Sei sulla pagina 1di 7

<<Contents>> <<Index>>

General SSS7740
PRM Advanced Diagnosis
Specications Server
GS 33Y05Q21-32E

GENERAL
The PRM Advanced Diagnostic function is an optional feature of the Plant Resource Management (PRM) package.
This function acquires parameter information required for diagnosis from devices connected to the FOUNDATION
eldbus and HART and can diagnoses plant equipment. The results of diagnosis are reected by PRM. Moreover,
device and unit diagnoses can also be performed using device parameter and process data.
Users can also create their own diagnostic applications using the PRM Advanced Diagnostic Application Software
Development Kit (PAA development kit NTPS220-S11, an optional package). Since the PAA development kit
includes standard sample diagnostic application templates, the diagnosis function is ready for use.

CONFIGURATION FOR PRM ADVANCED DIAGNOSIS


The PRM Advanced Diagnosis function are as follows.
PRM Advanced Diagnosis Server
PRM Advanced Diagnosis client
PRM Advanced Diagnostic Application

PRM Advanced Diagnosis client


Diagnostic navigator
Diagnostic tool

Ethernet

PRM server
Field Data acquisition
Exaopc
communication PRM Advanced Diagnosis server
OPC server
server Advanced Diagnosis server
Device Diagnosis Data Historian
PRM Advanced Diagnosis Application Software Development Kit

Control bus

FCS

FOUNDATION fieldbus H1
HART device
FOUNDATION fieldbus H1 device F01E.ai

PRM Advanced Diagnosis Server


The PRM Advanced Diagnosis Server consists of an Advanced Diagnosis Server and a Device Diagnosis Data
Historian.
Advanced Diagnosis Server
This function executes the diagnosis registered in the Advanced Diagnosis Server.

Device Diagnosis Data Historian


The PRM server acquires data for device diagnosis via a eld communication server or an OPC server, and passes
the data to the diagnostic application. The acquired data can also be stored in the Diagnosis Historian Server as
historical data.

PRM Advanced Diagnosis Client


The Diagnosis client allows for dening acquisition data for diagnosis, monitoring the diagnostic status, registering
the diagnostic application, executing diagnosis, starting and stopping diagnosis, and starting and stopping data
acquisition. The client function of diagnosis are as follows.
Diagnostic navigator
Diagnostic tool

Yokogawa Electric Corporation GS 33Y05Q21-32E


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan Copyright Jul. 26, 2006(YK)
Tel.: 81-422-52-5634 Fax.: 81-422-52-9802 5th Edition Jun. 1, 2010(YK)
<<Contents>> <<Index>> 2
CONFIGURATION OF PRM ADVANCED DIAGNOSIS FUNCTION
The following shows Conguration of function for Advanced Diagnosis.
View detailed information

PRM Advanced Diagnosis client

Diagnostic Start
Device navigator diagnostic Diagnostic tool
navigator
tool
Start diagnostic
module Install diagnostic application
Error notified

Advanced Diagnosis
server

Notified by e-mail Diagnosis module


PRM Advanced
Diagnostic
application (PAA)
ABC...!
Device Diagnosis
HIS Operation Guide Data Historian

PRM server

Acquisition service
F03E.ai

DIAGNOSTIC DATA ACQUISITION


PRM server acquire Diagnostic data.
Data is acquired via a eld communication server or an OPC server. The data acquired for diagnosis is as follows.
Data required by the diagnostic application
User-dened data
Data dened in the acquisition denition le

Data Required by Diagnostic Application


When Diagnostic modules are started using the Diagnostic navigator, the data which are required for the Diagnostic
modules are automatically registered as acquired data.

User-dened Data
The user can register arbitrary data as acquisition data. Registration can be performed from the Diagnosis client.

Data Dened in Acquisition Denition File


Data dened in the acquisition denition le can be made acquisition data. The acquisition denition le is supplied
by the device vendor. Two types of acquisition denition les are used: a Device Viewer denition le supplied by the
device vendor and an acquisition le that can be modied by the user.

All Rights Reserved. Copyright 2006, Yokogawa Electric Corporation GS 33Y05Q21-32E Nov. 30, 2007-00
<<Contents>> <<Index>> 3
DIAGNOSTIC EXECUTION
Device diagnosis is individually performed for each diagnostic module. Starting and stopping of diagnosis is also
individually performed for each diagnostic module. Multiple diagnostic modules make up a diagnostic application.

