Sei sulla pagina 1di 77

N-Series

Automatic Circuit Recloser


with Advanced Controller

Installation and Maintenance Manual


Notices

Scope of this This document describes the installation and Automatic Circuit Recloser with Advanced
Manual maintenance procedures for the N-Series Controller.

Limitations This document is copyright and is provided solely party, nor to be used as the basis of a tender or
for the use of the purchaser. It is not to be copied specification without the express written
in any way, nor its contents divulged to any third permission of the manufacturer.

Disclaimer The advisory procedures and information Consequently, this Manual is offered as a guide
contained within this Manual have been compiled only. It should be used in conjunction with the
as a guide to the safe and effective operation of customers own safety procedures, maintenance
products supplied by Nu-Lec Industries Pty Ltd. program, engineering judgement and training
qualifications.
It has been prepared in conjunction with
references from sub-assembly suppliers and the No responsibility, either direct or consequential, for
collective experience of the manufacturer. injury or equipment failure can be accepted by Nu-
Lec Industries Pty Ltd resulting from the use of this
In-service conditions for use of the products may
Manual.
vary between customers and end-users.

Copyright 2005 by Nu-Lec Industries Pty Ltd.


All rights reserved. No part of the contents of this
document may be reproduced or transmitted in
any form or by any means without the written
permission of the manufacturer.

iii
N-Series Automatic Circuit Recloser

iv
Contents

Contents

1 Scope of this Manual....................................... 1-1 Customer Compartment.................................................6-2


General ......................................................................... 1-1 7 Operator Control Panel ................................... 7-1
Equipment Versions Covered by this Manual ............... 1-1 Description .....................................................................7-1
Software Identification................................................... 1-1 Display Groups ..............................................................7-2
Abbreviations ................................................................ 1-1 Custom Menu.................................................................7-3
2 Introduction...................................................... 2-1 Changing Settings........................................................7-3
Terminology .................................................................. 2-3 Operator Settings.........................................................7-3
3 Installation........................................................ 3-1 Password Protected Settings.......................................7-3
Contents of Crate .......................................................... 3-1 Protection Settings .......................................................7-3
Unpacking Procedure.................................................... 3-1 Navigating Within Display Groups .................................7-3
Control Cable Connection ............................................. 3-1 Page Layout...................................................................7-3
Testing & Configuring.................................................... 3-2 Quick Keys.....................................................................7-4
Transport to Site............................................................ 3-2 Quick Key Configuration ..............................................7-4
Site Installation.............................................................. 3-2 Using a Quick Key .......................................................7-4
Tools Required............................................................ 3-3 8 Event Log.......................................................... 8-1
Parts Required (Not supplied by the manufacturer).... 3-3 Display Updating............................................................8-1
Site Procedure ............................................................ 3-3 Event Log Format ..........................................................8-1
Cable Tail Connections ............................................... 3-4 Using the ALT Key .......................................................8-1
Surge Arrester Mounting and Terminating .................. 3-5 Typical Event Log Displays............................................8-1
Earthing....................................................................... 3-5 9 Power System Measurements ........................ 9-1
LV Auxiliary Power from Mains ................................... 3-6 Power System Frequency..............................................9-1
LV Auxiliary Power from Dedicated Utility Trans......... 3-6 Real Time Displays ........................................................9-1
Auxiliary Power from Integrated Transformer ............. 3-6 Maximum Demand Indicator ........................................9-2
4 Comms and Accessories Installation ............ 4-1 10 Maintenance .................................................. 10-1
Radio Antenna .............................................................. 4-1 ACR Maintenance........................................................10-1
Protection of Radio Equipment ................................... 4-1 ACR SF6 Recharging ..................................................10-1
The Customer Compartment......................................... 4-2 Safety.........................................................................10-1
Connecting to the Terminal Block ............................... 4-2 Procedure ..................................................................10-1
Radio/Modem Power................................................... 4-2 ADVC Maintenance .....................................................10-3
IOEX2 Installation ......................................................... 4-3 Cleaning.....................................................................10-3
Communication Ports.................................................... 4-3 Battery Replacement .................................................10-3
RS232 ......................................................................... 4-4 Battery Heater Accessory ..........................................10-3
RS485 ......................................................................... 4-4 Door Seal ...................................................................10-3
V23 FSK...................................................................... 4-5 Battery Care.................................................................10-4
Ethernet....................................................................... 4-5 Abnormal Operating Conditions...................................10-4
Windows Switchgear Operating System (WSOS)......... 4-5 Low Power Mode .......................................................10-4
SCADA Protocols.......................................................... 4-6 Excess Close Operations...........................................10-4
5 Testing Your Installation .............................. 5-1 Fault Finding ................................................................10-4
Powering Up the ADVC................................................. 5-1 ADVC Check ..............................................................10-4
Battery........................................................................... 5-1 Replacement of Electronic Modules and Upgrades.....10-5
Connection between the ADVC and the ACR............... 5-2 11 Ratings and Specifications .......................... 11-1
Auxiliary Supply............................................................. 5-2 Equipment and Crating Dimensions ............................11-1
Work Tag....................................................................... 5-2 ACR .............................................................................11-1
Terminal Designation and Phase Rotation.................... 5-3 Breaking Duty ............................................................11-3
Setting Power Flow Direction ........................................ 5-3 Duty Cycle..................................................................11-3
Tripping and Closing ..................................................... 5-3 Bushing Boots............................................................11-3
Enable/Disable Switches............................................... 5-3 HV Cables..................................................................11-3
Mechanical Trip............................................................. 5-4 Current Transformers.................................................11-4
Secondary Injection Testing.......................................... 5-4 Environmental ............................................................11-4
Primary Injection Testing............................................... 5-4 ADVC ...........................................................................11-4
Power Flow Direction Testing ....................................... 5-4 General Specifications ...............................................11-4
On Load Checks ........................................................... 5-5 Power System measurements ...................................11-6
6 Control Electronics Operation........................ 6-1 SF6 Gas Pressure Measurement ................................11-6
Sealing & Condensation................................................ 6-1 App A Replaceable Parts & Tools................A-1
Auxiliary Power Source ................................................. 6-1 App B Dimensions ........................................B-1
Controller....................................................................... 6-1 App C Safety Data Sheet - Sulphur
PSU Module ................................................................ 6-1
CAPE Module.............................................................. 6-1
Hexafluoride..................................................C-1
Operator Interface/ Door Assembly............................... 6-2 Index................................................................ Index-I
WSOS Interface .......................................................... 6-2

v
N-Series Automatic Circuit Recloser

vi
Scope of this Manual

1 Scope of this Manual

General This manual describes the installation and Inevitably, not all details of equipment are
maintenance of the N-Series Automatic Circuit provided nor are instructions for every variation
Recloser and the Advanced Controller. or contingency during installation, operation or
Whilst every care has been taken in the maintenance.
preparation of this manual, no responsibility is
taken for loss or damage incurred by the For additional information on specific problems
purchaser or user due to any error or omission or requirements, please contact the
in the document. manufacturer or your distributor.

Equipment This manual applies to the following equipment:


Versions
Covered by N-Series Automatic Circuit Recloser N15 N27 N38-12.5 N38-16
this Manual
Advanced Controller ADVC

The model number is shown on the equipment applicable. Please contact the manufacturer or
rating plate. If your equipment does not show your local distributor.
one of these model numbers, this manual is not

Software The software loaded into the ADVC is identified The software version is shown on the Operator
Identification by its version number which has the form: Control Interface Switchgear Wear/General
Details page, in the field App.Ver:
AXX-XX.XX.
This precisely identifies the software loaded into
the microprocessor on the controller. - - - - - Switchgear Wear/General Details - - - - S
U Contact 100.0% Cubicle S/N 1234
In order to obtain effective technical support V Contact 100.0% App.Ver A41-01.01
from the manufacturer or your distributor it is W Contact 100.0%
vital to record the software version and to quote
these when making your inquiry. Without this
information it is impossible for our customer
See Section 7 (page 7-1) to find out how to use
service department to identify the software and
the Operator Control Panel.
provide correct support.

Abbreviations The following abbreviations are used in this


document:

ACR Automatic Circuit Recloser OCP Operator Control Panel


ADVC Advanced Controller PCOM Protection and communications module
BDU Basic Display Unit PSU Power supply unit
CAPE Control and protection enclosure PTCC Pole top control cubicle
CT Current Transformer SCEM Switch cable entry module
CVT Capacitive Voltage Transducer SWGM Switchgear module
MCB Miniature Circuit Breaker WSOS Windows Switchgear Operating System

Symbols The warning symbol indicates that the


adjacent text contains a warning.
The navigation symbol indicates that
the adjacent text contains OCP
navigation information. The caution symbol indicates that the
adjacent text details a situation in
The note symbol indicates that the
which care should be taken.
adjacent text contains information for
your particular attention.

1-1
N-Series Automatic Circuit Recloser

1-2
Introduction

2 Introduction
The N-Series remotely controlled and monitored the ACR is connected to the Advanced
automatic circuit recloser consists of an N- Controller (ADVC) via a control cable
Series automatic circuit recloser (ACR) through the base of the ADVC
combined with an Advanced Controller (ADVC). the ACR can be connected into an insulated
The N-Series ACR or bare conductor system.
consists of vacuum interrupters in a sealed, The ADVC reads and displays the information
stainless steel tank which is stored in the ACR and provides
protection and communication properties for the
the tank is filled with sulphur hexaflouride
ACR. The ADVC
(SF6) gas
consists of:
a pressure transducer is used to monitor gas
pressure in the tank an operator control panel mounted in the
door,
surge arresters can be directly fitted to the
an electronic switchgear controller that
ACR and should be fitted at installation
monitors the ACR, and provides
voltages are measured on each of the 6 communication and protection functions,
bushings
a power supply which also supplies power
current is measured on each phase for customer equipment,
the ACR itself retains information such as an accessories and customer equipment
serial number, switchgear type, operations compartment,
and contact wear, independently of the is powered by an auxiliary voltage supply of
ADVC 110, 220, or 240 volts AC.
the ACR can be tripped from the ground by a is connected to the ACR via a detachable
hookstick and then be locked out by opening control cable.
the isolating switches located on the ADVC.
The customer compartment provides ample
a clearly visible, external pointer shows room for equipment. Standard communications
whether the ACR is tripped or closed. cables can be used for connection to the
The ACR field-fitting kit includes a polymeric communications ports on the ADVC and power
bushing boot and predetermined length of 120 is readily accessible from the programmable
mm,185 mm, or 240 mm aluminium, insulated power terminal block. (Please refer to
water-tight cable tail rated at 250A, 400A, 630A Communications and Accessories Installation
for each of the six bushings. on page 4-1.)

2-1
N-Series Automatic Circuit Recloser
.

Figure 1: N-Series ACR Construction

2-2
Introduction

Customer
Equipment and
Accessories
Compartment

Control and
Protection
Enclosure
(CAPE)

Operator
Control
Panel (OCP)

Batteries

Power
Supply
Unit (PSU)

Figure 2: ADVC Components

Terminology The N-Series recloser bushings are identified as


U1, V1, and W1 on one side, usually the source
side, and U2, V2, and W2 on the other, usually
the load side. (Source and load side are
configurable.) See Figure 3 (page 2-3).

Figure 3: ACR Bushings

2-3
N-Series Automatic Circuit Recloser

2-4
Installation

3 Installation

Contents of Each crate includes: ADVC (which will normally contain two
Crate batteries unless arrangements have been
ACR. made to ship batteries separately).
Pole mounting bracket with clamps if Control cable.
ordered. If a substation mounting bracket Six cable tails (where supplied by the
was ordered it will be attached to the outside manufacturer) pre-terminated with either a
of the crate. threaded lug to screw into the bushings
directly or with a flat lug for bolting to a palm
Six bushing boots with clamping rings
already fitted onto the bushings.
attached.
On receipt, the contents should be checked for
Six tubes of electrical silicone grease to fill shipping damage and the manufacturer
the bushing boots. informed immediately if any is found.
One clamping ring spanner to fit boots to the Ensure that the ADVC is stored
bushings. indoors until installation on site. If
storage outdoors is unavoidable,
caulking gun.
ensure that the ADVC is kept in an
The appropriate mounting kit. upright position.

Unpacking Tools required: Lift the complete mounting bracket out of the
Procedure Wrecking bar to remove nails. crate.
Four D shackles, two slings and crane with a Take great care not to drop the
safe working load of 300kg to lift the ACR. bracket, which weighs nearly 30kg
(66lb), onto the ACR.
Screw Driver or Battery Drill with 8mm
socket.
16mm Spanner or Socket. Fit D-shackles to the lifting points on the
Procedure: ACR and lift it out of the crate and on to the
ground using the crane.
Remove top of crate and lift out the control
Tip the crate on to its side and remove the
cable and bushing boots. Store carefully in a
HV cables.
clean dry place.
Remove the bolts securing the ADVC and
Unscrew and remove the four (4) screws
slide the unit from the crate.
located on the wall of the crate. The
mounting bracket, mounting kit and the two The control cubicle weighs
pieces of wood that the screws have just approximately 40 kg (88lb).
been removed from are all secured together.

Control Cable When installing or testing the ACR it is To disconnect: (1) Hold the plug by the short
Connection necessary to connect and disconnect the control sides and grip hard to release the clips inside
cable either from the ACR, the ADVC or both. the plug (not visible). (2) Wriggle the plug to
The control cable is plugged into the base of the allow the clips to release. (3) Then pull the plug
ACR and the other end into the ADVC at the out.
bottom, right-most socket on the Control and
Protection Enclosure (CAPE).
To do this successfully requires the correct
technique:
Power down the control cubicle by switching
off all MCBs. This should be done whenever
connecting or disconnecting the control cable.
To connect: hold the plug by the long sides,
check orientation, gently locate it on the socket
and push firmly home. Check it has locked by
wriggling the plug. If the plug cannot be
pushed on with moderate force then it has not
been located properly. Heavy force is never Figure 4: Handling the control cable plug
required.

3-1
N-Series Automatic Circuit Recloser
Never pull the plug out by the
cable.

