Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
2.2 Functions 3
2.3 Components 4
2.4 Terminal 5
2.5 6
4.3 11
4.4 Repairs 12
4.5 13
5. Periodical
5.1 Service 14
inspections
5.2 15
6.3 18
6.4 19
7. SPACE information 20
SPACE 3000, Service manual 1 Preface, safety regulations
Contents
Preface......................................................................................... 3
Safety regulations ......................................................................... 4
Read this for your safety .................................................... 4
Excluded personnel ........................................................... 4
Extract from EN12999:2000 ............................................... 5
Extract from EN12644-1 .................................................... 6
2000-12-20 1
SPACE 3000, Service manual 1 Preface, safety regulations
2 2000-12-20
SPACE 3000, Service manual 1 Preface, safety regulations
PREFACE
PREFACE
This service manual describes the microprocessor
controlled electronic safety system, which is used to
control the various functions on a HIAB crane.
The information in this manual is divided into seven
different main sections. Some of the sections are
divided into subsections.
The new structure of the binder will make it easier for
you, the service engineer in the HIAB organisation, to
find the information you are looking for.
If for example a customer wants to have a winch
mounted on his crane, all information regarding electri-
cal connection and changing of settings will be found
under section 6.1 Connecting accessories.
If you want to learn more about how the system works
all information regarding function and components will
be found under section 2 System description.
We hope that you will like the improved layout of the
manual.
If there is something regarding the information or
structure in the manual that you think could be im-
proved please let us know. Your information will be of
great value to us and will be used when updating the
manual.
HIAB AB,
Product support dept.,
Technical documentation
2000-12-20 3
SPACE 3000, Service manual 1 Preface, safety regulations
SAFETY REGULATIONS
REGULATIONS
Read this for your safety
The HIAB Cargo Handling Equipment can be hazar-
dous if it is not operated correctly. Make sure you read
and understand the general safety information given in
this chapter.
The equipment must be operated in accordance with
the instructions given in the relevant Operators
Manual. Using the equipment in any other way or for
any other purpose is prohibited.
Warnings, cautions, notes and tips are given in this
manual. Their meanings are as follows:
WARNING
A Warning is given where wrong action could result in
death or injury to the operator and nearby personnel.
Warnings must always be adhered to, and given
precedence over written and verbal instructions as well
as Cautions.
CAUTION
A Caution is given where wrong action could result in
damage to the equipment. Cautions must always be
adhered to, and given precedence over Notes, and
written and verbal instructions.
NOTE!
A note emphasises an important piece of information or
an instruction.
Warnings and Cautions that apply to the general
operation of the HIAB Cargo Handling
Equipment are given in the relevant Operators Manual.
TIP!
Tip to make work easy to carry out.
Excluded personnel
Untrained personnel must not operate or carry out
repairs to the Cargo Handling Equipment.
4 2000-12-20
SPACE 3000, Service manual 1 Preface, safety regulations
2000-12-20 5
SPACE 3000, Service manual 1 Preface, safety regulations
NOTE!
Guidance for periodical checks,
inspections, examinations and tests is
given in ISO 12480-1.
NOTE!
Futher guidance is given in ISO 12482-1.
6 2000-12-20
SPACE 3000, Service manual 1 Preface, safety regulations
NOTE!
Further guidance is given in ISO 12480-1.
NOTE!
Guidance for the content of spare parts
manual is given in ISO 10973.
2000-12-20 7
SPACE 3000, Service manual 1 Preface, safety regulations
8 2000-12-20
SPACE 3000, Service Manual 2.1 Overview
2.1 Overview
Contents
General......................................................................................... 3
SPACE ......................................................................................... 4
CAN-Communication ......................................................... 4
Standard box (SPACE box) ................................................ 4
User interface .................................................................... 5
Column box ........................................................................ 5
Sensors ............................................................................. 5
Indicators ........................................................................... 5
Dump valve ........................................................................ 6
Signalling components ....................................................... 6
Function ....................................................................................... 7
SPACE Operating Principles ............................................. 7
Switch on ................................................................ 7
Beginning Operation ............................................... 8
During Operation .................................................... 8
SPACE, system overview .................................................. 9
2000-12-20 1
SPACE 3000, Service Manual 2.1 Overview
2 2000-12-20
SPACE 3000, Service Manual 2.1 Overview
GENERAL
SPACE 3000 is a microprocessor controlled electronic
safety system used to control the various functions on
a HIAB crane (Fig. 1).
SPACE stands for:
S = Speed
P = Payload
A = Accessories
C = Certificate
E = Electronics
1070-328
Fig. 1
2000-12-20 3
SPACE 3000, Service Manual 2.1 Overview
SPACE
SPACE
(Fig. 2) 1
1
A CL/DUO system consists of e.g.:
Empty box
Column box 2
Pressure sensors
4
Indicators
Dump valve
Spool sensors.
5
ADC
MSC valve
1070-327
CAN-Communication 1. Tilt indicators
2. Pressure sensors
The Standard box, the User interfaces and other 3. Column box
components such as Cabin warning are with 7-wire 4. Slewing sector indicators
5. Standard box
shielded cables. The modules use a CAN-bus for
6. Dump valve
communication. It was developed for the automotive 7. Spool sensors
industry with high demands on reliability and suppres-
sion of disturbances. The CAN-bus uses two wires, but
will still function if one of them is interrupted or shorted Fig. 2
to a permanent voltage.
Standard box
The Standard box is the heart of the system. The
microprocessor monitors crane operation.
Main power supply is connected to the Standard box.
4 2000-12-20
SPACE 3000, Service Manual 2.1 Overview
User interface
(Fig. 3)
The User interface is the communication centre of the
SPACE 3000. It gives information about the system
and is also where the user controls the system.
The User interface is located on the Standard box and
on an empty box. It can also be located on an ADC
Extended box (if present). Maximum four User
interfaces can be fitted on a crane.
1070-316
Column box SPACE 3000
Indicators
An indicator gives an on/off signal, which correspond to
e.g. the position of outer boom.
The inner boom and outer boom indicators (option on
certain cranes) give the position of the inner boom and
outer boom. The slewing sector indicators (option on
certain cranes) give information of slewing position of
the crane.
Sensors
A sensor gives an analogue signal, which correspond
to e.g. the pressure in the inner boom cylinder.
The pressure sensors register the pressures in the
inner boom and outer boom cylinders.
The spool sensors gives information of the position of
the spools.
2000-12-20 5
SPACE 3000, Service Manual 2.1 Overview
Dump valve
(Fig. 4)
The dump valve controls the oil flow:
Signalling components
Fig. 4
It is possible to connect additional warning lamps and
sounders to the HIAB cranes. The Cabin warning is a
popular factory fitted option, giving a warning to the
operator both from the truck cab and externally, that the
boom system is pointing upwards and should be
lowered before moving the truck.
Many of the additional warning systems are installed by
the equipment installers and designed to exact
customer requirements.
6 2000-12-20
SPACE 3000, Service Manual 2.1 Overview
FUNCTION
SP ACE Operating
SPACE
Principles
The purpose of this section is to give a brief overview of
the basic principles employed in the operation of the
SPACE system. It is not intended to be an accurate
description of a particular system, but a familiarisation
section for the engineer who has not worked with
SPACE before or one who has maybe not been in
contact with a full SPACE system for sometime.
Switch on
(Fig. 5)
SPACE is switched on by pressing the ON/OFF button
on the User interface.
If the button is pressed for more then 2 s when system ADC
is switched on the lamp test is activated, as long as
the button is pressed all red LEDs light, when
released all red LEDs continue to light for 3 s then all
green LEDs light for 3 s.
SPACE 3000
31
-3
70
10
Fig. 5
2000-12-20 7
SPACE 3000, Service Manual 2.1 Overview
Beginning operation
(Fig. 6)
When operation begins with the movement of a control
valve lever, the spool sensor for the relevant spool ADC
1070-325
SPACE 3000
hydraulic function to begin.
Fig. 6
During operation
(Fig. 7)
Whilst the crane is operating SPACE monitors signals
sent from the spool sensors, tilt indicators and pres-
sure sensors. In the event of any of the signals moving 100%
outside the pre-determined parameters set in SPACE,
a warning is given that the crane has reached 90% of
it's capacity the red LEDs 1-3 on the User interface 90%
will flash. If operation continues to increase the loading
of the crane the signal to the dump valve will be
switched off and crane operation will cease. The red
LEDs 1-4 will be lit constantly. SPACE will now wait
for an operation command that will reduce the loading
1070-314
on the crane and operation will restart automatically.
