Sei sulla pagina 1di 52

Home Generator Systems

Installation & Operators Manual

100/200 Amp Automatic


Transfer Switch
with ACPower Control Module
Thank you for your purchase of this Briggs & Stratton Power Products automatic transfer switch. This product is designed
for use with specific home standby generators and may not function with generators produced by other manufacturers.
Seek a qualified electrical professional to determine applicability of this equipment to generators manufactured by others.
When operated and maintained according to the instructions in this manual, your system will provide many years of
dependableservice.

This manual contains safety information to make you aware of the hazards and risks associated with this system and how to
avoid them. We have made every effort to provide for a safe, streamlined and cost-effective installation. As each installation
is unique, it is impossible to know of and advise of all conceivable procedures and methods by which installation might be
achieved. We do not know all possible hazards and/or the results of each possible method or procedure. It is important that
you read and understand these instructions thoroughly before attempting to install or operate this equipment. Save these
instructions for future reference.

This transfer switch requires professional installation before use. Refer to the Installation section of this manual for
instructions on installation procedures. Only licensed electrical contractors should install transfer switches. Installations must
strictly comply with all applicable federal, state and local codes, standards and regulations. Your installer should follow the
instructions completely.

Where to Find Us
You never have to look far to find Briggs & Stratton support and service for your system. Consult your Yellow Pages.
There are many authorized service dealers who provide quality service. You can also contact Technical Service by phone at
(800) 743 4115 between 8:00 AM and 5:00 PM CT, or on the Internet at BRIGGSandSTRATTON.COM.

For Future Reference


Please fill out the information below and keep with your receipt to assist in unit identification for future purchase issues.

Transfer Switch

Model Number

Revision

Serial Number

Date Purchased

Briggs & Stratton Power Products Group, LLC


900 North Parkway
Jefferson, WI 53549

Copyright 2009. All rights reserved. No part of this material may


be reproduced or transmitted in any form without the express written
permission of Briggs & Stratton Power Products Group, LLC.

2 BRIGGSandSTRATTON.COM
Table of Contents

Important Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . 4


Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Owner Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installing Dealer/Contractor Responsibilities . . . . . . . . . . . . . . . . . . . . . . . 5
Mounting Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Power Wiring Interconnections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Supervisory Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
System Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
System Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Testing the Automatic Transfer Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Schematic and Wiring Diagram, Models 071018 and 071019 . . . . . . . . . 14
Schematic and Wiring Diagram, Models 071020 and 071021 . . . . . . . . . 15

Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Product Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

3
SAVE THESE INSTRUCTIONS

Important Safety Instructions WARNING Low voltage wire cannot be installed in


same conduit as power voltage wiring.
SAVE THESE INSTRUCTIONS - This manual contains
important instructions that should be followed during
installation and maintenance of the equipment.
Failure to follow above warning could cause personal
Safety Symbols and Meanings injury, damage and/or malfunction of equipment.

WARNING Failure to properly ground equipment can


result in electrocution.
Electrical Shock Read Manual

The safety alert symbol indicates a potential personal


injury hazard. A signal word (DANGER, WARNING, or Do not touch bare wires.
CAUTION) is used with the alert symbol to designate a Do not use equipment with worn, frayed, bare or
degree or level of hazard seriousness. A safety symbol otherwise damaged wiring.
may be used to represent the type of hazard. The signal
Do not handle electrical cords while standing in water,
word NOTICE is used to address practices not related to while barefoot, or while hands or feet are wet.
personalinjury.
If you must work around a unit while it is operating, stand
DANGER indicates a hazard which, if not avoided, will on an insulated dry surface to reduce shock hazard.
result in death or serious injury. Do not allow unqualified persons or children to operate or
WARNING indicates a hazard which, if not avoided, could service equipment.
result in death or serious injury. In case of an accident caused by electrical shock,
CAUTION indicates a hazard which, if not avoided, could immediately shut down all sources of electrical power
result in minor or moderate injury. and contact local authorities. Avoid direct contact with
thevictim.
NOTICE addresses practices not related to personal injury.
The manufacturer cannot possibly anticipate every possible
circumstance that might involve a hazard. The warnings in WARNING Equipment contains high voltage that can
this manual, and the tags and decals affixed to the unit are, cause personal injury or death.
therefore, not all-inclusive. If you use a procedure, work
method or operating technique that the manufacturer does
not specifically recommend, you must satisfy yourself that Despite the safe design of the system, operating this
equipment imprudently, neglecting its maintenance or
it is safe for you and others. You must also make sure that
being careless can cause possible injury or death.
the procedure, work method or operating technique that you
choose does not render the equipment unsafe.
NOTICE Improper treatment of equipment can damage it
and shorten its life.
WARNING Only qualified electricians should attempt Use equipment only for intended uses.
installation of this equipment, which must strictly comply If you have questions about intended use, ask dealer or
with applicable codes, standards and regulations. contact Briggs & Stratton Power Products.
Do not expose equipment to excessive moisture, dust,
WARNING Certain components in this product and dirt, or corrosive vapors.
related accessories contain chemicals known to the State Remain alert at all times while working on this equipment.
of California to cause cancer, birth defects, or other Never work on the equipment when you are physically or
reproductive harm. Wash hands after handling. mentally fatigued.
If connected devices overheat, turn them off and turn off
their circuit breaker/fuse.

4 BRIGGSandSTRATTON.COM
Installation Installing Dealer/Contractor Responsibilities
Read and observe the safety rules.
We sincerely appreciate your patronage. For this reason,
we have made significant effort to provide for a safe, Read and follow the instructions given in this manual.
streamlined and cost-effective installation. Because each The installer may need to provide appropriate rated
installation is unique, it is impossible to know of and advise contactors based on loads to be controlled.
the trade of all conceivable procedures and methods by Check federal, state and local codes and authority
which installation might be achieved. Neither could we know having jurisdiction, for questions on installation.
of possible hazards and/or the results of each method or
Ensure generator is not overloaded with selected loads.
procedure. For these reasons,
If you need more information about the transfer switch, call
Only current licensed electrical should attempt system
(800) 743-4115, between 8:00 AM and 5:00 PM CT.
installations. Installations must strictly comply with all
applicable codes, industry standards and regulations.
Equipment Description
Your equipment is supplied with this combined Installation
The transfer switch is designed to transfer the selected
and Operators Manual. This is an important document and
loads found in normal residential installations to generator
should be retained by the owner after the installation has
power in the event of a utility power failure. The load is
been completed.
connected either to utility power (normal) or home standby
Every effort has been made to make sure that the information power (generator). The transfer switch monitors utility and
in this manual is both accurate and current. However, the generator voltages and will automatically connect to the
manufacturer reserves the right to change, alter or otherwise appropriate source of power.
improve the system at any time without prior notice.
These switches make it easy for a licensed electrician to
complete a home standby installation. Depending on the
Home Owner Responsibilities
specific model purchased, service conduit and conductors
To help you make informed choices and communicate can be wired directly from the hour-meter to the transfer
effectively with your installation contractor(s), switche a separate disconnect and associated wiring are not
Read and understand Owner Orientation before contracting required when installed per applicable federal, state and local
or starting your equipment installation. codes, standards and regulations.
To arrange for proper installation, contact the store at which Major components of the transfer switch are a 2 pole utility
you purchased your equipment, your dealer, or your utility disconnect circuit breaker, a 2 pole generator disconnect
power provider. circuit breaker, a 2 pole double throw transfer switch, control
The equipment warranty is VOID unless the system is circuit board, fused utility terminals and interconnecting
installed by licensed electrical professionals. wiring. The control board also has two inputs for current
transformers that sense generator current. These
Owner Orientation components are housed in a NEMA 3R enclosure that is
The illustrations provided are for typical circumstances and suitable for both indoor and outdoor installations.
are meant to familiarize you with the installation options The transfer switch is solenoid-operated from utility or
available with your system. generator inputs and contain suitable mechanical and
Local codes, appearance, and distances are the factors that electrical interlock switches to eliminate the possibility of
must be considered when negotiating with an installation connecting the utility service to the generator output. It
professional. As the distance from the existing electrical has ratings capable of switching full utility power into the
service increases, compensation in wiring materials must residence. In addition, a manual override lever is provided
be allowed for. This is necessary to comply with local codes for the transfer function.
and overcome electrical voltage drops. The control board has active circuits sensing utility and
These factors will have a direct effect on the overall price generator voltages. It creates a signal for the generator
of your equipment installation. start-up, switch transfer and retransfer when utility is
restored. The control board also contains red and green
NOTE: Your installer must check local codes AND obtain LEDs indicating the power sources available and two
permits before installing the system. relay operated contacts that provide supervisory control of
Read and follow the instructions given in this manual. external loads.
Follow a regular schedule in caring for and using your
equipment, as specified in this manual.

5
Delivery Inspection Mounting Guidelines
After opening the carton, carefully inspect the transfer The system circuitry is enclosed in a NEMA Type 3R
switch components for any damage that may have occurred enclosure suitable for indoor/outdoor use. Guidelines for
duringshipment. mounting the enclosure include:
IMPORTANT: If loss or damage is noted at time of delivery, Install enclosure on a firm, sturdy supporting structure.
have the person(s) making delivery note all damage on the The enclosure must be installed with minimum NEMA
freight bill and affix his signature under the consignors 3R hardware for conduit connections.
memo of loss or damage. If loss or damage is noted after
Level and plumb the enclosure. This can be done
delivery, contact the carrier for claim procedures. Missing or
by placing washers between the enclosure and the
damaged parts are not warranted.
mounting surface.
Shipment contents NEVER install the switch where any corrosive
Automatic transfer switch (1) substance might drip onto the enclosure.
Installation and operators manual (1) Protect the switch at all times against excessive
moisture, dust, dirt, lint, construction grit and corrosive
Current transformers (2)
vapors.
To be supplied by installer: Typical automatic transfer switch installations are depicted
Connecting wire and conduit below. It is best if the transfer switch is mounted near
the utility meter, either inside or outside. Discuss layout
Various specialty tools/equipment
suggestions/ changes with the owner before beginning the
system installation process.

071018 &071019 Emergency Main


Transfer Watt -
Control Wiring Contactor Load Distribution
Switch Hourmeter
Center Panel

Branch
Circuits

Hot Water
Heater
Generator

Air
Conditioner
Emergency Branch
Disconnect Switch
Circuits

071020 & 071022 Transfer Switch


Main
w/ Service Watt -
Control Wiring Contactor Distribution
Panel and Generator Hourmeter
Disconnect

Generator
Hot Water
Heater

Air
Conditioner

Branch Circuits Disconnect Switch

6 BRIGGSandSTRATTON.COM
Power Wiring Interconnections 4. Connect transfer switch to utility power:
All wiring must be the proper size, properly supported To connect models 071018 and 071019 to utility:
and protected by conduit. All wiring should be done per Connect copper feeder conductors from main
applicable federal, state and local codes, standards and distribution panel two-pole breaker to transfer switch
regulations. Obey wire type and torque specifications printed terminals marked UTILITY CONNECTION.
on the terminal blocks and neutral/ground connector. Connect copper conductor from main distribution panel
WARNING Low voltage wire cannot be installed in neutral bus33to transfer switch neutral terminal.
same conduit as power voltage wiring. Connect copper22 conductor from main distribution panel
ground bus to transfer switch GND terminal.
NOTE: Assure grounding electrode conductor is
Failure to follow above warning could cause personal connected and bonded per applicable federal, state and
injury, damage and/or malfunction of equipment. local codes, standards and regulations.
Complete the following connections between the transfer To connect models 071020 and 071021120V to utility:
switch, main distribution panel, utility power and generator. Connect utility service to transfer switch service
Use unstaller-supplied 300VAC or greater wire that complies disconnect circuit breaker terminals marked
with Table 310.16 in the National Electric Code. Apply the UTILITYCONNECTION. 120V
necessary correction factors and wire size calculations. Connect utility service neutral to transfer switch
NOTICE Improper installation can cause damage to the neutralterminal.
11
circuit boards and shorten their life. Installing circuit 5. Connect copper feeder conductors from 240V transfer
boards in live circuits will damage the board and is not switch breaker
44 GENERATOR CONNECTION terminals
covered by warranty. ALWAYSdisconnect ALL sources of to generator control panel breaker LINE1 and LINE2
power prior to servicing. terminals. Each conductor must pass through hole of
Remove all power prior to installing this equipment. current transformer before makingconnection.
Failure to do so could cause internal damage to the board
when making electrical connections.
Turn generator to OFF position. 44 11
Turn off utility power to the standby generator and
transfer switch.
Circuit
1. Set generators system switch to OFF position. 0 Breaker 22
2. Set generators circuit breaker to OFF (open) position.
3. Turn off utility power to the standby generator and
transfer switch. Ground Neutral

WARNING Battery posts, terminals and related


accessories contain lead and lead compounds, chemicals
known to the State of California to cause cancer and Ground Line 1 Line 2 Neutral
reproductive harm. Wash hands afterhandling.

To Transfer Switch
6. Plug current transformer leads into CT1 and CT2
terminals on control module.
7. Connect copper conductor from transfer switch
neutral terminal to generator control panel NEUTRAL
terminal. Observe control panel labeling for
terminalidentification.
8. Connect copper conductor from transfer switch GND
terminal to generator control panel GROUND terminal.
NOTE: Assure generator equipment grounding conductor
is connected per applicable federal, state and local codes,
standards and regulations.

