ABSTRACT
As we know, the term cogeneration means the combined production of electricity and thermal energy.
Undoubtedly, we are living at a time when the demand for energy is at its peak. Today, we cannot imagine
living without energy, whether it is electrical, thermal or of any other form. However, the production of
energy is not always friendly to the environment, especially when the raw material used for energy is heavy
oil, as in our case study. Last year Pristina, has started supplying thermal energy through cogeneration
project, project which has two thermal stations, one at the TPP Kosovo B (HES Heat Extracted Station)
where steam is extracted from medium and low pressure turbines and than heat exchange will take place
through a system of steam-water exchange at the heat exchanger , and the other station (HRS Heat Recived
Station) constructed at the District Heating Termokos where heat exchange will take place through a
system of water-water exchange. Surely the entire system is traversed by pre-insulated pipes of DN 600/800
with a total length of 11.4 km.
We focused on the role played by co-generation project on the preservation of the environment in general,
particularly in improving air quality, removing the production of thermal energy from heavy oil, and
replacing it with the installation of the system co-generation. Of course, in addition to many other benefits
that the project of co-generation has for the city, among the most important benefits is the improvement of
the air quality, considering that for 14 years, on average 12,000 of heavy oil were spent per season.
Also, we will analyse the thermal energy production in Prishtina throughout 14 years starting with the
heating season of 2001/2002 until the heating season of 2014/2015, when heating in Prishtina started
operating the new co-generation system
1. INTRODUCTION
During the burning of different fuels in air different pollutants are emitted, such as, sulfur
dioxide, carbon monoxide, nitrogen oxides and others who endanger the quality of the air.
Researching and monitoring air quality in urban and industrial areas is one of the basic steps of the
solution, where in most countries of the world, the problem of air polution is present. Monitoring
and controling air quality aims to reduce the content of harmful substances in it. Air pollution
affects not only air quality, but also indirectly the quality of groundwater, land, vegetation, forest
and climate [1].
In the city of Prishtina, air pollution appears from burning coal (lignite) in Kosovo power
plant and fuel oil combustion in the heat of the city, which releases a considerable amount of sulfur.
Conditions for maintaining air quality in this area are very unfavorable due to high emissions of
SO2, dust, and other pollutants, as well as due to unfavorable terrain.
XII-371
CYSENI 2016, May 26-27, Kaunas, Lithuania
ISSN 1822-7554, www.cyseni.com
The most reliable method for determining the emissions of pollutants discharged into the air is
measurement. The values obtained by measuring the concentration of SO2, NOx and CO gasses are
necessary to recalculate the content reference oxygen from 3% to 3% liquid fuel compared with the
limit values set out in the Regulation on limit values for emissions into the air from combustion
plants [2]. Emissions are calculated depending on the amount of fuel consumed and the
corresponding emission factor. For the calculation of emissions of pollutants the approach bottom-
up is used, by which the total emissions in any territory (region) is determined by the aggregation
(joining) of the emissions of all the individual sources in the defined territory.
In this paper our focus is on emissions caused by heating of Prishtina Termokos, as
enterprise specialized in providing heat. Data on the quantities of spent fuel (fuel oil) and measured
direct emissions of SO2, NOx and CO have been taken from the table overview of the measurement
results.The citys District Heating supplies about 12,000 customers (about 11,500 households
and 1,000 business entities-public institutions) [3]. This heating of hot objects approximately 1/5 of
Prishtina and the rest, heating use traditional fuels (wood, coal, fuel oil, oil, electricity, etc.). Two
years ago they started using cogeneration heating process in the city. This project is expanding and
it has has brought benefits to the city in terms of environmental protection because the heat is not
combustion in boilers, and therefore it has impacted environmental protection. Through this paper
we will demonstrate the importance of the project in providing heat cogeneration Prishtina city and
in reducing pollution.
For the heating of the city of Pristina crude oil of various qualities is used. Monitoring the
quality of liquid petroleum fuel is spread in three segments of control: Customs, the retail sales
points and deposits of petroleum importers. Method of determining the quality of liquid petroleum
derivatives and determination of their quality, appointed by the Administrative Instruction, is done
by lab. testing which applies standard testing methods.