SPACE will not accept any command that will in-
crease the loading of the crane once OLP has been
Fig. 7
activated.
8 2000-12-20
SPACE 3000, Service Manual 2.1 Overview
Control System
2000-12-20 9
SPACE 3000, Service Manual 2.2 Functions
2.2 Functions
Contents
General......................................................................................... 3
Functions ..................................................................................... 4
Overload protection (OLP) ................................................. 4
OLP Basic crane .................................................... 4
OLP Winch ............................................................. 5
OLP Manual extensions .......................................... 5
OLP Disconnection ................................................ 5
Automatic Duty Control (ADC) ................................ 6
Manual Speed Control (MSC) ................................. 6
Automatic Dumping of Oil (ADO) ............................ 7
Stability ............................................................................... 8
Slewing Sector ........................................................ 8
Fixed platform ......................................................... 9
Cabin warning ......................................................... 9
Automatic damping on slewing (ADS) .................... 9
2000-12-20 1
SPACE 3000, Service Manual 2.2 Functions
2 2000-12-20
SPACE 3000, Service Manual 2.2 Functions
GENERAL
This section contains functions that SPACE 3000 is
equipped with as a standard for the majority of cranes.
2000-12-20 3
SPACE 3000, Service Manual 2.2 Functions
FUNCTIONS
Overload protection (OLP)
1070-314
Fig. 1
extension outwards
Fig. 2
extension outwards
4 2000-12-20
SPACE 3000, Service Manual 2.2 Functions
OLP Winch
When winch reaches 90% of permitted load the winch
LED on the User interface starts flashing. At 100%
load OLP cuts in, stopping load increasing move-
ments. The LED has a steady red light until the
overload situation is over.
When the wire is almost completely unwound (three
turns left on drum) winch lowering is stopped. Operator
has to winch in to reverse situation.
NOTE!
For information how to change OLP-settings
for manual extensions, see section 6.2
Settings.
Fig. 5
2000-12-20 5
SPACE 3000, Service Manual 2.2 Functions
1070-335
SPACE 3000
chosen again after 60 seconds inactivity in these
functions.
ADC is automatically chosen at start up, which is
indicated by a LED on the user interface. Fig. 6
ADC increases the lifting capacity without any
reduction in lifting speed. In winch mode the lifting
capacity is increased.
-337
sensors on inner and outer boom cylinders. When the
1070
load is above approx. 90 % of the maximum allowed
load, SPACE activates MSC by opening a hydraulic
valve. The speed of the function is reduced to 25% in
one step. Fig. 7
MSC will be automatically switched off when the load
in cylinder decreases.
When MSC is activated the maximum stroke in the
spool is hydraulically reduced in both directions. The
operator will notice that the lever movement will be
reduced.
MSC increases the lifting capacity depending on type
of crane.
6 2000-12-20
SPACE 3000, Service Manual 2.2 Functions
2000-12-20 7
SPACE 3000, Service Manual 2.2 Functions
Stability
Slewing Sector
When the truck has insufficient stability in a certain
sector, e. g. in front of the cabin indicators can be
fitted defining this sector (Fig. 8). The system is
programmed to allow only reduced load in the indi-
cated sector. For load sensing inner boom cylinder
pressure is used.
1070-043
You may now slew the crane back or operate accord-
ing to normal OLP logic.
If you lift a load in a reduced sector and OLP cuts in, it Fig. 8
is possible to use normal OLP logic, but possible to
slew out of the sector only on the side where you
came into the sector.
NOTE!
For information how to set parameters
when using a special slewing sector
sector,, see
section 6.2 Settings.
8 2000-12-20
SPACE 3000, Service Manual 2.2 Functions
Fixed platform
(Fig. 9)
Fixed platform is known in some countries as Stand up
platform.
It is possible to connect this function to SPACE. It will
prevent the operator from slewing the boom into the
fixed platform or themselves.
Slewing sector, inner boom and outer boom angle
indicators are used to define permitted lifting areas
when operating the crane from fixed platform.
NOTE!
For information how to set parameters, see
section 6.2. Settings.
Fig. 9
Cabin warning
Signal in the cabin (normally a lamp) is possible if one
of following conditions is fulfilled:
2000-12-20 9
SPACE 3000, Service Manual 2.2 Functions
10 2000-12-20
SPACE 3000, Service Manual 2.3 Components
2.3 Components
Contents
General......................................................................................... 3
Boxes and sensors ...................................................................... 4
Connection plinths ............................................................. 4
Grease ............................................................................... 4
Bar code signs ................................................................... 4
Connection diagram ........................................................... 5
CL/DUO crane ........................................................ 5
PRO crane ............................................................. 6
Standard box ...................................................................... 7
Function .................................................................. 7
Connection plinths .................................................. 8
Jumpers ................................................................ 10
User interface ................................................................... 11
Function ................................................................. 11
Buttons .................................................................. 11
Indicator LEDs ..................................................... 12
Connection plinths ................................................ 14
Jumpers ................................................................ 15
Column box ...................................................................... 16
Function ................................................................ 16
Connection plinths ................................................ 16
Extended box ................................................................... 18
Function ................................................................ 18
Connection plinths ................................................ 19
Operation ................................................................................... 20
Jumper settings ............................................................... 20
Channels and connection plinths ..................................... 21
Slewing sector indicators ................................................. 22
Function ................................................................ 22
2000-12-20 1
SPACE 3000, Service Manual 2.3 Components
2 2000-12-20
SPACE 3000, Service Manual 2.3 Components
GENERAL
This section contains components that SPACE 3000
is equipped with as a standard and also describes a
number of accessories supplied by HIAB for the
majority of cranes.
2000-12-20 3
SPACE 3000, Service Manual 2.3 Components
Connection plinths
The connection boxes in SPACE 3000 consist of a
case with several cable inlets and a cover that is
mounted with screws. Under the cover there are
different types of connection plinths depending on the
box type.
The connections are marked with e.g. P2.1, P2.2,
P2.3 in pictures and wiring diagrams (Fig 1).
P2 is the connection plinth.
.1 is plinth number 1 which normally is the first from
left seen from the cable side.
Grease Fig. 1
Fig. 2
4 2000-12-20
SPACE 3000, Service Manual 2.3 Components
Connection diagram
The connection diagrams is show example of a CL/
DUO crane (Fig. 3) and a PRO crane (Fig. 4).
Below the diagrams are component lists.
CL/DUO crane
Fig. 3
2000-12-20 5
SPACE 3000, Service Manual 2.3 Components
PRO crane
4
6
5
3 7
2
8
1
23 9
22
24
25
21 10
26
24 V 11
17
16 12
20
1070-321
15 14
19
13
18
Fig. 4
6 2000-12-20
SPACE 3000, Service Manual 2.3 Components
Standard box
Function
(Fig. 5)
The Standard box is the central unit of the system. It There is two a digit indicator (A) in the box which
supplies power to all the other units in the system. It displays a number if an error should occur in the
consists of two parts, a connection terminal board and system and the number of errors.
a display. Example: The digit 4 and a dot, followed by 03 without
a dot indicates that there are four errors and the lowest
The Standard box distributes power to all the other number of these is no. 03.
modules of the system. Nominal supply is 24 V DC, If there are no errors the number 0 flashes.
but the system will be fully operational between
16V32V. The Standard box is aquipped with several automatic
fuses and one 7.5 A automotive fuse (B).
Fig. 5
2000-12-20 7
SPACE 3000, Service Manual 2.3 Components
Connection plinths
(Fig. 5)
Plinth Description
P1 From Spool sensors 1-4 P3 Communication with terminal
P1.1 Ground P3.1 Ground
P1.2 24 V P3.2 24 V
P1.3 Signal from spool sensor 1 (0-5 V) P3.3 Data out
P1.4 Signal from spool sensor 2 (0-5 V) P3.4 Data in
P1.5 Signal from spool sensor 3 (0-5 V)
P4 From on platform indicator/manual
P1.6 Signal from spool sensor 4 (0-5 V)
extension in indicator
P4.1 Ground
P2 From Spool sensors 5-6
P4.2 24 V
P2.1 Ground
P4.3 Signal from on platform indicator
P2.2 24 V
P2.3 Signal from spool sensor 5 (0-5 V)
P2.4 Signal from spool sensor 6 (0-5 V)
Fig. 5
8 2000-12-20
SPACE 3000, Service Manual 2.3 Components
2000-12-20 9
SPACE 3000, Service Manual 2.3 Components
Jumpers
(Fig. 6)
In the Standard box the jumpers are located in the
lower centre of the box. There is one row with five
jumpers.