Testing & The tests can be carried out on site or in the The LV auxiliary supply (if applicable) should be
Configuring workshop as preferred. connected as shown in Figure 6 (page 3-6).
Unpack the crate as above and put the HV Turn on the battery and auxiliary supply circuit
cables, boots and the control cable in a clean breakers at the bottom of the control cubicle and
safe place where they will not be damaged or carry out the following tests:
soiled. Make a temporary earth connection 1. Manual trip and close of the ACR.
between the ADVC and the ACR. 1mm copper
2. Insulation test the high voltage connections
wire is adequate for the purpose.
to earth to check for shipping damage on the
Raise the ACR using a crane or forklift in order high voltage side of the ACR.
to safely gain access to the bottom of the ACR. 3. Configure the protection settings.
Unbolt the cover plate 1 over the switch cable 4. Perform primary current injection as
entry module (SCEM) on the bottom of the ACR required.
5. Perform secondary current injection (if
required by your Authority) using a Test and
1 Training Set (TTS).
6. Fit and test a radio or modem if required.
7. Attend to the battery using the care
instructions given in Battery Care on
page 10-4.
Connecting the batteries with
reverse polarity will cause damage
and connect the ACR end of the control cable to
to the electronic systems.
the SCEM.
Lower the ACR on to props so that the control
An application note detailing workshop and field
cable is not damaged by being caught between
test procedures is available. Contact your agent
the base of the ACR and the floor.
or distributor.
Then connect the ADVC end of the cable to the
It may be desirable at this time to fit the cable
socket at the lower right-hand corner of the
tails and surge arresters to the ACR. See
CAPE located inside the ADVC cubicle. (See
Figure 5 (page 3-5).
Site Procedure, Step 15. on page 3-4.)

Transport to If the unpacking and testing was carried out in Disconnect the control cable from both ACR
Site the workshop then the ACR and ADVC must be and ADVC and put back the cover plate on the
transported safely to site. It is important the bottom of the ACR.
following steps are carried out:
Turn off all ADVC circuit breakers and Transport the ACR, ADVC and all parts in a
disconnect all auxiliary power supplies. safe and secure manner to site.

Site If you are replacing a pole-top control If the auxiliary supply is provided by an
Installation cubicle (PTCC) with an ADVC, the external VT connected through the ACR,
following should be considered: there are limitations to the supply ratings of
equipment that customers may fit. In ADVC,
The ADVC mounting points will be different1. General Specifications See Radio/Modem
Power Supply Continuous Power on
The connection to the auxiliary supply enters
page 11-5.
the cubicle at a different point.
Unlike the PTCC, the ADVC has locking
The earth stud is in a different position.
hinges on the door which prevent the door
Accessory cables may need extending. from swinging or blowing shut. When you
Unlike the PTCC which required an auxiliary open the door to 180, it locks into that
power supply rating of 50VA, the ADVC position. To close the door, disengage the
requires 100VA. hinge locks by raising the door slightly
before rotating it.

1. An accessory mounting bracket can be purchased to allow the use of the same mounting holes as were used with the
manufacturers PTCC. (Part No. 99800125)

3-2
Installation

Tools Required Torque wrench and metric socket set, Bushing boot clamping spanner, (supplied
normal engineers tools. by the manufacturer).
24mm Open ended drive to fit the torque
Tools to prepare pole as required.
wrench (commonly known as a Claw Foot).
This is only required with 630A cable tails Crane or other lift for ACR and ADVC, four D
which screw directly into the bushings and shackles and slings. A 1m spreader bar is
are tightened by a 24mm lock-nut. also useful, if the surge arresters are to be
Standard 300g cartridge applicator, fitted onto the ACR tank, to keep the slings
(Caulking Gun). away from the surge arresters when lifting.

Parts Required Two 20mm galvanised or stainless steel connection. See Figure 6 (page 3-6),
(Not supplied by bolts with washers and nuts etc. to bolt the Figure 8 (page 3-9) and Figure 9 (page 3-
the ACR mounting bracket to power pole. See 10).
manufacturer) Figure 7 (page 3-8). If the optional pole
20mm sealing cable entry glands to suit
clamps have been purchased this is not
auxiliary supply mains cables, 16mm sealing
required. cable entry glands to suit antenna or
Mounting parts for the ADVC. Either 20mm communications cable as required.
steel strapping or 10mm galvanised or
Antenna, antenna feeder cable, and surge
stainless steel bolts, nuts, etc.
arrester as required if a radio is fitted (unless
Fixing hardware for the control cable. This is
supplied by the manufacturer).
a 27mm (1 1/16) diameter sheathed conduit
and can be fixed to the pole with ties, straps, Aluminium jointing paste (250A and 400A
P-clips or saddles. cable tails only).
Earth wire and lugs for the earthing scheme Heat shrink or insulating tape (800A cable
and parts for LV mains auxiliary power tails only).

Site Procedure To erect and test the ACR and ADVC, carry out P1 1 on the SCEM located inside the
the following steps. Mounting details are given in ACR.
Figure 7 (page 3-8):

1. Transport to site and carry out testing prior to


erection as required. 1
2. Connect cable tails and surge arresters
before raising the ACR. See "Cable Tail
Connections" - page 3-4 and Surge Arrester
Mounting and Terminating on page 3-5.
3. Ensure that the pole is of sufficient strength
to support the ACR. A structural engineer See Figure 4 (page 3-1) for the correct way
may be needed to calculate the stresses to connect/disconnect the control cable.
involved. 9. Fit the retaining plate. 2

4. Securely mount the ACR mounting bracket


on the power pole.
2
5. Lift the ACR into position and lower it onto
the mounting bracket so that it sits on the The control cable retaining plate at
mounting bracket. See Figure 7 (page 3-8). the ACR end is differentiated by
6. Bolt the ACR to the mounting bracket with having one corner removed.
the four 12mm nuts and bolts provided.
Tighten to 50 Nm. 10. Run the control cable from the ACR down to
the ADVC.
7. Complete the high voltage connections as 11. If the ADVC is to be bolted to the pole, drill
shown in Figure 10 (page 3-11) or as the top hole and fit the bolt. If it is to be
appropriate for the site installation. strapped, feed the straps through the slots
8. Unbolt the SCEM compartment cover plate on the upper and lower mounting brackets.
from the bottom of the ACR. Remove the 12. Lift the ADVC into position and bolt or strap it
blanking plate and fit the control cable into to the power pole.
place. Connect the control cable to plug

3-3
N-Series Automatic Circuit Recloser
Note that the and then to the switchgear socket 2 on
ADVC mounts the CAPE.
have key holes as
shown here, so 2
that you can lift
the ADVC on to
16. For LV mains supply run auxiliary wiring as
the mounting bolt
shown in Figure 8 (page 3-9). Make the
and slide it into position.
connection inside the ADVC as shown in
When mounting the ADVC to a
Figure 6 (page 3-6).
wooden pole, use a spirit level to
ensure correct alignment, and 17. For LV supply from a dedicated transformer
minimise torque on the mounting supplied by the utility, connect as shown in
brackets. Figure 9 (page 3-10).
13. Attach the control cable to the power pole 18. For Integrated supply from an external
maintaining maximum available separation transformer, connect as shown in Figure 9
from the main earth bond (at 200mm for (page 3-10). (See also Auxiliary Power from
wood and concrete poles and 150mm for Integrated Transformer on page 3-6.)
steel poles). Ensure that there is enough 19. Power down the ADVC by switching off all
cable available at each end to permit MCBs. Note that this should be done
connection to the equipment. whenever connecting or disconnecting the
14. Run the earth connections as described in control cable from the ADVC.
"Earthing" - page 3-5. 20. Fit the batteries if they are not already in
It is vital that the earthing scheme place.
is carried out as described. Fitting the batteries with reverse
polarity will cause damage to the
electronic systems.
15. Connect the control cable from the ACR
through the base of the ADVC 1 21. If communications equipment is to be
installed go to Communications and
Accessories Installation on page 4-1.
22. Otherwise go to Testing Your Installation on
page 5-1.

Cable Tail HV cables are supplied in one of two forms: Push the boot down the cable to a distance
Connections Fitted with a lug to be bolted to a factory fitted approx. 1 metre from the termination (place a
palm on the end of the bushing (250 or 400A). small amount of grease on the closed end of
the boot to assist the boot to slide down the
Fitted with a threaded termination that is
cable). Fill the bushing boot with the silicone
screwed into the bushing (630A).
grease provided, starting at the closed end and
In both cases the procedure is to attach the finishing approx. 60 mm from the open end of
cable to the bushing and then cover with the the boot. Hint - as you fill the boot with grease,
bushing boot as detailed in the following keep sliding it down the cable as this pushes
sections, refer to Figure 5 (page 3-5). the grease up into the boot.
The bushing is supplied clean, and is
For cables terminated with a screw thread,
protected with a plastic cap. Ensure the cap is
ensure the thread, locknut and bushing
undisturbed and the bushing body and tin
plated central conductor or palm are clean and surfaces are clean and dry. Screw the tail into
undamaged. If the bushing has become soiled, the bushing by turning the whole cable tail.
clean it with methylated spirits. Sand or brush Tighten to 60 Nm using a spanner across the
the aluminium palm to remove oxide. brass locknut fitted. Take care to apply only
twisting forces to the terminal (no shear force)
Grease the bushing and the conductor with the
because of cable stiffness, cross threading is a
silicone grease provided (part number
possibility.
LUB058044).
Unpack the cable tail and bushing boots. For cables terminated with a lug, smear with
Check that the cable termination and the boot aluminium jointing paste and bolt the lug to the
are clean and undamaged. If necessary, clean bushing palm with the bolt provided and
with methylated spirits. tighten to a maximum of 62-65 Nm.

3-4
Installation
Grease the surface of the bushing, slide the
bushing boot down over the bushing while
rotating the boot to and fro. Fix into place using
the clamping ring and spanner provided. The
bottom of the boot should be firmly seated on
the top of the ACR tank. During the clamping
process silicone may bleed from the top of the
boot where the cable tail comes out. This is
normal and can be assisted by sliding a small
screwdriver into the boot alongside the cable
tail. Silicone grease will also come out around
the bottom of the bushing. This is normal.
Wipe off excess silicone grease with a clean
cloth.

The insulated cables supplied by the


Figure 5: Cable Tail Installation manufacturer are rated for use at the following
voltages and ratings:

Up to 15kV 100mm minimum clearance phase to phase, or phase to earth

>15kV to 38kV 150mm minimum clearance phase to phase, or phase to earth

Smaller clearances may cause degradation of


cable insulation.

Surge Arrester The ACR is type tested for Impulse Withstand brackets using the holes provided. Top holes are
Mounting and Voltages up to 170kV depending on the model. 12mm diameter, side holes are 16mm diameter.
Terminating See "Ratings and Specifications" - page 11-1 In this way most types of surge arrester can be
When there is a possibility that lightning or accommodated.
network switching conditions may produce peak The brackets are tilted to maximise phase/
voltages in excess of 70% of the Impulse phase clearance. The user should check that
Withstand Voltage, the manufacturer phase/phase and phase/earth clearance will be
recommends the use of suitably rated surge sufficient for their particular surge arresters and
arresters connected to each terminal of the line voltages. For some types of side clamping
ACR. surge arresters, the phase/earth clearance may
The arresters should be mounted on the be insufficient at the centre phase on the pole
mounting brackets supplied by the manufacturer side at higher voltages. In this case the surge
and earthed as described in Figure 8 (page 3-9). arrester can be mounted on the side of the
power pole or an increased clearance ACR
If the arresters are not mounted
mounting bracket fitted.
close to the ACR the protection they
provide is significantly reduced. Connections from the surge arresters to the
cable tails can be made by stripping off the
Lightning induced damage to the ACR or ADVC cable tail insulation and using a parallel or T
voids the warranty if surge arresters are not type clamp to make the connection to the cable
fitted. tail. The connection should be made far enough
up the tail so that phase/phase and phase/earth
Mounting brackets are provided for surge clearances are maintained. The cable tail is
arresters on the tank of the ACR. This is watertight1, so additional water blocking where
illustrated in Figure 10 (page 3-11) and Figure 7 the insulation has been removed is not required,
(page 3-8). however it is good practice to tape the joint
The surge arresters can be mounted on top of using a bitumen or mastic tape, to maintain the
the brackets or clamped to the side of the cabling system insulation.

Earthing Figure 8 (page 3-9) shows the earthing common This arrangement earths the ACR frame and the
to all installations. surge arresters directly to earth through a main

1. The 800A cable is not water-blocked, so must be taped.

3-5
N-Series Automatic Circuit Recloser
earth bond consisting of a copper conductor of the ACR frame and control cubicle frame whilst
70 sq. mm. Any surges will flow down this path. surge currents are flowing down the main earth
Do not earth surge arresters by a bond. No other connections to earth from the
different path, doing this may control cubicle are allowed since surge currents
cause damage to the control will also flow in those paths. Follow this
electronics or ACR. Also, any arrangement on both conducting and insulating
antenna should be bonded to the power poles.
ACR or the main earth bond.
The control cubicle is connected to this main Keep the main earth bond physically separated
earth bond by a tee-off. The control cubicle from the control cable, as they run down the
electronics are internally protected from power pole, by the maximum spacing available
potential differences which may occur between and at least 150mm.

LV Auxiliary Where LV mains are connected to the control cubicle when surge currents are flowing. Fit
Power from cubicle to provide auxiliary power the additional LV surge arresters to all the other LV
Mains connection must connect the neutral of the LV phases (if they exist), to balance the supply for
system to a tee-off from the main earth bond as other users connected to the LV system.
shown in Figure 8 (page 3-9). A low voltage If local conditions or wiring rules prohibit
surge arrester must also be fitted from the LV bonding the HV and LV systems in this way,
phase connection to this tee-off. providing the auxiliary supply to the control
This connection scheme bonds the LV and HV cubicle from the LV mains system is not
earths and so protects the primary insulation of possible. Instead, use one of the alternative
the auxiliary supply transformer in the control arrangements detailed below.

Figure 6: LV Auxiliary Supply Connection

LV Auxiliary Figure 9 (page 3-10) shows wiring and earthing Figure 9 (page 3-10) shows that the transformer
Power from if a dedicated transformer is supplied by the and any steelwork is earthed to the switchgear
Dedicated utility. Note that this should not be used to tank and that one side of the transformer
Utility supply any other equipment without consulting secondary is earthed to the earth stud on the
Transformer the manufacturer to ensure that no hazard is equipment panel inside the control cubicle.
caused to the control cubicle electronics.