Diagnostic application A Diagnostic application B

consisting of multiple diagnostic modules


Diagnostic module A-1 Diagnostic module B-1
Diagnostic application

Diagnostic module A-2 Diagnostic module B-2

Diagnostic module A-nnn Diagnostic module B-nnn

Diagnosis server consisting of multiple diagnostic applications


F02E.ai

Figure: Relationship between Diagnostic Modules and Diagnostic Applications

DEVICE DIAGNOSTIC DATA HISTORIAN


Device Diagnostic Data Historian is the function to acquire and store diagnosis-related parameters. Parameter data
acquired by the diagnosis server can be stored as historical data. Data that is stored includes eld device parameters
and results obtained by calculations performed for diagnosis execution.

NOTIFYING DETECTED ERRORS TO USER


When an error is detected by diagnosis, the following methods are used to notify the user.
HIS Operation Guide Message
E-mail Notication
PRM Client Maintenance Alarm Message
Device Status Icons in Device Navigator of PRM client

BUILDING DIAGNOSTIC APPLICATION


PRM Advanced Application Software Development Kit (PAA Development Kit) allows the user to build his/her own
unique diagnostic application. PAA Development Kit also runs on the diagnosis server (PRM server). A diagnostic
application that was created is registered in the diagnosis server from the PRM client. PAA Development Kit includes
sample diagnoses. Diagnostic applications can be easily built by modifying and referring to these sample diagnoses.
The following sample diagnoses are included in the kit.
Upper and lower limit check
Area monitoring
Monitoring difference between multiple devices
Monitoring errors of automatic reciprocating compressor

MULTI-PURPOSE DIAGNOSTIC TOOL


When diagnostic application is created, graphical user interface (GUI) dedicated to it must be created at the same
time. The PRM Advanced Diagnosis server function includes a multi-purpose diagnostic tool that displays the past
data trend and thresholds. It is not necessary to create a dedicated diagnostic tool for simple diagnosis such as
threshold decision.

All Rights Reserved. Copyright 2006, Yokogawa Electric Corporation GS 33Y05Q21-32E Nov. 30, 2007-00
<<Contents>> <<Index>> 4
PRM ADVANCED DIAGNOSIS SERVER SPECIFICATIONS
The diagnosis server specications differ depending on the other server functions that runs on the diagnosis server.

The server functions that coexist with Diagnosis server


Diagnosis server Diagnosis server Diagnosis server, historian server
Packages that run on the diagnosis server
only and historian server and eld communication server
Types of simultaneously executable diagnostic
10 10 10
applications
Number of simultaneously executable modules 3,000 1,000 300
Diagnosis cycle 1 to 1 day 1 to 1 day 1 to 1 day
Number of acquisition points for device diagnosis 30,000 points 10,000 points 3,000 points
Number of acquisition points for device diagnosis
31,000 points 11,000 points 3,100 points
historian
Number of data items unique to diagnosis 1,200,000 400,000 120,000
Number of acquisition points to be stored 60,000 points 30,000 points 10,000 points
Number of devices supported by a single
5 devices; a single diagnostic module can handle data of up to 5 devices.
diagnostic module
Number of data items supported by a single
400 data items; a single diagnostic module can handle up to 400 parameters.
diagnostic module

All Rights Reserved. Copyright 2006, Yokogawa Electric Corporation GS 33Y05Q21-32E Nov. 30, 2007-00
<<Contents>> <<Index>> 5
OPERATING ENVIRONMENT
The diagnosis client function is included in the PRM client function.
PRM Advanced Diagnosis server consists of Advanced Diagnosis server to diagnose PAA and Device Diagnosis Data
Historian with Historian database. The following shows hardware requirements for these two servers. When they are
used in the same PC, CPU requirement is that for Advanced Diagnosis server and main storage capacity and disc
capacity requirement is the total amount required for each server.

Advanced Diagnostic server hardware requirements

Number of devices
300 units or less 1000 units or less 3000 units or less
Pentium4 2.8 GHz or higher
Pentium4 2.8 GHz or higher required
Pentium4 2.8 GHz or higher required
CPU Xeon Dual 2.8 GHz or higher
required Xeon Dual 2.8 GHz or higher
recommended
recommended
For Windows Server 2008:
For all applicable Windows OS: For all applicable Windows OS:
2 GB or greater recommended
Main storage capacity 1 GB or greater required 1 GB or greater required
For other applicable Windows OS:
2 GB or greater recommended 2 GB or greater recommended
1 GB or greater required
Disc capacity 1 GB or greater free area 3 GB or greater free area 8 GB or greater free area

Diagnosis Data Historian server hardware requirements

Number of devices
300 units or less 1000 units or less 3000 units or less
Pentium4 2.8 GHz or higher
Pentium4 2.8 GHz or higher required
Pentium4 2.8 GHz or higher required
CPU Xeon Dual 2.8 GHz or higher
required Xeon Dual 2.8 GHz or higher
recommended
recommended
512 MB or greater required 512 MB or greater required 1 GB or greater required
Main storage capacity
1 GB or greater recommended 1 GB or greater recommended 2 GB or greater recommended
Disc capacity 6 GB or greater free area 15 GB or greater free area 35 GB or greater free area
PRM database (*1) 3 GB 10 GB 30 GB