Fig. 6
10 2000-12-20
SPACE 3000, Service Manual 2.3 Components
User interface
Function
(Fig. 7)
The User interface is the communication centre of the
SPACE 3000. It gives information about the system
and is also where the user controls the system.
The User interface is mounted on the Standard box
and the extended box (if present). It can also be
mounted on an Empty box. Maximum four User
interfaces can be fitted on a crane.
Buttons
(Fig. 7)
1. Power On Fig. 7
Enables power to SPACE. If button is pressed for
more then 2 s when system is on the LED test is
activated, as long as the button is pressed all red
LED`s light, when released all red LED`s continue to
light for 3 s then all green LED`s light for 3 s.
2. Release
Enables power to:
- OLP release if crane has OLP
- Dump valve/valves if not OLP, if Extended box
present also dump valve 2 (switched off after 10
minutes and when a crane function is used
dump valve 2 is always switched off).
3. Emergency stop
In danger the emergency stop button is pressed.
Power to the dump valve is cut and the crane stops.
The emergency stop button is to be turned
clockwise to reset.
4. Horn
Enables power to the horn if present.
5. Manual extension
Enables power to manual extension logic.
2000-12-20 11
SPACE 3000, Service Manual 2.3 Components
Indicator LEDs
(Fig. 8)
The display consists of eight LED`s which indicates 4
3 5
button positions, errors, stability sector, winch etc.
6
For detailed information, see table below.
2
There are also two groups of LED`s in the inner boom
and outer boom. Each group contain four LED`s. Two ADC
10
are two-coloured, green/red, and two are red. The
purpose of the LED`s is to show the pressure in the
cylinders. For detailed information, see table below.
1070-339
SPACE 3000
1 9 8 7
Fig. 8
12 2000-12-20
SPACE 3000, Service Manual 2.3 Components
2000-12-20 13
SPACE 3000, Service Manual 2.3 Components
Connection plinths
(Fig. 9)
Plinth Description
P1 CAN (From/to Standard box)
P1.1 Ground
P1.2 24 V
P1.3 CAN +
P1.4 CAN -
P1.5 Emergency stop out
P1.6 Emergency stop in
P1.7 On/off
Fig. 9
14 2000-12-20
SPACE 3000, Service Manual 2.3 Components
Jumpers
(Fig. 10)
The jumpers are located in the higher right side of the
User interface. There is one row with five jumpers.
Fig. 10
2000-12-20 15
SPACE 3000, Service Manual 2.3 Components
Column box
Function
(Fig. 11)
This connection box is fitted to the crane column. All
the signals from the pressure sensors and indicators
(max. 7) on the boom system are collected in the box.
The Column box is connected to the SPACE box using
a 9-conductor cable.
Connection plinths
(Fig. 11)
P1 To Standard box
P1.1 Ground
P1.2 24 V
P1.3 Signal from inner boom pressure sensor
(4-20 mA)
P1.4 Signal from outer boom pressure sensor
(4-20 mA)
P1.5 Signal from outer boom tilt indicator
(10 or 19 mA)
P1.6 Signal from inner boom tilt indicator
(10 or 19 mA)
P1.7 Signal from winch indicator (4-20 mA)
P1.8 Signal from second tilt indicator or inner &
outer boom fixed platform angle indicator
(0/24 V)
P1.9 Signal from hydaulic extension in indicator
or second tilt indicator (0/24 V)
Fig. 11
16 2000-12-20
SPACE 3000, Service Manual 2.3 Components
2000-12-20 17
SPACE 3000, Service Manual 2.3 Components
Extended box
Function
(Fig. 12)
The Extended box is present if Space 3000 is
equipped with MSC, ADS or external dump.
Fig.12
18 2000-12-20
SPACE 3000, Service Manual 2.3 Components
Connection plinths
P1 To ADS valve P7 CAN (From/to extra boxes)
P1.1 Ground, not same potential as other ground. P7.1 Ground
P1.2 24 V (1 A) P7.2 24 V
P7.3 CAN +
P2 From ADS pressure 1
P7.4 CAN -
P2.1 24 V
P7.5 Emergency stop out
P2.2 Signal from pressure sensor (4-20 mA)
P7.6 Emergency stop in
2000-12-20 19
SPACE 3000, Service Manual 2.3 Components
OPERATION
OPERATION
Jumper settings
The Standard box and the different User interfaces
must be configured in the correct way otherwise the
system will not function.
Fig.14
20 2000-12-20
SPACE 3000, Service Manual 2.3 Components
C 19
C 13 C 11 C9
C 12 C 10 C8 C 15
C 20 C 14 C 21 C 22
C5
C4
C3
C2
C1
C0
C 17 C 6 C7
B
C 18
1070-332
Fig.15
2000-12-20 21
SPACE 3000, Service Manual 2.3 Components
NOTE!
For information and settings, see section
Connecting accessories 6.1.
Spool sensor
(Fig. 17)
The spool sensors give information of the position of
the spools. There are two different spool sensors, one
for two spools and one for four spools. The sensors are
fitted directly on the valves. -342
1070
NOTE!
For information and settings, see section
Settings 6.2. Fig.17
22 2000-12-20
SPACE 3000, Service Manual 2.3 Components
Winch box
Function
The winch can be positioned on the loader body, inner
boom, outer boom, outer end of the crane, jib or the
outer end of the jib. OLP-logic is dependent on where
the winch is positioned.
The winch can have four indicators connected to a
special Winch box (Fig. 18) according to:
NOTE!
These plugs are different from the plugs in
the Column box.
Fig. 18
2000-12-20 23
SPACE 3000, Service Manual 2.3 Components
Logic operation
The 2-tonne winch has a torque indicator, WLOAD (1)
and a switch for three turns remaining WEND (2) as
standard (Fig. 19).
Winches can also be equipped with a WTOP indicator
(hook near the boom) and a WDIS indicator (cable fully
wound in).
NOTE!
For information and settings, see section 6.1
Connecting accessories.
Plug
If you disconnect the winch and instead connect a tool
to the winchs valve function you must connect a plug
in the contact on the cable which runs between the
SPACE system and the winch box. This plug tells
SPACE that the winch is disconnected and that the
function should be regarded as a tool (Fig. 20).
Fig. 20
24 2000-12-20
SPACE 3000, Service Manual 2.3 Components
Connection plinths
(Fig. 21)
P1 To Column box
P1.1 Ground
P1.2 24 V
P1.3 Signal (4-20 mA, in steps) from winch
indicators
P2 - P5 From winch indicators
Px.1 Ground
Px.2 24 V
Px.3 Signal from winch indicator (0-24 V)
Fig. 21
2000-12-20 25
SPACE 3000, Service Manual 2.3 Components
26 2000-12-20
SPACE 3000, Service Manual 2.4 Terminal
2.4 Terminal
Contents
Handheld PC ................................................................................ 3
Equipment needed for HIAB terminal ................................. 4
New Users .............................................................. 4
HP95/200 Users ..................................................... 4
Things to be aware of when using a handheld PC ............. 5
Battery Power ......................................................... 5
Time Bug ................................................................ 5
Memory Cards ........................................................ 5
Installation of HIAB Windows CE terminal programs ......... 6
What is needed? ..................................................... 6
Installation ............................................................... 6
Windows CE terminal functions ................................................... 7
Login .................................................................................. 7
Main menu ......................................................................... 7
Init ...................................................................................... 7
Init System Overview .............................................. 8
Init Auto ................................................................... 8
Init Type .................................................................. 11
Init Levers .............................................................. 11
Calibrate ................................................................ 11
Variables .......................................................................... 12
Detailed ................................................................. 13
User Interface ....................................................... 13
Extended ............................................................... 14
Errors ............................................................................... 15
Error Counters ...................................................... 15
Parameters ...................................................................... 16
Change Par Value ................................................. 16
2000-12-20 1
SPACE 3000, Service Manual 2.4 Terminal
File ................................................................................... 16
Counters .......................................................................... 17
Service log ............................................................ 17
Reset Counters .................................................... 17
Dos terminal ............................................................................... 18
General ............................................................................ 18
Init Auto ................................................................. 18
Variable list ....................................................................... 22
Variables ..................................................................................... 22
OLP ................................................................................. 24
MSC ................................................................................. 24
Analogue inputs................................................................ 25
Levers .............................................................................. 25
Pressure sensors ............................................................ 26
Digital inputs .................................................................... 26
Stability ............................................................................. 28
Various ............................................................................. 28
Timers ........................................................................................ 29
Timer list .......................................................................... 29
Parameters ................................................................................ 30
Parameter list .................................................................. 30
OLP ................................................................................. 32
MSC ................................................................................. 33
Pressure sensors ............................................................ 33
Digital inputs .................................................................... 34
Stability ............................................................................. 35
Service ............................................................................. 36
Various ............................................................................. 37
2 2000-12-20
SPACE 3000, Service Manual 2.4 Terminal
HANDHELD PC
A Handheld PC is a small computer that has Windows
CE as its operating system.