7
9. Connect the transfer switch UTILITY 240 VAC Supervisory Control Wiring
terminals to generators 240 VAC terminals An air conditioner can be used with the supervisory contacts
using installer supplied 300VAC or greater copper on either terminals A-A or B-B. Terminals A-A can only be
wire, minimum #14 AWG conductors via supplied used with supervisory control. Large loads can only be used
twopoleconnector. with contactor control on terminals B-B. Examples of each
10. Connect T/R and GND terminals on transfer system are described below.
switch control board (B) to the generators control 1. The terminal strip on the control module in transfer
panel (A) TxRx and TxRx GND terminals using switch has four connections for customer use. There
#18 AWG twisted pair copper conductors, no greater are two sets of Normally Closed contacts available.
than 200 ft in length, 300 volt 75C-90C via supplied They will be activated when generator power is
tenpoleconnector. required. These can be used for supervisory control
of large connected loads on generator. Loads will
be allowed to operate if there is enough generator
poweravailable.
NOTE: There are two wireways provided to keep the
A supervisory loads separated from each other.
2. Terminals A-A on control module are rated for
24VAC and air conditioner contactor control. Contacts
are connected in series with the air conditioner
contactor control circuit.
B Air Conditioner Contactor

11. Tighten all wire connections/fasteners to proper torque. A 24 VAC


See label inside transfer switch enclosure for proper
torque values.
A
When connecting to circuit board terminal blocks,
fasten only one wire to each connector screw. 3. Terminals B-B on control module are rated for 1 Amp
125 VAC and installer supplied contactor to control
Connector tightening torques shall be asfollows: a large load, such as an electric hot water heater.
Utility - 50 in-lb (5.5 Nm) Ground - 50 in-lb (5.5 Nm) Contacts are connected in series with the contactor
control circuit.
Generator - 50 in-lb (5.5 Nm) Control - 12 in-lb (1.4 Nm)
Neutral - 110 in-lb (12.5Nm) Fuseblocks - 12 in-lb (1.4Nm) Contactor

Use oxide inhibitor on all aluminum terminations. B Neutral

All terminal and bus lugs are suitable for copper wire of
60/75C rating. B 120 VAC

4. Tighten all wire connections/fasteners to proper torque.


The illustrations on the following pages show typical
See label inside transfer switch enclosure for proper
completed installations. Your actual installation will vary.
torque values.

8 BRIGGSandSTRATTON.COM
To Utility Models 071018 & 071019
L1 N
L2

Ground Neutral
Bus Bus

Main
Distribution
Panel Two Pole
Breaker

G
L1
L2
N

Utility
Connection

Generator
Connection T/R and GND
Automatic to Generator
Transfer
Switch Load
Connection Supervisory
Contacts

Ground
Terminal
Neutral
Terminal
CTs

N 240
B&S Generator
E1 VAC UTILITY 240VAC to Generator
E2
G
G
N L1
L2 Essential Circuit
E1 Sub Panel
N
E2
G

Ground Neutral
Bus Bus

TXRX

TXRX Gnd

240VAC

9
To Utility Models 071020 & 071021

N
L2
L1

Generator CTs
Connection

Utility
Connection T/R and Gnd
Automatic to Generator
Transfer Load
Switch Connection

Supervisory
Contacts

Ground
Terminal
Neutral
Terminal

N
L2
L1
G

240
N
VAC
B&S Generator E1 UTILITY 240VAC
E2 to Generator
G

N Ground Neutral
E1 Bus Bus
E2
G

TXRX

TXRX Gnd Main


240VAC Distribution
Panel

10 BRIGGSandSTRATTON.COM
System Setup Operation
You must perform the following before operating the system:
To select automatic transfer operation, do the following:
If generator is installed in an area regularly subjected
1. Set service disconnect switch that sends utility power
to temperatures below 40F (4C), select a 50 second
to transfer switch contactor to ON position.
warm up time by moving jumper installed on JP2 from
20 position to 50 position. 2. Install 15 Amp fuse in generators control panel.
3. Set generators circuit breaker to ON position.
3 Position 2 Position
Switch SW2
JP2
Switch SW1
4. Set generators system switch to AUTO position.
The system will now be in automatic operation mode.
When the generator is providing power to the transfer
switch, the control module is constantly monitoring
generator power. If the air conditioner is called to run, and
there is sufficient generator power available, the controller
will close contacts A-A to air conditioner contactor.
Contacts B B will open before contacts A-A close. If loads
are too great for the generator, contacts A-A and/or B-B will
CT1 & CT2
Connectors open. When air conditioning is not needed, A-A will open. If
enough power is available, B-B will close.

Enclosure Door
To open door, press the spring-load door lock to the right
and pull down on the door.
Supervisory
Contacts

Set two-position SW1 on the control module to match


the fuel supplied to the home standby generator, either
NG or LP.
Set three-position SW2 on the control module to
match the KW rating of the home standby generator:
12,15or20.

System Test
To close and latch door, push door closed against enclosure.
With the generator system switch in AUTO, turn the service
While in this position, push door upwards. This will cause
disconnect feeding the transfer switch to the OFF position.
spring-load door lock to engage and latch door in place.
After a few minutes the generator will start and the transfer
switch will transfer to generator power. NOTE: Enclosure door MUST be closed and latched at all
times except when system is being serviced.
To return to utility power, turn the service disconnect feeding
the transfer switch to the ON position.

Controls
Other than a Manual Override lever, there are no operator
controls because this is an automatic transfer switch. The
manual override is to be used only by licensed professionals.

11
Testing the Automatic Transfer Switch Maintenance
Turn the main distribution panel breaker or service
The transfer switch is designed to be maintenance free under
disconnect feeding the transfer switch contactor to the Off
normal usage. However, inspection and maintenance checks
position. The systems automatic sequence will initiate.
should be made on a regular basis. Maintenance will consist
To return to utility power, turn the main distribution panel
mainly of keeping the transfer switch clean.
breaker or service disconnect to the On position.
Visual inspections should be done at least once a month.
Utility Fail Access to transfer switch must not be obstructed. Keep
The generator senses when utility voltage is below 3feet (92 cm) clearance around transfer switch. Check
70percent of nominal. Engine start sequence is initiated for an accumulation of dirt, moisture and/or corrosion
after 6second time delay. on and around the enclosure, loose parts/hardware,
cracks and/or discoloration to insulation, and damaged or
Engine Warm-Up discoloredcomponents.
Time delay to allow for engine warm-up before transfer. Use Exercise the transfer switch at least once every three months
jumper on control board to select delay of 20 seconds or as described in Testing the Automatic Transfer Switch unless
50seconds. a power outage occurs and home generator system has gone
through an automatic sequence. Allow generator to run for at
Transfer least 30minutes.
Transfer from utility to generator supply occurs after voltage Contact a licensed electrical professional to inspect and clean
is above set levels. Minimum engine run time is 5 minutes the inside of the enclosure and other components of your
after transfer. home generator system at least once a year.
Utility Pickup When Calling for Assistance
Voltage pickup level is 80 percent of nominal voltage. You must have the Model Number and Serial Number from
Retransfer the unit ID label at hand if it is necessary to contact a local
service center regarding service or repair of this unit. Obtain
Retransfer from generator to utility power is approximately this information from the unit ID label located on or inside
10 seconds after utility voltage supply is above pickup level the enclosure.
and minimum run time is completed.
To contact Briggs & Stratton call (800) 743 4115, between
Engine Cool Down 8:00 AM and 5:00 PM CT.
Engine will run for 60 seconds after retransfer.
Installation Inspection
Before placing the generator system into service, inspect the
entire installation carefully.
Complete the Installation Checklist supplied with the
generator as you make the inspection. Ensure all items have
been filled-in and all signatures have been obtained. Instruct
the owner to mail the white copy to:
Warranty Registration
P. O. Box 239
Jefferson, WI 53549

12 BRIGGSandSTRATTON.COM
Troubleshooting
Problem Cause Correction
Automatic transfer switch does not 1. G enerator breaker open. 1. R eset generator circuit breaker.
transfer to generator 2. Generator voltage not acceptable. 2. Refer to generator manual.
1. M ain distribution panel breaker open 1. Reset main distribution panel breaker
(Models 071018 & 071019 only). (Models 071018 & 071019 only).
Automatic transfer switch does not 2. Service disconnect breaker open 2. Reset service disconnect breaker
transfer to utility (Models 071020 & 071021 only). (Models 071020 & 071021 only).
3. Utility voltage not acceptable. 3. Wait for utility voltage to return
tonormal.
Generator is still running after switch
Engine cool down period. Engine should stop after 1 minute.
transfers to utility power
1. A
 -A or B-B contacts not 1. C heck A-A or B-B contacts for proper
operatingcorrectly. operation and/or check control wiring
Supervised loads (air conditioner, etc.) to external load.
are not operating when generator is 2. Too much load on generator. 2. Decrease load to generator.
supplying power 3. C urrent transformer not connected. 3. Plug CT connectors into
controlboard.
4. Broken current transformer. 4. Contact local service center.

1. M inimum engine run time has 1. Wait five minutes for transfer switch
Generator is still running after utility notelapsed. to retransfer to utility power.
power is restored 2. Fuse(s) in transfer switch is defective. 2. Check fuse(s) and replace
ifnecessary

13
Schematic and Wiring Diagram, Models 071018 and 071019

14 BRIGGSandSTRATTON.COM
Schematic and Wiring Diagram, Models 071020 and 071021

15
BRIGGS & STRATTON POWER PRODUCTS GROUP, LLC TRANSFERSWITCH OWNER WARRANTY POLICY

Effective November 1, 2005 replaces all undated Warranties and all Warranties dated before November 1, 2005

LIMITED WARRANTY
Briggs & Stratton Power Products Group, LLC will repair or replace, free of charge, any part(s) of the equipment that is defective in material or
workmanship or both. Transportation charges on product submitted for repair or replacement under this warranty must be borne by purchaser. This
Warranty
warranty is effective for the time periods and subject to the conditions stated below. For warranty service, find the nearest Authorized Service Dealer in
our dealer locator map at BRIGGSandSTRATTON.COM.
THERE IS NO OTHER EXPRESS WARRANTY. IMPLIED WARRANTIES, INCLUDING THOSE OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE, ARE LIMITED TO ONE YEAR FROM PURCHASE, OR TO THE EXTENT PERMITTED BY LAW. ANY AND ALL IMPLIED WARRANTIES ARE
EXCLUDED. LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES ARE EXCLUDED TO THE EXTENT EXCLUSION IS PERMITTED BY LAW. Some
states or countries do not allow limitations on how long an implied warranty lasts, and some states or countries do not allow the exclusion or limitation
of incidental or consequential damages, so the above limitation and exclusion may not apply to you. This warranty gives you specific legal rights and you
may also have other rights which vary from state to state or country to country.

WARRANTY PERIOD

Consumer Use 3 years


Commercial Use None

The warranty period begins on the date of purchase by the first retail consumer or commercial end user, and continues for the period of time stated in the
table above. Consumer use means personal residential household use by a retail consumer. Commercial use means all other uses, including use for
commercial, income producing or rental purposes. Once equipment has experienced commercial use, it shall thereafter be considered as commercial use for
purposes of this warranty. Equipment used for prime power in place of utility are not applicable to this warranty.
NO WARRANTY REGISTRATION IS NECESSARY TO OBTAIN WARRANTY ON BRIGGS & STRATTON PRODUCTS. SAVE YOUR PROOF OF PURCHASE
RECEIPT. IF YOU DO NOT PROVIDE PROOF OF THE INITIAL PURCHASE DATE AT THE TIME WARRANTY SERVICE IS REQUESTED, THE MANUFACTURING
DATE OF THE PRODUCT WILL BE USED TO DETERMINE THE WARRANTY PERIOD.

ABOUT YOUR WARRANTY

We welcome warranty repair and apologize to you for being inconvenienced. Any Authorized Service Dealer may perform warranty repairs. Most warranty
repairs are handled routinely, but sometimes requests for warranty service may not be appropriate. For example, warranty service would not apply if
equipment damage occurred because of misuse, lack of routine maintenance, shipping, handling, warehousing or improper installation. Similarly, the
warranty is void if the manufacturing date or the serial number on the equipment has been removed or the equipment has been altered or modified. During
the warranty period, the Authorized Service Dealer, at its option, will repair or replace any part that, upon examination, is found to be defective under normal
use and service. This warranty will not cover the following repairs and equipment:
Normal Wear: Outdoor Power Equipment, like all mechanical devices, needs periodic parts and service to perform well. This warranty does not cover
repair when normal use has exhausted the life of a part or the equipment.
Installation and Maintenance: This warranty does not apply to equipment or parts that have been subjected to improper or unauthorized installation
or alteration and modification, misuse, negligence, accident, overloading, improper maintenance, repair or storage so as, in our judgment, to adversely
affect its performance and reliability. This warranty also does not cover normal maintenance such as adjustments, cleaning and fuse replacement.
Other Exclusions: This warranty excludes wear items or damage or malfunctions resulting from accidents, abuse, modifications, alterations, or
improper servicing. Accessory parts are excluded from the product warranty. This warranty excludes failures due to acts of God and other force
majeure events beyond the manufacturers control. Also excluded is used, reconditioned, and demonstration equipment. 198180E, Rev. C, 12/31/2006

BRIGGS & STRATTON POWER PRODUCTS GROUP, LLC


JEFFERSON, WI, USA

16 BRIGGSandSTRATTON.COM
Automatic Transfer Switch

Product Specifications
Model 071018 Model 071020
Rated Maximum Load Current* Rated Maximum Load Current*
(at 25C/77F)....................................................... 100 Amps (at 25C/77F)....................................................... 100 Amps
Rated AC Voltage..................................................... 250 Volts Rated AC Voltage..................................................... 250 Volts
Poles..................................................................................... 2 Poles..................................................................................... 2
Frequency...................................................................... 60 Hz Frequency...................................................................... 60 Hz
Fault Current Rating........ 22,000 RMS Symmetrical Amperes Fault Current Rating........ 22,000 RMS Symmetrical Amperes
Supervisory Contacts Rating: Supervisory Contacts Rating:
A-A Terminals.................................................... 24 Volt AC A-A Terminals.................................................... 24 Volt AC
B-B Terminals.................... 1 Amp, 125 Volt AC, Pilot Duty B-B Terminals.................... 1 Amp, 125 Volt AC, Pilot Duty
Normal Operating Range..... -20F (-28.8C) to 104F (40C) Normal Operating Range..... -20F (-28.8C) to 104F (40C)
Weight.............................................................25 lbs. (11 kg) Weight.............................................................40 lbs. (18 kg)

Model 071019 Model 071021


Rated Maximum Load Current* Rated Maximum Load Current*
(at 25C/77F)....................................................... 200 Amps (at 25C/77F)....................................................... 200 Amps
Rated AC Voltage..................................................... 250 Volts Rated AC Voltage..................................................... 250 Volts
Poles..................................................................................... 2 Poles..................................................................................... 2
Frequency...................................................................... 60 Hz Frequency...................................................................... 60 Hz
Fault Current Rating........ 25,000 RMS Symmetrical Amperes Fault Current Rating........ 25,000 RMS Symmetrical Amperes
Supervisory Contacts Rating: Supervisory Contacts Rating:
A-A Terminals.................................................... 24 Volt AC A-A Terminals.................................................... 24 Volt AC
B-B Terminals.................... 1 Amp, 125 Volt AC, Pilot Duty B-B Terminals.................... 1 Amp, 125 Volt AC, Pilot Duty
Normal Operating Range..... -20F (-28.8C) to 104F (40C) Normal Operating Range..... -20F (-28.8C) to 104F (40C)
Weight.............................................................38 lbs. (17 kg) Weight.............................................................63 lbs. (29 kg)

*This transfer switch is certified in accordance with UL (Underwriters Laboratories) 1008 (transfer switch equipment).

