiling slab for interior lation with vapour retarder and
of membranes of wood-based panels insulation airtightness layers consisting of
Windows in solid walls membranes
Sealing 4 Sticking 9
of membrane overlaps of panel joints Sticking 13
of membrane overlaps
Sealing 4 Sealing 9
General Knee wall Sealing 13
Knee wall Bargeboard Knee wall
Bargeboard Ground or ceiling slab Bargeboard
Middle purlin Interior wall Skylights
Ground or ceiling slab Windows
Interior wall
Penetrations 15
Windows
Penetrations 10 Pipes or cables
Beams or angular components Chimneys
Skylights
Pipes or cables
Penetrations 6 Sockets without installation layer
Beams or angular components
Pipes or cables
Chimneys

pro clima 02.2014 | www.proclima.com 2


Air sealing for refurbishment Construction inside Refurbishment solution, air sealing at
Luftdichtung innen mit Dampfbremsbahnen

projects centre of structure

16 89 18 89

89
Safe structures are achieved by taking advantage of potential for avoiding structural damage to the greatest possible extent. Appropriate planning
and the installation of the vapour retarder and airtightness layers are critical here.

Air sealing for refurbish-


ment projects

Refurbishment
solutions 16
Sub-and-top installation
Sealing, detail views
Refurbishment solutions,
air sealing at centre of
structure 18
1:1 solution
2:1 solution
Sealing, detail views

3 pro clima 02.2014 | www.proclima.com


Interior air sealing with vapour retarder membranes Interior Construction

Interior air sealing with


airtightness / vapour
control membranes
Legend
Alternative
1 Airtight membrane
INTELLO
INTELLO PLUS
DB+

2 Adhesive tape
TESCON VANA 2
TESCON No.1 1
UNI TAPE 2

1
3 Joint adhesive
ORCON F
ORCON CLASSIC
ORCON LINE
ECO COLL for DB+ Sticking membrane overlaps Sticking membrane overlaps
perpendicular to rafter parallel to rafter
4 Plaster sealing tape
CONTEGA PV*)

5 Sealing tape
TESCON PROFIL

6 Rafter 1

7 Airtight layer of wall 1


2
8 Rafters parallel to inside of
3
wall A
7
9 Pressure lath 6

10 Fibrous compartment insulation

11 Roof decking
Sealing at knee wall Sealing at knee wall
12 Roof sealing
for masonry structures for timber structures

13 Vapour barrier Alternative


14 Insulation material

Info
8
*) Gypsum plasters have very B
C

1
B,

good adhesion on CONTEGA 3 1


fleece. A bonding bridge e.g. 4
a reinforcing mortar must Alternative
be used for lime and cement
plasters.
9
B

Sealing at Gable 4

pro clima 02.2014 | www.proclima.com 4


Interior Construction Interior air sealing with vapour retarder membranes

Sealing in general Tips


A Ensure that the joint
Always clean the subsurface carefully. If neces- diffusion (e. g. PE or alu) on concrete surfaces,
between the base purlin
sary, apply primer to subsurfaces with insuf- the dry process is recommended for ORCON F/
and the rafter is sealed.
ficient load-bearing capacity or with a sandy ORCON CLASSIC. Sealing to smooth subsurfac-
substrate. es: With one of the pro clima adhesive tapes B Leave slack when applying
the membrane to allow for
Sealing to rough subsurfaces: Only adhesive tapes should be used on unpro-
relative motion between
ORCON F / ORCON CLASSIC for vapour retarders tected metal parts, e.g. iron, due to the risk of
components.
made from fleece/sheeting. corrosion.
ECO COLL for vapour retarders made from paper. C Pressure lath generally not
Unevenness of up to 2 cm in depth can be filled Achieving the best air seal possible is critical for
required. Recommended for
using pro clima air-sealing joint adhesives for all structures. For this reason, we recommend Delayed drying of the
example, in the case of rough concrete slabs. that air tightness be checked using a pro clima
adhesive, e.g. when
When sealing sheeting that strongly hinders WINCON or blower door measurement.
installing the vapour
retarder during frost
Subsurface with insuffi-

cient load-bearing capacity

D Under certain circumstances,


additional insulation with
hygric separation may be
necessary. Contact our
Engineering Hotline for a
release. > Call:
+49 (0) 62 02 27 82.0
1
1 B
B 5 2
3