2000-12-20 3
SPACE 3000, Service Manual 2.4 Terminal
Handheld System
Handheld PC. Currently we support only Hewlett
Packard HP 680/690. Do not buy anything else but
these computers, since the programs depend very
much on the hardware of the Handheld PC,
especially the processor.
HP95/200 Users
HIAB will continue to update the DOS programs to
work with the latest versions of Space boxes.
HP Interfaces 361 0888 and 367 3103 will remain as
spare parts.
4 2000-12-20
SPACE 3000, Service Manual 2.4 Terminal
Things to be aware of
when using a handheld PC
Battery Power
The Handheld PC does not get any power whatsoever
from the SPACE system, so it needs to have fully
charged batteries at all time.
The Handhelds have a feature that turns off the power
after between 15 minutes when on battery power. The
battery of a HP 690 lasts for 7-8 hours of continuous
use. If the battery is fully charged when starting a job
the battery power should not be a problem.
Time Bug
Currently there is a time bug in Windows CE, when the
date is asked for in the programs the returned date
from Windows CE is incorrect.
Symptom:
S3000 CE.exe will not start due to an illegal year.
Wrong year in the file headers from files saved using
the HIAB terminal programs.
Solution:
Chose a city within USA when selecting Home City,
this cures the time problem. But set the date and time
to your date and time.
Memory Cards
HIAB will not sell memory cards for Handheld
systems. This is because the programs come on a PC
Diskette.
Handheld systems support the RAM cards that were
used for HP 95/200. An even better and cheaper
memory card is CompactFlash cards which have a
much higher storage capacity than RAM cards.
It is a good idea to put a backup of the terminal
programs onto a CompactFlash card so you dont
need to reinstall the HIAB terminal programs if the
battery is completely drained. Do also remember to
take backups of Crane.dat and Crane.s3d.
2000-12-20 5
SPACE 3000, Service Manual 2.4 Terminal
Installation of HIAB
Windows CE terminal
programs
What is needed?
A PC with Windows 95 or later.
Installation
This installation assumes that the program to install is
Space CE. Use the same procedure for the other
terminal programs.
6 2000-12-20
SPACE 3000, Service Manual 2.4 Terminal
WINDOWS CE
TERMINAL FUNCTIONS
Login
(Fig. 3)
Type in your User ID and Password then
click on button OK.
(Fig. 4)
At the top is the program version of the
Space 3000, and the program serial
number.
Below that, there is the crane serial
number and further down we have the
Crane Type.
Top right is your Access level, and below
is your Display level.
From access level Service its possible
to chose diplay level Diagnostic. Fig. 4
Init
(Fig. 5)
Here are all the Init Menus:
System Overview, Auto, Type, Levers and
Prog SerNo.
Fig. 5
2000-12-20 7
SPACE 3000, Service Manual 2.4 Terminal
Sub menu 1
Slew Sector 1 and 2
(Fig. 7)
Here you set which slewing sectors are
present is the system. You can choose Automatic Parameter Initialization
Slew Sector 1 Slew Sector 2 Winch Ext In Indicator Manual Extension
from: Yes Yes
Sector Type: Sector Type: Cap (%) 50 75
- No Sector No No
Platf 1 Low OLP Pressure Settings (bar)
- OLP ADS Height Warn
IB +2% 265
- Stop Cap (%) 60 Cap (%) 60
Yes Yes
273
No No OB +1%
- Platf 0 Low
1070-365
- Platf 1 Low Cancel OK
- Platf 2 Low
- Platf 2S Low
Fig. 7
No sector:
No slewing sector sensor is present in
system.
OLP:
Is used when the crane has a stability
sector.
Stop:
Stops the crane when entering the
slewing sector.
8 2000-12-20
SPACE 3000, Service Manual 2.4 Terminal
used for the Fixed Platform. Slew Sector 1 Slew Sector 2 Winch Ext In Indicator Manual Extension
Sector Type: Sector Type: Yes Yes Cap (%) 50 75
No No
Platf 1 Low OLP Pressure Settings (bar)
Platf 0 Low: ADS Height Warn
IB +2% 265
No tilt indicators for the Fixed Platform. Cap (%) 60 Cap (%) 60
Yes Yes
No No OB +1% 273
1070-365
Platf 1 Low: Cancel OK
Platf 2S Low:
Tilt indicators connected in series for the
Fixed Platform on both inner and outer
boom.
This setting is only used when both
platform indicators are connected to
plinth P3 in Column box.
Cap (%):
Only used if the sector is set as OLP,
and sets the capacity of the inner boom
pressure when crane is in the slew
sector.
Winch
(Fig. 7)
Yes & No. Tells SPACE 3000 if Winch is
mounted or not.
Ext In Indicator
(Fig. 7)
Yes & No. Tells SPACE 3000 if a
hydraulic extension in indicator is
mounted or not.
ADS
(Fig. 7)
Yes & No. Tells SPACE 3000 if ADS is
mounted or not.
2000-12-20 9
SPACE 3000, Service Manual 2.4 Terminal
Height Warn
(Fig. 7)
If the crane has a tilt indicator on the Automatic Parameter Initialization
Slew Sector 1 Slew Sector 2 Winch Ext In Indicator Manual Extension
inner boom this option will be set to Yes, Sector Type: Sector Type: Yes Yes Cap (%) 50 75
whether you have a Height Warning kit or Platf 1 Low OLP
No No
Pressure Settings (bar)
not. The program checks if the crane is ADS Height Warn
IB +2% 265
Yes Yes
equipped with an M-Link, which needs an Cap (%) 60 Cap (%) 60
OB +1% 273
No No
inner boom tilt indicator. Which means
1070-365
that if you have selected the correct Cancel OK
Manual Extension
(Fig. 7)
Sets the capacity when Manual
extension is selected on the User
Interface. The first value (should be the
lowest value) is used when the hydraulic
extensions are fully in or if no ext_in
sensor is connected and the second
value (higher) when the hydraulic
extensions are out.
10 2000-12-20
SPACE 3000, Service Manual 2.4 Terminal
Init Type
Sub menu 1
(Fig. 8)
Sets parameters for the selected crane
type. Click select to set the parameters.
Button File is only used if more than one
Crane.dat file is used
.
Fig. 8
Init Levers
Sub menu 1
(Fig. 9)
This menu can be used for three things;
Firstly to check if the calibration of the
levers was good or not. Move the lever on
the valve and see that the sliders on the
screen will move appropriately. Secondly
you can also see if the correct function is
connected to this lever, the name of the
function is above the slider. Third, see if
the correct functions are used for this Fig. 9
crane. The Terminal checks parameter
lev_ad_chan to see what functions are
used, and then only shows those func-
tions on the screen. To calibrate the
levers press button Calibrate.
Calibrate
Sub menu 2
(Fig. 10)
Follow the instructions on the screen
when calibrating the levers. To skip a
Tool lever press button Skip Lever. To
abort calibration press Back. You dont
have to press any key during calibration
just follow the commands on the screen.
As opposed from the DOS version where
you have to press Enter after every Fig. 10
command.
2000-12-20 11
SPACE 3000, Service Manual 2.4 Terminal
Variables
(Fig. 11)
This display is called the Summary display.
Here you can read off several variables simultaneously.
Here you can do a lot of troubleshooting by viewing the information from the variables.
Fig. 11
2 Pressure MPa Shows current working pressure in inner and outer boom in MPa (ib_p_mom and ob_p_mom).
% Shows current working pressure in inner and outer boom in % of maximum pressure (ib_p_filt
and ob_p_filt).
Lim Shows maximum permitted working pressure in inner and outer boom in %.