Briggs & Stratton Power Products Group, LLC


900 N. Parkway
Jefferson, Wisconsin, 53549 U.S.A.

17
Reserved

18 BRIGGSandSTRATTON.COM
Home Generator Systems

Manual de Instalacin y del Operario

100/200 Amperios
Interruptor de
transferencia automtica
Gracias por comprar este conectador automtico de Briggs & Stratton Power Products. Este producto est diseado para
utilizarse con generadores de reserva domsticos especficos y puede no funcionar con generadores producidos por otros
fabricantes. Recurra a un electricista profesional cualificado para determinar la aplicabilidad de este equipo en generadores
fabricados por terceros. Si se utiliza y mantiene de acuerdo con las instrucciones de este manual, su sistema le proporcionar
muchos aos de funcionamiento fiable.

Este manual contiene informacin de seguridad para que usted conozca los peligros y riesgos propios de este sistema y
cmo evitarlos. Se ha realizado el mximo esfuerzo para que la instalacin resulte segura, sencilla y econmica. Debido a que
cada instalacin es nica, es imposible conocer y recomendar todos los procedimientos y mtodos posibles para efectuarla.
No conocemos todos los riesgos y/o resultados posibles de cada mtodo o procedimiento existente. Es importante que lea
y comprenda perfectamente estas instrucciones antes de intentar instalar o utilizar este equipo. Guarde estas instrucciones
para futuras consultas.

Este el conectador requiere instalacin profesional antes de utilizarse. Consulte las instrucciones sobre los procedimientos
de instalacin en la seccin Instalacin del presente manual. Los conectador slo deben ser instalados por electricistas con
licencia. Las instalaciones deben cumplir estrictamente la totalidad de los cdigos, estndares y regulaciones federales,
estatales y locales vigentes. El instalador debe seguir las instrucciones detalladamente.

Ubicacin
Nunca debe ir demasiado lejos para encontrar el soporte y servicio de Briggs & Stratton para su sistema. Consulte las
Pginas Amarillas. Existen mltiples distribuidores de servicio autorizados que ofrecen un servicio de calidad. Tambin puede
comunicarse con el Servicio tcnico por telfono al (800) 743 4115 de 8:00 a. m. a 5:00 p. m. Hora del Centro, o a travs de
Internet en BRIGGSandSTRATTON.COM.

Para futuras consultas


Llene la siguiente informacin y conserve su factura para facilitar la identificacin de la unidad en caso de que surjan
problemas relacionados con la compra en el futuro.

Conectador automtico

Nmero de modelo

Revisin

Nmero de serie

Fecha de compra

Briggs & Stratton Power Products Group, LLC


900 North Parkway
Jefferson, WI 53549

Copyright 2009. Reservados todos los derechos. Queda


prohibida la reproduccin o transmisin de este material, sea
cual sea la forma empleada para ello, sin el permiso previo y por
escrito de Briggs & Stratton Power Products Group, LLC.

2 BRIGGSandSTRATTON.COM
Tabla de contenido

Instalacin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Orientacin al propietario . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Responsabilidades del distribuidor / tcnicoinstalador . . . . . . . . . . . . . . . 5
Pautas de montaje . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Interconexin de los cables de alimentacin . . . . . . . . . . . . . . . . . . . . . . . 7
Cableado de control de supervisin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Configuracin del sistema . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Prueba del sistema . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Controles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Funcionamiento . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Prueba del conectador automtico . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Mantenimiento . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Resolucin de problemas . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Garanta . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Especificaciones del producto . . . . . . . . . . . . . . . . . . . . . . . 15

3
Guarde estas instrucciones
Instrucciones importantes
deseguridad
GUARDE ESTAS INSTRUCCIONES - Este manual contiene ADVERTENCIA Los cables de baja tensin no se
instrucciones importantes que se deben seguir durante la pueden instalar en el mismo conducto que los
instalacin y el mantenimiento del equipo. cables de suministro de energa.

Smbolos sobre la seguridad y significados Si no se respeta esta indicacin pueden producirse


lesiones, daos y/o fallos de funcionamiento del equipo.

ADVERTENCIA Una conexin a tierra defectuosa del


Descarga elctrica Lea el manual equipo puede provocar la electrocucin.

El smbolo de alerta de seguridad indica un posible


riesgo para su integridad fsica. Se utiliza una palabra de No toque los cables pelados.
sealizacin (PELIGRO, ADVERTENCIA o ATENCIN) junto
No utilice el equipo con cables desgastados,
con el smbolo de alerta para designar un grado o nivel
deshilachados o deteriorados de cualquier otra forma.
de gravedad de riesgo. Se puede utilizar un smbolo de
seguridad para representar el tipo de riesgo. La palabra de No manipule los cables elctricos si se encuentra en
una zona hmeda, est descalzo o tiene las manos o los
sealizacin AVISO se utiliza para hacer referencia a una
piesmojados.
prctica no relacionada con una lesin fsica.
Si tiene que trabajar junto a una unidad en
PELIGRO indica un riesgo que, de no evitarse, provocar funcionamiento, mantngase en una superficie aislada y
la muerte o lesiones de gravedad. seca para reducir el riesgo de descarga elctrica.
ADVERTENCIA indica un riesgo que, de no evitarse, No permita que personas no cualificadas o nios utilicen
podra provocar la muerte o lesiones de gravedad. o reparen el equipo.
ATENCIN indica un riesgo que, de no evitarse, podra En caso de accidente provocado por una descarga
provocar lesiones leves o moderadas. elctrica, desconecte inmediatamente todos los
suministros de energa elctrica y pngase en contacto
AVISO hace referencia a una prctica no relacionada con una
con las autoridades locales. Evite el contacto directo con
lesin fsica. la vctima.
El fabricante no puede prever toda circunstancia que conlleve
un riesgo potencial. Por tanto, las advertencias de este
manual, as como las etiquetas y calcomanas adheridas a ADVERTENCIA El equipo contiene alta tensin que
la unidad, no incluyen todos los riesgos posibles. Si utiliza puede provocar lesiones o la muerte.
un procedimiento, mtodo de trabajo o tcnica de uso no
recomendado especficamente por el fabricante, deber A pesar de la seguridad del diseo del sistema, si ste se
asegurarse de que es seguro tanto para usted como para utiliza con imprudencia, ignorando su mantenimiento o
otras personas. Tambin deber asegurarse de que el sin las debidas precauciones, se pueden producir lesiones
procedimiento, mtodo de trabajo o tcnica de uso que elija o incluso la muerte.
no hace que el equipo sea inseguro.
AVISO Un tratamiento inadecuado del equipo puede
ADVERTENCIA La instalacin de este equipo debe estropearlo y acortar su vida til.
cumplir estrictamente la totalidad de los cdigos, Utilice el equipo slo para los usos previstos.
estndares y regulaciones vigentes, por lo que slo debe En caso de dudas sobre su uso, dirjase al distribuidor o a
ser llevada a cabo por un electricista cualificado. Briggs & Stratton Power Products.
No exponga el equipo a un exceso de humedad, polvo,
suciedad o vapores corrosivos.
ADVERTENCIA Determinados componentes en
este producto y los accesorios relacionados contienen Mantngase alerta en todo momento cuando utilice este
sustancias qumicas declaradas cancergenas, causantes equipo. Nunca lo utilice ni manipule en condiciones de
de malformaciones, y otros defectos congnitos por el fatiga fsica o mental.
Estado de California. Lvese las manos despus de Si se calientan excesivamente los dispositivos conectados,
manipular estos elementos. apguelos y abra sus interruptores o quite sus fusibles.

4 BRIGGSandSTRATTON.COM
Instalacin Lea y siga las instrucciones que se indican en
estemanual.
Realmente valoramos que nos haya elegido. Por este Siga un plan regular de cuidado y uso del equipo, como
motivo, se ha realizado un esfuerzo importante para que se indica en este manual.
la instalacin resulte segura, sencilla y econmica. Debido
a que cada instalacin es nica, es imposible conocer y Responsabilidades del distribuidor /
recomendar todos los procedimientos y mtodos posibles
tcnicoinstalador
para efectuarla. Tampoco conocemos todos los riesgos
y/o resultados posibles de cada mtodo o procedimiento. Lea y respete las normas de seguridad.
Por tanto, la instalacin del sistema slo puede ser Lea y siga las instrucciones que se indican en
llevada a cabo por un electricista con licencia vigente. estemanual.
Las instalaciones deben cumplir estrictamente la Consulte con el propietario para determinar las cargas
totalidad de los cdigos, estndares de la industria y que van a controlarse y sus prioridades.
regulacionesvigentes.
Es posible que el instalador tenga que proporcionar
Su equipo se suministra con este Manual de instalacin contactores nominales adecuados con base en las
y del operario combinado. Se trata de un documento cargas que van a controlarse.
importante que el propietario debe conservar despus de
Consulte la normativa vigente en caso de dudas sobre
haber terminado la instalacin.
la instalacin.
Se ha realizado el mximo esfuerzo para reunir en este
Asegrese de que las cargas seleccionadas no
manual la informacin ms precisa y actualizada. No
sobrecargan el generador.
obstante, el fabricante se reserva el derecho de modificar,
alterar o mejorar de cualquier otra forma el sistema en Si necesita ms informacin sobre el conectador, llame al
cualquier momento y sin previo aviso. (800) 743-743-4115, de 08:00 a 17:00 CT.

Responsabilidades del propietario Descripcin del equipo


Para tomar decisiones bien fundadas y comunicarse El conectador est diseado para transferir las cargas
eficazmente con el tcnico instalador, seleccionadas de una instalacin residencial normal
al suministro del generador en caso de un fallo en el
Lea y comprenda la seccin Orientacin al propietario
suministro de alimentacin de la red pblica. La carga
antes de contratar o iniciar la instalacin del equipo.
se conecta al suministro de servicio general (normal)
Para solicitar la instalacin, pngase en contacto con la o al suministro domstico de reserva (generador). El
tienda en la que adquiri el equipo, con su distribuidor o con conectador monitoriza las tensiones de la red pblica y del
la compaa elctrica. generador y conecta automticamente la carga a la fuente de
La garanta del equipo quedar ANULADA a menos alimentacin apropiada.
que electricistas profesionales con licencia instalen Con estos interruptores, un electricista cualificado puede
elsistema. completar fcilmente una instalacin domstica de
reserva. Dependiendo del modelo del especfico comprado,
Orientacin al propietario la unidad contiene un seccionador de servicio y un
Las ilustraciones incluidas corresponden a circunstancias conectador automtico en una misma caja. El conducto y
habituales y tienen por objeto familiarizarle con las opciones los conductores de servicio se pueden cablear directamente
de instalacin del sistema. desde el contador hasta el conectador. No es necesario
La normativa local, la apariencia y las distancias son los instalar un seccionador distinto, con su correspondiente
aspectos que debern tenerse en cuenta al negociar la cableado, para cumplir toda la normativa vigente.
instalacin con un profesional. Al aumentar la distancia Dependiendo del modelo del especfico comprado, los
desde el servicio elctrico, se deber prever una componentes principales del conectador son un disyuntor
compensacin en cables y otros materiales necesarios seccionador de servicio bipolar, un interruptor bipolar de 2
para cumplir la normativa local vigente y evitar cadas de posiciones de contacto, una tarjeta de circuito impreso del
tensinelctrica. mdulo de control, terminales con fusibles de deteccin de
Estos factores tendrn un efecto directo en el precio total tensin de la red pblica y cableado de interconexin. Las
de la instalacin del equipo. tarjetas de circuito impreso se encuentran en una caja tipo
3R segn NEMA, que es adecuada para uso en interiores y a
NOTA: El instalador deber comprobar la normativa local
la intemperie.
Y obtener los permisos correspondientes antes de instalar
elsistema.