Sealing to roughly sawn middle Sealing to planed middle purlin


purlin

1 2 3
D
12
14
12 11 13
11
10 10

1
3 2
1

(1) Membrane only (2) Gravel (3) Green roof

Flat roof Flat roof (insulation cover, e.g. for


shading)

5 pro clima 02.2014 | www.proclima.com


Interior air sealing with vapour retarder membranes Interior Construction

Interior air sealing with vapour retarder membranes continued

Legend
1
1 Airtight membrane
INTELLO 3
INTELLO PLUS 4
DB+ 1
13

2 Wind-sealing membrane 1 10
SOLITEX UD
C,D
A

3 Adhesive tape
TESCON VANA
TESCON No.1 14

4 Adhesive tape
UNI TAPE

5 Window sealing tape Sealing at interior wall Sealing at reinforced concrete,


CONTEGA SL*) ceiling or ground slab
6 Window sealing tape
CONTEGA IQ*)
1 1
7 Sealing tape
TESCON PROFIL
5 6 5 7 8
8 TESCON INCAV in corner areas

9 TESCON INVEX in corner areas

10 Joint adhesive
ORCON F
ORCON CLASSIC
ORCON LINE
ECO COLL for DB+
1 1
11 Pipe grommet
ROFLEX **)

12 Installation box
Sealing at windows, Sealing at windows,
INSTAABOX at the side of the frame on the frame

13 Exterior wall
Alternative
1 1
14 Interior wall

3 4
Info
*) Fold tape into the corners of
the window. Stick tape to the 7 9
airtightness layer in an airtight 2
manner after this layer has
been installed.

**) Alternatively, pipes can be


sealed using short strips of 1
TESCON VANA or TESCON No.1. 1

Penetration
Beams or angular components

pro clima 02.2014 | www.proclima.com 6


Interior Construction Interior air sealing with vapour retarder membranes

Tips
7 8 A The airtightness layer
should not be compromised
close to interior walls.

B Stick in the groove of the


1 skylight. There must be no
7 8
B tensile loading on the

B
sealing due to the weight
1 1 of the thermal insulation. If
3 4 1 necessary, the insulation
7
1 should be supported by
8
a substructure.
3 4

C Clean the concrete surface


Sealing at skylights Sealing at skylights carefully. Bind particulate
Longitudinal cross-section Transverse cross-section dust with an undercoat of
TESCON PRIMER AC or
TESCON PRIMER RP
Alternative where necessary.

D Level off unevenness around


brackets and screws using
airtightness joint adhesive.

1 1

3 3

11

1 1

Pipe feed-through with Pipe feed-through with


grommet adhesive tape

13 1

3 4

12

Inclusion of sockets
Without a service zone

7 pro clima 02.2014 | www.proclima.com


Interior air sealing with vapour retarder membranes Interior Construction

Interior air sealing with vapour retarder membranes continued

Legend Chimney penetration


1 Airtight membrane Sealing at chimneys is governed by the German Prefabricated chimneys made from concrete
INTELLO Specimen Firing Ordinance (MFeuV) and DIN V are airtight by nature. However, chimneys made
INTELLO PLUS 18160 -1: 2006-01 in Germany. According to from shaped
DB+ these regulations, flammable components may blocks (e.g. expanded clay) are not. The
not be attached directly to chimneys because of consequence of this is that a significant lack
2 Wood-based panel (e.g. OSB) the risk of a chimney fire. According to the or- of airtightness results if moulded bricks are
dinance and standard listed above, components not plastered, but instead only cladded with
3 Sealing tape with a small contact area form an exception plasterboard; this can significantly worsen the
DA-S here, e.g. underlay/sarking membranes and air change rate of a building. Chimneys made
vapour retarders. from moulded bricks must be covered with at
4 Adhesive tape least a thin layer of plaster on all sides. If the
TESCON VANA For this reason, these membranes can generally chimney is to be installed beside an adjacent
TESCON No.1 be attached directly. If necessary, consult your wall, the layer of plaster must be applied before
RAPID CELL*) local district chimney sweep. the individual bricks are laid.
UNI TAPE

5 Plaster sealing tape


CONTEGA PV **)