The value is normally 100 but can be higher if ADC and/or MSC is activated. If manual
extension or an OLP slewing sector indicator is activated the value is lower than 100.
(ib_olp_lim and ob_olp_lim).
3 Lev % Shows signals from spool sensors. Maximum is +/- 100 (lever).
4 Max + Shows maximum permitted spool stroke in % of full stroke for each function and
Max - direction. 0 means that the movement is stopped (max_speed_p and max_speed_n).
5 Tilt Shows signals from inner and outer boom tilt indicator.
up = up
down = down
? = not connected
(ib_tilt and ob_tilt)
12 2000-12-20
SPACE 3000, Service Manual 2.4 Terminal
6 Sect Sect shows one sector value if only one slewing sector is set for this crane, otherwise it will show
both sector values. (stab_sects)
7 Platform Platform is the indicators for the Fixed Platform. From the top of this box and down we have:
In or Out of the Fixed Platform slewing sector.
Inner boom Fixed Platform tilt indicator up or down.
Outer boom Fixed Platform titl indicator up or down.
On, if there is a person on the Fixed Platform, otherwise Off.
(stand_ib_low, stand_ob_low and stand_on)
Detailed
Sub menu 1
(Fig. 12)
Select variable class and then select
variable. The variable value will now be
shown in the variable value box.
Fig. 12
User Interface
Sub menu 1
(Fig. 13)
Translates the variable cov_stat file to
plain text. Here you can see the status
of the User Interfaces of the system.
Only the UIs that are connected are
shown. The status is shown with simple
Yes/No answers.
Fig. 13
2000-12-20 13
SPACE 3000, Service Manual 2.4 Terminal
Extended
Sub menu 1
(Fig. 14)
Translates the variable ext_stat file to
plain text. Here you can see the status
of the Space 3000 Extended box, if one
is connected to the system. The follow-
ing text strings can be shown:
- Input from Extended Slewing Sector
positive
- Input from Extended Slewing Sector
Fig. 14
negative
- Incoming Emergency Stop voltage OK
- Outgoing Emergency Stop voltage OK
- ADS output on
- Dump 2 connected
- MSC connected
- ADS connected
- Dump 2 output faulty
- MSC output faulty
- ADS output faulty
- The +24V fuse has tripped
- The lever 7 input: XX. Where XX is the
lever input value.
- The lever 8 input: XX. Where XX is the
lever input value.
- The On Platform input: XX. Where XX is
the On platform input value.
- The Extra Sensor input: XX. Where XX
is the Extra Sensor input value.
- ADS pressure 1 input byte: XX. Where
XX is the ADS input value.
- ADS pressure 2 input byte: XX. Where
XX is the ADS input value.
14 2000-12-20
SPACE 3000, Service Manual 2.4 Terminal
Errors
(Fig. 15)
Shows current Errors in Space. The
errors are continuously updated from
Space. Button Clear Errors is used to
tell Space to clear the errors manually. If
the error still persists then it is not
cleared, otherwise it is cleared. Most
errors are cleared when the reason for
the error disappears.
Button Error Count will take you to error Fig. 15
counters.
Error Counters
Sub menu 1
(Fig. 16)
Shows a count of all errors in this Space
box since it was produced. Press button
Reset to reset the right column of the
error counters. This can be used to
check what kind of errors that have
occurred since the last time the crane
was in a workshop.
Fig. 16
2000-12-20 15
SPACE 3000, Service Manual 2.4 Terminal
Parameters
(Fig. 17)
This is where you can check and set
parameter values. Select parameter
class and then a Parameter. When a
parameter is selected its value will be
shown in the Parameter Value box. To
change a parameter click button
Change Par Value or double click on
the parameter name.
Fig. 17
Fig. 18
File
(Fig. 19)
Load, loads a coded parameter file (.sav)
that was saved with the Save button.
Save As Text saves parameters,
counters, diary and error counters to a
file as text. This file can be opened later
with any text editor (Word, Notepad
etc.). Save As Code saves all data from
this Space box to a coded file. This file
cannot be viewed with a text editor. The Fig. 19
purpose of this coded file is to get a
complete picture of what this crane has
been doing and its settings. Can only be
viewed by certain personnel at HIAB.
16 2000-12-20
SPACE 3000, Service Manual 2.4 Terminal
Counters
(Fig. 20)
Shows counter and timer values. This
menu is continuously updated from
Space, so if a timer has a new value it is
automatically updated.
Fig. 20
Service log
Sub menu 1
(Fig. 21)
In access level Diagnostic it is possible
Timers and Counters
to view the Service log by clicking on
dump_time 23:31
Yes. lift_ctr 40
srvc_tot_time_left 1950:12
This question will not appear in access srvc_use_time_left 986:45
level Service. tot_time
use_time
56:52
14:23
Service
1070-367
Back
Fig. 21
Reset Counters
Sub menu 2
(Fig. 22)
Click on Yes to reset Service counters.
Timers and Counters
NOTE! dump_time 23:31
lift_ctr 40
For more information about srvc_tot_time_left 1950:12
srvc_use_time_left 986:45
timer and counter settings, see tot_time 56:52
section 5.1 Service. use_time 14:23
Service
1070-366
Back
Fig. 22
2000-12-20 17
SPACE 3000, Service Manual 2.4 Terminal
DOS TERMINAL
General
This section only describes the Init Auto menu in DOS.
The Init Auto menu is the menu that differs most from
Windows CE.
For more information about the DOS terminal and the
different menus, see SPACE service manual.
Init Auto
Sub menu 1
Navigation in menu:
%, & = Move between parameters.
ENTER = Change between values.
Slewing Sectors
(Fig. 23)
Here you set which slewing sectors that are
present in the system. It is possible to have
two slewing sectors.
You can choose from:
- NO
- OLP
- STOP
- PLATF0
- PLATF1
- PLATF2
- PLATF2S
Fig. 23
18 2000-12-20
SPACE 3000, Service Manual 2.4 Terminal
NO:
No slewing sector sensor is present in system.
OLP:
Is used when the crane has a stability sector. If OLP is
chosen the capacity (%) of the inner boom pressure
when crane is in the slewing sector should be set in
line below OLP.
STOP:
Stops the crane when entering the slewing sector.
PLATF0:
No tilt indicators for the Fixed Platform.
PLATF1:
One tilt indicator on the inner boom.
PLATF2:
Tilt indicators for the Fixed Platform on both inner and
outer boom. The indicators are not connected in
series.
PLATF2S:
Series connected tilt indicators for the Fixed Platform
on both inner and outer boom.
This setting is only used when both platform indicators
are connected to plinth P3 in Column box.
2000-12-20 19
SPACE 3000, Service Manual 2.4 Terminal
Winch
(Fig. 24) Fig. 24
YES & NO. Tells SPACE 3000 if a winch
is mounted or not.
ADS
(Fig. 24)
YES & NO. Tells SPACE 3000 if ADS is
mounted or not.
20 2000-12-20
SPACE 3000, Service Manual 2.4 Terminal
Fig. 25
Fig. 26
2000-12-20 21
SPACE 3000, Service Manual 2.4 Terminal
VARIABLES
S ?b_olp_lim These variables show the present OLP activating pressure for the inner or
OLP
D mm_active This variable shows in which Multi Mode the crane currently is.
D mm_off_?cnt These variables show how many lifts or how many seconds remain until
the Multi Mode returns to hook mode.
S anin These variables contain the raw data from the analogue inputs.
Analogue
D lever This variable shows the lever position [%]. Should correspond to the
amount of oil that flows trough the valve.
Pressures
S ?b_tilt These variables show the actual state of the inner or outer boom tilt
indicator (0 = down, 1 = up, -1 = not connected).
Digital inputs
D digin This variable shows the state of the eight voltage supervision signals.
S ext_in_inp This variable shows the actual state of the crane hydraulic extensions in
input.
(0 = extension in, 1 = extension out, -1 = not in use)
22 2000-12-20
SPACE 3000, Service Manual 2.4 Terminal
Display
S lo_load_inp This variable shows the actual state of the crane capacity reducing input
(0 = off, 1 = on, -1 = not connected).
S man_ext_sel This variable shows whether manual extensions are selected or not
(selected with the manual extension switch on the User Interface).
D stand_?b_low These variables show the actual state of the stand platforms inner or
outer boom too low indicator
(0 = low, 1 = high, -1 = not connected).
D stand_on This variable shows the actual state of the person on platform indicator
Digital inputs
D voltin This variable shows the state of the eight digital input pins.