Auxiliary Power The manufacturer can provide a dedicated An external transformer is mounted on the front
from Integrated voltage transformer outside the ACR tank which of the tank as shown in Figure 9 (page 3-10)
Transformer connects directly into the control electronics. which also shows suggested HV connections.
This is called an Integrated Auxiliary Supply. The secondary of the external transformer
connects into the SCEM on the underside of the

3-6
Installation
ACR. To connect the transformer secondary, No additional earthing for Integrated Auxiliary
remove the SCEM compartment cover plate, Supply is required in addition to the common
pass the cable which is pre-fitted with a cable earthing shown in Figure 9 (page 3-10).
gland through the hole, secure the gland, If the secondary of the VT is
connect the auxiliary supply to the screw earthed, electronics damage will
terminal block on the SCEM and replace the occur.
compartment cover.

3-7
N-Series Automatic Circuit Recloser

Figure 7: ACR Mounting and Dimensions

3-8
Installation

Figure 8: Common Earthing and LV Supply

3-9
N-Series Automatic Circuit Recloser

Figure 9: Utility Auxiliary Transformer

3-10
Installation

Figure 10: HV Termination

3-11
N-Series Automatic Circuit Recloser

3-12
Communications and Accessories Installation

4 Communications and Accessories Installation


Ensure that the ADVC is switched
off before proceeding with the
installation of any accessory.

Radio Antenna Mount the antenna and run the antenna feed to antenna, enters the cubicle via the 16mm hole
the ADVC or run external communications cable provided on the underside of the cubicle.
to the ADVC. The communication cable/radio

Comms cable/
Radio Antenna
Entry

Underside of
cubicle

Figure 11: Cable Entry

Protection of It is highly advisable to connect a gas discharge A feed-through or bulkhead type arrester fitted
Radio type of surge arrester in the antenna feed to the to the bottom of the control cubicle is ideal. If
Equipment radio. Failure to do so will result in loss of radio fitted internally the surge arrester should be
and control electronics protection which could earthed to an equipment panel mounting stud by
lead to complete electronic failure due to
the shortest possible wire. Holes are provided
lightning activity.
for a bulkhead surge arrester.
A failure of this nature is not covered
by the products general warranty If a surge arrester is not fitted then the co-axial
arrangements. earth screen should be earthed to the
equipment panel by the shortest possible wire.

4-1
N-Series Automatic Circuit Recloser

The Customer At the top of the customer equipment Equipment installed in this compartment can be
Compartment compartment is an accessory mounting rail for powered from the terminal block also mounted
installing customer equipment and accessories. on the rail.

Radio
Supply
(+)Terminals
IOEX
Supply
(+)Terminals
Heater
Supply
(+)Terminal
(-)Terminal Earth
(-)Terminals

Figure 12: Accessory Mounting Rail

Connecting to Insert a 4 mm screwdriver or similar tool into the be inserted. Release and remove the
the Terminal square hole above the appropriate wiring point screwdriver then gently tug the inserted cable to
Block on the terminal block. Angle the head of the ensure that it is firmly gripped.
screwdriver slightly upwards and push it in, then
lever it downwards.

Figure 13: Ins


erting a screwdriver into the wiring clamp Figure 14: Inserting stripped cable end
into wiring point
This action will correctly position the wiring
clamp so that the stripped end of the cable can

Radio/Modem The battery-backed power supply for a radio/ If the auxiliary power fails, battery power can be
Power modem is provided on the terminal block as conserved by automatically shutting down the
described above1. See Figure 12 (page 4-2) for radio/modem power supply. The shutdown takes
the correct radio connection point. place after the radio holdup time, set in System
The radio/modem power supply voltage is set by Status RADIO - S: Radio Hold 60 min. page by
the user in System Status the user, has elapsed. If the Radio Hold time is
RADIO - S: Radio Supply 12 Volts page. This is set to zero then the radio supply will not
a password protected parameter. shutdown, except under special circumstances

1. The power supply is not isolated.

4-2
Communications and Accessories Installation
or until the unit powers down. The radio/modem without passwords in System Status
power supply is restored when the auxiliary RADIO - S: Radio Supply ON page. If the radio
supply returns to normal. supply has shutdown it will be indicated on
The radio/modem power supply can be turned System Status: RADIO - S.
on and off by the operator for radio maintenance

IOEX2 The Input Output Expander (IOEX2) module enclosure which is mounted on, and earthed via,
Installation provides optically isolated inputs and voltage the DIN rail in the customer enclosure as shown
free outputs to allow connection to external in the following picture: (See Appendix B for
devices. It is installed in a die cast, sealed IOEX2 dimensions.)

Earth
(-)Terminals
IOEX2 Power Supply

RS232 Controller Port

Figure 15: IOEX 2 Module

The IOEX2 is suspended from the DIN rail by To fit the IOEX2:
two fittings on its rear surface:
1 Holding the IOEX2 perpendicular, place the
upper hooks of the hanging fittings over the
top edge of the DIN rail.
2 Push the IOEX2 firmly against the back
surface of the Customer compartment until
the lower end of the hanging fittings engage
with the bottom edge of the DIN rail.
3 Push the green/yellow earth terminal firmly
on to the DIN rail until it is engaged at both
the top and bottom.
4 Connect the IOEX2 supply using the cable
provided to the terminal block connection
point as shown in Figure 12 (page 4-2).

5 Connect the communications cable to Port B


on the CAPE. This RS 232 port is assigned
Figure 16: Rear of IOEX 2 Module by default to the IOEX2. Excess cable
should be run through the cable duct.

Communication The ADVC has numerous communications ports Not all ports are available for use at the same
Ports available to the user: time. The ports can be enabled/disabled via
WSOS.
Permanently available ports are:
RS232 Port D
Serial Port E (dedicated to the OCP)
10 base T Ethernet
Any 3 of the 5 following ports are available:

4-3
N-Series Automatic Circuit Recloser
RS 232 Port A (enabled by default) The ports typically have three uses:
RS232 Port B (enabled by default)
WSOS communications
RS 232 Port C (enabled by default)
RS485 (disabled by default) SCADA communications
V23 FSK (disabled by default) IOEX communications

RS232 Four RS232 ports (A to D) are provided to telephone dial up modem, or RS232 radio
connect to conventional modems that provide modem. All four ports have standard 9 pin D
the correct signalling for the communications male connectors and have the following pin
network used, e.g. optical fibre modem, or connections:

Port
RS232
Direction Use
Pin No
A B C D

1 To ADVC Data Carrier Detect (DCD) Yes Yes

2 To ADVC Rx Data (RxD) Yes Yes Yes Yes

3 From Tx Data (TxD) Yes Yes Yes Yes


ADVC

4 From Data Terminal ready Yes Yes


ADVC (DTR)

5 0V (ground/earth) Yes Yes Yes Yes

6 Not connected

7 From Request to Send (RTS) Yes Yes


ADVC

8 To ADVC Clear to Send (CTS) Yes Yes

9 Resered Yes

Table 1: RS232 Pin Connections

All RS-232 ports are not isolated from one Use of serial ports to connect
another or from the controller electronics. They directly to other devices outside
therefore can only be connected to devices the controller can cause damage
inside the controller that are powered by the and void warranty. If connections
controller radio supply, including modems, to other devices are required then isolation
optical isolators, and radios. interfaces MUST be used.

RS485 An RS485 port has been provided to enable


higher speed multi-drop connections that often Pin Direction Use
occur within substations. The RS-485 port is a
female RJ45 connector. 1 Not connected

2 To ADVC Rx Data (Rx +)

3 Not connected

4 To ADVC Rx Data (Rx -)

5 Not connected

6 From ADVC Tx Data (Tx +)

7 Not connected

8 From ADVC Tx Data (Tx -)

9 Shield

Table 2: RS485 Pin Connections

4-4
Communications and Accessories Installation

V23 FSK An in-built FSK modem provides half-duplex The Push to Talk (PTT) signal is used to key up
V23 signalling at 1200 bits per second. This a radio transmitter. PTT is implemented using a
interface is primarily designed for use with voice Field Effect Transistor (FET) with an on
frequency radio systems and provides additional resistance of 3.3 ohm. When PTT is asserted
signals for this purpose. the transistor is turned on and connects the PTT
The V23 connector is RJ45: signal to 0V.
A busy signal can be provided by the radio to
indicate receive channel busy. High level is
+2.0V to +3.3V, and low level is 0V to +0.5V.
The busy signal should be driven by an open
collector output or current limited to 10 mA.
Levels in excess of 13V should
not be applied. The FET is rated for
a maximum of +32V and negative
voltages are not permitted.
Pin Direction Use Transmit and receive are unbalanced signals
relative to 0 volts and are not isolated. If a
1 To ADVC Receive, 10 kOhm impedance
DC level is imposed by the radio on the
Sensitivity 0.1 2V pk-pk
transmit line then this should be less than
2 0 Volts (ground/earth) 2.5 VDC.

3 Not connected If multiple ACRs are in use in a substation


application they can be connected to a single
4 To ADVC Busy, 5 kOhm impedance radio using the 600ohm line isolator accessory
available from the manufacturer.
5 Not connected

6 From ADVC Transmit, 600 Ohm impedance


Level 2.5V pk-pk

7 Not connected

8 From ADVC Push to talk (PTT)

9 Shield

Table 3: V23 Pin Connections

Ethernet The controller has a 10 base T Ethernet port.


The port is a RJ45 female connector. Pin Direction Use
If the controller is connected to a
LAN or WAN then it is strongly 1 From ADVC Tx Data (Tx -)
recommended that: 2 From ADVC Tx Data (Tx +)
1.Firewalls be used to limit user
access to the controller 3 To ADVC Rx Data (Rx +)
2.Ethernet switches be used to
4 Not connected
limit the volume of Ethernet data
reaching the controller's 10Base-T 5 Not connected
port. (Use of Ethernet hubs is not
recommended.) 6 To ADVC Rx Data (Rx -)

7 Not connected

8 Not connected

Table 4: Ethernet Pin Connections

Windows Windows Switchgear Operating System the port are 57600 baud, 8 bit, no parity, and 1
Switchgear (WSOS) is a software package available on a stop bit. WSOS communication set up
Operating PC that enables configuration, control and parameters are user configurable.
System monitoring of the controller.
(WSOS) The controller has its hatch port physically
connected to Port A via an interconnecting
cable. The default WSOS communications via

4-5
N-Series Automatic Circuit Recloser

SCADA SCADA communications are available on the


Protocols controller and supported protocols can be - - - - - - - - - - - - - OPTION 4 - - - - - - - - - - - - S
assigned to any of the RS232 ports as well as DNP Available RDI Available
the V23 port.
All currently supported protocols can be viewed Trace Available
on SYSTEM STATUS - OPTIONS 4. Protocols
must be available before they will appear in the
communications menu. Once you make a SCADA protocol available,
the communication parameters can be
configured. Refer to the Operator Manual and
protocol technical information for more detail.

4-6
Testing Your Installation

5 Testing Your Installation


The following sections give details of how the Ensure that earthing has been carried
ACR and ADVC, installed as described in out as described in Earthing on
Installation on page 3-1, should be prepared page 3-5.
for operation. Check that no visible damage has occurred
Check that the installation and during the installation.
external connections have been Carry out any visual and electrical tests, such as
carried out as described in this insulation and contact resistance, considered
manual and in accordance with necessary to prove that the installation is sound.
local regulations.

Powering Up 1 Turn on the battery circuit breaker, 3 Turn on the VT supply to cubicle circuit
the ADVC breaker if the auxiliary supply is being
provided by an integrated transformer.
4 Powering up the ADVC with the ACR
connected will cause the ADVC to read data
from the ACR. This will take up to 60
seconds during which the message:
READING - Do NOT disconnect
Switchgear will flash at the top of the
display. The System OK LED on the OCP
should flash to indicate that the ADVC is
powered and functioning.
5 If the configuration file containing the
settings to be used in operation has not
The batteries are capable of previously been loaded, it should be loaded
supplying very high currents. now using WSOS, or the settings should be
Always turn off the battery circuit entered via the OCP.
breaker before connecting or The ACR and ADVC are now ready for
disconnecting the batteries in the cubicle. operation. Prior to energising the ACR, you
Never leave flying leads connected to the should perform the following checks to confirm
battery. that the equipment is fully operational and
2 Turn on the auxiliary supply circuit breaker if properly configured.
the auxiliary supply is being provided by
If you are familiar with navigating
either an LV mains or dedicated auxiliary
Operator Control Interface display
transformer.
groups, proceed with the checks
described below. Otherwise, please
read the chapter, Operator Control Panel on
page 7-1 before continuing.

Battery For this and all subsequent tests you


will need to check settings on display
group pages (See Display Groups on
- - - - - - - - - - SWITCHGEAR STATUS - - - - - - - - - S
page 7-2.) You may also have to
Work Tag OFF SF6 Normal 37kPag
check the Event Log (See Event Log on
Aux Supply Normal Battery Normal 27.5V
page 8-1.)
Switch Connected Switch Data Valid
1 In the System Status group, go to page
SWITCHGEAR STATUS - S The battery may be in any one of four states:
2 Check the Battery status. Normal; OFF; Low; High. At this point, the
battery state should be Normal with a
voltage within the range 23 to 29.5V.

5-1
N-Series Automatic Circuit Recloser
Ensure the Aux Supply status is Normal. If recent event) contains the Battery OFF
not, you cannot perform the remaining event.
battery checks at this stage. When the battery status is Low Volts,
3 Switch the battery circuit breaker off and but the voltage is close to the normal
check that the battery status changes to range lower limit, the battery will
OFF. (Allow 3 - 5 seconds.) charge up when the auxiliary supply is
turned on. If the voltage is very low, replace the
4 Go to page EVENT LOG and check that battery.
the bottom line of the display (the most 5 Switch the battery back on.