6 Joint adhesive
ORCON F
ORCON CLASSIC
ORCON LINE
1 1
7 ECO COLL for DB+
6 7 6 7
8 Exterior wall
C

D
C,

9 Interior wall
6 7 6 7
D

1 1
C

C,

Info

*) Care is required when crossing


Sealing to plastered chimney Sealing to concrete chimney
occurs in the case of adhesion
using RAPID CELL:
ORCON F / ORCON CLASSIC,
ORCON LINE and ECO COLL
have no adhesion on the
siliconised surface of pro clima
RAPID CELL fast adhesive tape.
Transfer tape consisting of
TESCON VANA, TESCON No.1,
TESCON INVIS or UNI TAPE
must be applied perpendicular
to the fast adhesive tape for
these air seals.

**) Gypsum plasters have very


good adhesion on CONTEGA
fleece. A bonding bridge e.g.
a reinforcing mortar must
be used for lime and cement
plasters.

pro clima 02.2014 | www.proclima.com 8


Interior Construction Interior air sealing with wood-based panels

Interior air sealing with


derived timber sheathing (e.g. OSB)
Level wood-based panels such as OSB, plywood Tips
or chipboard panels can be used as an airtight-
ness layer if joints and connections are sealed A With the DKF double nozzle,
in an airtight manner. two parallel lines of ORCON F/
ORCON CLASSIC can be
applied simultaneously.

Alternative B The airtightness layer should


not be broken close to interior
walls.
2
4 C Clean the subsurface carefully.
Bind particulate dust with an
6 undercoat of TESCON PRIMER
2
A

3 AC or TESCON PRIMER RP
where necessary.
Sealing panel joints
D The bond between the vapour
retarder and smooth, pore-free,
non-sanding pre-fabricated
chimneys can also be carried
out using TESCON VANA
1 or TESCON No.1. If necessary,
apply primer to the subsurface
here too.

4
2
5
2

Sealing at knee wall Sealing at Gable

1
8 6
3
A

2 Alternative
C

4
B

4
9 3
6

Sealing at interior wall Sealing to solid ceiling or ground slab

9 pro clima 02.2014 | www.proclima.com


Interior air sealing with wood-based panels Interior Construction

Interior air sealing with wood-based panels continued

Legend 2
2
1 Airtight membrane 4 4
INTELLO 8
INTELLO PLUS 5 6 1 5 7 1
DB+

2 Wood-based panel (e.g. OSB)

3 Wind-sealing membrane
SOLITEX UD
SOLITEX PLUS

4 Adhesive tape
TESCON VANA
TESCON No.1
RAPID CELL Sealing at windows, Sealing at windows,
UNI TAPE at the side of the frame on the frame
5 Window sealing tape
CONTEGA SL*) 2 Alternative 2

6 Window sealing tape


CONTEGA IQ*) 4

7 Sealing tape
TESCON PROFIL
3
8 TESCON INCAV in corner areas
7
9 Cable grommet
KAFLEX mono / KAFLEX duo

10 Pipe grommet
ROFLEX
Penetration of beams or
11 Installation box
INSTAABOX
angular components

Info 4

*) Fold tape into the corners of 2


the window. Stick tape to the
airtightness layer in an airtight
manner after this layer has
been installed. A

Sealing to beam, without penetration

pro clima 02.2014 | www.proclima.com 10


Interior Construction Interior air sealing with wood-based panels

Tips
A It is often easier to plan the
airtightness layer in such a
way that is does not need to
10 be broken close to the ceiling
levels.

10

Pipe feed-through

2 2
9 9

Cable feed-through

11

Inclusion of switches and sockets,


without a service zone

11 pro clima 02.2014 | www.proclima.com


Interior air sealing for masonry structures Interior Construction

Interior air sealing


for masonry structures
Legend 4

1 Airtight membrane 1
INTELLO
INTELLO PLUS
5
2 Airtight membrane D
INTESANA Alternative
DA
12 2
11
3 Sealing tape
DA-S
2
11 11
A

4 Airtight
interior plaster layer 11

5 Adhesive tape Sealing at ground or ceiling slab with Air sealing to non-plastered areas
TESCON VANA interior insulation
TESCON No.1