S wdis This variable shows the actual state of the winch disabled signal
(0 = off, 1 = on, -1 = not connected).
S wend This variable shows the actual state of the winch 3 coils left indicator
(0 = off, 1 = on, -1 = not connected).
S wload This variable shows the actual state of the winch overload indicator
(0 = off, 1 = on, -1 = not connected).
S wtop This variable shows the actual state of the winch top position indicator
(0 = off, 1 = on, -1 = not connected).
S stab_? These variables show the current status of the slewing sector indicators
(negative and positive for three different sectors).
Stability
S stab_sect This variable shows the combined (worst case) status of the slewing
sectors.
D apo_ctr This variable shows the time (minutes) left to the Automatic Power Off.
Various
D max_speed_? These variables show the actual maximum permitted speed [%] for each
function in both directions (negative and positive).
2000-12-20 23
SPACE 3000, Service Manual 2.4 Terminal
OLP
ib_olp_lim display: S
ob_olp_lim
These variables show the present OLP activating pressure for the inner or outer boom (in % of
the working pressure ib_p_lim and ob_p_lim).
This value is normally 100, but changes according to MSC status, Multi -Mode, stability
conditions and so on.
olp_rel_w_ctr display: S
This variable shows the number of seconds that remains until the OLP release mode can be
activated again.
MSC
ib_msc_on display: D
ob_msc_on
These variables show if the MSC is active or not.
mm_active display: D
This variable shows in which Multi Mode the crane currently is.
The modes are:
0 Tool Mode (Basic capacity)
1 Hook Mode (mm_?b_olp_add[0] capacity used, typically +10%)
2 Winch Mode (mm_?b_olp_add[1] capacity used, typically +5%)
mm_off_lcnt display: D
mm_off_tcnt
These variables show how many lifts (mm_off_lcnt) or how many seconds (mm_off_tcnt)
remain until the Multi Mode returns to hook mode.
24 2000-12-20
SPACE 3000, Service Manual 2.4 Terminal
Analogue inputs
anin display: S
These variables contain the raw data from the analogue inputs.
A value of 0 corresponds to a input voltage of 0 V or a current of 0 mA.
The full scale value is 255 and corresponds to a input voltage of +5 V or current of 22.7 mA.
st_anin display: D
This is a special version of the analogue inputs variable. This variable contains all the
Standard Box physical analogue inputs (not even channel number related).
Levers
lever display: D
This variable shows the lever position [%]. Should correspond to the amount of oil that flows
through the valve.
2000-12-20 25
SPACE 3000, Service Manual 2.4 Terminal
Pressure sensors
ib_p_filt display: S
ob_p_filt
These variables show the filtrated relative pressure [%].
?b_p_mom display: S
This variable shows the actual momentan pressure in bars.
Digital inputs
ib_tilt display: S
ob_tilt
These variables show the actual state of the inner or outer boom tilt indicator
(0 = down, 1 = up, -1 = not connected).
digin display: D
This variable shows the state of the eight voltage supervision signals:
ext_in_inp display: S
This variable shows the actual state of the crane hydraulic extensions in input
(0 = extension in, 1 = extension out, -1 = not in use)
lo_load_inp display: S
This variable shows the actual state of the crane capacity reducing input
(0 = off, 1 = on, -1 = not connected).
man_ext_sel display: S
This variable shows whether manual extensions are selected or not (selected with the manual
extension switch on the User Interface).
If a Hydraulic extension in indicator is connected, this variable can also get the value 2 which
means that manual extension are selected, but the crane extensions are out (ext_in_inp = 0)
which means use the higher man_ext_load[1].
26 2000-12-20
SPACE 3000, Service Manual 2.4 Terminal
stand_ib_low display: D
stand_ob_low
These variables show the actual state of the stand platforms inner or outer boom too low
indicator
(0 = low, 1 = high, -1 = not connected).
stand_on display: D
This variable shows the actual state of the person on platform indicator
(0 = off, 1 = on, -1 = not connected).
voltin display: D
This variable shows the state of the eight digital input pins:
wdis display: S
This variable shows the actual state of the winch disabled signal
(0 = off, 1 = on, -1 = not connected).
(wdis is activated when the inputs for both wend and wtop are activated at the same time).
wend display: S
This variable shows the actual state of the winch 3 coils left indicator
(0 = off, 1 = on, -1 = not connected).
wload display: S
This variable shows the actual state of the winch overload indicator
(0 = off, 1 = on, -1 = not connected).
wtop display: S
This variable shows the actual state of the winch top position indicator
(0 = off, 1 = on, -1 = not connected).
2000-12-20 27
SPACE 3000, Service Manual 2.4 Terminal
Stability
stab_n display: S
stab_p
These variables show the current status of the slewing sector indicators (negative
and positive for three different sectors).
stab_sect display: S
This variable shows the combined (worst case) status of the slewing sectors. A zero
means that the crane is not in any sector. -1 means that the crane has entered a restricted
sector in the negative direction and +1 that the sector is entered in the positive direction. 2
means that the entering direction is unknown or that two conflicting sectors are active.
stab_sects display: S
This variable shows the status of the slewing sectors. A zero means that the crane is
out of the restricted sector. -1 means that the sector has been entered in the negative
direction and +1 that the sector is entered in the positive direction. 2 means that the entering
direction is unknown (indicator error or conflict with the valve position)
Various
apo_ctr display: D
This variable shows the time (minutes) left to the Automatic Power Off.
max_speed_n
max_speed_p display: D
These variables show the actual maximum permitted speed [%] for each function in both
directions (negative resp positive). These values reflects the status of the MSC, the different
OLPs and the LO_SPEED errors.
28 2000-12-20
SPACE 3000, Service Manual 2.4 Terminal
TIMERS
Timer list NOTE!
S=Service In this manual all timers are written in plain
D=Diagnostic style.
S dump_time This timer counts how many minutes the dump valve output has been on.
D ib_OLP_ctr These timers counts how many times an inner boom or outer boom OLP-
ob_OLP_ctr situation has occurred in the system.
D ib_prewarn_ctr This timer counts how many times the inner boom pre-warning pressure
level has been reached.
D lift_ctr This timer counts how many lifts have been done with the crane.
D man_ext_ctr This timer counts how many time the Manual Extension or lo_load logic
is activated.
D man_ext_time This timer counts how many minutes the crane has been used with
Manual Extensions selected at the User interface or with the lo_load_inp
active.
D OLP_rel_ctr This timer counts how many times the OLP release function has been
used.
S srvc_lifts_left This timer counts down how many lifts are left until the next service.
S srvc_tot_time_left This timer counts how many tot_time minutes are left until the next
service.
S srvc_use_time_left This timer counts how many use_time minutes are left until the next
service.
D stab_OLP_ctr This timer counts how many times an inner boom OLP situation has
occurred because of some slewing sector limitation.
S tot_time This timer counts how many minutes the power has been on to the
Standard box.
S use_time This timer counts how many minutes the crane has been used (lever not
centred and oil not dumped).
D wi_OLP_ctr This timer counts how many times the winch overload indicator (wload)
has been activated.
2000-12-20 29
30
Analogue inputs: Explaining the menu
C=channel P=plinths in SPACE box Ext=Extended box
A1 A2 A3 A4 A5 A6 A7 A8
C0 P1.3 C1 P1.4 C2 P1.5 C3 P1.6 C4 P2.3 C5 P2.4 C6 Ext-P5.3 C7 Ext-P5.4
spool sensor 1 spool sensor 2 spool sensor 3 spool sensor 4 spool sensor 5 spool sensor 6 spool sensor 7 spool sensor 8
Analogue inputs
B1 B2 B3 B4 B5 B6 B7 B8
C8 P5.8 C9 P5.7 C10 P5.6 C11 P5.5 C12 P5.4 C13 P5.3 C14 P6.3 C15 P6.4
Second tilt Winch indicators tilt tilt pressure pressure slewing sector 0 slewing sector 0
indicator (ib) indicator (ib) indicator (ob) sensor (ob) sensor (ib) positive indicator negative indicator
platform logic
C1 C2 C3 C4 C5 C6 C7 C8
C16 P5.9 C17 Ext-P4.3 C18 Ext-P10.3
hydraulic on platform extra sensor not currently not currently not currently not currently not currently
extension in indicator used used used used used
indicator
SPACE 3000, Service Manual
Note: On program versions 1.1---1.22 values may be displayed in boxes C4 and C6. Ignore these values they have no relevance to anin [19].
