MT6070iP MT8070iP INSTALLATION INSTRUCTION

1. Installation and Startup Guide 2. Unpacking the Unit Note! 7. Calibration Mode
Unpack and check the delivery. If damage is found, 1. Connect positive DC line to the + terminal and Launch Project Manager, select MT6000/8000 iP Series
Read these instructions carefully before installing, notify the supplier. the DC ground to the - terminal. in Type field, select Ethernet or USB cable, and then click
operating or perform maintenance in this equipment. 2. Please do not connect HMI with PLC and PC Calibrate Touch Panel button to start calibration.
(1)
simultaneously to prevent potential difference from
This document covers the installation of destroying USB ports of HMI and PC.
MT6070/8070iP Series HMI, for the detailed (2)

specifications and operation, please refer to brochure 5. System Settings


and EasyBuilder 8000 user manual. (3) When HMI is powered up and displays image,
click the system setting button (default System
Install environment: (4) Password: 111111). It is necessary to connect the
MT6070/8070iP Series HMI HMI to your network through a RJ45 cable (N/A for
NEMA rating 1. Installation Instruction, 2-sided A4 *1 MT6070iP).
is NEMA 4 rated. 8. Communication Connections
MT6070/8070iP Series has
2. Human Machine Interface *1 Note!
been tested to conform to 3. Power Connector *1 Com2 (RS485 2 W) supports MPI 187.5K.
European CE requirements. 4. Brackets & Screws *1 pack
This means that the circuitry 9 pin, male, D-sub
is designed to resist the Note! COM1 (RS232)
Electrical environment effects of electrical noise.
Go to the Network tab, you may choose to auto get
Place the operator panel on a stable surface during DHCP IP, or designate your own IP. COM2 (RS485)
This does not guarantee installation. Dropping it or letting it fall may cause
noise immunity in severe
cases. Proper wire routing
damage.
and grounding will insure COM2 COM2
proper operation. 3. Installation Instructions COM1
PIN# Symbol (RS485) (RS485)
(RS232)
(1) Make sure that the displays Secure the operator panel in position, using all the 4W 2W
are installed correctly and fastening holes and the provided brackets and screws: 1 Rx- Rx- Data-
that the operating limits are
followed. Avoid installing units 2 Rx+ Rx+ Data+
in environments where severe (A) 3 Tx- Tx-
mechanical vibration
or shocks are present. 6. EasyBuilder 8000 Software 4 Tx+ Tx+
Cutout
(B)
(2) Do not operate the unit Settings 5 GND GND
in areas subject to explosion
hazards due to flammable
Launch EasyBuilder 8000 software, select your
6 TxD TxD
Environmental gases, vapors or dusts. project file, press F7 shortcut key to open the download
considerations (3) Do not install the unit where dialog box: for MT6070iP, select USB cable/For MT8070iP, 7 RTS RTS
acid gas, such as SO2 exists. select Ethernet>IP tab>Enter your HMI IP>Click Download 8 CTS CTS
Type A (mm) B (mm)
(4) This device should be to download this project file to HMI (please refer to
mounted in the vertical MT6070iP 192 138 EasyBuilder 8000 User Manual for software operation 9 RxD RxD
position and for use on the flat details).
surface enclosure. MT8070iP 192 138
(5) Conform to UL508
Software available free-of-charge at www.weg.net.
(ISBN 0-7629-0404-6)
machine safety for use 4. Power Connections
in Pollution Degree 2
Environment.

24 V dc FG

24 V dc
Cable Different cables are required for FUSING REQUIREMENTS!
requirement various devices. If the display does not come on within
Restrict cable length to less than 500 5 seconds of power up, remove power.
(150 m) for RS485/422 devices and An internal fuse will prevent damage if
50 (15 m) for RS232 devices to avoid the polarity of the DC power is incorrect.
communications problems. Check wiring for proper connections
Shielded cable must be used for long and try to power up again.
CAUTION! lengths or cables run in an electrically HIGH VOLTAGE!
noisy environment. An Internal fuse will prevent damage for
Do not run cables next to AC power overcurrent condition however it isnt
lines or near sources of electrical noise. guaranteed. DC voltage sources should
Be sure that the cable ends have been provide proper isolation from main AC
inserted all of the way into mating power and similar hazards.
connectors and are secure. EMERGENCY STOP!
HARDWARE CONSIDERATIONS! A hard-wired emergency stop
The system designer should be aware should be fitted in any system using
that devices in Controller systems HMI to comply with ICS Safety
could fail and thereby create an unsafe Recommendations.
condition. Furthermore, electrical SUPPLY VOLTAGE CONDITION!
interference in an operator interface Do not power the HMI and inductive DC
can lead to equipment start-up, which loads, or input circuitry to the controller,
could result in property damage and/or with the same power supply. Note: the
physical injury to the operator. 24 V dc output from some controllers may
If you use any programmable control not have enough current to power the HMI.
systems that require an operator, be
WIRE ROUTING!
aware that this potential safety hazard
1. Power wire length should be minimized
exists and take appropriate precautions.
(Max: 500 m shielded, 300 m unshielded).
Although the specific design steps
2. Please use twisted pair cables for
depend on your particular application,
power wire and signal wire and conform
the following precautions generally
to the impedance matching.
apply to installation of solid-state
3. If wiring is to be exposed to lightning
programmable control devices, and
or surges, use appropriate surge
conform to the guidelines for installation
suppression devices.
of Controllers recommended in
4. Keep AC, high energy, and rapidly
NEMA ICS 3-304 Control Standards.
switching DC power wiring separated
PROGRAMMING CONSIDERATIONS! from signal wires.
To conform with ICS Safety 5. Add a resistor and capacitor in the parallel
Recommendations, checks should be connection between the ungrounded
placed in the controller to ensure that DC power supply and the frame ground.
all writable registers that control critical This provides a path for static and high
parts of plant or machinery have limit frequency dissipation. Typical values to use
checks built into the program, with an are 1 M Ohm and 4,700 pF.
out-of-limit safe shut down procedure
to ensure safety of personnel.
Note!
Make sure that all local and
CAUTION! national electrical standards
are met when installing the unit.
Contact your local authorities to
determine which codes apply.
POWER!
The HMI can be powered by DC power
only, voltage range: 24 20% Volts DC,
compatible with most controller DC
systems. The power conditioning circuitry
inside the unit is accomplished by a
switching power supply. The peak starting
current can be as high as 2 A.