5
El conectador es accionado por un solenoide alimentado Contenido del paquete
desde las entradas de la red pblica o del generador y tiene Conmutador de transferencia de energa automtico (1)
interruptores de enclavamiento mecnicos y elctricos,
Manual de instalacin y operario (1)
adecuados para eliminar la posibilidad de conectar la red
pblica a la salida del generador. Sus valores nominales son Transformadores de corriente (2)
suficientes para conectar toda potencia de la red pblica a la No incluye:
residencia. Para la funcin de transferencia hay una palanca Cable y conducto de conexin.
de cancelacin manual.
Herramientas/equipos especiales diversos
La tarjeta de circuito impreso del mdulo de control tiene
circuitos activos que detectan las tensiones de la red Pautas de montaje
pblica y del generador. Genera una seal para el arranque El conectador automtico est encerrado en una caja tipo
del generador, el conectador, la retransferencia cuando se 3R NEMA, que es adecuada para uso en interiores y a la
restablece la tensin en la red pblica y los perodos de intemperie. Las directrices para el montaje de conectador
enfriamiento del generador. La tarjeta de control contiene automtico incluyen:
tambin luces rojas y verdes que indican las fuentes de
alimentacin disponibles y dos contactos accionados por Instale el conmutador sobre una estructura de soporte
rel que proporcionan el control de supervisin de cargas firme y resistente.
crticas externas. El interruptor se debe instalar con conexiones mnimas
de conduit de fo de hardware de NEMA 3R.
Inspeccin en el momento de la entrega Para evitar distorsiones en el conmutador, nivele
Despus de abrir la caja de cartn, con cuidado inspeccione la unidad si es necesario. Puede hacerlo colocando
el contenido para detectar cualquier dao que pudiera haber arandelas entre el compartimiento del conmutador y la
ocurrido durante el envo. superficie de montaje.
IMPORTANTE: Si detecta faltas o daos en el momento Nunca instale el conmutador en un lugar en el cual
de la entrega, solicite a la persona que realiza la entrega pueda producirse el goteo de alguna sustancia
que anote todos los daos en Ia nota de entrega y que la corrosiva en el compartimiento.
firme bajo el rea de prdidas y daos del remitente. Si se Proteja permanentemente al conmutador contra
detectan faltas o daos despus de la entrega, pngase en humedad excesiva, polvo, suciedad, pelusas, arenilla
contacto con el transportista para solicitar informacin sobre para construccin y vapores corrosivos.
el procedimiento de reclamacin. La garanta no cubre las
A continuacin se ilustra la instalacin habitual del
partes faltantes o daadas.
conectador automtico. Lo mejor es montarlo cerca del
contador de la compaa elctrica en el interior o en el
exterior. Antes de iniciar el proceso de instalacin del
sistema, analice los cambios y sugerencias de diagramacin
con el propietario de la unidad.
Tpico Contador
Cableado de control de vatios
Centro de Conmutador Panel del hora
Contactor carga de de disyuntor
emergencia transferencia principal

Circuitos
derivados

Calentador
de agua
Generador

Circuitos derivados Acondicionador


de emergencia de aire
Seccionador

6 BRIGGSandSTRATTON.COM
Interconexin de los cables de alimentacin 4. Conecte el conectador al suministro de la red pblica:
Todos los cables deben ser de tamao adecuado y estar Para conectarPRECAUCIN
los modelos 071018 y 071019 al
Los de
suministro cables
la redde baja tensin no se
pblica:
bien sujetos y protegidos por el conducto. Todo el cableado
pueden instalar en el mismo conducto
debe realizarse de acuerdo con la totalidad de los cdigos, Conecte loslos
que conductores
cables de de suministro
cobre del disyuntor
de bipolar
estndares y regulaciones federales, estatales y locales del panel de distribucin principal a los terminales
vigentes. Siga las especificaciones del tipo de cables y par Sidel
no conectador
se respeta esta indicacin
con la pueden CONNECTION
marca UTILITY producirse
impresas en los bloques de terminales y el conector neutral/ daos y/o el de
(conexin equipo
la redpuede funcionar incorrectamente.
pblica).
conexin a tierra. Conecte el conductor de cobre del bus neutro del
ADVERTENCIA Los cables de baja tensin no se panel de distribucin principal al terminal neutro
pueden instalar en el mismo conducto que los delconectador.
cables de suministro de energa. Conecte el conductor de cobre del bus de tierra del
panel de distribucin principal al terminal de tierra
Si no se respeta esta indicacin pueden producirse (GND) del conectador.
lesiones, daos y/o fallos de funcionamiento del equipo.
NOTA: Compruebe que el conductor del electrodo
33 est conectado conforme a los
de conexin a tierra
Haga las siguientes conexiones entre el conectador, el panel
de distribucin principal, la red pblica y el generador. Utilice cdigos, estndares 22 y regulaciones federales, estatales y
el cable de 300V CA o ms suministrado por el instalador, localesvigentes.
que cumple con la Tabla 310.16 del Cdigo Nacional de Para conectar los modelos 071020 y 071021 al
Electricidad. Aplique los factores de solucin y clculos del suministro de la red pblica:
tamao del cable necesarios. Conecte el servicio de la red pblica al conectador, y
desconecte los terminales del disyuntor con 120Vla marca
AVISO La instalacin inadecuada puede daar las tarjetas
UTILITY CONNECTION (conexin de la red pblica).
de circuito impreso y acortar su vida til. La instalacin
de las tarjetas de circuito impreso en los circuitos activos Conecte el neutro de la red pblica al terminal neutro
daa la tarjeta y no se incluye en la cobertura de la del conectador. 120V
garanta. SIEMPRE desconecte TODAS las fuentes de 5. Conecte los conductores de cobre de los terminales
alimentacin antes de dar mantenimiento. GENERATOR CONNECTION (conexin del generador)
Desconecte la corriente antes de instalar este equipo. 11
del disyuntor del conectador al disyuntor240V del panel de
Si no se respeta esta indicacin, pueden producirse
daos internos en la tarjeta cuando se hagan las control del44 conectador al terminal de LINE1 y LINE2 del
conexioneselctricas. generador. Cada conductor debe pasar por el orificio
del transformador de corriente antes de realizarse
Site el generador en la posicin OFF.
laconexin.
Apague el suministro de la red pblica del generador de
reserva y el conectador.
44 11
1. Ponga el interruptor del sistema del generador en la
posicin OFF.
2. Ponga el disyuntor del generador en la posicin
OFF(abierta). 0 Disyuntor 22
3. Apague el suministro de la red pblica del generador de
reserva y el conectador.
Tierra Neutro
ADVERTENCIA Las patillas de las bateras, los
terminales y los accesorios relacionados contienen plomo
y compuestos de plomo - sustancias qumicas declaradas
cancergenas y causantes de malformaciones congnitas Tierra Linea 1 Linea 2 Neutro
por el Estado de California. Lvese las manos despus de
manipular estoselementos.

Hacia el conectador
6. Conecte los cables del transformador de corriente a los
terminales CT1 y CT2 del mdulo de control.
7. Conecte el conductor de cobre del terminal neutro del
conectador al terminal neutro del panel de control del
generador. Observe el panel de control el etiquetar
para la identificacin terminal.

7
8. Conecte el conductor de cobre del terminal GND (de Cableado de control de supervisin
tierra) del conectador al terminal de tierra (GROUND) Se puede utilizar un sistema de aire acondicionado con los
del panel de control del generador. contactos de supervisin en cualquiera de los terminales A-A
NOTA: Compruebe que el conductor de conexin a tierra o B-B. Los terminales A-A se pueden utilizar solamente con
del equipo generador est conectado conforme a la control de supervisin. Las cargas grandes se pueden usar
normativavigente. solamente con control de contactor en los terminales B-B. A
9. Conecte los terminales UTILITY 240 VAC del continuacin se describen ejemplos de cada sistema.
conectador a los terminales 240 VAC del generador 1. La regleta de terminales del mdulo de control del
con el cable de cobre de 300V CA o ms suministrado conectador dispone de cuatro conexiones para uso del
por el instalador, mediante cables de 14 AWG como cliente. Hay dos conjuntos de contactos Normalmente
mnimo del conector de dos polos suministrado. Cerrados que se activarn cuando sea necesario
10. Conecte los terminales T/R y GND en la tarjeta de utilizar la electricidad del generador. Se pueden utilizar
control del conectador (B) a los terminales TxRx y para el control de supervisin de grandes cargas
TxRx GND del panel de control del generador (A) conectadas al generador. Ejemplo: acondicionador
con conductores de cobre de par torcido de 18AWG, de aire, calentador de agua, etc. Las cargas podrn
con una longitud mxima de 61 m (200 pies), de funcionar siempre que la potencia del generador
300V, 75 C-90 C, mediante el conector de diez seasuficiente.
polossuministrado. NOTA: Hay dos conductos para cables que permiten
mantener separadas las cargas de supervisin.
2. Los terminales A-A del mdulo de control se utilizan
para controlar el contactor del acondicionador de aire.
Los contactos se conectan en serie con el circuito de
A control del contactor del aire acondicionado.
contactor del aire acondicionado

A 24 VAC
A
B
3. Los terminales B-B del mdulo de control permiten
11. Apriete de todas las conexiones de los cables y que el instalador conecte un contactor para controlar
elementos de fijacin al par adecuado. Consulte los una carga importante. Ejemplo: calentador elctricos de
valores de par correctos en la etiqueta dentro de la caja. agua. Los contactos se conectan en serie con el circuito
Al hacer la conexin a los bloques de terminales de de control del contactor.
la tarjeta de circuito impreso, sujete slo un cable a contactor
cada tornillo del conector.
La torsin de ajuste de los conectores debe ser B Neutro

lasiguiente: B 120 VAC


Servicio pblico - 5.5 Nm Conexin a tierra - 5.5 Nm
Generador - 5.5 Nm Control - 1.4 Nm 4. Apriete de todas las conexiones de los cables y
Neutral - 12.5 Nm Cajas de fusibles - 1.4 Nm elementos de fijacin al par adecuado. Consulte
Utilice inhibidor de xido en todas las terminaciones los valores de par correctos en el interior de la caja
dealuminio. delconectador.
Todas las lengetas de las terminales y barras de
distribucin son ideales para alambre de cobre aprobado
para 60/75 C.
La ilustracin en la pgina siguientes demuestra una
instalacines terminada tpica. Su instalacin real variar.

8 BRIGGSandSTRATTON.COM
A la
Tored pblica
Utility Para modelos 071018 & 071019
L1 N
L2
Barra de Barra de
Ground
distribucin Neutral
distribucin
de conexin
Bus a de conexin
Bus a
tierra neutro

Main
Panel de distribucin
Distribution
principal Dos polos
Two Pole
Panel
disyunctor
Breaker

G
L1
L2
N

Conexin del servicio


Utility
pblico de energa
Connection
elctrica

Generator
Conexin al
Connection
generador T/R y T/R
GNDand GND
al generador
Automatic to Generator
Interruptor de
Transfer
transferencia
Switch
automtica Conexin
Load de
carga
Connection Contactos de
Supervisory
supervisin
Contacts

Groundde
Terminal
conexin a tierra
Terminal
Neutral
Terminal
neutral
Terminal
CTs
CTs

N 240
B&S
Al Generator
generador UTILITY 240VAC
E1 VAC UTILITY 240VACalto
generador
Generator
E2
G
G
N L1
L2 Essential Circuit
E1 Panel de distribucin
N Sub Panel
E2
G

Barra
Ground de Barra de
Neutral
distribucin
Bus distribucin
Bus
de conexin a de conexin a
TXRX tierra neutro

TXRX Gnd

240VAC

9
A laTo
redUtility
pblica Para modelos 071020 & 071021

N
L2
L1

Generator CTs
Conexin al
generador
Connection

Conexin del
servicio pblico
Utility
de energa
Connection
elctrica T/R and
Conexin Gnd
de T/R y GND
Automatic
Interruptor de toalGenerator
generador
Transfer
transferencia Loadde la
Conexin
Switch
automtica Connection
carga

Supervisory
Contactos de
supervisin
Contacts

Orejetas de
Ground
conexin a tierra
Terminal
(GND) Terminales
Neutral
NEUTRAL
Terminal
(neutro)

N
L2
L1
G

240
N
VAC
B&S Generator
Al generador E1 UTILITY 240VAC
UTILITY 240VAC al
E2 to generador
Generator
G
Barra Barra
N Ground
conductora Neutral
conductora
E1 Ground
Bus Bus
NEUTRAL
E2 (tierra) (neutro)
G

TXRX

TXRX Gnd Mainde


Panel
240VAC Distribution
distribucin
principal
Panel

10 BRIGGSandSTRATTON.COM
Configuracin del sistema Funcionamiento
Deber llevar a cabo las siguientes operaciones en el mdulo
Para seleccionar el funcionamiento automtico del
de control antes de poner el sistema en funcionamiento:
conectador, haga lo siguiente:
Si el generador est instalado en una zona normalmente
1. Ponga el seccionador de servicio que enva tensin de
expuesta a temperaturas inferiores a 4 C (40 F),
la red pblica al contactor del conectador en la posicin
seleccione un tiempo de calentamiento de 50 segundos
ON (cerrado).
moviendo el puente instalado en JP2 de la posicin 20
a la posicin 50. 2. Instale el fusible de 15 A en el panel de control
delgenerador.
Conmutador de Conmutador de
JP2 3. Ponga el disyuntor del generador en la posicin ON.
3posiciones 2posiciones
4. Ponga el conmutador del sistema del generador en la
posicin AUTO.
El sistema estar entonces en el modo de
funcionamientoautomtico.
Cuando el generador suministra energa al conectador, el
controlador supervisa permanentemente la potencia del
generador. Si se intenta activar el acondicionador de aire y
de que la potencia disponible del generador es suficiente,
CT1 & CT2 el controlador cierra los contactos A-A de conexin al
contactor del acondicionador de aire. Los contactos B-B
se abren antes del cierre de los contactos A-A. Si las
cargas son excesivas para el generador, los contactos
A-A y/o B-B se abren. Cuando no es necesario utilizar el
Contactos de aire acondicionado, el contacto A-A se abre. Si la potencia
supervisin disponible es suficiente, el contacto B-B se cierra.

Puerta de la caja
Para abrir la puerta, oprima la cerradura de la puerta
accionada con resorte hacia la derecha y tire de la puerta.

Ponga el conmutador de dos-posiciones SW1 en la


posicin adecuada para su sistema, NG o LP.
Ponga el conmutador de tres-posiciones SW2) de
forma que coincida con el valor nominal de kW del
generador instalado.

Prueba del sistema


Con el interruptor del sistema del generador en AUTO, site
el seccionador de servicio que suministra alimentacin
al contactor del conectador en la posicin OFF. Despus
de unos minutos, el generador arrancar y el conectador
cambiar al suministro del generador.
Para volver a utilizar el suministro de alimentacin de la
red pblica, site el seccionador de servicio que suministra Para cerrar y bloquear la puerta, empjela y cirrela hacia
alimentacin al conectador en la posicin ON. la caja. Mientras se encuentra en esta posicin, empuje
la puerta hacia arriba. Esto provocar que la cerradura de
la puerta accionada con resorte se enganche y bloquee la
Controles puerta en su lugar.
Aparte de la palanca de cancelacin manual, el conectador no NOTA: La puerta de la caja DEBE estar cerrada y bloqueada
tiene ningn otro mando, ya que es automtico. La cancelacin en todo momento excepto cuando se est dando
manual es para uso exclusivo de profesionalescualificados. mantenimiento al sistema.