2000-12-20
2.4 Terminal
SPACE 3000, Service Manual 2.4 Terminal
2000-12-20 31
SPACE 3000, Service Manual 2.4 Terminal
PARAMETERS
Parameter list NOTE!
S=Service In this manual all parameters are written in
D=Diagnostic bold style.
Access
Display
D D mlink_mode This parameter sets if the crane has a mechanical link or not
S S olp_lim This parameter sets the default OLP limit pressure for inner and
outer boom OLP systems
S S prew_horn_on This parameter sets how many times the horn should beep
OLP
S S prew_horn_time This parameter sets how long the pre-warning horn beeps
should be.
S S stop_tool_?_load When the inner boom pressure (ib_p_filt) is higher than this
level, the positive direction of TOOL_1 or TOOL_2 is stopped
Digital inputs
D D ext_in_chan This parameter sets the channel number for the crane
extension in indicator
S S ib_tilt_chan This parameter sets the channel number for the inner boom tilt
indicator.
D D lo_load_inp_chan This parameter is a digital input with which the crane capacity
can be reduced.
32 2000-12-20
SPACE 3000, Service Manual 2.4 Terminal
Access
Display
Class Parameter name Description of parameters
D D lo_load_inp_load The inner boom capacity is limited to this value [%] when the
lo_load_inp_chan is set and the lo_load_inp variable is off.
Digital inputs
D D man_ext_load The inner boom capacity is limited to this value [%] when the
manual extension mode is selected on User interface.
D D stand_?b_low_chan These parameters set the channel number for the inner and
outer boom tilt indicators for the fixed platform.
D D stand_on_chan This parameter sets the channel number for the person on
platform indicator.
D D stab_?_chan These parameters set the channel number for the two slewing
sector indicators negative or positive side.
S S stab_olp This parameter sets the level (in %) to which the inner boom
OLP pressure limit will reduce when the slewing is inside an
Stability
D D stab_sect_type This parameter sets the type of the three different slewing
sectors.
S S apo_time This parameter sets the Automatic Power Off time in minutes.
Various
S S dump_time This parameter sets the number of seconds the dump valve
should remain active after all levers have been centred.
2000-12-20 33
SPACE 3000, Service Manual 2.4 Terminal
OLP
mlink_mode access: D display: D limits: 0..1 default:0
This parameter tells if the crane has a mechanical link (mlink_mode = 1) or not
(mlink_mode = 0).
Note that the ib_tilt_chan-parameter also has to be set for the mechanical link logics to
work. If ib_tilt_chan is set, but mlink_mode = 0, the ib_tilt signal is used for high inner
boom warning only.
Note! This parameter will always default to 100 % when the power is switched on.
34 2000-12-20
SPACE 3000, Service Manual 2.4 Terminal
MSC
msc_act_mode access: S display: S limits: 0..2 default: 1
This parameter describes how the MSC is activated:
0: Auto The MSC is automatically activated when the inner or outer boom
pressures reach the MSC limit. Levers that are deflected more than the
MSC limit, are hydraulically forced back to the MSC limit.
2: Zero-pos. The MSC is activated only when all levers are centred. This means that
when the crane load increases, you will first get an OLP at the crane
nominal capacity (100%). When you center the levers, the MSC will be
activated (also limiting the valve spool strokes) and the crane capacity will
increase with ??_msc_olp_add %.
Pressure sensors
ib_p_lim_corr
ob_p_lim_corr access: S display: S limits: -20..+3 default: 0
These parameters adjust the ib_p_lim or ob_p_lim values.
2000-12-20 35
SPACE 3000, Service Manual 2.4 Terminal
Digital inputs
ext_in_chan access: D display: D limits: -1..24 default: -1
This parameter sets the channel number (usually 19) for the crane hydraulic extension in
indicator (used to give a higher manual extension load when the crane extensions are out).
36 2000-12-20
SPACE 3000, Service Manual 2.4 Terminal
Stability
stab_n_chan access: D display: D limits: -1..24 default: -1, -1, -1
stab_p_chan
These parameters set the channel number for the two slewing sector indicators, negative
or positive side.
2000-12-20 37
SPACE 3000, Service Manual 2.4 Terminal
Service
srvc_lifts access: D display: D limits: 0..30000 default: 10000
This parameter sets the number of lifts (lift_ctr) in a service interval (Set 0 to disable the
function).
38 2000-12-20
SPACE 3000, Service Manual 2.4 Terminal
Various
ads_mode access: D display: D limits: 0..1 default: 0
This parameter activates the ADS system. A zero means that the crane does not have ADS
and 1 that the crane has ADS.
Note that the Extended box, the two ADS pressure sensors and a ADS valve also must be
present.
2000-12-20 39
SPACE 3000, Service Manual 2.4 Terminal
40 2000-12-20
SPACE 3000, Service Manual 3 Delivery settings
3 Delivery settings
Contents
2000-12-20 1
SPACE 3000, Service Manual 3 Delivery settings
2 2000-12-20
SPACE 3000, Service Manual 3 Delivery settings
CONNECTION OF A
24 V POWER SUPPLY
All new cranes are supplied with an 8-metre power
supply cable connected to the SPACE 3000 standard
box.
Connect this cable to a 15 A power output provided by
the truck manufacturer.
If the cable needs to be replaced with a longer cable
the minimum cable area is 2.25 mm.
CONNECTION OF A OIL
COOLER
2000-12-20 3
SPACE 3000, Service Manual 3 Delivery settings
INITIATION OF THE
SYSTEM
All the basic settings in SPACE 3000 are made at the
factory and no further adjustments are necessary.
NOTE!
If accessories have been fitted to the crane
during installation refer to section 6.1
Connecting accessories for connection and
setting details.
4 2000-12-20
SPACE 3000, Service Manual 3 Delivery settings
2000-12-20 5
SPACE 3000, Service Manual 3 Delivery settings
Windows CE terminal
1. Connect a HP Jornada terminal to
SPACE.
1070-382
50
remain set until SPACE is switched off.
When SPACE is switched on again the
Fig. 2
Olp_lim parameter will automatically
reset to 100 %.
6 2000-12-20
SPACE 3000, Service Manual 3 Delivery settings
DOS terminal
1. Connect a HP 95 terminal or a 200
model of Handheld PC to SPACE.
SPACE-3000 v1.20/Nov 20 2000/n:125
2. Type User Name and press ENTER.
Crane s/n: Default
Type Password, press ENTER and the
Crane Type: Default
Main menu is displayed. Customize parameters
Class: OLP
3. Press F3 - PARS from Main menu.
olp_horn_on olp_horn_time
4. Highlight OLP using the arrow keys olp_lim prew_horn_on
and press ENTER. prew_horn_time
1070-383
6. In the new value window type in 130
(Fig. 4).
Fig. 3
7. Press ENTER and then F10 - EXIT
twice to return to the Main menu.
1070-384
Fig. 4
2000-12-20 7
SPACE 3000, Service Manual 3 Delivery settings
8 2000-12-20
SPACE 3000, Service Manual 4.1 Troubleshooting methods
Contents
General......................................................................................... 3
Troubleshooting organization ............................................. 4
Reading out errors on Standard box ....................... 5
2000-12-20 1
SPACE 3000, Service Manual 4.1 Troubleshooting methods
2 2000-12-20
SPACE 3000, Service Manual 4.1 Troubleshooting methods
GENERAL
This section covers SPACE system troubleshooting. It
gives information how the troubleshooting is carried out
and what measures are to be taken before the crane is
returned to the customer.
1070-340
2000-12-20 3
SPACE 3000, Service Manual 4.1 Troubleshooting methods
Troubleshooting
5. Customer comes back and no
organization error code is stored in SPACE:
SPACE:
To determine in which of the systems the error lies: Select ERRS/Errors on main menu.
4. No error is found
Select COUNT/Error Count. Reset error counter in
right column by selecting RESET/Reset
RESET/Reset.
Ask the customer to come back if the error symptom
occurs again.