Table 1. Physico-chemical analysis of heavy oil (mazut) for 20082011
Density Viscosity
Low heating
gr/cm3 cSt tn W S Ashes
Sample o value Hu,
C % % %
kJ/kg
50 oC 15 oC 100 oC 50 oC
1 0.929 0.951 29.1 225.8 187 0.030 1.400 0.040 42723
2 0.931 0.953 30.4 239.5 198 0.037 1.350 0.037 41185
3 0.929 0.951 29.1 225.8 187 0.030 1.400 0.040 42793
4 0.931 0.953 30.4 239.5 198 0.050 1.350 0.037 41185
5 0.955 0.976 9.2 74.1 132 0.030 1.870 0.043 36827
6 0.921 0.943 30.3 239.3 178 0.030 1.450 0.021 40787
7 0.924 0.946 29.7 233.1 175 0.030 1.310 0.028 41041
8 0.914 0.936 20.9 142.0 170 0.030 1.660 0.030 40946
9 0.924 0.946 29.3 227.7 179 0.030 1.540 0.020 41976
10 0.911 0.933 7.6 29.2 200 0.050 0.100 0.034 36450
11 0.928 0.950 30.6 241.3 188 0.041 1.510 0.050 41968
12 0.921 0.942 19.4 115.4 140 0.010 1.330 0.043 41353
13 0.910 0.923 24.3 75.6 190 0.020 1.190 0.035 41968
14 0.925 0.947 22.3 155.8 180 0.500 1.410 0.035 43015
XII-372
CYSENI 2016, May 26-27, Kaunas, Lithuania
ISSN 1822-7554, www.cyseni.com
From the statistical data on the content of fuel oil components Table 1, the table is arranged in
the form suitable for the respective anlalysis of calculated indicators: average value, maximum
value, minimum, median, fashion, variance and standard deviation. These calculations are made for
the purpose of determining the standard deviation and distribution of components for subsequent
analysis. The results obtained arranged are shown in Table 2.
Table 2. Cumulative features of heavy oil (mazut) analysis
S Ashes Hu
% % kJ/kg
Count 22 22 22
Maximum 1.87000 0.05000 43015
Minimum 1.19000 0.02000 36450
Average 1.45591 0.03636 41169
Median 1.42500 0.03700 41535
Mod 1.40000 0.03700 41185
Variance 0.01880 0.00005 2827082
Standard deviation 0.13710 0.00729 1681
Based on the results obtained from the observations during the analysis of the emissions of
boiler components, as well as of distribution and normal deviation, according to the following
equation , we can also obtain the equations of the normal distribution
f x
N
2
exp x / 2 .
2
(1)
After replacing the values of the statistical model of normal distribution curves we come up
with the following results for S, H and Hu:
f x S
22
0.13710 2
exp x 1.45591 / 2 0.13710 ,
2
(2)
f x H
22
0.0729 2
exp x 0.03636 / 2 0.0729 ,
2
(3)
f x Hu
22
1681 2
exp x 41169 / 2 1681 .
2
(4)
XII-373
CYSENI 2016, May 26-27, Kaunas, Lithuania
ISSN 1822-7554, www.cyseni.com
measurement is performed with electrochemical cells. Smoke gases analyzer with measurement
probes is shown in Fig. 1.
Table 3. Average limit values of emissions from heavy oil (mazut) boiler
The values of fuel consumption for heating seasons during 20042015 are given in Table 4,
and the values of thermal energy for the same period in Table 5.
Heating seasons Oct. Nov. Dec. Jan. Feb. Mar. Apr. Total
XII-374
CYSENI 2016, May 26-27, Kaunas, Lithuania
ISSN 1822-7554, www.cyseni.com
For the purpose of analysis the method for calculating emissions of pollutants discharged into
the air as follows is used: sulfur oxides expressed as sulfur dioxide (SO2), nitrogen oxides (NOx)
and carbon monoxide (CO) by CORINAIR (Core Inventory of Air emissions in Europe) [6]
emissions calculation methodology that provides accurate calculation, comprehensive and
sustainable emission of pollutants.