11
Prueba del conectador automtico Mantenimiento
Ponga el seccionador de servicio que alimenta el conectador
En condiciones normales de uso, el conectador no requiere
en la posicin Off (desconectado) Se realizar la secuencia
mantenimiento. No obstante, se recomienda examinar el
automtica correspondiente. Para volver a la alimentacin
conectador y realizar comprobaciones de forma peridica.
desde la red pblica, ponga el seccionador de servicio en la
Principalmente, el mantenimiento consiste en la limpieza
posicin On (conectado).
delconectador.
Fallo de la red pblica Lleve a cabo un examen visual al menos una vez al mes.
El sensor de tensin de la red pblica detecta cundo esta La va de acceso al conectador debe permanecer libre de
tensin est por debajo del 70% de la nominal. Tras un obstculos. Deje un espacio mnimo de 92 cm (3 pies)
retardo de 6 segundos, se inicia la secuencia de arranque alrededor del conectador. Compruebe la presencia de
delmotor. polvo acumulado, humedad o corrosin sobre la caja o a
su alrededor, piezas flojas, grietas o prdida de color del
Calentamiento del motor aislamiento y componentes daados o descoloridos.
Retardado de tiempo para permitir el calentamiento del Ponga en funcionamiento el conectador al menos una vez
motor antes de la transferencia. Utilice el puente de la tarjeta cada tres meses siguiendo las instrucciones de la seccin
de control para seleccionar el retraso de 20 segundos o Prueba del conectador automtico, a menos que el sistema
50segundos. generador domstico se haya activado automticamente
como resultado de un corte de suministro elctrico. Deje
Transferencia funcionar el generador durante un mnimo de 30 minutos.
Las transferencias de alimentacin desde la red pblica a Pngase en contacto con un electricista cualificado para
la alimentacin de reserva se producen cuando la tensin examinar y limpiar el interior de la caja y otros componentes
del equipo de reserva est por encima de los niveles del sistema de generador domstico al menos una vez
especificados. El tiempo mnimo de funcionamiento del alao.
motor despus de la transferencia es de 5 minutos.
Si llama para solicitar ayuda
Recuperacin de la red pblica
Debe tener a la mano el nmero de modelo y nmero
El nivel de recuperacin de la tensin es el 80% de la de serie de la etiqueta de ID de la unidad si es necesario
tensinnominal. comunicarse con un centro de servicio local en relacin con
Retransferencia el mantenimiento o la reparacin de esta unidad. Obtenga
esta informacin de la etiqueta de ID de la unidad ubicada en
Retransferencia de la alimentacin de reserva a la la caja o dentro de sta.
alimentacin de la red pblica 10 segundos despus de
que la tensin de la red pblica se site por encima del Para comunicarse con Briggs & Stratton, llame al
nivel de recuperacin y ha transcurrido el tiempo mnimo (800) 743 4115, de 8:00 a. m. a 5:00 p. m. hora del centro.
defuncionamiento.
Inspeccin posterior a la instalacin
Enfriamiento del motor Antes de poner el sistema en servicio, inspeccione toda la
El motor funcionar durante 60 segundos despus de instalacin cuidadosamente.
producirse la retransferencia. Cumplimente la Lista de control de la instalacin
suministrado su generador mientras realiza la inspeccin.
Asegrese de incluir todos los elementos y de obtener todas
las firmas correspondientes. Indique al propietario que debe
enviar la copia blanca por correo a:
Warranty Registration
P. O. Box 239
Jefferson, WI 53549

12 BRIGGSandSTRATTON.COM
Resolucin de problemas
Problemo Causa Accion
1. El disyuntor del generador 1. Rearme el disyuntor del generador.
El conectador automtico no transfiere estabierto.
la conexin al generador 2. La tensin del generador no 2. Consulte el manual del generador.
esaceptable.
1. El disyuntor bipolar del panel 1. Rearme el disyuntor de disyuntor bipolar
de distribucin principal est del panel de distribucin principal
abierto (modelo 071018 (modelo 071018 y071019).
y071019).
El conectador automtico no transfiere
2. El disyuntor de desconexin de 2. Rearme el disyuntor de desconexin de
la conexin a la red pblica
servicio est abierto (modelo servicio (modelo 071020 y071021).
071020 y071021).
3. La tensin de la red pblica no 3. Espere a que se restablezca la normalidad
es aceptable. en la tensin de la red pblica.
El generador sigue funcionando
El perodo de enfriamiento El motor debera detenerse despus de
despus de que el conectador
delmotor. 1minutos.
transfiera la conexin a la red pblica
1. Los contactos A-A o B-B no 1. Compruebe si los contactos A-A y B-B
funcionan correctamente. funcionan correctamente y verifique el
cableado de control de la carga externa.
Las cargas supervisadas
2. La carga del generador 2. Reduzca la carga del generador.
(acondicionador de aire, etc.) no
esexcesiva.
funcionan cuando el generador
3. El transformador de corriente 3. Conecte los conectores CT a la tarjeta
suministra energa
no conectado. decontrol.
4. El transformador de corriente 4. Pngase en contacto con su centro de
est averiado. servicio tcnico.

1. No ha transcurrido el tiempo 1. Espere cinco minutos a que el conectador


El generador sigue funcionando de funcionamiento mnimo vuelva a utilizar la tensin de la
cuando se restablece la alimentacin delmotor. redpblica.
elctrica de la red 2. El o los fusibles del conectador 2. Compruebe los fusibles y sustityalos si
son defectuosos. fuera necesario.

13
POLTICA DE GARANTA PARA EL PROPIETARIO DEL CONECTADOR DE BRIGGS & STRATTON POWER PRODUCTS GROUP, LLC

Fecha de entrada en vigor: 1 de Noviembre de 2005. Sustituye a todas las garantas sin fecha y a las de fecha anterior al 1 de Noviembre de 2005

GARANTA LIMITADA
Briggs & Stratton Power Products Group, LLC reparar o sustituir sin cargo alguno cualquier componente del equipo que presente defectos de
materiales y/o mano de obra. Los gastos de transporte de las producto enviadas para reparar o sustituir conforme a los trminos de esta garanta
corrern a cargo del comprador. El periodo de vigencia y las condiciones de esta garanta son los que se estipulan a continuacin. Para obtener servicio
en garanta, localice el distribuidor de servicio autorizado ms prximo en nuestro mapa de distribuidores, en www.BRIGGSandSTRATTON.COM.

Garanta
NO EXISTE NINGUNA OTRA GARANTA EXPLCITA. LAS GARANTAS IMPLCITAS, INCLUIDAS LAS DE COMERCIABILIDAD O IDONEIDAD PARA UN FIN
CONCRETO, SE LIMITAN A UN AO DESDE LA FECHA DE COMPRA O AL LMITE DE TIEMPO PERMITIDO POR LA LEY. QUEDAN EXCLUIDAS TODAS
LAS GARANTAS IMPLCITAS QUEDA EXCLUIDA LA RESPONSABILIDAD POR DAOS SECUNDARIOS Y DERIVADOS HASTA EL LMITE PERMITIDO
POR LA LEY. Algunos pases o estados no permiten limitar la duracin de una garanta implcita ni excluir o limitar los daos secundarios y derivados.
Por tanto, es posible que las limitaciones y exclusiones mencionadas no sean aplicables en su caso. Esta garanta le otorga determinados derechos
legales y es posible que tenga otros derechos que pueden variar de un pas o estado a otro.

PERODO DE GARANTA

Uso del consumidor 3 Aos


Uso comercial ninguno

El perodo de garanta comienza en la fecha de compra del primer consumidor o usuario comercial final y se prolonga durante el tiempo especificado en
la siguiente tabla. Uso del consumidor significa uso domstico personal por parte de un consumidor final. Uso comercial significa cualquier otro uso,
incluidos los usos con fines comerciales, de generacin de ingresos o alquiler. Una vez que el equipo se haya usado con fines comerciales, se considerar
como equipo de uso comercial a efectos de esta garanta. Los equipos utilizados para suministrar energa en sustitucin de un servicio pblico no pueden
acogerse a esta garanta.
NO ES NECESARIO REGISTRAR LA GARANTA PARA OBTENER SERVICIO DE BRIGGS & STRATTON PRODUCTS. GUARDE SU RECIBO DE COMPRA. SI NO
APORTA LA PRUEBA DE LA FECHA DE COMPRA INICIAL, SE UTILIZAR LA FECHA DE FABRICACIN DEL PRODUCTO PARA DETERMINAR EL PERODO
DEGARANTA.

ACERCA DE LA EQUIPO GARANTA

Esperamos que disfrute de nuestra garanta y le pedimos disculpas por las molestias causadas. Cualquier distribuidor de servicio autorizado puede llevar a
cabo reparaciones en garanta. La mayora de las reparaciones en garanta se gestionan normalmente, pero algunas veces la solicitud de servicio en garanta
puede no ser procedente. Por ejemplo, la garanta no ser vlida si el equipo presenta daos debidos al mal uso, la falta de mantenimiento, el transporte, la
manipulacin, el almacenamiento o la instalacin inadecuados. De manera similar, la garanta quedar anulada si se ha borrado la fecha de fabricacin o el
nmero de serie del equipo, o si el equipo ha sido alterado o modificado. Durante el perodo de garanta, el distribuidor de servicio autorizado podr reparar
o sustituir, a su libre eleccin, cualquier pieza que, previa inspeccin, sea defectuosa en condiciones normales de uso y servicio. Esta garanta no cubre las
reparaciones y equipos que se detallan a continuacin:
Desgaste normal: Al igual que cualquier otro aparato mecnico, los equipos de uso en exteriores necesitan piezas y mantenimiento peridicos para
funcionar correctamente. Esta garanta no cubre las reparaciones cuando el uso normal haya agotado la vida til de una pieza concreta del equipo.
Instalacin y mantenimiento: Esta garanta no cubre los equipos ni las piezas cuya instalacin sea incorrecta o no haya sido autorizada, ni aquellos
que hayan sido objeto de cualquier tipo de alteracin, mal uso, negligencia, accidente, sobrecarga o mantenimiento, reparacin o almacenamiento
inadecuados que, a nuestro juicio, haya afectado negativamente a su funcionamiento y su fiabilidad. La garanta tampoco cubre el mantenimiento
normal, como los ajustes y la limpieza y cambio de los fusibles.
Otras exclusiones: Tambin quedan excluidos de esta garanta el desgaste de los artculos tales y los daos derivados de accidentes, uso indebido,
modificaciones, alteraciones, servicio inadecuado. Los accesorios quedan excluidos de la garanta del producto. Esta garanta excluye los fallos
debidos a hechos fortuitos y a otros acontecimientos de fuerza mayor que escapan al control del fabricante. Tambin se excluyen los equipos usados o
reacondicionados y los destinados a demostraciones. 198180S, Rev. C, 12/31/2006

BRIGGS & STRATTON POWER PRODUCTS GROUP, LLC


JEFFERSON, WI, EE.UU

14 BRIGGSandSTRATTON.COM
Interruptor de transferencia automtica

Especificaciones del producto


Modelo 071018 Modelo 071020
Corriente de carga nominal mxima a 25C (77F)*..... 100 A Corriente de carga nominal mxima a 25C (77F)*..... 100 A
Tensin nominal c.a....................................................... 250 V Tensin nominal c.a....................................................... 250 V
Polos..................................................................................... 2 Polos..................................................................................... 2
Frecuencia...................................................................... 60 Hz Frecuencia...................................................................... 60 Hz
Valor nominal de la corriente Valor nominal de la corriente
conexin a tierra . ....................22,000 A eficaces, simtrica conexin a tierra . ....................22,000 A eficaces, simtrica
Valor nominal de los contactos Valor nominal de los contactos
de supervisin A-A.................................................. 24 V CA de supervisin A-A.................................................. 24 V CA
de supervisin B-B.................. 1A, 125 V CA rgimen piloto de supervisin B-B................. 1A, 125 V CA, rgimen piloto
Rango operativo normal...... -28.8C (-20F) to 40C (104F) Rango operativo normal...... -28.8C (-20F) to 40C (104F)
Peso.................................................................11 kg (25 lbs). Peso..................................................................18 kg (40 lbs)

Modelo 071019 Modelo 071021


Corriente de carga nominal mxima a 25C (77F)*..... 200 A Corriente de carga nominal mxima a 25C (77F)*..... 200 A
Tensin nominal c.a....................................................... 250 V Tensin nominal c.a....................................................... 250 V
Polos..................................................................................... 2 Polos..................................................................................... 2
Frecuencia...................................................................... 60 Hz Frecuencia...................................................................... 60 Hz
Valor nominal de la corriente Valor nominal de la corriente
conexin a tierra . ....................25,000 A eficaces, simtrica conexin a tierra . ....................25,000 A eficaces, simtrica
Valor nominal de los contactos Valor nominal de los contactos
de supervisin A-A.................................................. 24 V CA de supervisin A-A.................................................. 24 V CA
de supervisin B-B................. 1A, 125 V CA, rgimen piloto de supervisin B-B................. 1A, 125 V CA, rgimen piloto
Rango operativo normal...... -28.8C (-20F) to 40C (104F) Rango operativo normal...... -28.8C (-20F) to 40C (104F)
Peso..................................................................17 kg (38 lbs) Peso..................................................................29 kg (63 lbs)

*Este conectador est certificado conforme a la norma UL (Underwriters Laboratories) 1008 (equipos conectadores).
Briggs & Stratton Power Products Group, LLC
900 N. Parkway
Jefferson, Wisconsin, 53549 U.S.A.