Connection 1 In the System Status group, go to page Invalid) then re-plugged (Switch status
between the SWITCHGEAR STATUS - S Connected), the Switch Data status will
ADVC and the 2 Check the Switch status.
remain Invalid during the time taken to read
ACR switch data from the SCEM, and a message
to that effect is displayed.
- - - - - - - - - - SWITCHGEAR STATUS - - - - - - - - - S If Switch Data remains Invalid, check the
Work Tag OFF SF6 Normal 37kPag following:
Aux Supply Normal Battery Normal 27.5V
Examine each end of the control cable,
Switch Connected Switch Data Valid
checking for bent or broken pins and rectify if
found. Also check the socket at both the
It may be in either of two states: Connected SCEM and P1 in the ADVC for damage.
or Disconnected. Connected is the normal If the pins are OK, the cable itself may be
state. If Switch is Disconnected, check the faulty1, therefore test the control cable for
control cable at both ends. If the status continuity.
remains Disconnected, the cable may be
If Switch Data remains Invalid, check the
faulty.
power supply to the SCEM by checking the
3 Check that the Switch Data status is Valid. voltage on Pins 2 and 5 of the control cable.
In normal operation, if Switch status is The voltage should be approximately 36VDC
Connected, Switch Data will be Valid. if the auxiliary supply is present or
If the control cable has been unplugged approximately 26VDC if running on
(Switch Disconnected, Switch Data batteries.

Auxiliary 1 In the System Status group, go to page switch off the VT supply to cubicle circuit
Supply SWITCHGEAR STATUS - S breaker. Check that the Aux Supply status
changes to Fail. (Allow 3 - 5 seconds.)
2 Check the Aux Supply status.
4 Check that the battery voltage has dropped
by approximately 2V, and that the battery
- - - - - - - - - - SWITCHGEAR STATUS - - - - - - - - - S remains in Normal state.
Work Tag OFF SF6 Normal 37kPag If the battery voltage continues
Aux Supply Normal Battery Normal 27.5V dropping, and the battery state is
Switch Connected Switch Data Valid LOW, the batteries may be flat. If
the batteries are flat, replace
T
them.
he auxiliary supply may be in either of two
states: Normal or Fail. 5 Go to page EVENT LOG and check that
Ensure the battery status is Normal. the bottom line of the display (the most
3 If using LV auxiliary supply, switch the recent event) contains the Aux Supply Off
auxiliary supply off, OR if using integrated event.
auxiliary supply and the VT is energised, 6 Switch the auxiliary supply back on.

Work Tag 1 In the System Status group, go to page


OPERATOR SETTINGS 1 - S. Check that - - - - - - - - - - SWITCHGEAR STATUS - - - - - - - - - S
LOCAL CONTROL is ON. Work Tag OFF SF6 Normal 37kPag
2 In the System Status group, go to page Aux Supply Normal Battery Normal 27.5V
SWITCHGEAR STATUS - S Switch Connected Switch Data Valid
3 Check the Work Tag status.

1. It is possible for the Switch status to be showing Connected though thecontrol cablet core is faulty, causing the Switch
Data to show Invalid.

5-2
Testing Your Installation
The tag has two possible settings: Applied or 6 Go to page EVENT LOG and check that
OFF. OFF is the default. the bottom line of the display (the most
4 Press the SELECT key to select the work tag recent event) contains the Work Tag Applied
field. event.
5 Press to change the setting to Applied
7 Return to page
and then press ENTER to activate the setting.
The message: WORK TAG APPLIED will SWITCHGEAR STATUS - S and change the
flash at the top of the display. setting back to OFF.

Terminal The power system phase assigned to each set


Designation of bushings on the ACR must be correctly
- - - - - TERMINAL DESIGNATION/ROTATION - - - - - S
and Phase indicated at the time of installation of the ADVC.
A Phase = Bushings U1 + U2 Phasing ABC
Rotation This process is called setting the phasing.
Setting the phasing affects all the displays,
B Phase = Bushings V1 + V2
events, etc., concerned with recloser terminals,
C Phase = Bushings W1 + W2
for example: voltage measurements, live/dead
terminal displays and maximum current events.
3 Press the ENTER key when you have the
Normal/default phasing is A, B and C for required phase combination. The controller
bushings U, V and W. Normal/default phase then orientates the currents and voltages to
rotation is ABC. match the selection.
4 In the Phasing field, select the phase
If the phasing at the ACR and/or phase rotation rotation - either ABC or ACB.
of the network are different from the defaults,
you must set the phasing and/or the phase 5 Go to page EVENT LOG and check that
rotation. the bottom line of the display (the most
recent event) contains the Phasing order
Phasing is set from the System Status page event.
TERMINAL DESIGNATION/ROTATION - S 6 After the phasing has been set, you should
1 Press the SELECT key to select the Phasing record the details on the label on the rear of
field. the control cubicle door (above the operator
panel) to indicate the relationship between
2 Press to change the setting. the bushings and phases.

Power Flow The ACR is a symmetrical device meaning that Power flow direction setting is used to
Direction either side can be connected to the power determine:
Setting source.
Whether the source or load corresponds to
Consequently, after installation, the controller (1) or (2) on the voltage measurement
must be configured to designate the source displays.
side. Which direction is positive power flow for use
The power flow direction is configured on page on the kWh totals in the Maximum Weekly
SYSTEM STATUS - PHASE VOLTAGE and POWER Demand display and APGS.
FLOW: Which is the source or load for Live Load
and may be either Blocking.
Source 1, Load 2 or Source 2, Load 1. Which is the source or load for Directional
When changed, this reverses the power flow Blocking/Protection.
direction but not the phasing.

Tripping and If system conditions allow, tripping or closing 2 Tripping and closing should cause the LED
Closing can be carried out at this point. on the appropriate TRIP/CLOSE button to
1 Trip and close the ACR from the ADVC. See illuminate which should agree with the
Operator Control Panel on page 7-1. for position of the pointer on the ACR.
information on the Trip and Close controls.

Enable/ For each of the CLOSE and TRIP keys in turn, test When the CLOSE or TRIP mechanism is
Disable ENABLE and DISABLE by: disabled, the message
Switches 1 Disable either mechanism e.g. CLOSE. The TRIP or CLOSE circuit is isolated

5-3
N-Series Automatic Circuit Recloser
will flash in every display page title, alternately mechanism the Event Log should display
with the actual title of the page. Trip Coil Isolate.)
3 With both mechanisms disabled, check that
2 Go to page EVENT LOG and check that pressing each of the CLOSE and TRIP keys
the bottom line of the display (the most is ineffective.
recent event) contains the Close Coil Isolate 4 Enable both CLOSE and TRIP mechanisms.
event. (For the same test of the TRIP

Mechanical 1 Use a hook stick to manually trip the ACR 2 Go to page EVENT LOG and check that
Trip via the manual trip lever. the bottom line of the display (the most
recent event) contains the Mechanical Trip
event.

Secondary If secondary injection testing is required to test If tripping and closing of the ACR is possible and
Injection protection settings but operation of the ACR is preferred, perform secondary injection testing
Testing not possible, secondary injection can be with the TTS in parallel mode.
performed with a suitable current injection set Any secondary injection must use a
with the Test and Training Set (TTS) in frequency which corresponds to the
standalone mode connected to the ADVC, and frequency set in the controller.
the ACR disconnected.

Primary If the ACR can be isolated from the network,


Injection primary injection testing can be performed if
Testing required.

Power Flow This test is to ensure that the source and load 2 With the recloser energized but still open, in
Direction designations are correct. System Measurement, go to SOURCE
Testing This test is valid only if the ACR is SIDE VOLTAGES - M
being supplied from a single source 3 Check the source side voltages - either
and can be energised before closing. phase to ground or phase to phase e.g.

Since either side of the recloser can be - - - - - - - - SOURCE SIDE VOLTAGES- - - - - - - - M


connected to the power source, the controller A1 phase to ground 6350 Volt
must be configured to designate the source B1 phase to ground 6350 Volt
side. C1 phase to ground 6350 Volt
The power flow direction is configured in System
Status on the PHASE VOLTAGE and POWER
FLOW - S page. 4 In the System Status group, go to page
If the 1-side bushings are connected to the LIVE/DEAD INDICATION - S
source, the setting 1 should be Source 1,
Load 2.
- - - - - - - - -LIVE/DEAD INDICATION - - - - - - - - S
1 Display the page and check the Source, A1 Live A2 Dead
Load configuration. B1 Live B2 Dead
C1 Live C2 Dead
- - - - - - PHASE VOLTAGE and POWER FLOW - - - - - S
LIVE if > 2000V Supply Timeout 4.0s
Power Signed Source 1, Load 2 1 5 If Steps 3 and 4 indicate an incorrect power
Display Ph/Gnd Volt flow setting, return to Step 1, change the
setting and repeat Steps 2-4.

The correct power flow setting can be confirmed


by energising the ACR while it is open.

5-4
Testing Your Installation

On Load Once the ACR is closed and taking load, the Use this page to confirm that system
Checks following on-load checks can be carried out. To measurements and power flow signs are as
confirm correct operation, check the current expected.
against a known reading.
3 Go to the System Measurement page
1 Go to the System Measurement page SOURCE VOLTAGE LOAD e.g.
CURRENT e.g.
SOURCE - - - - - - - - VOLTAGE - - - - - - - - - LOAD M
- - - - - - - - - - - - - CURRENT - - - - - - - - - - - - - M 11000 Volt A-P 11000 volt
A Phase 123 Amp Earth 6 Amp 11000 Volt B-P 11000 volt
B Phase 128 Amp Ipps 11000 Volt C-P 11000 volt
C Phase 121 Amp Inps

This page displays the system voltage either as


2 Then to SYSTEM MEASUREMENTS e.g. phase to ground or phase to phase values as
configured on the System Status, Phase Voltage
and Power Flow page.
- - - - - - - - - SYSTEM MEASUREMENTS - - - - - - - - M
Current 100 Amp Power (P) 1829 kW Source and load side voltages should be the
Voltage 6350 Volt Power (Q) 533 kVAR same when the ACR is closed.
Frequency 50.0Hz Power Factor 0.96 4 Go to MAXIMUM DEMAND INDICATOR.
Press SELECT to display RESET
MAXIMUM DEMAND INDICATOR -M.
Press SELECT again to reset the flags.

5-5
N-Series Automatic Circuit Recloser

5-6
Control Electronics Operation

6 Control Electronics Operation


The ADVC is purposely designed for outdoor Figure 23 (page B-2) shows the cubicles
pole mounted operation. The cubicle is vented dimensions.
and insulated to minimise internal temperature
variation and maximise battery life.

Sealing & All cubicle vents are screened against vermin Condensation can be expected to form under
Condensation entry and the cubicle door is sealed with some atmospheric conditions such as tropical
replaceable foam tape. storms. However, condensation will be on metal
Complete sealing against water entry under all surfaces where it is of no consequence. The
conditions is not expected e.g. during operation water runs out in the same way as any other
in the rain. Instead, the design is such that if any water entering the cubicle. Condensation will
water does enter, it will run out of the bottom run out of the bottom or be dried by ventilation
without affecting the electrical or electronic and self heating.
parts. The extensive use of stainless steel and
other corrosion proof materials ensures that the All electronic modules are fully sealed and have
presence of moisture has no detrimental effects. self heating.

Auxiliary The auxiliary supply is used to maintain charge A low power mode is activated when the
Power Source on the sealed lead-acid batteries that provide batteries are nearly exhausted due to loss of the
standby power when auxiliary power is lost. The auxiliary supply. This mode minimises power
controller monitors the status of both the consumption while still maintaining basic
auxiliary and battery supplies. functionality.

Controller The controller consists of 3 modules (See Basic Display Unit (BDU).
Figure 17 (page 6-3): The ADVC block diagram is given in Figure 18
Power supply unit (PSU) (page 6-4).
Control and protection enclosure (CAPE)

PSU Module The PSU module supplies power to the CAPE, (country customizable). The incoming power is
and to the customer compartment. The PSU protected and isolated by a circuit breaker. The
module: supply from the batteries is protected and
connects to the batteries isolated by a circuit breaker.
controls the supply from external auxiliary
The electronic components are contained inside
sources
a housing that provides environmental
filters these supplies and manages the protection, sealing and EMI shielding. The
battery power level. power outlet, circuit breakers and switches are
It also performs battery testing and has a non- easily accessible when the ADVC door is
volatile, real time clock. A general purpose opened. The batteries are located and retained
power outlet is available as an optional extra on the exterior top of the PSU module.

CAPE Module The CAPE Module comprises two printed circuit provides EMC shielding for the CAPE
board assemblies and the trip and close electronics.
capacitors housed in a die-cast aluminium
enclosure. The two printed circuit board The PCOM is the heart of the ADVC and
assemblies are: includes the data acquisition hardware
(including a powerful Digital Signal Processor)
PCOM: Protection and Communication
and communications hardware (Ethernet,
Module
RS232, RS485 and V23). All user-interface,
SWGM: Switchgear Module
measurement, protection, communication and
The CAPE enclosure is manufactured from control functionality is provided by software
pressure die-cast aluminium. The front surface running on the PCOM. The PCOM includes a
with the user and switchgear connectors, and PowerPC microprocessor, a DSP, an FPGA, 16
the rear surface, are gasketed to provide an Mbytes of flash memory and 24 Mbytes of RAM
IP65 Degree of Protection. The enclosure also memory.

6-1
N-Series Automatic Circuit Recloser
The SWGM contains the switchgear interface protection and filtering devices and high voltage
hardware, SCEM interface hardware, EMC inverters for the trip and close capacitors.

Operator The operator interface is provided by a separate can be latched open, is the usual access point
Interface/ Door module - the basic display unit (BDU) with its to the OCP.
Assembly own processor. The BDU comprises the
electronics compartment cover, an operator When you are commissioning the ADVC, you
control panel (OCP) with LCD display, a can lock the door open and swivel the OCP
membrane keyboard and its controlling open 90 degrees to the door. See Figure 17
microprocessor and the WSOS communications (page 6-3). This allows you to gain access to the
port. OCP at the same time as commissioning the
The BDU is attached to the door of the cubicle equipment in the customer compartment.
and the operator control panel (OCP) can be
accessed through a hatch in the front door. The BDU plugs into Port E of the CAPE and
Under normal circumstances the hatch, which uses this port for its power and communications

WSOS Interface Connect your PC serial port to the maintenance DB9 male to DB9 female, straight-through
port provided below the OCP. Use an RS232, cable.