XII-375
CYSENI 2016, May 26-27, Kaunas, Lithuania
ISSN 1822-7554, www.cyseni.com
3.4. Emissions Calculating of ashes and gases thrown of the smoke stacg output
XII-376
CYSENI 2016, May 26-27, Kaunas, Lithuania
ISSN 1822-7554, www.cyseni.com
Fig. 2. The quantities of pollutants emitted into the air of the valley of Pristina by boilers during the
heating season (the period of six months)
Quantities emissions SO2, CO, NOx and ash function S, Hu and B for the respective borders
of smoke gases discharged from boilers are given in Fig. 3.
ES=f(B,S) ECO=f(B,Hu)
600 8000
500
6000
ECO [t/6muaj]
ES [t/6muaj]
400
300 4000
200
2000
100
0 0
2 4.5
15000 15000
1.5 10000 4 4 10000
x 10
5000 5000
1 0 3.5 0
S [%] B [t/6muaj] Hu [kJ/kg] B [t/6muaj]
EFNOx=f(B,Hu)
EA=f(B,S)
4
x 10
12
10
10
EFNOx [t/6muaj]
8
8
EA [t/6muaj]
6
6
4 4
2 2
0 0
4.5 0.06
15000 15000
0.04
4 4 10000 10000
x 10
0.02
5000 5000
3.5 0 0 0
Hu [kJ/kg] B [t/6muaj] S [%] B [t/6muaj]
Fig. 3. Emissions Quantites ES = F(B, S), ECO = F(B, Hu), ENOx = F(B, Hu), EA = F(B, S)
XII-377
CYSENI 2016, May 26-27, Kaunas, Lithuania
ISSN 1822-7554, www.cyseni.com
According to the analysis of the results obtained, we can see that the average values of SO2
emissions from boilers reach a value of 255.32 tons / 6 months. Emissions of CO, reach the average
values of 3629.0 tonnes / 6 months. Nox emissions achieve the average values of up to 60165.58
tons / 6 months, while the average values of grace and average value dross 3.21 mark ton / 6
months. Maximum contamination occurred in the heating season 2004/05 amounts of pollutant
emissions as follows:
Total SO2 emissions = 406.41 t / 6 m,
Total emissions of CO = 5804.08 t / 6 m,
Total NOx emissions = 18 779 t / 6 m,
Total emissions of ash and 5.11 dross = t / 6 m.
5. CONCLUSION
According to indicators of overall emissions of SO2, NOx and CO, obtained based on the
measurement, analysis and calculation methodology CORINAIR it is noted that much greater
emissions are from the boilers. The main cause of the increase of SO2 emissions from boilers is
sulfur content in fuel oil. The main causes of increased emissions of CO are inadequate combustion
conditions and the condition of the combustion chamber and chimney. Overall emissions of NOx
boilers are lower than the estimated value of the boiler as a result of low temperatures in the
combustion chamber. High emissions of CO discharged from boilers are due to poor combustion
and therefore it is necessary to take appropriate technical and technological solutions to reduce
emissions of CO to protect public health. NOx emissions are minimal, and SO2 emissions occur as a
result of fuel quality and low temperatures in the combustion chamber. The average values of SO2,
CO and NOx from fuel oil to heat the boilers are significantly lower than the prescribed limit
values, which can be seen from Tables 1 and 3. Limit values for emissions of gaseous pollutants are
mainly the result of fuel quality and combustion conditions, namely the relatively good technical
condition and technological boiler.
From the results obtained, we suggest that the extension of heating network for the city of
Pristina should intensify and increase the capacity of the system of cogeneration and reduce the
number of boilers and bodies heating with solid fuels and liquid in parts of the city of Prishtina.
6. REFERENCES
1. ZHONGCHAO, T. Air Pollution and Greenhouse Gases From Basic Concepts to Engineering
Applications for Air Emissions Control. Springer Singapor + Business Media Singapore 2014.
2. Law on integrated prevention pollution control: LAW NO. 03/L-043.
3. District Heating Termokos JSC Prishtin Data from archive of D.H Termokos (schemes
of principle operation and information materials).
4. BIRHADIC, V., SISIC, M., GOLETIC, ., IMAMOVIC, N. Comparative analysis of the
measured and calculated values of air emissions from local boiler. Nauno-struni skup sa
meunarodnim ueem KVALITET 2013, Neum, B&H, 06. 08. Juni 2013.
5. www.testo350.com Portable Emission Analyzers.
6. www.eea.europa.eu European Environment Agency.