15
Reserved

16 BRIGGSandSTRATTON.COM
Home Generator Systems

Guide dInstallation et dUtilisation

100/200 A Commutateur
de transfert automatique
Nous vous remercions davoir achet ce commutateur de transfert automatique de Briggs & Stratton Power Products. Ce
produit est conu pour tre utilis avec des gnratrices de secours rsidentielles spcifiques et risque de ne pas fonctionner
avec des gnratrices fabriques par dautres socits. Ayez recours un professionnel en lectricit qualifi pour dterminer
lapplicabilit de ce produit aux gnratrices fabriques par dautres socits. Si vous respectez les directives dutilisation et
dentretien de ce manuel, vous pourrez vous fier votre systme durant de nombreuses annes.

Ce manuel contient des renseignements sur la scurit pour vous informer des dangers et des risques associs ce systme
et de la faon de les viter. Nous avons tout fait pour fournir un produit dont linstallation soit scuritaire, facile et conomique.
Comme chaque installation est unique, il est impossible de connatre et de recommander une marche suivre prsentant
toutes les mthodes et consignes dinstallation possibles. De plus, nous ne connaissons pas tous les dangers et/ou rsultats
potentiels de chaque mthode ou procdure. Il est important de bien lire et comprendre entirement ces directives avant de
tenter dinstaller et dutiliser cet quipement. Conservez ces directives aux fins de consultation ultrieure.

Ce commutateur de transfert ncessite une installation avant lutilisation. Consultez la section Installation de ce manuel
pour les directives concernant les procdures dinstallation. Seuls des entrepreneurs en lectricit qualifis devraient installer
des systmes de gestion de lalimentation. Toute installation doit tre conforme lensemble des codes, normes et rglements
applicables (fdraux, provinciaux et locaux). Linstallateur doit suivre ces directives la lettre.

O nous trouver
Vous naurez jamais chercher bien loin pour trouver un centre de soutien et de service Briggs & Stratton pour votre systme.
Consultez les Pages Jaunes. De nombreux distributeurs de service aprs-vente agrs offrent un service de qualit. Vous
pouvez aussi joindre le Service technique en composant le (800) 743-4115, entre 8 h et 17 h HNC ou communiquer avec eux
par Internet ladresse BRIGGSandSTRATTON.com.

des fins de consultation ultrieure


Veuillez fournir les renseignements suivants et les conserver avec votre reu pour vous aider dans lidentification de lappareil
lors de vos prochains achats dquipement.

Commutateur de transfert

Numro de modle

Rvision

Numro de srie

Date dachat

Briggs & Stratton Power Products Group, LLC


900 North Parkway
Jefferson, WI 53549

Copyright 2009. Tous droits rservs. Aucune partie de ce manuel ne peut


tre reproduite ou transmise sous nimporte quelle forme sans lautorisation
expresse crite de Briggs & Stratton Power Products Group, LLC.

2 BRIGGSandSTRATTON.COM
Table des matires

Directives de scurit importantes . . . . . . . . . . . . . . . . . . . . 4


Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Conseils au propritaire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Responsabilits du dtaillant / de lentrepreneur charg de linstallation . . 5
Directives dassemblage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Interconnexions du cblage dalimentation . . . . . . . . . . . . . . . . . . . . . . . . . 7
Cblage de contrle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Configuration du systme . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Mise lessai du systme . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Commandes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Mode dutilisation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Mise lessai du commutateur de transfertautomatique . . . . . . . . . . . . . 12

Entretien . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Dpannage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Garantie . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Caractristiques du produit . . . . . . . . . . . . . . . . . . . . . . . . 17

3
Conservez ces directives
Directives de scurit importantes
CONSERVEZ CES DIRECTIVES Ce manuel renferme
dimportantes directives quil faut suivre durant linstallation AVERTISSEMENT Les fils de basse tension ne peuvent
et lentretien de lquipement. pas tre installs dans le mme conduit que les fils
dalimentation.
Symboles de scurit et leur signification
Le non-respect de cet avertissement pourrait entraner
des blessures personnelles et lendommagement ou le
mauvais fonctionnement de lquipement.
Choc lectrique Lisez le manuel
Le symbole dalerte de scurit indique un risque AVERTISSEMENT Si lquipement nest pas mis la
potentiel de blessure personnelle. Un mot signal (DANGER, terre comme il se doit, il y a risque dlectrocution.
AVERTISSEMENT ou ATTENTION) est utilis avec un
symbole dalerte pour vous indiquer le degr ou le niveau
du risque. Un symbole de scurit peut tre utilis pour Ne pas toucher aux fils dnuds.
reprsenter le type de risque. Le mot signal AVIS est Ne pas utiliser lquipement si le cblage est us,
utilis pour traiter les pratiques qui ne sont pas relies aux effiloch, dnud ou autrement endommag.
blessures personnelles. Ne pas manipuler les cordons lectriques les pieds dans
Le mot signal DANGER indique un danger qui, sil nest leau ou les pieds nus ou lorsque les mains ou les pieds
pas vit, causera la mort ou des blessures graves. sont mouills.
Le mot signal AVERTISSEMENT indique un risque Si vous devez travailler autour dune unit alors quelle est
qui, sil nest pas vit, pourrait causer la mort ou des en marche, placez-vous sur une surface sche isole afin
de rduire les risques de choc lectrique.
blessuresgraves.
Ne pas laisser les personnes non qualifies ou les enfants
Le mot signal ATTENTION indique un risque qui, sil utiliser ou entretenir lquipement.
nest pas vit, pourrait causer des blessures mineures
En cas daccident caus par un choc lectrique, mettez
oumodres.
immdiatement toutes les sources dalimentation
Le mot AVIS est utilis pour les pratiques qui ne sont pas lectrique hors tension et communiquez avec les autorits
relies aux blessures personnelles. locales. vitez tout contact direct avec la victime.
Le fabriquant ne peut anticiper toutes les circonstances
potentielles pouvant comporter un danger. Par consquent, AVERTISSEMENT lLquipement fonctionne une
les avertissements contenus dans le prsent manuel, tension leve qui peut entraner des blessures ou
ainsi que les plaques et les dcalques apposs sur lunit la mort.
nenglobent pas toutes les possibilits. Si vous utilisez
une procdure, une mthode de travail ou une technique En dpit de la conception scuritaire du systme, le fait
dopration non spcifiquement recommande par le doprer lquipement de faon imprudente, de ne pas
fabricant, vous devez vous assurer quelle ne compromet lentretenir ou dtre ngligent peut causer des blessures
pas votre scurit ni celle des autres. Vous devez galement et la mort.
vous assurer que la procdure, la mthode de travail ou
la technique dopration que vous choisissez ne rend pas AVIS Le traitement inadquat de lquipement peut
lquipement dangereux. lendommager et rduire sa dure de vie utile.
Nutilisez lquipement que pour les applications pour
AVERTISSEMENT Seuls les lectriciens qualifis lesquelles il a t conu.
peuvent procder linstallation de cet quipement, Si vous avez des questions propos de lutilisation prvue
laquelle doit respecter strictement les codes, normes et de cet appareil, consultez votre dtaillant ou communiquez
rglements applicables. avec Briggs & Stratton Power Products.
Nexposez pas lquipement lhumidit excessive, la
poussire, la salet ou aux vapeurs corrosives.
AVERTISSEMENT Certains composants de ce produit
ainsi que les accessoires relis contiennent des produits Demeurez alerte en tout temps lorsque vous travaillez sur
chimiques reconnus par ltat de la Californie comme cet quipement. Ne travaillez jamais sur lquipement si
causant des cancers, des malformations congnitales, ou vous tes fatigu physiquement ou mentalement.
dautres problmes de reproduction. Nettoyez-vous les Si les appareils branchs surchauffent, teignez-les et
mains aprs la manipulation. mettez leur disjoncteur ou fusible hors tension.

4 BRIGGSandSTRATTON.COM
Installation REMARQUE : Votre installateur est tenu de vrifier les codes
locaux ET dobtenir les permis requis avant de procder
Nous sommes vraiment reconnaissants de vous compter linstallation du systme.
parmi nos clients. Pour cette raison, nous avons dploy Vous devez lire et suivre les directives indiques dans
tous les efforts pour vous offrir un produit dont linstallation ce manuel.
soit scuritaire, facile et conomique. Comme chaque
installation est unique, il est impossible de connatre et de tablissez un programme dentretien et dutilisation
recommander une marche suivre prsentant toutes les rgulier de votre quipe, tel quindiqu dans ce manuel.
mthodes et consignes dinstallation possibles. De plus,
nous ignorons les dangers et/ou les rsultats potentiels
Responsabilits du dtaillant / de lentrepreneur
propres chaque mthode ou procdure. Voil pourquoi charg de linstallation
seuls des entrepreneurs en lectricit qualifis devraient Vous devez lire et respecter les rgles de scurit.
procder linstallation de ce systme. Toute installation Vous devez lire et suivre les directives indiques dans
doit tre conforme lensemble des codes ainsi que des ce manuel.
normes et des rglements de lindustrie applicables.
Il se peut linstallateur doive fournir les contacteurs
Votre quipement vous est livr avec le prsent Manuel nominaux appropris selon les charges contrler.
dinstallation et dutilisation . Ce manuel est un document
Vrifiez les codes fdraux, provinciaux et locaux et
important; conservez-le aprs avoir termin linstallation.
auprs des autorits comptentes si vous avez des
Tout a t fait pour sassurer que les renseignements questions concernant linstallation.
contenus dans le prsent manuel sont exacts et jour.
Sassurer que la gnratrice nest pas surcharge par
Toutefois, le fabriquant se rserve le droit de changer, de
des charges slectionnes.
modifier ou encore damliorer le systme en tout temps
sans pravis. Si vous avez des questions concernant linstallation,
consultez votre installateur ou votre dtaillant ou tlphonez
Responsabilits du propritaire au (800) 743-4115 de 8 h 17 h HNC.
Afin de vous aider faire des choix aviss et communiquer
Description de lquipement
efficacement avec lentrepreneur qui procdera
linstallation, veuillez lire attentivement la section Conseils Le commutateur de transfert est conu pour transfrer des
au propritaire avant de commencer linstallation de votre charges slectionnes retrouves habituellement dans les
quipement ou de la confier un entrepreneur. installations rsidentielles rgulires vers lalimentation
de la gnratrice dans le cas dune panne de courant du
Pour assurer une installation adquate, veuillez contacter le
service public. La charge est branche lalimentation de
magasin qui vous a vendu votre quipement, votre dtaillant
service (normal) ou lalimentation de secours rsidentielle
ou votre fournisseur de services dlectricit.
(gnratrice). En contrlant la tension de service et celle
Si linstallation du systme nest pas effectue par de la gnratrice, le commutateur de transfert se branche
un professionnel en lectricit certifi, la garantie automatiquement la source dlectricit approprie.
seraANNULE.
Ces commutateurs facilitent linstallation du groupe
lectrogne par un lectricien autoris. Selon le modle
Conseils au propritaire
de dtail achet, un interrupteur de dbranchement de
Les illustrations se rapportent des cas types et ont lalimentation de service et un commutateur de transfert
pour but de vous familiariser avec les diffrentes options automatique sont intgrs au botier de lunit. Les
dinstallation du systme dont vous disposez. conducteurs et le conduit de lalimentation de service
Au moment de ngocier avec un installateur professionnel, peuvent tre directement branchs de votre compteur au
il faudra tenir compte des facteurs suivants : les codes de commutateur de transfert. Un cblage de dbranchement
scurit locaux, lapparence et les distances. Plus la distance et connexe distinct nest pas requis lorsque linstallation
entre lappareil et le service dalimentation lectrique existant est conforme aux normes, la rglementation et aux codes
est grande, plus on aura besoin de compenser par les fdraux, provinciaux et locaux.
matriaux de cblage. Cette contrainte est ncessaire pour Selon le modle de dtail achet, les principaux lments du
vous conformer aux codes locaux et pour surmonter les commutateur de transfert sont constitus dun disjoncteur
chutes de tension lectrique. bipolaire dinterruption de lalimentation de service,
Ces facteurs auront une incidence directe sur le prix total un interrupteur bipolaire bidirectionnel, un module de
de linstallation de votre quipement. commande comprenant une carte de circuit imprim, des
bornes de dtection de tension avec fusible et le cblage de
raccordement. Les circuits du systme se trouvent dans un
botier de type NEMA 3R adapt pour un usage lintrieur
et lextrieur.

5
Le commutateur de transfert lectromagntique est actionn Contenu de lenvoi
par la tension de service et de la gnratrice et comporte Commutateur de transfert automatique (1)
des contacteurs dinterdiction mcaniques ou lectriques
Manuel de dinstallation et lutilisation (1)
appropris qui liminent le risque de brancher lalimentation
de service la sortie de la gnratrice. Sa capacit nominale Transformateurs de courant (2)
est suffisante pour commuter toute la puissance de service Articles non fournis :
de la rsidence. Le commutateur comporte un levier de Conduit et fil de branchement
priorit pour transfrer lalimentation manuellement.
Divers outils/quipements spcialiss
La carte du module de commande comprend des circuits
actifs qui contrlent les tensions de service et de la Directives dassemblage
gnratrice. Elle produit les signaux de dmarrage de
Les circuits du systme se trouvent dans un botier de type
la gnratrice ainsi que de transfert et de retransfert
NEMA 3R adapt pour un usage lintrieur et lextrieur.
lorsque lalimentation de service est rtablie et la fin du
Voici les directives dassemblage du botier :
refroidissement de la gnratrice. Le module de commande
comprend aussi des voyants rouge et vert indiquant Installez le botier sur une structure portante ferme
les sources dalimentation disponibles et deux contacts etrobuste.
commands par relais pour le contrle des charges Le botier doit tre install avec la quincaillerie
critiquesexternes. de raccordement de conduits cote au
minimumNEMA3R.
Vrification de la livraison Nivelez et aplombez le botier. Ceci peut tre accompli
Aprs avoir ouvert le carton, examinez avec soin le en insrant des rondelles entre le botier et la surface
contenu la recherche de dommages potentiels subis de fixation.
durantlexpdition. Ninstallez jamais le dispositif dans un endroit o une
IMPORTANT : Au moment de la livraison, si vous remarquez substance corrosive pourrait sinfiltrer.
des dommages ou des pices manquantes, demandez au Protgez le dispositif en tout temps contre lhumidit,
livreur de noter tous les dommages sur la facture de fret et les poussires, les salets, les peluches, le gravier et
dapposer sa signature dans lespace rserv cette fin. Si les vapeurs corrosives.
vous remarquez des dommages ou des pices manquantes
Voici ci-dessous une installation typique du commutateur
aprs la livraison, communiquez avec le transporteur
de transfert automatique. Il est recommand dinstaller le
pour connatre les procdures de rclamation. Les pices
commutateur prs du compteur de lalimentation de service,
manquantes ou endommages ne sont pas garanties.
soit lintrieur ou lextrieur. Discutez des suggestions
/ changements de disposition avec le propritaire avant
dentamer le processus dinstallation du systme.