Customer The compartment is fitted with a panel tray that a terminal block for the radio supply and power
Compartment facilitates the mounting of your equipment e.g. a for accessories such as an IOEX. An accessory
radio or modem including any special interfaces. heater can also be fitted which is controlled by
See Figure 17 (page 6-3). The compartment has the PSU.

6-2
Control Electronics Operation

Operator Interface Customer Equipment Compartment

CAPE Batteries PSU

Figure 17: Advanced Controller

6-3
N-Series Automatic Circuit Recloser

Figure 18: ADVC Block Diagram

6-4
Operator Control Panel

7 Operator Control Panel

Description The operator control panel (OCP) is the user OCP turns ON automatically when the hatch is
interface to the basic display unit (BDU) which is opened, or if the door is opened and the panel is
mounted on the door of the ADVC.The OCP repositioned as shown in Figure 17 (page 6-3)
consists of a four-line liquid crystal display and OFF when it is closed. The OCP also turns
(LCD) and keypad with switches and light OFF automatically if no keys are pressed for 10
emitting diodes (LEDs), which are used to select minutes. Pressing any key for 1 second will
and monitor the functionality of the ACR. The reactivate it.

2 17 16 14

15 13
3

6 12 11

5 4

7 9 8 10

Figure 19: Operator Control Interface

Number Item Description

Display Back-lit LCD, 4 line with 40 characters per line.


1

Close key Generates a Close request to the CAPE when the OCP is active. A red LED is
2
embedded in the key.
Enable/ Disables the Close key. When the switch is in the isolate (Disable)position the close coil
3
Disable Close in the ACR is electrically disconnected from the control electronics. Thus the switch
switch provides a physical isolation point for the control circuitry. The ACR cannot be closed
and an audible alarm in the OCP will sound. The Close key operates normally when the
switch is in the Enable position.
Trip key Generates a Trip request to the CAPE when the OCP is active. A green LED is
4
embedded in the key.
Enable/ Disables the Trip key. When the switch is in the isolate (Disable) position the trip coil in
5
Disable Trip the ACR is electrically disconnected from the control electronics. Thus the switch
switch provides a physical isolation point for the control circuitry. The ACR cannot be opened
and an audible alarm in the panel will sound. The Trip key operates normally when the
switch is in the Enable position.
Custom Menu Gives access to the custom menu which was configured using WSOS5. The custom
6 key menu is configured to provide a regular, updated data display by allowing a cycle of up
to 12 screens. See Custom Menu on page 14-7.
System OK The red System OK LED flashes while the BDU is ON.
7

Enter key Press this key in order to commit a setting change that has been made. (Unlike the
8
adjacent Quick Keys, the ENTER key is not configurable.)
Configurable Default linkage is to AUTO ON/OFF. See Quick Keys on page 7-4.
9
Quick Key

Table 5: Operator Control Interface Keys

7-1
N-Series Automatic Circuit Recloser

Number Item Description

Configurable Default linkage is to PROT GROUP. See Quick Keys on page 7-4.
10
Quick Key
Configurable Default linkage is to EARTH PROT. See Quick Keys on page 7-4.
11
Quick Key
Configurable Default linkage is to LOCAL/REMOTE. See Quick Keys on page 7-4.
11 12 Quick Key

13
RIGHT scroll Select the next screen in a display group or, if a setting is selected, increase its
key value.
SELECT key Press to SELECT a setting.
14

15
LEFT scroll Select the previous screen in a display group or, if a setting is selected, decrease
key
its value.
MENU scroll Displays the first page of the next group. Pressing the MENU key after changing a
16
key setting causes the setting change to take effect.
ALT The alternative function key gives access to an alternative Event Log display.
17

Table 5: Operator Control Interface Keys

As well as each isolate/enable while the ACR is tripped will prevent the
switch affecting its associated operation of the CLOSE button thus preventing
button, isolating the TRIP button a manual close on to a fault.

Display The OCP displays are organized into logical Each page consists of fields. A field may contain
Groups groups called Display Groups. Within each either:
group is a menu of pages and some pages have a setting, which can be changed - ON/OFF
sub-pages. is the most common; or
a status.
(There are labels similar to that shown below
affixed to the door of the ADVC.) .

7-2
Operator Control Panel

Custom Menu It is possible to configure a custom menu more information. Where a custom menu has
comprising those display group pages which are been configured, you access it by pressing the
particularly required, or those used most Custom Menu button on the OCP.
frequently. Please see the Operation Manual for

Changing Three types of settings can be changed: Password protected settings


Settings Operator settings Protection settings

Operator Find the display page containing the setting to 4 Press SELECT to highlight the setting. A
Settings be changed: highlighted setting blinks.

1 Press the MENU key to display the group Alternatively, if a QUICK KEY is linked to the
you require. setting, you can use it to go directly to relevant
display page where you will find the highlighted
2 Communications Group (only) is divided into setting. (See Quick Keys on page 7-4.)
subgroups for different protocols. Press 5 Once you have selected the setting to be
SELECT to display the subgroup you
changed, use or to change its
require.
setting.
3 Press to display the page you require. 6 Press ENTER to activate the new setting.

Password Some settings are password protected. You will 4. Press Enter.
Protected be prompted for a password before you can
change the setting. To enter the password: While the operator panel is ON you will not be
Settings
required to enter the password again.
1. Press either of the keys until the
first character of the password is displayed. The default factory password is AAAA but you
can change it using the Windows Switchgear
2. Press the SELECT key. Operator System (WSOS) program. The factory
3. Repeat Steps 1 and 2 until the password is password does not have to be remembered -
complete. the controller prompts you for it automatically.

Protection Protection settings are password protected. To When you have completed making all the
Settings change a protection setting, follow the steps setting changes you require, press ENTER. The
detailed in the Operator Settings section above following text will be displayed:
but, in addition, enter the password when
prompted. When you have completed the CHANGED ACTIVE PROTECTION SETTING
setting change by pressing ENTER, the [A]
following message will flash at the top of the
The changed active PROTECTION SETTINGS
screen:
are now in service. Select the MENU or
Active Protection Setting has changed. ENTER key to continue.

At this point, the changed setting will be The changed settings are now in service. Press
displayed but not in service. If further setting MENU or ENTER to return to the normal menu
changes are required, they can be made now. display.

Navigating Refer to the diagram inside the OCP hatch, the


Within Display ADVC door or to the Operations Manual for
Groups details of navigation within groups.

Page Layout The display area consists of four lines, each indicating the display group to which the page
forty characters long.The top line of the display belongs:
is the page title. To the right of the title is a letter,

7-3
N-Series Automatic Circuit Recloser

S System Status Display Group The next three lines are the data on display.
Most pages have six data fields.
E Event Log

M Measurement Display Group

P Protection Display Group

A Automation Display Group

C Communications Setup

Quick Keys The operator settings that you will frequently Otherwise, any one of the following settings can
change can each be linked to a Quick Key. You be linked to one of the four Quick Keys: .

use a Quick Key for instant display and selection


LOCAL/Remote / Hit & Run
of the linked setting which, otherwise, you would
have to find by navigation. Loop Auto ON/OFF
You can link operator settings to individual Quick Prot Group
Keys using the operator control panel or WSOS.
Reset Flags
For more detail, refer to the Operations manual.
Work Tag ON/OFF
A Quick Key can be set to Blank, if it is not
required. Auto ON/OFF
Protection OFF

Negative Phase Sequence


(NPS) ON/OFF/Alarm

Cold Load ON/OFF

Earth Prot

Live Block

Table 6: Quick Key Configurable Settings

Quick Key The Quick Keys default configuration is given in .


Configuration Table 5: (page 7-1). The ability to re-configure
the Quick Keys must be made available from the - - - - - - - - - QUICK KEY SELECTION - - - - - - - - -S
SYSTEM STATUS - OPTIONS 3 page:
LOCAL/Remote Earth Prot
Auto ON/OFF Enter Prot Group
- - - - - - - - - - - - - OPTIONS 3 - - - - - - - - - - - - S
Config QK Available - - APGS Not Allowed
Gas Lout Available Pressor to scroll through the list of
U/O Freq Available settings that can be linked to Quick Keys.
Press MENU or ENTER when the required setting
is displayed.
If Config QK is Available, make changes on the To configure another Quick Key, press SELECT
SYSTEM STATUS - QUICK KEY SELECTION and repeat the above procedure.
page:
Each setting can only be assigned to one
Quick Key.
- - - - - - - CHANGE QUICK KEY SELECTION - - - - - - S If the operator selects a function that has
been assigned to another Quick Key that
LOCAL/Remote Ground Prot selection will revert to a blank setting.
Work Tag Enter Loop Auto When a Quick Key is changed an event is
generated in the Event Log.
Changing the quick keys
To configure a Quick Key, press SELECT or configuration requires updating of
ENTER. The following screen is displayed with the OCP quick keys using
the first setting selected (blinking) adhesive labels supplied with the
ADVC. Failure to match software
and panel may cause incorrect
operation of controller.

Using a Quick 1 Press a Quick Key at any time to display the selected:
Key relevant page, with the linked setting

7-4
Operator Control Panel
2 Press the same Quick Key again to display return to the page that was displayed when
the next setting option for that setting. you first pressed the Quick Key.1
Repeat until you have displayed the setting
you require. Whenever a Quick Key is in use the
and SELECT keys are disabled.
3 Press the ENTER key to activate the
displayed setting AND, after a short delay, to

1. A particular option may not be available to the operator if it has been disabled on the SYSTEM STATUS-OPTIONS page

7-5
N-Series Automatic Circuit Recloser

7-6
Event Log

8 Event Log
When the status of the control electronics or Events are dated, time stamped to a 10ms
switchgear changes, events are generated resolution and displayed in the order in which
which are recorded in an Event Log for display they occurred.
to the operator. Examples of such events are The key scrolls the display downward to
Load Supply On or Lockout. show older events, the key scrolls the
Events are viewed on the Event Log pages and display upward to show more recent events.
can also be up-loaded and viewed with the Pressing the key removes the title of the
Windows Switchgear Operating System. display to make more room for events. The title
The event log display looks like this: will only be restored when the event log is
selected again from the top level menu.

- - - - - - - - - - - - -EVENT LOG - - - - - - - - - - - -E
10/01/01 12:09:02.06 Battery Normal
10/01/01 12:09:03.95 Panel close req
10/01/01 12:09:37.95 Load Supply ON

Display The event log display will update automatically events occur they are entered at the bottom of
Updating with new events, provided the most recent event the screen and the older events are scrolled up.
is on the bottom line of the screen. When new

Event Log Each event occupies one line of the event log. the event description.
Format The standard display contains (reading from the Additional information e.g. event source is
left): recorded and can be made visible if you press
the date of the event, the ALT key while the event is displayed.
the time of the event, and

Using the ALT If the Alt key is pressed whilst the event log is on Additional event details are available where the
Key display, the date and time details may be combination of the source plus event description
replaced with extra information that includes, at alone will not precisely identify the event e.g.
far left, the event source and followed by, if protection events or events sourced to WSOS.
applicable, additional event details. Examples of Examples of additional details are:
source codes are:
the protection group
curve
Identifier Event (settings change) source
trip number
WSOS Windows SOS change port identification
protocol.
OCP Operator control panel change

PTCL SCADA protocol change

IOEX IOEX change

Typical Event A typical sequence of events for a phase/phase Reset Time has expired, as shown in Figure 21
Log Displays fault, which had instantaneous protection on the (page 8-2).
first trip and inverse time protection on the
second trip, with two trips to lockout might be as
shown in Figure 20 (page 8-2).
However, if the fault was cleared after the first
trip has occurred, the controller will generate a
Sequence Reset event once the Sequence

8-1
N-Series Automatic Circuit Recloser

- - - - - - - - - - - - - - - - - - - - - - - EVENT LOG- - - - - - - - - - - - - - - - - - - - - E

07/01/01 07:02:53.90 Pickup Start of fault

07/01/01 07:02:53.92 Prot Group A Active Protection Group A

07/01/01 07:02:53.92 Phase Prot Trip Phase Element caused trip

07/01/01 07:02:53.92 Prot Trip 1 1st trip 20ms after pickup

07/01/01 07:02:53.92 A Max 543 AMP Peak A phase current

07/01/01 07:02:53.92 B Max 527 AMP Peak B phase current

07/01/01 07:02:54.76 Automatic Reclose 1st Reclose

07/01/01 07:02:54.77 Pickup Pickup again

07/01/01 07:02:57.24 Prot Group A Active Protection Group A

07/01/01 07:02:57.24 Phase Prot Trip Phase Element caused trip

07/01/01 07:03:04.24 Prot Trip 2 2nd trip 2.47 sec later

07/01/01 07:03:04.24 A Max 453 AMP Peak A phase current

Figure 20: Event Log example - Phase to Phase fault

- - - - - - - - - - - - - - - - - - - - - - - - EVENT LOG- - - - - - - - - - - - - - - - - - - - - E

07/01/01 07:02:53.90 Pickup Start of fault

07/01/01 07:02:53.92 Prot Group A Active Protection Group A

07/01/01 07:02:53.92 Phase Prot Trip Phase Element caused trip

07/01/01 07:02:53.92 Prot Trip 1 1st trip 20ms after Pickup

07/01/01 07:02:53.92 A Max 543 AMP Peak A phase current

07/01/01 07:02:53.92 B Max 527 AMP Peak B phase current

07/01/01 07:02:54.76 Automatic Reclose 1st Reclose

07/01/01 07:02:64.76 Sequence Reset Reclose Successful

Figure 21: Sequence Reset example

8-2
Power System Measurements

9 Power System Measurements


The current transformer (CT) signals and total and per phase power (kW, kVA, kVAR),
voltage screen (CVT) signals from the recloser total and per phase power factor,
are digitised by the ADVC and used to provide a harmonics,
variety of data for the operator.
earth current, and
The ADVC measures up to 10 power system sequence components.
components:
In addition the ADVC also measures several
A, B, C, phase and spill currents, internal values such as:
phase-earth voltage on all six terminals. CAPE temperature,
The ADVC uses the above measurements to switchgear temperature1
derive many system measurements including: auxiliary voltage,
frequency, gas pressure,
phase to phase voltages, battery voltage.