6 Adhesive tape (double-sided)


DUPLEX 4
4
connect technology
(integrated self-adhesive zones) 8 9 10 7 8 9

7 Sealing tape
TESCON PROFIL

Window sealing tape


8 CONTEGA SL*)
9 CONTEGA FC*)
10 CONTEGA IQ*)
4 4
11 Joint adhesive
ORCON F
ORCON CLASSIC
Sealing at windows, at the side of Sealing at windows, on the frame,
ORCON LINE
the frame, masonry wall masonry wall
12 ISO filling layer or plaster not
applied as far as bottom

13 Beam

14 Rafter

Info
*) Fold tape into the corners of
the window. Stick tape to the
airtightness layer in an airtight
manner after this layer has
been installed.
Gypsum plasters have very good
adhesion on CONTEGA fleece.
A bonding bridge e.g. a rein-
forcing mortar must be used
for lime and cement plasters.

pro clima 02.2014 | www.proclima.com 12


Interior Construction Air sealing with external roof insulation

Air sealing with external


roof insulation
Alternative Tips
A Clean the subsurface care-
fully. Bind particulate dust
with an undercoat of TESCON
2 PRIMER AC or TESCON
PRIMER RP where necessary.
2
B If more than 20 % of the
5 thermal insulation (of total
6 thermal resistance) is located
before the vapour retarder,
diffusion verification is to be
carried out where necessary.

C Ensure that the joint


Sticking membrane overlaps between the base purlin and
the rafter is sealed.

D Adhesive tape plastered over

E Corners with TESCON INVEX


2
2 11

7
B 2
7
11 E
11
13 3 13

11 11
C

14 14

4 4

Sealing at knee wall Sealing at knee wall


(offset main rafter) (continuous main rafter)

In the case of over-rafter insulation, the


airtightness layer must be planned in detail in
advance, particularly in joint areas. Careful in-
stallation is essential, as testing of the airtight-
ness is only partially possible with overpressure
and artificial fog for example, using pro clima
WINCON as the airtightness layer is no longer
directly accessible.

13 pro clima 02.2014 | www.proclima.com


Air sealing with external roof insulation Interior Construction

Air sealing with external roof insulation continued

Legend

1 Airtight membrane
INTESANA

2 Airtight membrane
DA
1 2
11 10 9 9 1 2
3 Airtight interior plaster layer 7 7

4 Adhesive tape
TESCON VANA
TESCON No.1
3 3
5 Sealing tape
TESCON PROFIL
TESCON INCAV in corner areas Sealing at bargeboard with Sealing at bargeboard with
interrupted boarding interruption at first visible rafter
6 Plaster sealing tape
CONTEGA PV*)
Alternative
7 Joint adhesive
ORCON F
ORCON CLASSIC
ORCON LINE

8 Pipe grommet
ROFLEX**) 7
1 2 6 1 2
9 Wooden decking

10 Mortared wall cap


3 3
11 Roof lath

12 Roof sealing
Sealing at bargeboard, interior

Info

*) Gypsum plasters have very


good adhesion on CONTEGA
fleece. A bonding bridge e.g.
2
a reinforcing mortar must 1
be used for lime and cement 5
plasters. 5 4
5
**) Alternatively, pipes can be A
4
sealed using short strips of 1 2 1 2
TESCON VANA or TESCON No.1. 2
1

Sealing at skylights - Longitudinal Sealing at skylights


section Cross-section

pro clima 02.2014 | www.proclima.com 14


Interior Construction Air sealing with external roof insulation

Alternative Tips
A For sealing at skylights,
pro clima DA or INTESANA must
protrude sufficiently from the
roof surface so that they can be
attached to the frame of the
4 window using a strip of vapour
8 retarder.
4 Alternatively, the membrane can
4
be extended with an additional
strip of vapour retarder as far as
2 2
1 1 the window frame. Sealing to
the window frame is carried out
using pro clima TESCON PROFIL.