Typique
Cblage de contrle Watt-
Panneau de Panneau du heuremtre
Commutateur
Contacteur distribution disjoncteur
de transfert
durgence principal

Circuits de
drivation

Chauffe-
eau

Gnratrice

Circuits de drivation
durgence Climatiseur

Interrupteur de dbranchement

6 BRIGGSandSTRATTON.COM
Interconnexions du cblage dalimentation 4. Branchez le commutateur de transfert lalimentation
Tout le cblage doit tre de la bonne dimension, soutenu de service :
convenablement et protg par un conduit. Tout le cblage Pour brancher les modles 071018 et 071019
doit tre conforme aux codes, normes et rglements lalimentation de service :
applicables (fdraux, provinciaux et locaux). Respectez Raccordez les conducteurs en cuivre partir du
les spcifications relatives au type de fil et au serrage se disjoncteur bipolaire du panneau de distribution
trouvant sur les blocs de branchement et le raccord neutre/ principal aux bornes UTILITY CONNECTION du
de mise la terre. commutateur de transfert.
Raccordez le conducteur en cuivre partir de la barre
AVERTISSEMENT lLquipement fonctionne une
tension leve qui peut entraner des blessures ou omnibus neutre du panneau de distribution principal
la mort. la borne neutre du commutateur de transfert.
Raccordez le conducteur en cuivre partir de la barre
En dpit de la conception scuritaire du systme, le fait omnibus de mise la terre du panneau de distribution
doprer lquipement de faon imprudente, de ne pas principal la borne GND du commutateur
lentretenir ou dtre ngligent peut causer des blessures detransfert.
et la mort. 33 : Assurez-vous que llectrode de terre est
REMARQUE
Effectuez les raccords suivants entre le commutateur de raccorde selon
22 les normes, les rglements et les codes
transfert, le panneau de distribution principal, lalimentation fdraux, provinciaux et locaux applicables.
de service et la gnratrice. Utilisez un fils de 300 V CA ou Pour brancher les modles 071020 et 071021
un fil de calibre suprieur, conforme au Tableau 310.16 lalimentation de service :
du Code national de llectricit. Appliquez les facteurs de Raccordez lalimentation de service aux bornes de
correction ncessaires et les calculs de grosseurs de fils. disjoncteur de lalimentation UTILITY CONNECTION
120V
du commutateur de transfert.
AVIS Une installation inadquate peut causer des
dommages aux cartes de circuit et rduire leur dure de Branchez le neutre de service public la borne neutre
vie utile. Linstallation de cartes de circuit imprim dans du commutateur de transfert. 120V
des circuits aliments causera des dommages la carte 5. Branchez les conducteurs dalimentation en cuivre des
et qui nest pas couverts par la garantie. Dbranchez bornes GENERATOR CONNECTION du disjoncteur
TOUJOURS TOUTES les sources dalimentation lectrique 11 de transfert au disjoncteur du panneau
du commutateur
avant lentretien. 240V
Retirez toutes les sources dalimentation avant dinstaller de commande44 de la gnratrice aux bornes LINE1
lquipement. La ngligence de cette consigne pourrait et LINE2. Tous les conducteurs doivent tre
causer des dommages internes la carte lors de passs par louverture du transformateur de courant
ltablissement des raccordements lectriques. avant que la connexion ne soit effectue.
Placez le commutateur de la gnratrice la position
OFF (ARRT).
Fermez lalimentation de service la gnratrice auxiliaire 44 11
et au commutateur de transfert.

1. Rglez linterrupteur de la gnratrice la position OFF. Circuit


0 Breaker 22
2. Rglez le disjoncteur de la gnratrice la position
OFF(ARRT).
Mise
3. Fermez lalimentation de service la gnratrice la terre
Neutre
auxiliaire et au commutateur de transfert.

AVERTISSEMENT Les bornes, les cosses ainsi que


Mise
tous les accessoires relis la batterie contiennent du la terre
Ligne 1 Ligne 2 Neutre
plomb et des composs de plomb - produits chimiques
reconnus par ltat de la Californie comme causant des
cancers et dautres problmes de reproduction. Nettoyez-
vous les mains aprs la manipulation. Vers le commutateur de transfert

6. Branchez les fils du transformateur de courant


aux bornes CT1 et CT2 sur le module
decommande.

7
7. Branchez le conducteur en cuivre partir de la Lillustration la page suivants montre une installations
borne neutre du commutateur de transfert la borne ralise typique. Votre installation relle variera.
neutre du panneau de commande de la gnratrice.
Observez le panneau de commande marquer pour Cblage de contrle
lidentificationterminale. Un climatiseur peut tre utilis avec des contacts de
8. Branchez le conducteur en cuivre partir de la supervision sur les bornes A-A ou B-B. Les bornes A-A
borne GND du commutateur de transfert la ne peuvent tre utilises quavec une commande de
borne GROUND du panneau de commande de supervision. Les charges importantes ne peuvent tre
lagnratrice. utilises quavec une commande de contacteurs sur les
REMARQUE : Assurez-vous que le conducteur de mise la bornes B-B. Des exemples de chacun des systmes sont
terre est raccord selon les normes, les rglementations et prsents ci-dessous.
les codes fdraux, provinciaux et locaux applicables. 1. La barrette de raccordement du module de commande
9. Branchez les bornes UTILITY240VAC du du commutateur de transfert comporte quatre raccords
commutateur de transfert aux bornes 240VAC de lusage du client. Deux ensembles de contacts
la gnratrice en utilisant un fil en cuivre 300V CA normalement ferms sont disponibles. Ils sont activs
fourni par linstallateur ou dun fil en cuivre de calibre lorsque la gnratrice est mise en marche. Ils peuvent
suprieur, des conducteurs dune grosseur minimum servir au contrle dimportantes charges branches la
de 14 AWG laide du connecteur bipolaire. gnratrice comme. Exemple: climatiseur, chauffe-eau,
etc. Les charges peuvent tre actives pourvu que la
10. Branchez les bornes T\R et GND du tableau de gnratrice produise la puissance ncessaire.
commande du commutateur de transfert (B) aux bornes
TxRx et TxRxGND du tableau de commande REMARQUE: Deux goulottes guide-fils sont fournies afin de
de la gnratrice (A) en utilisant des conducteurs en garder les charges de contrle loignes lune de lautre.
cuivre paire torsade de 18 AWG, pas plus long 2. Les bornes A-A du module de commande
de 200 pieds, 300Volts, 75 C-90 C laide du servent la commande du contacteur du climatiseur.
connecteur dedix ples. Les contacts sont branchs en srie au circuit de
commande du contacteur du climatiseur.
contacteur du climatiseur

A 24 VAC

A A
3. Les bornes B-B du module de commande servent
au contrle des charges importantes par le contacteur
fourni par linstallateur. Exemple : chauffe-eau
lectriques. Les contacts sont branchs en srie au
B
circuit de commande du contacteur.
contacteur
11. Serrez au couple appropri tous les raccords de fils et
attaches. Consultez ltiquette lintrieur du botier B Neutre

pour connatre les couples de serrage appropris.


Lors du raccordement aux blocs de branchement
B 120 VAC

de la carte de circuit imprim, ne fixez quun fil


chaque vis de connexion. 4. Serrez au couple appropri tous les raccords de fils
et attaches. Consultez la partie intrieure du botier
Les couples de serrage des connecteurs sont les suivants: du commutateur de transfert au sujet des couples
Service - 5,5 Nm Terre - 5,5 Nm deserrage.
Groupe lectrogne - 5,5Nm Commande - 1,4 Nm
Neutre - 12,5 Nm Blocs-fusibles - 1,4 Nm
Utilisez un inhibiteur doxydation sur toutes les bornes
enaluminium.
Toutes les languettes de contact des bornes et des ports
conviennent pour du fil de cuivre prvu pour 60/75C.

8 BRIGGSandSTRATTON.COM
Pour les modles 071018 & 071019
Vers lalimentation
To Utilityde service

L1 N
L2

Barre
Groundde Neutral
Barre
mise
Bus Bus
neutre
laterre

Mainde
Panneau
distribution
Distribution
principal
Panel Two Pole
Disjoncteur
Breaker
bipolaire

G
L1
L2
N

Branchement
Utility de
lelectricit de
Connection
service

Generator de
Branchement Connexion de Tx Rx et
Connection
la gnratrice miseT/R
laand
terreGND
Tx Rx de
Automatic to
la Generator
gnratrice
Commutateur
Transfer
detransfert
Switch Load
Raccordement
Connection
descharges Supervisory
Contacts decontrle
Contacts
Terminaux
Ground
de mise la
Terminal
terre
Neutral
Terminaux
Terminal
neutre
CTs

N 240
B&S
Vers laGenerator
gnratrice UTILITY240VAC
E1 VAC UTILITY 240VAC to Generator
E2 verslegnratrice
G
G
N L1
L2 Essential Circuit
E1 Panneau de distribution
N Sub Panel
E2
G

Ground
Barre de Neutral
Barre
Bus
mise Bus
neutre
laterre
TXRX

TXRX Gnd

240VAC

9
To Utility
Vers lalimentation de service Pour les modles 071020 & 071021

N
L2
L1

Generatorde
Branchement
CTs
la gnratrice
Connection

Branchement
Utility
de lelectricit Connexion de Tx Rx et
Connection
de service T/R and Gnd
mise la terre Tx Rx de
Automatic tolaGenerator
gnratrice
Commutateur Load
Transfer Raccordement
detransfert
Switch Connection
des charges

Supervisory
Contacts de
Contacts
contrle

Ground de
Terminaux
Terminal
mise la terre
Neutral
Terminaux
neutre
Terminal

N
L2
L1
G

240
N
VAC
B&S Generator
La gnratrice E1 UTILITY 240VAC
UTILITY240VAC
E2
verslegnratrice
to Generator
G

Barre
Groundde Neutral
N Barre
mise la
E1 Bus
terre
Bus
neutre
E2
G

TXRX

TXRX Gnd Main de


Panneau
240VAC distribution
Distribution
principal
Panel

10 BRIGGSandSTRATTON.COM
Configuration du systme Mode dutilisation
Vous devez effectuer les tapes suivantes sur le module de
Pour actionner le transfert automatique, suivez la procdure
commande avant dutiliser le systme :
dcrite ci-dessous:
Si la gnratrice est situe dans une zone rgulirement
1. Rglez sur ON linterrupteur de dbranchement de
soumise des tempratures infrieures 40F (4C),
lalimentation de service qui transmet lalimentation de
slectionnez une dure de rchauffement de 50
service linterrupteur de transfert.
secondes en dplaant le cavalier install sur JP2 de la
position 20 la position 50. 2. Installez le fusible de 15 ampres dans le panneau de
commande de la gnratrice.
Interrupteur 3 Interrupteur 3. Rglez le disjoncteur principal de la gnratrice
JP2
positions 2 positions
surON.
4. Rglez linterrupteur de systme AUTO.
Le systme est maintenant en mode de
fonctionnementautomatique.
Lorsque la gnratrice transmet de la puissance
linterrupteur de transfert, le contrleur surveille
continuellement la puissance de la gnratrice. Lorsquune
demande dactivation du climatiseur est mise, et que la
Connecteurs puissance disponible de la gnratrice est suffisante, le
de CT1 et CT2 contrleur ferme les contacts A-A vers le contacteur
du climatiseur. Les contacts B-B souvrent avant la
fermeture des contacts A-A . Les contacts A-A ou
B-B souvrent lorsque les charges sont trop importantes
Contacts de
pour la gnratrice. Les contacts A-A souvrent lorsque
contrle le climatiseur doit tre mis en marche. Les contacts
B-B se ferment lorsquil ny a pas suffisamment de
puissancedisponible.

Porte de botier
Rglez linterrupteur deux positions la position Pour ouvrir la porte, appuyez sur le verrouillage ressort de
NG ou LP, selon la position approprie la porte la droite et tirez la porte.
votresystme.
Rglez e commutateur trois positions de sorte
quil corresponde la valeur nominale en KW de la
gnratrice utilise : 12,15,ou20.

Mise lessai du systme


Pendant que linterrupteur de la gnratrice est la position
AUTO, placez le disjoncteur de lalimentation de service
alimentant le contacteur du commutateur de transfert la
position OFF. Au bout de quelques minutes, la gnratrice
samorcera, et le commutateur de transfert passera
lalimentation par la gnratrice.
Pour revenir lalimentation de service, rglez le disjoncteur
de lalimentation de service alimentant le commutateur de
transfert la position ON.

Commandes
Pour fermer et verrouiller la porte, poussez la porte contre
Outre le levier de priorit, aucune autre commande de le botier. cette position, poussez la porte vers le haut.
loprateur nest disponible puisquil sagit dun commutateur Le verrouillage ressort de la porte sengagera alors et
de transfert automatique. Seuls des techniciens verrouillera la porte cette position.
professionnels qualifis peuvent utiliser la commande
REMARQUE : La porte du botier DOIT tre ferme et
manuelle de priorit.
verrouille en tout temps sauf lors de lentretien du systme.