Power System The controller must be set for the correct power This is set on page
Frequency system frequency either 50 or 60 Hz. SYSTEM STATUS - PHASE VOLTAGE and POWER
FLOW

Real Time The first five screens of the System The Positive Phase Sequence Current
Displays Measurements group contain real time displays. (IPPS) and Negative Phase Sequence
They are: Current (Inps).
1 System Measurements
2 Current (includes phase angles) - - - - - - - - - - - - - CURRENT - - - - - - - - - - - - - M
3 Voltage A Phase 123 Amp Earth 6 Amp
4 Sequence Voltage B Phase 128 Amp Ipps 120
C Phase 121 Amp Inps 10
5 Power
The ninth screen, Maximum demand Indicator, Voltage
also contains some real time data. The voltages displayed can be either phase
Data displayed is as follows: to phase or phase to earth.
This is a selectable item from
System Measurements
page
This is a summary page. The current and
voltage values displayed are an average of
SYSTEM STATUS - PHASE VOLTAGE and
POWER FLOW: Display Ph-Ph Vol
the three phases.
Frequency is measured on the first available
bushing. Frequency is Unavailable if all SOURCE- - - - - - - - - VOLTAGE - - - - - - - - - LOAD M
bushings are dead. 11000 Volt A-P 11,000 Volt
11000 Volt B-P 11,000 Volt
- - - - - - - - - SYSTEM MEASUREMENTS - - - - - - - - M 11000 Volt C-P 11,000 Volt
Current 100 Amp Power (P) 1638 kW
Voltage 6350 Volt Power (Q) 476 kVAR
Frequency 50.0Hz Power Factor 0.86 Sequence Voltage
This screen displays the Zero, Positive and
Negative phase sequence voltages.
Current
This screen displays, for each phase, the - - - - - - - - - - SEQUENCE VOLTAGE- - - - - - - - - - M
current and phase angle. Uzps 100 Volt
The earth current. Upps 11,000 Volt
Unps 200 Volt

1. The ADVC measures the temperature of the SCEM in the ACR and from that, calculates the switchgear temperature.

9-1
N-Series Automatic Circuit Recloser
Power Real Power (kW), this is a signed quantity
This screen displays real and reactive unless Power Flow Unsigned has been
power, as well as the power factor on a per selected on page
phase basis. SYSTEM STATUS - PHASE VOLTAGE and
POWER FLOW: Power Flow Signed/Unsigned
Power Factor (PF), this is an unsigned
- - - - - - - - - - - - - - POWER- - - - - - - - - - - - - - M quantity.
A P 540 kW Q 158 kVAR PF 0.86
B P 551 kW Q 167 kVAR PF 0.86
C P 547 kW Q 151 kVAR PF 0.86

Maximum As stated above, the first five System


Demand Measurements screens are real time. The next
four screens contain historical data, except for - - - - - - - MAXIMUM DEMAND INDICATOR - - - - - - - M
Indicator
the ninth screen which contains a mixture of real A 0A Max 0A 01/01 00:00:00
time and historical data. B 0A Max 0A 01/01 00:00:00
C 0A Max 0A 01/01 00:00:00

9-2
Maintenance

10 Maintenance
Maintenance can be carried out using standard Be careful to ensure that if working
electricians and mechanics tools. on the ADVC with the door open in
heavy rain, water does not enter
the circuit breakers or general
power outlet.

ACR No user maintenance of the ACR mechanism is Every five years the bushing boots should be
Maintenance required. checked, cleaned if necessary and the pointer
The ACR should be returned to the checked to ensure it is free from mechanical
manufacturer for refurbishment if the obstructions. In areas of high atmospheric
mechanical duty or breaking duty is exceeded. pollution more frequent cleaning may be
This is checked by examining the remaining appropriate.
contact life on the Operator Control Panel. At suitable intervals check the gas low alarm is
When the remaining contact life in any phase not showing on the operator control panel. If gas
approaches zero, the ACR has reached the end low is showing, this may indicate a leak which
of its life and must be replaced. must be found. Recharging the ACR SF6 using
A warning is displayed in the event log a gas fill adaptor is described below.
when the remaining contact life reaches
20%.

ACR SF6 The ACR is refilled to a pressure of 35kPa on altitudes above 1000m the gauge pressure
Recharging the gauge corrected by +0.46kPa for every should be corrected for altitude.
degree Celsius above 20 Celsius and -0.46kPa Do not attempt to recharge the gas
for every degree below 20 Celsius. For without first removing the ACR
from service.

Safety REMOVAL FROM SERVICE Replacement O-Ring to suit the gas fill valve
The gas fill valve is located between the ACR nut, Part No: ORG 025024.
body and the mounting bracket. 32mm Ring Spanner.
To fit the Gas Fill Adaptor whilst in service it is 250mm Adjustable Wrench.
necessary to approach the ACR.
Silicone O-Ring Grease (DOW 111 or
Ensure that the ACR is removed from service equivalent), Nu-Lec Part No: LUB058044.
before fitting the gauge and taking a reading.
Temperature Gauge.
SULPHUR HEXAFLUORIDE SAFETY DATA SHEET
ACR Manufacturers Gas Fill Adaptor:
See Appendix C for reproduction of original
Material Safety Data Sheet. Part No: GFA-003 (for CIG cylinders).
Part No: GFA-004 (for Linde Gas
EQUIPMENT REQUIRED
cylinders).
Use of the correct tools and equipment will
reduce the risk of sub-component or fastenings (Standard gas supply hose GFA-002 is 2m
damage during this procedure. long).

Procedure PREPARATION Record the ambient temperature as this will be


The gas filling procedure may be conducted on required when calculating the fill pressure.
an ACR either in the field or within a workshop. CONNECTING THE GAS CYLINDER TO THE GAS FILL
If to be conducted in the field, ensure that the VALVE.
ACR is removed from service until the 1 Remove the protective plastic transportation
procedure is complete. cap from the cylinder valve.

10-1
N-Series Automatic Circuit Recloser
Cylinder pressure gauge and regulator valve. tank starts to fill with gas, the pressure
Tank pressure gauge will display the increasing pressure:
gauge and Care must be taken not to over-pressurise
shut-off valve the tank. A relief valve is fitted to the gas fill
adaptor. If the tank pressure exceeds 60
kPa, the valve will open and vent to
atmosphere.
Pressure in excess of that required and 60
kPa must be removed using a reclamation
Cylinder pressure
gauge and unit or similar means.
regulator The tank's pressure may be checked at any time
valve by closing the shut-off valve:
Allow the gas pressure gauge to stabilise
before taking a reading.
2 Fit the Gas Fill Adaptor to the cylinder and Open the shut-off valve to recommence the
tighten using the correct spanner: gas flow in to the tank.
3 Open both the shut-off and gas cylinder CONFIRMING THE GAS PRESSURE
valves. 13 If the ADVC is connected to the ACR, the
4 Adjust the regulator valve until gas flows OCP display may be used to confirm the gas
through and purges the line. pressure within the tank against the reading
at the Tank Pressure gauge:
5 Immediately close the shut-off valve.
Close the shut-off valve and allow the gauge
6 Ensure the adaptor is free of dirt or to stabilise.
contaminants before inserting into the valve.
Note the gas pressure gauge reading.
Locking pin 14 To confirm that the readings shown on the
gas cylinder pressure gauge and the
Switchgear Status page are the same go to
the
SYSTEM STATUS - SWITCHGEAR STATUS
Handle page

- - - - - - - - - SWITCHGEAR STATUS - - - - - - - - - S
Work Tag OFF SF6 Normal 37kPag
Aux Supply Normal Battery Normal 27.5V
7 Insert the gas line adaptor into the gas fill SWGR Connected SWGR Data Valid
valve:
8 Retract the locking pin on the gas fill tool and -
DISCONNECTING THE GAS FILL ADAPTOR
slide it over the gas fill boss on the tank.
Allow the locking pin to spring into the 15 Close the shut-off valve.
groove. Gently check that the tool cannot be 16 Fully close the gas cylinder valve.
pulled off. 17 Turn the regulator anti-clockwise to reduce
9 Push the handle into the plug and rotate the internal pressure on the regulator:
anticlockwise until the bayonets drop into the Never disconnect the gas line
slots. Continue to rotate until it becomes without first reducing the pressure
difficult to turn. Do not force the handle on the regulator.
further.
FILLING WITH GAS 18 Disconnect the gas fill adaptor from the gas
10 Calculate the gas pressure required for the fill valve.
local conditions: 19 Firmly tighten the gas fill plug by rotating the
handle of the gas fill tool clockwise.
The default gas pressure is 35 kPa.
20 Retract the locking pin and slide the tool
The final pressure is dependent upon the from the switch.
ambient temperature at the site.
21 Open the shut-off valve to purge the gas
For temperatures above 20 C, add 0.46 kPa line.
for each degree in temperature. 22 Remove the gas fill adaptor from the gas
For temperatures below 20 C, deduct 0.46 cylinder.
kPa for each degree in temperature. 23 Refit the protective plastic cap on the
11 Open the shut-off valve to commence the adaptor to protect the thread form during
flow of gas into the recloser tank. further transportation.
12 Slowly turn the regulator clockwise to 24 Store the adaptor and cylinder.
increase the flow of gas into the tank. As the

10-2
Maintenance

ADVC Maintenance of the ADVC is required every five Take care to ensure, when accessing
Maintenance years. The manufacturer recommends the work the cubicle compartment in heavy rain,
described below. that water does not penetrate the circuit
breakers.

Cleaning Check for excessive dirt on the cubicle, Ensure that the mesh covering the air vents and
particularly the roof, and clean off. the water drainage holes in the base are clean.

Battery Battery replacement is recommended after a Ensure that battery polarity is


Replacement period of five years. See "Battery Care" - correct.
page 10-4 .
The procedure is: 3 Turn on the battery circuit breaker and
1 Turn off the battery circuit breaker. ensure that Battery Normal status, is
2 Unplug batteries and replace with new restored on the page
batteries. SYSTEM STATUS-SWITCHGEAR STATUS

Battery Heater Where the battery heater accessory has been 4 Remove batteries and replace with new
Accessory fitted the following procedure should be batteries.
followed: Ensure that battery polarity is
1 Turn off the battery circuit breaker. correct.
2 Disconnect batteries and heater.
3 Open straps and remove heater box. 5 Replace the heater box, close straps.
The battery heater box is heavy 6 Reconnect batteries and heater.
and should be removed with 7 Turn on the battery circuit breaker and
caution. Do not tilt the heater box. ensure that Battery Normal status, is
The cover may slide off and the restored on the page
batteries may fall out.
SYSTEM STATUS-SWITCHGEAR STATUS

Battery (+) Battery (-)

Heater Connection

Battery heater failure will be reported in


the Event Log.

Door Seal Check the door sealing rubber for perishing or


undue hardening. If necessary renew the seal.

10-3
N-Series Automatic Circuit Recloser

Battery Care The battery is predicted to provide good they should be taken out, cycled and have
performance for the recommended five year their capacity checked before being returned
service period. This is based on the battery to service.
manufacturer's data. No battery warranty is To cycle a battery, discharge with a 10 Ohm 15
given by the manufacturer of the ADVC. Watt resistor to a terminal voltage of 10V. Next,
Once in service, batteries need little care. recharge it with a voltage regulated DC supply
Procedures for storage and other contingencies set to 13.8V. A 3A current limited supply is
are as follows: appropriate.
Batteries should be stored at a temperature Battery type, either standard or extended
of between 0C to 30C (32F to 86F) and temperature, is given in Appendix A. More
cycled every six months. Batteries should be information on the battery care is available from
stored for a maximum of one year. the battery manufacturer.
Batteries should be cycled prior to putting These batteries are capable of
into service if they have not been cycled supplying very high currents.
within three months. When shipped by the Always turn off the battery circuit
manufacturer the batteries will have been breaker before connecting or
cycled within the previous 30 days. disconnecting the batteries in the cubicle.
If the batteries become exhausted in service Never leave flying leads connected to the
and are left for more than two weeks without battery.
auxiliary supply being restored to the ADVC

Abnormal The operation of the capacitor charging inverter following features are used to protect the ADVC
Operating can be affected under abnormal conditions such in this situation while still allowing the ACR to
Conditions as when the battery capacity is very low. The keep operating.

Low Power When the batteries are nearly exhausted, the cannot be recharged quickly enough. Operator
Mode ADVC will change its capacitor charging mode close and trip operations can be performed, but
from normal to low power. In low power mode at a longer time interval than normal. If an
the controller takes longer to charge the operator trip or close request is denied, a Cap
capacitors and the radio supply is shut down. A Chrg event will be logged.
Low Power Mode event is logged whenever To return to normal power mode, the auxiliary
this happens. supply must have been switched back on for a
When a trip occurs in low power mode, the minimum of 15 minutes, and the batteries may
recloser will go to lockout if the capacitors have to be replaced.

Excess Close During testing it is possible to carry out so many service (it only happens during excessive
Operations trip/close operations that the capacitor charging testing).
inverter shuts itself down before it overheats. It When this happens the inverter shuts down for 5
takes more than 20 operations within a minute minutes and a Cap Excess Closes event is
to do this and is not going to happen while in logged. During this time all trip/close requests
will be denied.

Fault Finding

ADVC Check Fault finding within the ADVC involves with the display itself and the BDU should be
determining whether the fault lies in the replaced.
electronic modules, the wiring or elsewhere. The If the display is operating, check the
electronic modules are user replaceable items. SYSTEM STATUS - SWITCHGEAR STATUS
Other faults require the ADVC to be returned to
the factory. page for an indication of any power supply
problems (Aux Supply Fail and/or Battery
A suggested fault finding approach is as follows: OFF) which can be traced and rectified.
If the System OK LED on the OCP is If the System OK LED is not flashing, check
flashing then the CAPE microprocessor and for loss of power. Check that the BDU is
the BDU microprocessor are running. If the plugged in to the CAPE. Check that the
OCP does not operate there is a problem battery circuit breaker is on and that full

10-4
Maintenance
battery voltage is present at the terminals. If power supply is present then attempt to go
Check the presence of aux supply on the on-line with WSOS to determine whether the
aux supply circuit breaker. Check that the CAPE is functioning correctly. Replace the
supply between the PSU and CAPE has not CAPE or BDU as required.
been disconnected. Rectify if a problem is If this does not rectify the problem then the
discovered. ADVC should be returned for factory repair.