*1 Device database capacity indicates disc capacity required for a year, which is calculated under the following condition:
Collect 10 numerical parameters in 10-minute periods per device
Save one diagnosis in 10-minute periods per device

SOFTWARE REQUIREMENT
Advanced Diagnostic Server
Windows Server 2008 Standard Edition Service Pack 2
Windows Server 2003 Service Pack 2
WIndows Server 2003 R2 Sercvice Pack 2
Windows XP Professional Service Pack 3
Windows Vista Business Edition Service Pack 1/Service Pack 2

DIagnosis Data Histrian Server


Windows Server 2003 Service Pack 2
WIndows Server 2003 R2 Sercvice Pack 2
Windows XP Professional Service Pack 3

All Rights Reserved. Copyright 2006, Yokogawa Electric Corporation GS 33Y05Q21-32E Jun. 1, 2010-00
<<Contents>> <<Index>> 6
MODELS AND SUFFIX CODES
PRM Advanced Diagnostic Server
Description
Model SSS7740 PRM Advanced Diagnostic (Server) [Media model: SSSSM02-C11]
-S Basic software license
-C Multiple software licenses (for 2 or more)
Sufx Codes
1 Always 1
1 English version
/N0100 Maximum number of applications: 1
/N0200 Maximum number of applications: 2
Option Codes
/N0500 Maximum number of applications: 5
/N1000 Maximum number of applications: 10
Note: Diagnosis Data Historian Server does not support Windows Vista Business Edition Service Pack 1, Service Pack 2 and
Windows Server 2008 Service Pack 2.

PRM Advanced Diagnostic Server (for Expansion)


Description
Model SSS7740 PRM Advanced Diagnostic (Server) [Media model: SSSSM02-C11]
-A Software license for additional devices
Sufx Codes 1 Always 1
1 English version
/N0102 Expand maximum number of applications: 1 to 2
/N0105 Expand maximum number of applications: 1 to 5
/N0110 Expand maximum number of applications: 1 to 10
Option Codes
/N0205 Expand maximum number of applications: 2 to 5
/N0210 Expand maximum number of applications: 2 to 10
/N0510 Expand maximum number of applications: 5 to 10

PRM Advanced Diagnostic Server (for Upgrading R2 - R3)


Description
Model SSS7740RU PRM Advanced Diagnostic (Server) Upgrade [Media model: SSSSM02-C11]
-S Basic software license
-C Multiple software licenses (for 2 or more)
Sufx Codes
1 Always 1
1 English version
/N0100 Number of diagnostic application: 1
/N0200 Maximum number of diagnostic application: 2
Option Codes
/N0500 Maximum number of diagnostic application: 5
/N1000 Maximum number of diagnostic application: 10

Note: Purchase upgrading license from R2 to R3 in accordance with every license (basic as well as multiple) you purchased in
R2. Specify the number of diagnostic application you purchased in R2.
Note: Please order this model name, when you want to upgrade the PRM Advanced Diagnostic Server version.
Note: Diagnosis Data Historian Server does not support Windows Vista Business Edition Service Pack 1, Service Pack 2 and
Windows Server 2008 Service Pack 2.

PRM Advanced Diagnostic Application Software Kit


Please order NTPS220-S11. The software license and instruction manual are issued by ordering this software.
Software media is not issued because the program of this software itself is included in media SSSSM02-C11; the
electronic document is included in media SSSSD02-C11.

All Rights Reserved. Copyright 2006, Yokogawa Electric Corporation GS 33Y05Q21-32E Jun. 1, 2010-00
<<Contents>> <<Index>> 7
TRADEMARKS
PRM is a registered trademark of Yokogawa Electric Corporation.
CENTUM is a registered trademark of Yokogawa Electric Corporation.
FOUNDATION of FOUNDATION eldbus is a registered trademark of Fieldbus Foundation.
HART is a registered trademark of the HART Communication Foundation.
Pentium is a registered trademark of Intel Corporation.
Ethernet is a registered trademark of XEROX Corporation
Windows and Windows Vista are registered trademarks of Microsoft Corporation in the United States and/or other
countries.
Other product and company names in this document are trademarks or registered trademarks of their respective
holders.

All Rights Reserved. Copyright 2006, Yokogawa Electric Corporation GS 33Y05Q21-32E Jun. 1, 2010-00
Subject to change without notice.