Pipe or cable feed-throughs There must be no tensile loading


on the sealing due to the weight
of the thermal insulation. If
necessary, the insulation should
Please also observe the general infor- be supported by a substructure.
mation on sealing to chimneys on page
8. B Stick overlaps in the vapour
retarder in corner areas using
2 pro clima TESCON No.1 /
7 1 TESCON VANA.
B,C,D
C Clean the subsurface care-
fully. Bind particulate dust with
B,C,D 7
an undercoat of TESCON PRIMER
AC or TESCON PRIMER RP where
2 necessary.
1
3 3
D The bond between the vapour
retarder and smooth, pore-free,
non-sanding pre-fabricated
Sealing to chimneys
chimneys can also be carried out
using TESCON VANA or TESCON
No.1. If necessary, apply primer
to the sub-surface here too.
1 2 3
E Under certain circumstances,
additional insulation with hygric
E separation may be necessary.
12 Contact our Engineering Hotline
9
for a release. > Call:
+49 (0) 62 02 27 82.0

1
9

(1) Membrane only (2) Gravel (3) Green roof

Vapour retarder for diffusion-tight


flat roof

15 pro clima 02.2014 | www.proclima.com


Air sealing for refurbishment projects Interior Construction

Refurbishment solutions
Air sealing for sub-and-top,
tub-shaped and renovation wallpaper
Legend
1 Airtight membrane 1 2 3
DASATOP

2 Airtight membrane
INTESANA
INTELLO 12
DB+ 6

A
7 6
2 3 6 2
3 Airtight membrane 8 7
7 8
DA 8
4 Vapour retarder membrane
SANTA
(1) Membrane only (2) Gravel (3) Green roof
5 Adhesive tape
TESCON VANA Vapour retarder, external installa- Flat roof, installation of vapour
TESCON No.1 tion, tub-shaped retarder, tub-shaped
6 Joint adhesive
ORCON F
ORCON CLASSIC

7 Joint adhesive
ECO COLL for DB+

8 Joint adhesive
14
ORCON LINE
13
9 Pipe grommet 1
ROFLEX*) 15
4
B
10 Cable grommet
KAFLEX

11 Rafter

12 Strap Vapour retarder, interior, Vapour retarder, external installation,


renovation wallpaper sub-and-top
13 Position held by 3-4 mm of
1 2 3
hard fibre or chipboard, for
example.

14 Doubling

15 Existing inner cladding


(airtight) 6
16 Purlin
1

Info

*) Alternatively, pipes can be


sealed using short strips of
TESCON VANA or TESCON No.1.

Sub-and-top installation
Sealing at bargeboard

pro clima 02.2014 | www.proclima.com 16


Interior Construction Air sealing for refurbishment projects

Tips

A Clean the subsurface care-


fully. Bind particulate dust
with an undercoat of TESCON
PRIMER AC or TESCON
1 PRIMER RP where necessary.
1

6 B The pro clima SANTA renova-


16
8 tion wallpaper fulfils the
C 6 16 function of a vapour retarder.
8 11 To ensure airtightness, the
C 6 subsurface (e. g. plaster on
8 11 Heraklith woodwool boards
or plasterboards) is to be
attached to the adjacent
Knee wall sealing, sub-and-top with Knee wall sealing, sub-and-top with components in a permanently
offset rafter continuous rafter elastic and joint-free manner.

C Ensure that the joint


between the base purlin and
the rafter is sealed.

1 1
2
2

9
5 10

Pipe feed-through for sub-and-top Cable feed-through for sub-and-top


and tub-shaped and tub-shaped

Please also observe the


general information on
sealing to chimneys on
page 8.
1 1
A
A

6 8 6 8

A A
6 8
6 8

1 1

Sub-and-top installation Sub-and-top installation


Sealing to plastered chimney Sealing to concrete chimney

www.proclima.de 17 pro clima 02.2014 | www.proclima.com


Air sealing for refurbishment projects Interior Construction

Refurbishment solutions
Air sealing at centre of structure
Legend
1 Over-rafter insulation
wood fibre underlay panel

2 Over-rafter insulation, mineral


fibre, wood or cellulose fibre, 1
2 1
flax, hemp 3
4 3 12 A
3 Airtight membrane A B
DASAPLANO 0.01 connect 11 11 11

13 14 13
4 Airtight membrane 14
DASAPLANO 0.50 connect

5 Adhesive tape
TESCON VANA
TESCON No.1 Standard structure, 1:1 solution **) Standard structure, 2:1 solution **)
6 Sealing tape
TESCON PROFIL
Sealing detail views show the 1:1
7 TESCON INCAV in corner areas structure with insulation cover con-
sisting of wood fibre underlay panels.
8 Joint adhesive E
ORCON F
Sealing for 2:1 structure is carried
out in an manner. 1 3
ORCON CLASSIC
ORCON LINE