Replacement Electronic modules are user replaceable. Care PSU and CAPE firmware can be upgraded
of Electronic should be taken to avoid damage to the through WSOS. Refer to the Operator Manual
Modules and modules while they are outside the cubicle and for further details.
Upgrades replacement should only be carried out by Removal of parts from modules will
competent personnel. void the warranty.

10-5
N-Series Automatic Circuit Recloser

10-6
Ratings and Specifications

11 Ratings and Specifications

Equipment
and Crating
Dimensions Equipment Weights

Part Weight kg (lbs)

Control cable 6 (13)

Control cubicle 37 (81) (without


accessories and with
7Ah batteries)

HV cables (185mm2 Al cables, qty 6, length as ordered) complete with bushing 26 (57)
boots.

Pole Mounted ACR 225 (495)

Pole mounting bracket 24 (53)

Sundry Mounting items 8 (18)

Gross weight of crate 404 (890)

Dimensions mm (ins)

Cubicle (See Appendix B) 1000mm x 375mm x


305mm (39.4 x 14.8 x
12.0)

Crate Dimensions

Width 1160mm (45.7)

Depth 730mm (28.7)

Height 1640mm (64.6)

ACR

Rated Voltage

N15 15.5 kV

N27 27 kV

N38a 38 kV

Rated Continuous Current 800 Amp

Emergency Load Current - carrying capability (8 Hours)

N15 850 Amp

N27 850 Amp

N38 - 12.5 kA 850 Amp

N38 - 16 kA 850 Amp

Rated Frequency 50/60 Hz

Rated Load Breaking Current 800 Amp

Rated Cable Charging Breaking Current (N15 and N27) 25 Amp

Rated Cable Charging Breaking Current (N38) 40 Amp

Rated Single Capacitor Bank Breaking Current 250 Amp

Rated No-Load Transformer Breaking Current 22 Amp

11-1
N-Series Automatic Circuit Recloser

Rated Symmetrical Interrupting Current 12.5 kA

Rated Asymmetrical Short-circuit Making Current (peak) 31.5 kA

Rated Symmetrical Making Current (rms) 12.5 kA

Rated Short-time Withstand Current (rms) 12.5 kA

Rated Duration of Short-circuit 3 sec

Rated Peak Withstand Current (peak) 31.5 kA

Short Time Current Recovery Time 180 sec

Impulse Withstand Phase/Phase, Phase/Earth, Across Interrupter

N15 110kV

N27 150kV

N38 170kV

Impulse Withstand Phase/Phase, Phase/Earth, Across Interrupter when SF6 70kV


replaced by dry air

Power Freq Withstand Phase/Phase, Phase/Earth, Across Interrupter

N15 50kV

N27 60kV

N38 70kV

Closing Mechanism Solenoid

Opening Mechanismb Spring

D.C. Resistance Bushing/Bushing N15/N27 <100 micro Ohm

D.C. Resistance Bushing/Bushing N38 <140 micro Ohm

Tank Construction Welded Stainless Steel

Insulating Medium SF6 Gas

SF6 Operating Gas Pressure at 20C at sea level 10 to 35kPa Gauge

Maintenance Intervalc 5 Years

Earthingd 12mm stud provided

Applicable Standards

N15 and N27 IEC 62271-100,


IEC 60694
ANSI C37.60

N38 IEC 60694


ANSI C37.60

a. A 16 kA for 3 secs, 40 kA peak rated device is also available.


b. The opening mechanism is operated either by solenoid or manual lever.
c. In heavily polluted environments regular checking/cleaning of insulators should be carried out as required.
d. Earthing details in Earthing on page 3-5 must be strictly adhered to.

11-2
Ratings and Specifications

Breaking Duty The duty limits of the ACR are shown in the for each interrupter by the ADVC on the basis of
table below. It is rated for ANSI C37.60 duty fault current and mechanical operations.
cycle.Contact wear is automatically calculated The remaining contact life is shown on the
operator control panel.

ACR Model Mechanical Contact Wear


Operationsa
Rated Loada. 6 kA Fault 12.5 kA Fault 16 kA Fault

N15 10,000 10,000 1,000 100 N/A

N27 10,000 10,000 1,000 50 N/A

N38 10,000 10,000 1,000 520 500

a. Equipment manufactured before 01 November 1999 is rated for 3 000 operations.

Duty Cycle Maximum allowable duty cycle at full short Open-2s-Close.


circuit current rating: Open-2s-Close.
Open-0.5s-Close. Open followed by 300 second recovery time.

Bushing Boots The ACR is normally supplied with outdoor characteristics of the boot alone (disregarding
elastomeric bushing boots. The boots suit the cable insulation) are detailed in the following
insulated cable sized 16-32 mm diameter and table.
comprise an unscreened insulated system.The

N15/N27-Boot Part No: INS020F - Silicone

Taut string phase to earth clearance 400mm (15.8)

Creepage 777mm (30.6)

N15/N27/N38-Boot Part No: R01-318 - Silicone

Taut string phase to earth clearance 465mm (18.3)

Creepage 1100mm (43.3)

HV Cables Cable is usually provided by the manufacturer equipment only if suitably insulated and
pre-cut and terminated to fit the ACR bushings watertight cable and terminations are used.
and rated to suit the requirements of the utility. Contact the manufacturer or your local
Alternatively cable can be supplied by the utility distributor to check cable type for suitability.
if appropriate (e.g. to terminate HV Aerial Standard cable supplied by the manufacturer is
Bundled Cable). The manufacturer warrants the detailed in the following table.

Lug Size - mm2 Stranding Material Rating (Amps)

300 61/2.52 Copper 800

240 19/4.01 Aluminium 630

185 19/3.5 Aluminium 400

80 7/3.75 Aluminium 250

11-3
N-Series Automatic Circuit Recloser

Current There is no access to current transformer


Transformers connections on the equipment. This data is
supplied for information only.

Ratio 2000:1

Accuracy 10 Amp - 800 Amp 0.5%

Accuracy 800 Amp - 12500 Amp 2.5%

Environmental

Operating Temperature -40C to +50C

Operating Humidity 0 to 100%

Operating Solar Radiation 1.1kW/m max

Operating Altitudea 3000m max

a. For altitudes above 1000 meters some ratings must be de-rated per ANSI C37.60.

ADVC

General
Specifications
Cubicle material 316 stainless steel

Cubicle shell sealing IP 44

Electronic enclosure sealing IP 65

Wind loading resistance of structure >160km/hr

Wind loading on door when latched in open position >70km/hr

Angle of hatch opening 135

Angle of door opening 180

Operating temperature range -10C to 50C

Extended operating temperature range (battery heater required) -40C to 50C

Maximum radiation 1.1kW/m2

Humidity 0 to 100%

Standard control cable lengtha 7m (23)

Maximum vertical separation from ACR with standard control cable. 5m (16.4)

Maintenance intervalb 5 years

Auxiliary supply voltage (LV AC mains supply) As Ordered +10 -20%

Required auxiliary supply rating 100 VA

Battery (With battery heater option, 12AH batteries are standard.) 2 x 12V 7.2Ah

Battery hold up time from fully charged at 25C 38 hours with 7Ah
52 hours with 12Ah

Capacity available for communications, hold up time (no heater, OCP or IOEX) 20 hours
13.8V TX:2.1A, 15min, RX 320mA

Battery recharge time (new battery to 80% nominal capacity) 10 hours

11-4
Ratings and Specifications

Battery replacement intervalb. 5 years

Battery Low Voltagec 23V

Battery High Voltagec. 32V

Earthingd 10mm earth stud

Battery Heater Power (where fitted) 10W

Battery Heater Element Life 30,000hrse

Radio/Modem
A radio or modem may be fitted by the manufacturer or by the utility, for remote communications. Space,
power and data interfaces are provided within the control cubicle.

Radio/Modem Power Supply Voltage (set by user) 5 - 15V DC

Radio/Modem Power Supply Continuous Power 26W

Radio/Modem Power Supply Max Power 104W for 15 min with


20% duty cycle, 8A max

Radio/Modem Space on Radio Panel 300 x 250 x 150mm

Radio/Modem Interface V23, RS232, RS485

Radio/Modem Power Shutdown Time 1 - 1440 mins

Shutdown time increment 10 secs

Control Electronics

Continuous Primary current 1000A

Short time primary current 16kA for 3s

Short time current recovery time 60 sec

Required auxiliary supply rating 32VAC, 100VA

Real time clock hold time 20 days

Recloser Operations 20 in 1 minute, 1 per


minute thereafter

Controller EMC Ratings

EN55022 Conducted Disturbance Emissions Complied Class A

EN55022 Radiated Disturbance Emissions Complied Class A

EN61000-3-2 Quasi-Stationary Current Harmonics Complied Class A

EN61000-3-2 Voltage Fluctuations and Flicker Complied

EN61000-4-2 Immunity to Electrostatic Discharge Complied Level 4

EN61000-4-3 Immunity to Radiated Electromagnetic Fields Complied

EN61000-4-4 Immunity to Electrical Fast Transients Complied Level 4

EN61000-4-5 Surge Immunity Complied Level 4

EN61000-4-6 Immunity to Conducted Disturbances Complied

EN61000-4-11 Immunity to Voltage Dips and Interruptions Complied

a. Other control cable lengths available-4, 11 and 20 meters.


b. Battery replacement interval is influenced by environmental temperature.
c. Temperature compensated at 48mV/C.
d. Earthing details in Earthing on page 3-5 must be strictly adhered to.
e. If the heater is required for 6 months at say an average of 10 hours per day, it would be required for appoximately 2,000
hours running time per year, thus giving 15 years life.

11-5
N-Series Automatic Circuit Recloser

Power System HV line measurements on all three phases are


measurements made as follows:

Voltage Range (RMS Phase/Earth) N15/N27 2 - 15kV

Voltage Range (RMS Phase/Earth) N38 2 - 25kV

Voltage Resolution 1V

Voltage Accuracya 2.5% 25V

Live Terminal Threshold Voltage rangeb 2 - 15kV

Live Terminal Threshold Voltage setting resolutionb. 1V

Live Terminal Threshold Voltage accuracya.b. 5% 250V

Live Terminal Threshold Hysteresis -20%

Phase Current Range (True RMS) 2.5 - 800 Amp

Earth Current Range (True RMS) 1 - 800 Amp

Current Resolution 1 Amp

Phase Current Accuracya. 1.0% 1 Amp over


range 10 - 800 Amp

Earth Current Accuracya. 1.0% 1 Amp over


range 1 - 800 Amp

Apparent Power Range 0 - 54 MVA

Apparent Power Resolution 1 kVA

Apparent Power Accuracya. 3% over range 20 - 800


Amp

Real Power Rangec d -54 MW - +54 MW

Real Power Accuracya.c.d. 3% at PF > 0.9

Real Power Resolution 1 kW

Reactive Power Rangec. -54 MVAr - +54 MVAR

Reactive Power Resolution 1 kVAR

Reactive Power Accuracya. 4% at PF < 0.5

Unsigned Power Factor 0.5 - 1.0

Power Factor Resolution 0.01

Power Factor Accuracy 0.05

Measurement Filter Time Constant (Step Response) 2 sec

Measurement Update Rate 0.5 sec

a. Includes accuracy of switchgear current and voltage transformers.


b. Used for Live/Dead display, Live Load Blocking and Loss Of Supply detection.
c. In database for transmission by a protocol.
d. Used to accumulate kWh reading for weekly maximum demand data.

SF6 Gas
Pressure Nominal Pressure at 20C 35 kPa Gauge
Measurement
Gas Pressure Display Resolution 1 kPa

Gas Pressure Display Accuracy 5 kPa

Gas Low Alarm Setting 15 kPa Gauge @ 20 C

Gas Low Alarm Accuracy 5 kPa

11-6
Appendix A Replaceable Parts & Tools
All replacement parts listed in the following table
are available from the manufacturer.

ACR Part Stock or Part Number

1100mm Bushing Boot Silicone R01-318

770mm Bushing Boot Silicone INS021

Boot Clamping Ring N01-055

Boot Clamping Ring Spanner R01-260

Cable Tail Kit: Quantity 6 of 990000100


250 Amp, 3m cable fitted with bushing boot, lug and cable palm

Cable Tail Kit: Quantity 6 of 990000105


400 Amp, 3m cable fitted with bushing boot, lug and cable palm

Cable Tail Kit: Quantity 6 of 990000110


630 Amp, 3m cable fitted with bushing boot and screw termination

Cable Tail Kit: Quantity 6 of 990000115


800 Amp, 3m cable fitted with bushing boot, lug and cable palm

Control Cable 7m N03-602

Control Cable 11m N03-633

Control Cable 20m N03-635

Gas Fill Adaptor Kit 990003050

Manual Operation Set N07-600

Silicone Grease for boot installation - 300g tube LUB058044.

Silicone O-Ring grease: Dow 111 Valve and o-ring grease. LUB058040

ADVC Part Stock or Part Number

Antenna Surge Arrester ELCMIS0211

Basic Display Unit (BDU1 - NuLec English) 998000025

Basic Display Unit (BDU1 - Merlin Gerin English) 998000026

Basic Display Unit (BDU1 - NuLec USA) 998000028

Battery 12 V 7.2 Ah Sealed Lead Acid, set of 2 997000000

Battery 12 V 12 Ah Sealed Lead Acid, set of 2 998000055

Battery Heater 998000040

CAPE Housing Main Gasket ADC-101

Control and Protection Enclosure (CAPE1 - for manufacturers switch) 998000015

Control Cubicle Body 998000045

Control Cubicle Door 998000050

Control Cubicle Door Seal (24 mm x 6 mm, Black) NEO091008

Customer Tray 1 998000030

Customer Tray Terminal Block 998000035

Fiber optic modem 998000090

IOEX2 998000080

A-1
N-Series Automatic Circuit Recloser

ADVC Part Stock or Part Number

Pole mount adapter for PTCC retrofit 998000125

Power Supply Unit (PSU1 - English international) 998000020

Power Supply Unit (PSU1 - English USA) 998000020

PSU Main gasket ADC-110

Tait radio accessory 99800085

Test and Training Set (TTS) TTS1-02

WSOS cable 998000095

USB to serial converter 998000100

A-2
Appendix B Dimensions

ACR
Dimensions

Figure 22: ACR Dimensions

B-1
N-Series Automatic Circuit Recloser

ADVC
Dimensions

Figure 23: ADVC Dimensions

B-2
Pole Mounting
Brackets

Figure 24: N15/24 Pole Mount Bracket

Figure 24: N 38 Pole Mount Bracket

B-3
N-Series Automatic Circuit Recloser

IOEX2
Dimensions

Figure 25: IOEX 2 Dimensions

B-4
Appendix C Safety Data Sheet - Sulphur Hexafluoride
The following is reproduced from the original
data sheet supplied by LINDE Gas Pty Ltd.

