As per ANSI/IEEE Std 80-1986 code Enter Your Data in White back
:Enter Your Details:
Length of Area Occupied by Earthing Grid la 105 mt
Width of Area Occupied by Earthing Grid lb 66 mt
Fault level at Incoming Bus fault 5000 MVA
Incoming Voltage Vin 132 KV
Outgoing Voltage Vout 66 KV
Soil Resistivity q 40 -m
Resistance of Main Eartjing Mat 0.5
Resistance of surface Material (Crushed Rock ) qs 3000 -m
Thickness of Surface Material (Crushed Rock) hs 0.1 mt
Depth of Earthing Grid Conductor h 0.5 mt
Diameter of Earthing Grid Conductor d 36 mm2
Reference Depth of Grid 1 mt
Area Occupied by Earthing Grid 6930 m2
Spacing between Parallel Conductor of Grid D 5 mt
Duration of Fault (To determine Size of earthing Mat) t 3 sec
Duration of Fault (To determine safe Step & Touch Potential) t 0.5 sec
Margine Factor in Earthing Mat against corrossion and Rusting 100.00%
Number of Adjacement Earthing Mat Conductor nm 23 nos
Relaction Factor K -0.973684
Constant (KS) Ks 0.3314497
Constant (Ki) Ki 4.612
Number of Parallel Conductor in Longitudinal direction na 21
Number of Parallel Conductor in Transverse direction nb 13
No of Lighting Arrestors 10
No of Transformers 2
Decrement Factor for entire duration of Fault(to allow asymetrical of
Df
the Fault curernt wave) 1
Corrective projection factor according for the relative increase fault
Cp 1.1
current during S/S life( Zero future system growth Cp=1)
Ambient Temperature Ta 35 0C
Maximum allowable Temperature Tm 1084 0C
Temperature of Thermal Co-efficient of resisitivty at 0C Ko
Thermal Capacity Factor TACP 3.8466 J/cm3/c
Thermal Co-efficient of resistiivty at referance Temp of Tr & 0.00378
Earthing Conductor
Standard Dia of Conductor (mm)
32 804
36 1018
40 1257
0
0
0
0
0
0
0
0
0
0.00189
N FOR SUB STATION Jignesh.Parmar www.electricalnotes.wordpres
1017.9
0.55 0.55