9 Pipe grommet 11
ROFLEX* )
C
10 Cable grommet
KAFLEX 8
15
11 Fibrous compartment insulation

12 Fibrous, sorptive compartment


insulation, at least 4 cm Sealing at knee wall with offset
rafters
13 Laths

14 Inner cladding

15 Rafter
E
16 Wall cap 3
1
1
Info 3
F 11 16
8
*) Alternatively, pipes can be
11
sealed using short strips of C
TESCON VANA or TESCON No.1.
8
**) Different recommendations
may be made by the manufac- 15
turers of insulation materials; in
such cases, the manufacturers
recommendations apply. Sealing at knee wall with continuous Sealing at bargeboard
rafters

pro clima 02.2014 | www.proclima.com 18


Interior Construction Air sealing for refurbishment projects

Tips

A DASAPLANO 0.01 connect


with monolithic pore-free
membrane required.
3 Installation only possible with
3
wood fibre underlay panel
without additional underlay
10
9 membrane.
5 1
1
B In the case of 2:1 insulation
cover, a sorptive insulation
11 material (e.g. wood fibreboard
11 or cellulose) with a thickness
of at least 4 cm is required in
the space between the rafters
Pipe feed-through Cable feed-through directly underneath the
DASAPLANO 0.01.

C In vertical area, place as much


insulation as possible on the
cold side of the airtight
membrane.
3
D Clean the subsurface care-
D

3
D

8
8 fully. Bind particulate dust
with an undercoat of TESCON
11 D PRIMER AC or TESCON PRIMER
D 1
8 RP where necessary.
1 8
11 E Guide the underlay membrane
into the first panel joint.

F TESCON INVEX in corner areas

Sealing to plastered chimney Sealing to concrete chimney

Please also observe the


3
general information on
sealing to chimneys on
page 8.
5
6 7
6
1 7
5
5
3

11

1
11

Sealing at skylights Longitudinal Sealing at skylights Cross-section


section

19 pro clima 02.2014 | www.proclima.com


Additional system solutions for
sealing of the
building envelope
INTELLO maximum reliability system
INTELLO vapour retarder and air sealing system
Maximum protection against structural damage and mould
also for sophisticated civil engineering structures.
Interior air Humidity-variable sd value 0.25 to >25 m.
sealing

New protection for existing structures


the DASATOP system
The DASATOP sub-and-top refurbishment system
Optimised for roof restoration from the outside.
Refurbishm
and moderni ent Quick, simple, reliable!
sation

Best possible protection for roofs and walls


the SOLITEX system
Highly permeable roof lining and facade membranes
The best quality for reliable structures that are free of structural
Exterior win
d damage and mould for roofs and walls.
sealing

Secure bonding and detail solutions


All-round adhesive tapes and joint adhesives for interior and exterior use
Plaster sealing tapes
Sealing grommets

You can also visit Information and ordering


pro clima ONLINE! You can obtain information on all pro clima
systems, tender information and brochures
Further information and quickly and simply by contacting our
background information at information service:
Phone: +49 (0) 62 02 27 82.0
Fax: +49 (0) 62 02 27 82.21
eMail: info@proclima.com
www.proclima.com
The applications and conditions described here are based on current state-of-the-art research and practical experience. We reserve the right to change the recommended structures and
processing methods and to further develop and thus alter the quality of individual products. We would be glad to inform you about the current state of engineering knowledge at the time
that your installation is carried out.

MOLL
Further information about application and construction is given in the pro clima For Stockists contact
planning documentation and application recommendations. If you have any questions, Ireland baukologische Produkte GmbH
please call the pro clima technical hotline Ireland and UK: T. 046 9432104 Rheintalstrae 3543
F. 046 9432435 D-68723 Schwetzingen
Ecological Building Systems ltd.
UK Germany
2014-07 DIG-247

Main St, Athboy


T. 01228 711511 +49 (0) 62 02 - 27 82.0
Co Meath
F. 01228 712280
Phone: +353 469432104 +49 (0) 62 02 - 27 82.21
Fax: +353 469432435 info@proclima.com
info@ecologicalbuildingsystems.com
www.ecologicalbuildingsystems.com
www.proclima.com

Potrebbero piacerti anche