Product:
MSDS No: 110 Sulphur Hexafluoride
Version 1.18 dated 29/06/99

1 IDENTIFICATION OF THE SUBSTANCE / PREPARATION AND OF THE COMPANY

MSDS No: 110

Product Name Sulphur Hexafluoride

Chemical Formula SF6

Company Identification LINDE Gas Pty Ltd., 66 Loftus Rd, YENNORA, 2161 NSW Australia

Emergency Phone 1300-65-7070 (24 hour service)


Numbers

2 COMPOSITION / INFORMATION ON INGREDIENTS

Substance / Preparation Substance

Components/Impurities Contains no other components or impurities which will influence the


classification of the product.

CAS Nr 02551-62-4

EEC Nr (from EINECS) 219-854-2

3 HAZARDS IDENTIFICATION

Hazards Identification Liquefied gas.


In high concentrations may cause asphyxiation.

4 FIRST AID MEASURES

Inhalation In high concentrations may cause asphyxiation. Symptoms may include


loss of mobility / consciousness. Victim may not be aware of
asphyxiation. Remove victim to uncontaminated area wearing self
contained breathing apparatus. Keep victim warm and rested. Call a
doctor. Apply artificial respiration if breathing stopped.

Skin / eye contact Immediately flush eyes thoroughly with water for at least 15 minutes.
Apply a sterile dressing. Obtain medical assistance.

Ingestion Ingestion is not considered a potential route of exposure.

5 FIRE FIGHTING MEASURES

Specific hazards Exposure to fire may cause containers to rupture or explode.


Non flammable.

Hazardous combustion If involved in a fire the following toxic and/or corrosive fumes may be
products produced by thermal decomposition:
a) Hydrogen fluoride
b) Sulphur dioxide

Suitable extinguishing All known extinguishments can be used.


media

Specific methods If possible, stop flow of product. Move container away or cool with water
from a protected position.

Special protective Use self-contained breathing apparatus and chemically protective


equipment for fire fighters clothing.

C-1
N-Series Automatic Circuit Recloser

Product:
MSDS No: 110 Sulphur Hexafluoride
Version 1.18 dated 29/06/99

6 ACCIDENTAL RELEASE MEASURES

Personal precautions Evacuate area.


Wear self-contained breathing apparatus when entering area unless
atmosphere is proved to be safe.
Ensure adequate air ventilation.

Environmental precautions Try to stop release.


Prevent from entering sewers, basements and workpits or any other
place where its accumulation can be dangerous.

Clean up methods Ventilate area.

7 HANDLING AND STORAGE

Handling and storage Suck back of water into the container must be prevented.
Do not allow backfeed into the container.
Use only properly specified equipment which is suitable for this product,
its supply pressure and temperature. Contact your gas supplier if in any
doubt.
Refer to suppliers container handling instructions.
Keep container below 50 C in a well ventilated place.

8 EXPOSURE CONTROLS / PERSONAL PROTECTION

Exposure limit value for Great Britain: STEL: 1250 ppm LTEL: 100 ppm (EH 40/97).
country Germany: MAK = 1000 ppm.

Personal protection Ensure adequate ventilation.


Do not smoke whilst handling product.

9 PHYSICAL AND CHEMICAL PROPERTIES

Molecular weight 146

Melting point -50.8 C

Boiling point -64(s) C

Critical temperature 45.5 C

Relative density, gas 5 (air = 1)

Relative density, liquid 1.4 (water = 1)

Vapour pressure 20 C 21 bar

Solubility mg/l water 41 mg/l

Appearance/Colour Colourless gas

Odour No odour warning properties

Other data Gas/vapour heavier than air, may accumulate in confined spaces
particularly at or below ground level.

10 STABILITY AND REACTIVITY

Stability and reactivity Stable under normal conditions.


Thermal decomposition yields toxic products which can be corrosive in
the presence of moisture.

11 TOXICOLOGICAL INFORMATION

General No known toxicological effects from this product.

12 ECOLOGICAL INFORMATION

General No known ecological damage caused by this product.

13 DISPOSAL CONSIDERATIONS

General Do not discharge into any place where its accumulation could be
dangerous. Contact supplier if guidance is required.

C-2
Product:
MSDS No: 110 Sulphur Hexafluoride
Version 1.18 dated 29/06/99

14 TRANSPORT INFORMATION

Proper shipping name Sulphur hexafluoride.

UN Nr 1080.

Class/Div 2.2

ADR/RID Item Nr 2.2 A

ADR/RID Hazard Nr 20

Labelling ADR Label 2: non flammable toxic gas.

Other transport information Avoid transport on vehicles where the load space is not separated from
the drivers compartment.
Ensure vehicle driver is aware of the potential hazards of the load and
knows what to do in the event of an accident or an emergency.
Before transporting product containers ensure that they are firmly
secured and:
a) cylinder valve is closed and not leaking.
b) valve outlet cap nut or plug (where provided) is correctly fitted.
c) valve protection device (where provided) is correctly fitted.
d) there is adequate ventilation.
e) compliance with applicable regulations.

15 REGULATORY INFORMATION

Number in Annex I of Dir Not included in Annex I.


67/548

EC Classification Not classified as dangerous substance.

EC Labelling (Symbols, No EC Labelling required.


R&S phrases)

16 OTHER INFORMATION

Asphyxiant in high concentrations.


Keep container in well ventilated place.
Do not breathe the gas.
Ensure all national/local regulations are observed.
Contact with liquid may cause cold burns/frost bite.
The hazard of asphyxiation is often overlooked and must be stressed during operator training.
Before using this product in any new process or experiment, a thorough material compatibility and
safety study should be carried out.
Details given in this document are believed to be correct at the time of going to press. Whilst proper
care has been taken in the preparation of this document, no liability for injury or damage resulting from
its use can be accepted.

-END OF SAFETY DATA SHEET-

C-3
N-Series Automatic Circuit Recloser

C-4
Index

Index

A Maintenance ................................................ 10-3


Abnormal operating conditions ............................10-4 control cubicle mounting ...................................... 3-4
ACR .......................................................................1-1 control cubicle weight ........................................... 3-1
ADVC ....................................................................1-1 cubicle storage ..................................................... 3-1
ALT .......................................................................7-2 cubicle vents ........................................................ 6-1
atmospheric pollution ..........................................10-1 custom menu ........................................................ 7-3
Auxiliary power Custom Menu key ................................................ 7-1
From integral transformer ...............................3-6 D
From mains .....................................................3-6 designating the source side ................................. 5-4
Source ............................................................6-1 Display ................................................................. 7-1
auxiliary supply ......................................................6-1 Display Groups ..................................................... 7-2
auxiliary voltage ....................................................2-1 door sealing rubber ............................................ 10-3
B E
basic display unit ...................................................6-2 Earthing ................................................................ 3-5
batteries ................................................................6-1 Enable/Disable Close switch ................................ 7-1
Battery .................................................................10-4 Enable/Disable Trip switch ................................... 7-1
Care ..............................................................10-4 Enter key .............................................................. 7-1
Replacement ................................................10-3 Equipment Versions Covered by this Manual ...... 1-1
battery care .........................................................10-4 Event
BDU ............................................................... 1-1, 6-2 Log ................................................................. 8-1
breaking duty .......................................................10-1 Excess Close Operations ................................... 10-4
Bushing boot .........................................................3-4 F
Clamping ring spanner ...................................3-3 Fault
bushing boots ......................................................10-1 Finding ......................................................... 10-4
bushings ................................................................2-3 Feed-through or bulkhead type arrester ............... 4-1
C G
Cable Tail Gas discharge surge arrester ............................... 4-1
Connections ....................................................3-4 Gas fill adaptor ................................................... 10-1
Kit ...................................................................1-1 gas fill valve ........................................................ 10-1
Capacitor charging inverter .................................10-4 gas filling procedure ........................................... 10-1
CAPE ............................................................ 1-1, 6-1 Gas Low
caution symbol ......................................................1-1 Alarm ........................................................... 10-1
Check H
Control cubicle ..............................................10-4 High Voltage connections .................................... 3-3
checking battery status ................................. 5-1, 5-2 hookstick .............................................................. 2-1
checking the Aux Supply status ............................5-2 HOT LINE ............................................................. 7-1
Circuit breaker Hot Line Tag ......................................................... 7-1
Maintenance .................................................10-1 I
SF6 Recharging ............................................10-1 Installation ............................................................ 3-1
Clamping ring spannerbushing boot ...................3-3 Integrated
Clamping ringbushing boot .................................3-5 Auxiliary supply .............................................. 3-6
Cleaning ..............................................................10-1 IOEX
Close key ..............................................................7-1 Card ............................................................... 4-3
Communications K
Interfaces ........................................................4-1 keypad .................................................................. 7-1
condensation .........................................................6-1 L
Configurable Quick Key ........................................7-1 LEFT scroll key .................................................... 7-2
Configuration .........................................................5-1 Live/Dead indication ............................................. 9-1
Connecting the cables ...........................................3-4 LOCAL/REMOTE ................................................. 7-2
contact life ...........................................................10-1 LOOP AUTO ........................................................ 7-2
Contents of crate ...................................................3-1 Low Power mode ............................................... 10-4
Control and protection enclosure ..........................6-1 low power mode ................................................... 6-1
Control cable .........................................................3-1 LV
Connection .....................................................3-1 Surge arrester ................................................ 3-6
Control cubicle LV auxiliary supply
Check ...........................................................10-4 Connection ..................................................... 3-6
Cleaning .......................................................10-3 From dedicated utility transformer ................. 3-6
Construction ...................................................6-1

Index-I
N-Series Automatic Circuit Recloser
M Replacement of electronic modules ................... 10-5
Main earth bond ................................................... 3-6 replacement parts ................................................. 1-1
Maintenance .............................................. 10-1, 10-3 reverse polarity ..................................................... 3-4
maintenance port ................................................. 6-2 RIGHT scroll key .................................................. 7-2
mechanical duty ................................................. 10-1 S
MENU scroll key ................................................... 7-2 SCADA ................................................................. 4-6
modem ................................................................. 4-2 SCEM ................................................................... 1-1
Mounting brackets ................................................ 3-5 Sealing and condensation .................................... 6-1
N SELECT key ......................................................... 7-2
navigation symbol ................................................ 1-1 Select key ............................................................. 7-3
navigation within groups ....................................... 7-3 setting the phasing ............................................... 5-3
note symbol .......................................................... 1-1 settings ................................................................. 7-2
O SF6 ....................................................................... 2-1
OCI ....................................................................... 1-1 SF6 ..................................................................... 10-1
OCP .............................................................. 6-1, 7-1 Silicone grease ..................................................... 3-4
Operator Control Panel ........................................ 6-1 Site installation ..................................................... 3-2
operator control panel .......................................... 7-1 Site procedure ............................................... 3-3, 5-3
operator interface ................................................. 6-2 Software
P Capability ....................................................... 1-1
pages ................................................................... 7-2 software version ................................................... 1-1
Parts and tools ..................................................... 1-1 status .................................................................... 7-2
Parts required ....................................................... 3-3 sub-pages ............................................................. 7-2
password .............................................................. 7-3 sulphur hexaflouride ............................................. 2-1
PCOM .................................................................. 1-1 Supervisory Control and Data Acquisition ............ 4-6
pointer ................................................................ 10-1 Surge arresters ..................................................... 3-5
Power Factor (PF) ................................................ 9-2 LV .................................................................. 3-6
Power Flow direction ............................................ 5-3 Mounting and terminating .............................. 3-5
Power supply unit ................................................. 6-1 SWGM .................................................................. 1-1
Power System measurements ............................. 9-1 T
Press to Talk (PTT) .............................................. 4-5 Test and Training Set ........................................... 1-2
Protection Testing & configuring ............................................ 3-2
Of radio equipment ........................................ 4-1 Tools required ...................................................... 3-3
Protection settings ................................................ 7-3 Transport to site ................................................... 3-2
PSU ............................................................... 1-1, 6-1 Trip key ................................................................. 7-1
PSU module ......................................................... 6-1 TRIP or CLOSE LED .......................................... 10-4
PTCC ................................................................... 1-1 U
Q Updating the Event Log ........................................ 8-1
Quick Key ............................................................. 7-4 user interface ........................................................ 7-1
quick keys ............................................................ 7-4 V
R vermin ................................................................... 6-1
radio ..................................................................... 4-2 Voltage free output contacts ................................. 4-3
Radio Aerial .......................................................... 4-1 W
Radio holdup time ................................................ 4-2 warning symbol .................................................... 1-1
radio/modem power supply voltage ..................... 4-2 Windows Swirchgear Operating System .............. 4-5
Real Power (kW) .................................................. 9-2 Windows Switchgear Operating System (WSOS) 8-1
Real Time Displays .............................................. 9-1 Windows Switchgear Operator System ................ 7-3
recloser bushings ................................................. 2-3 WSOS .................................................................. 7-4
Recloser earthing ................................................. 3-5 WSOS Interface ................................................... 6-2
re-configuring the Quick Keys .............................. 7-4

Index-II
III
N-Series Automatic Circuit Recloser

IV
Nu-Lec Industries Corporate office & USA office As standards, specifications and designs change from time to
factory time, please ask for confirmation of the information given in this
publication.
35-37 South Street 1252 Old Alpharetta Road
Lytton, 4178 Alpharetta, Georgia
Queensland 30005-3986
Australia United States of America
ADC-1007-NI

Tel: +61 7 3249 5444 Tel: +1770 521 2000


Fax: +61 7 3249 5888 Fax: +1770 521 2100

e-mail: sales@nulec.com.au e-mail: sales@nulec.com


http://www.nulec.com.au http://www.nulec.com
09/2005

Potrebbero piacerti anche