11
Mise lessai du commutateur de Entretien
transfertautomatique
Le commutateur de transfert est conu pour ne ncessiter
Rglez linterrupteur de dbranchement alimentant le aucun entretien dans le cadre dune utilisation normale.
commutateur de transfert sur Off. La squence Toutefois, il faut effectuer des inspections et des vrifications
automatique commencera. Pour revenir lalimentation de dentretien rgulirement. Lentretien consiste principalement
service, rglez linterrupteur de dbranchement sur On. garder le commutateur de transfert propre.
Panne de lalimentation de service Une inspection visuelle doit tre effectue au moins une
fois par mois. Laccs au commutateur de transfert ne doit
Le gnratrice dtecte la chute de la tension de service
pas tre obstru. Laissez un dgagement dau moins 1
sous 70 pourcent de la tension nominale. La squence
m (3 pi) autour du commutateur de transfert. Vrifiez les
de dmarrage du moteur commence aprs un dlai de
accumulations de salet, moisissure et/ou de corrosion sur
6secondes.
le botier et autour de celui-ci, les pices/quincaillerie lches,
Rchauffement du moteur les fissures et/ou de la dcoloration sur lisolant et les
lments endommags ou dcolors.
Prvoyez un dlai de rchauffement du moteur avant le
transfert. Utilisez un cavalier sur le tableau de commande Faites fonctionner le commutateur de transfert au moins
pour slectionner un dlai de 20 secondes ou de une fois tous les trois mois tel quexpliqu dans la section
50secondes. Mise lessai du commutateur de transfert automatique,
moins quune panne de courant ne survienne et que le
Transfert groupe lectrogne rsidentiel nait effectu une squence
Le transfert de lalimentation de service la gnratrice automatique. Laissez la gnratrice fonctionner pendant au
se produit aprs que la tension de la gnratrice dpasse moins 30minutes.
un seuil prdtermin. Aprs le transfert, le moteur tourne Communiquez avec un professionnel en lectricit certifi
durant au moins 5 minutes. pour linspection et le nettoyage de lintrieur du botier et
des autres composantes de votre systme de gnratrice
Prise en charge de lalimentation de service rsidentielle au moins une fois par anne.
La tension de prise en charge est de 80pourcent de la
tension nominale. Si vous tlphonez pour de laide
Ayez en main les numros de modle et de srie inscrits
Retransfert
sur ltiquette didentification de lunit si vous devez
Le transfert de lalimentation de la gnratrice communiquer avec un centre de service local pour lentretien
lalimentation de service se fait 10 secondes aprs que la ou la rparation de cette unit. Vous pouvez obtenir des
tension de service ait dpass le niveau de prise en charge et renseignements sur ltiquette didentification de lunit se
temps dexcution minimum est achev. trouvant sur le botier ou lintrieur de celui-ci.
Refroidissement du moteur Pour communiquer avec Briggs & Stratton, veuillez appeler
au (800) 743 4115 de 8 h 17 h HNC.
Le moteur tourne pendant 60 secondes aprs le transfert.
Vrification installation
Avant de mettre en service le groupe lectrogne, vrifiez
minutieusement lensemble de linstallation.
Tout en procdant la vrification, remplissez la liste de
vrification de linstallation fourni avec votre gnrateur.
Assurez-vous que tous les lments sont cochs et
que toutes les signatures ont t obtenues. Indiquez au
propritaire quil doit poster la copie blanche :
Warranty Registration
P. O. Box 239
Jefferson, WI 53549

12 BRIGGSandSTRATTON.COM
Dpannage
PROBLMES. CAUSE SOLUTION
1. Le disjoncteur de la gnratrice 1. Rarmez le disjoncteur de
Le commutateur de transfert
estouvert. lagnratrice.
automatique ne transfre pas
2. La tension de la gnratrice nest 2. Reportez-vous au manuel de
lagnratrice
pas adquate. lagnratrice.

1. Lutilit dbranche le disjoncteur 1. Rarmez le utilit dbranche le


ouvert (modles 071018 et disjoncteur (modles 071018 et
071019seulement). 071019 seulement).
Le commutateur de transfert
2. Le disjoncteur de lalimentation de 2. Rarmez le disjoncteur de
automatique ne transfre pas
service est ouvert (modles 071020 lalimentation de service (modles
lalimentation de service
et 071021 seulement. 071020 et 071021 seulement.
3. La tension de lalimentation de 3. Attendez que la tension de service
service nest pas adquate. revienne la normale.

La gnratrice continue de fonctionner


La priode de refroidissement na pas Le moteur devrait steindre aprs
aprs que le commutateur eut transfr
tcomplte. 1minute.
lalimentation de service

1. L es contacts A-A ou B-B ne 1. V


 rifiez le fonctionnement des
fonctionnent pas correctement. contacts A-A ou B-B et/ou
le cblage de commande vers des
charges externes.
Les charges rglables (climatiseur, 2. Charge trop leve pour 2. Diminuez la charge sollicite de
etc.) ne fonctionnent pas lorsque la lagnratrice. lagnratrice.
gnratrice alimente des appareils 3. Transformateur de courant 3. Raccordez les connecteurs du
pasconnect. transformateur de courant au
tableau de commande.
4. Transformateur de 4. Communiquez avec un centre de
courantdfectueux. service local.

1. La priode de fonctionnement 1. Attendez cinq minutes pour que le


La gnratrice demeure en minimum du moteur ne sest commutateur de transfert transfre
marche aprs le rtablissement de pascoule. lalimentation de service.
lalimentation de service 2. Le ou les fusibles du commutateur 2. Vrifiez le ou les fusibles et
de transfert sont dfectueux. remplacez-les au besoin.

13
Reserved

14 BRIGGSandSTRATTON.COM
Reserved

15
GARANTIE DU PROPRITAIRE DU COMMUTATEUR DE TRANSFERT BRIGGS & STRATTON POWER PRODUCTS GROUP, LLC

Prise deffet au 1 er Novembre 2005, annule et remplace toutes les garanties prcdentes et les garanties antrieures au 1 er Novembre 2005

GARANTIE LIMITE
Briggs & Stratton Power Products Group, LLC rparera ou remplacera, sans frais, toutes pices dquipement dfectueuses comportant un vice
de matriau ou un dfaut de fabrication ou les deux. En vertu de la prsente garantie, les frais de transport des produit soumises pour rparation
ou remplacement sont la charge de lacheteur. La prsente garantie sera en vigueur durant les priodes stipules ci-dessous et est assujettie aux
conditions stipules ci-dessous. Pour obtenir des services en vertu de la garantie, veuillez consulter notre Outil de recherche dun Service aprs-vente
agr au http://www.BRIGGSandSTRATTON.COM afin de trouver un distributeur de service aprs-vente agr dans votre rgion.
Garantie
IL NEXISTE AUCUNE AUTRE GARANTIE EXPRESSE. LES GARANTIES IMPLICITES, INCLUANT CELLES DE QUALIT MARCHANDE ET DADAPTATION
UN USAGE PARTICULIER, SONT LIMITES UNE PRIODE DUN AN PARTIR DE LA DATE DACHAT OU JUSQU LA LIMITE PERMISE PAR LA LOI,
TOUTE GARANTIE IMPLICITE EST EXCLUE. LA RESPONSABILIT POUR DOMMAGES ACCESSOIRES OU INDIRECTS EST EXCLUE DANS LA MESURE
O UNE TELLE EXCLUSION EST PERMISE PAR LA LOI. Certains tats/provinces ou pays nautorisent aucune restriction sur la dure dune garantie
implicite, et certains tats/provinces ou pays nautorisent pas lexclusion ou la limitation des dommages conscutifs ou indirects. Par consquent, les
restrictions et exclusions dcrites ci-dessus pourraient ne pas sappliquer dans votre cas. La prsente garantie vous accorde certains droits lgaux
spcifiques et vous pourriez galement en avoir dautres, qui peuvent varier dun tat ou dune province lautre et dun pays lautre.

PRIODE DE GARANTIE

Usage par un consommateur 3 ans


Usage des fins commerciales aucune

La priode de garantie dbute la date dachat par le premier acheteur au dtail ou par le premier utilisateur commercial final, et se prolonge pour la dure
stipule dans le tableau ci-dessus. Usage par un consommateur signifie utilisation domestique personnelle dans une rsidence, par lacheteur au dtail.
Usage des fins commerciales signifie toute autre utilisation, y compris des fins commerciales, gnrant de revenus ou de location. Aux fins de la
prsente garantie, ds quun quipement a t utilis commercialement une fois, il est par la suite considr comme tant dusage des fins commerciales.
Lquipement utilis pour lalimentation principale nest pas couvert par la prsente garantie.
POUR EXERCER LA GARANTIE SUR TOUT PRODUIT FABRIQU PAR BRIGGS & STRATTON, IL NEST PAS NCESSAIRE DE LENREGISTRER. CONSERVEZ
LE REU COMME PREUVE DACHAT. SI, LORS DUNE RCLAMATION DE GARANTIE, VOUS NE POUVEZ PROUVER LA DATE INITIALE DE LACHAT, NOUS
UTILISERONS LA DATE DE FABRICATION DU PRODUIT COMME DATE DE RFRENCE POUR DTERMINER LA PRIODE DE GARANTIE.

PROPOS DE LA QUPEMENT GARANTIE

Nous acceptons de faire effectuer les rparations couvertes par la garantie et tenons nous excuser pour tout inconvnient subi. Tout agent dun service
aprs-vente agr peut excuter les rparations couvertes par la garantie. La plupart des rparations couvertes par la garantie sont traites automatiquement;
cependant, il arrive parfois que les demandes de service en vertu de la garantie soient non fondes. Par exemple, la garantie ne couvre pas les dommages
causs lquipement par une utilisation abusive, par un manque dentretien priodique, durant lexpdition, la manutention ou lentreposage, ou en raison
dune installation inadquate. De mme, la garantie sera annule si la date de fabrication ou le numro de srie appos lquipement a t enlev ou si
lquipement a t chang ou modifi. Durant la priode de garantie, le distributeur de service aprs-vente agr rparera ou remplacera, son gr, toute
pice qui, aprs examen, est trouve dfectueuse la suite dune utilisation et dun entretien normaux. La prsente garantie ne couvre pas les rparations et
les quipements suivants:
Usure normale: Comme tout autre dispositif mcanique, les groupes lectrognes dextrieur ncessitent lentretien priodiques de certaines pices
pour fonctionner adquatement. La prsente garantie ne couvre pas les frais de rparation des pices ou des quipements dont la dure de vie utile a
t dpasse la suite dune utilisation normale.
Installation et entretien: La prsente garantie ne couvre pas les quipements ou les pices qui ont fait lobjet dune installation ou de modifications
et de changements inadquats ou non autoriss, dune mauvaise utilisation, de ngligence, dun accident, dune surcharge, dentretien inadquat, de
rparation ou dentreposage qui, selon nous, auraient nui la performance et la fiabilit du produit. De plus, la garantie ne couvre pas lentretien
normal tel que le rglage, le nettoyage et remplacement de fusible.
Exclusions supplmentaires: La prsente garantie exclut les pices qui susent ou tout dommage ou tout mauvais fonctionnement rsultant dun
accident, dune utilisation abusive, de modifications, de changements ou dun entretien inadquat du systme. La garantie du produit ne couvre pas les
pices accessoires. Cette garantie exclut toute dfaillance due une catastrophe naturelle ou toute autre force majeure hors du contrle du fabricant.
Est aussi exclu tout quipement us, remis neuf ou de dmonstration. 198180F, Rev. C, 12/31/2006

BRIGGS & STRATTON POWER PRODUCTS GROUP, LLC


JEFFERSON, WI, USA

16 BRIGGSandSTRATTON.COM
Commutateur de transfert

Caractristiques du produit
Modle 071018 Modle 071020
Charge nominale maximum 25C (77F)*...... 100 Ampres Charge nominale maximum 25C (77F)*...... 100 Ampres
Tension nominale C.A.............................................. 250 Volts Tension nominale C.A.............................................. 250 Volts
Ples..................................................................................... 2 Ples..................................................................................... 2
Frquence...................................................................... 60 Hz Frquence...................................................................... 60 Hz
Intensit de dfaillance nominale....................22,000 Ampres Intensit de dfaillance nominale....................22,000 Ampres
Symtriques RMS Symtriques RMS
Valeur nominale des contacts Valeur nominale des contacts
de contrle A-A................................................... 24 Volt c.a. de contrle A-A................................................... 24 Volt c.a.
de contrle B-B............................... 1 ampre, 125 Volt c.a., de contrle B-B............................... 1 ampre, 125 Volt c.a.,
rgime de fonctionnement asservi rgime de fonctionnement asservi
Plage dutilisation normale... -28.8C (-20F) to 40C (104F) Plage dutilisation normale... -28.8C (-20F) to 40C (104F)
Poids...................................................................11 kg (25 lb) Poids...................................................................18 kg (40 lb)

Modle 071019 Modle 071021


Charge nominale maximum 25C (77F)*...... 200 Ampres Charge nominale maximum 25C (77F)*...... 200 Ampres
Tension nominale C.A.............................................. 250 Volts Tension nominale C.A.............................................. 250 Volts
Ples..................................................................................... 2 Ples..................................................................................... 2
Frquence...................................................................... 60 Hz Frquence...................................................................... 60 Hz
Intensit de dfaillance nominale....................25,000 Ampres Intensit de dfaillance nominale....................25,000 Ampres
Symtriques RMS Symtriques RMS
Valeur nominale des contacts Valeur nominale des contacts
de contrle A-A................................................... 24 Volt c.a. de contrle A-A................................................... 24 Volt c.a.
de contrle B-B............................... 1 ampre, 125 Volt c.a., de contrle B-B............................... 1 ampre, 125 Volt c.a.,
rgime de fonctionnement asservi rgime de fonctionnement asservi
Plage dutilisation normale... -28.8C (-20F) to 40C (104F) Plage dutilisation normale... -28.8C (-20F) to 40C (104F)
Poids...................................................................17 kg (38 lb) Poids...................................................................29 kg (63 lb)

*Ce commutateur de transfert est certifi tre conforme la norme 1008 (quipement de commutation de transfert) de UL
(Underwriters Laboratories).

Briggs & Stratton Power Products Group, LLC


900 N. Parkway
Jefferson, Wisconsin, 53549 U.S.A.

17
Reserved

Manual No. 201705GS Rev. C (3/11/2009)