4 2000-12-20
SPACE 3000, Service Manual 4.1 Troubleshooting methods
2000-12-20 5
SPACE 3000, Service Manual 4.1 Troubleshooting methods
6 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
4.2 Troubleshooting
Contents
How to use troubleshooting .......................................................... 4
E0: Supply voltage to Standard box too low ................................. 6
E1: Voltage feed to sensors too low ............................................. 8
E2: Voltage feed to dump valve too low ...................................... 12
E3: Emergency button pushed in ............................................... 14
E4: Error in dump valve circuit ................................................... 18
E5: Error in emergency chain .................................................... 20
E6: Supply voltage to Column box too low ................................. 24
E7: Supply voltage to terminal too low ........................................ 36
E8: Supply voltage to CAN-bus too low ...................................... 38
E9: Voltage feed to horn too low ................................................. 44
E10: Extended box error ............................................................ 46
E11, E20, E27, E28, E29, E30: Internal error ............................. 50
E12, E13, E14, E15: Spool sensor signal too low or to high ...... 52
E16, E17: Spool sensor signal too low or too high ..................... 54
E18, E19: Spool sensor signal too low or too high ..................... 56
E20: Inner boom fixed platform angle indicator,
signal too low or too high .................................................... 58
E21: Winch box, signal too low or too high ................................ 62
E22: Inner boom tilt indicator, signal too low or too high ............. 66
E23: Outer boom tilt indicator, signal too low or too high............ 70
E23: Outer boom tilt indicator, signal too low or too high............ 72
E24: Outer boom pressure sensor, signal too low or too high ... 74
E25: Inner boom pressure sensor, signal too low or too high .... 78
E31: Slewing sector 1, faulty signal ........................................... 82
E32: Slewing sector 2, faulty signal ........................................... 84
E33: Slewing sector 3, faulty signal ........................................... 86
E34: Winch, indicator error ........................................................ 88
2000-12-20 1
SPACE 3000, Service Manual 4.2 Troubleshooting
2 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
2000-12-20 3
SPACE 3000, Service Manual 4.2 Troubleshooting
1
E3: Emergency button pushed in
2
Condition:
E3 is set when the Standard box records that there is no voltage on connection P7.6 in Standard box.
Error reasons: 3
- Stop button pushed in
- Emergency stop chain is broken or shorted to ground
- Defective User interface
- Contact resistance in connections
User interface 2
Voltage is below 15,0 V.
Disconnect wire/strapping from
Check and replace defective
2 P2.5
cable to User interface 1.
Test for min. 15,0 V between P2.5
Replace User interface 2 if no
and P2.6.
error is found
Connect wire/strapping to P2.5 10
4 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Description of troubleshooting
charts
1. Error code headline
Gives information about error code number, compo-
nent and signal status
2. Condition
Gives information under which conditions that
SPACE sets an error code.
3. Error reasons
Gives information about possible error reasons. The
most likely is placed first.
4. Rectangle
A rectangle gives information about what to check,
disconnect, measure etc.
6. Thick arrow
A thick arrow shows the flow if measuring values etc.
are correct in the square.
Some troubleshootings will be continued on next
page.
9. Thin arrow
A thin arrow shows the flow when an action has been
taken and the error is corrected.
10. H exagon
Hexagon
The hexagon is the end of the troubleshooting.
Check crane according to 6 Final check of crane in
section 4.1 Troubleshooting organization.
2000-12-20 5
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Vehicle battery voltage too low
- Contact resistance in connections or fuse holder
Standard box
Remove fuse. Voltage is below 16,0 V.
2 Test for min. 16,0 V in fuse holder Check fuse holder for oxidation
Replace fuse
Finish
6 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
1 2
P10.1
P10.2
2000-12-20 7
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Voltage wire to a sensor shorted to ground
- Defective spool sensor
- Defective indicator on control platform
- Defective slewing sector indicator
Standard box
Disconnect wire from P1.2. E2 is not active
1 Clear errors. Replace spool sensor no.
Check if E1 is still active. 1-4 (P1)
Connect wire to P1.2
Standard box
Disconnect wire from P2.2. E2 is not active
2 Clear errors Replace spool sensor no.
Check if E1 is still active. 5-6 (P2)
Connect wire to P2.2
8 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
1 2
P2.2
P1.2
2000-12-20 9
SPACE 3000, Service Manual 4.2 Troubleshooting
E1 is not active.
Standard box Disconnect control platform
Disconnect wire from P4.2. sensor.
3 Clear errors Clear errors.
Check if E1 is still active. Check if E1 is still active.
Connect wire to P4.2 Replace cable if E1 is active.
Replace sensor if E1 is not
active
E1 is not active.
Disconnect slewing sector indica-
Replace defective slewing
tors one by one from connection
sector sensor.
box.
4 Replace cable between
Clear errors before disconnecting
Standard box P6 and slewing
the next sensor.
sensors if E1 is still active
Check if E1 is active.
when all slewing sectors are
Connect cables to connecton box
disconnected
Finish
10 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
3 4
P4.2
2000-12-20 11
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Voltage wire to dump valve shorted to ground
- Contact resistance in connections
- Defective dump valve
E2 is not active.
Replace dump valve.
Finish
12 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
P 9.2
2000-12-20 13
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Stop button pushed in
- Emergency stop chain is broken or shorted to ground
- Defective User interface
- Contact resistance in connections
14 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
1 2
P2.6 P2.6
P2.5 P2.5
2000-12-20 15
SPACE 3000, Service Manual 4.2 Troubleshooting
Finish
16 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
3 4
P2.6 P7.6
P2.5
P7.5
2000-12-20 17
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Interruption in ground cable and/or voltage cable between Standard box and dump valve
- Defective dump valve
- Contact resistance in connections
- Dump valve relay in Standard box is jammed
Standard box
Disconnect wire from P9.2.
Measure resistance between the Resistance is incorrect.
2 wire and P9.1 Replace cable to dump valve
Should be 20-100 .
Connect wire to P9.2.
Finish
18 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
1 2
9.2
P9.1
2000-12-20 19
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Emergency stop chain is shorted to voltage
- Defective User interface
User interface 1
Push in the emergency stop. Voltage is above 1,0 V.
Disconnect wire from P2.6. Check and replace defective
1 Test for max. 1,0 V between P1.1 cable to Standard box.
and P1.6 Replace User interface 1 if no
Connect wire to P2.6. error is found
Pull out the emergency stop
User interface 2
Push in the emergency stop. Voltage is above 1,0 V.
Disconnect wire/strapping from Check and replace defective
2 P2.6 cable to User interface 1
Test for max. 1,0 V between P1.1 Replace User interface 2 if no
and P1.6. error is found
Connect wire/strapping to P2.6.
Pull out the emergency stop
20 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
1 2
P2.6 P1.6 P1.1 P2.6 P1.6 P1.1
2000-12-20 21
SPACE 3000, Service Manual 4.2 Troubleshooting
Finish
22 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
3 4
P2.6 P1.6 P1.1 P7.6
P7.5
2000-12-20 23
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Voltage cable to a boom sensor shorted to ground
- Defective pressure sensor
- Defective tilt indicator
- Defective winch sensor
- Defective hydraulic in indicator
- Defective fixed platform angle sensor
- Defective connection box
E6 is not active.
Column box Disconnect pressure sensor,
Disconnect wire from P4.1. inner boom.
2 Clear errors. Clear errors.
Check if E6 is still active. Check if E6 is still active.
Connect wire to P4.1 Replace cable if E6 is active.
Replace sensor if E6 is not
active
24 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
1 2
P1.2
P4.1
2000-12-20 25
SPACE 3000, Service Manual 4.2 Troubleshooting
E6 is not active.
Column box Disconnect pressure sensor,
Disconnect wire from P4.3. outer boom.
3 Clear errors Clear errors.
Check if E6 is still active. Check if E6 is still active.
Connect wire to P4.3 Replace cable if E6 is active.
Replace sensor if E6 is not
active
E6 is not active.
Column box Disconnect tilt indicator, outer
Disconnect wire from P4.5. boom.
4 Clear errors. Clear errors.
Check if E6 is still active. Check if E6 is still active.
Connect wire to P4.5 Replace cable if E6 is active.
Replace indicator if E6 is not
active
26 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
3 4
P4.3 P4.5
2000-12-20 27
SPACE 3000, Service Manual 4.2 Troubleshooting
E6 is not active.
Disconnect tilt indicator, inner
Column box
boom.
Disconnect wire from P4.7.
5 Clear errors.
Clear errors.
Check if E6 is still active.
Check if E6 is still active.
Replace cable if E6 is active.
Connect wire to P4.7
Replace tilt indicator if E6 is
not active
28 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
Location
5
P4.7
2000-12-20 29
SPACE 3000, Service Manual 4.2 Troubleshooting
E6 is not active.
Disconnect voltage supply
from P2.2 and winch indicators
one by one form P2.2, 3.2, 4.2
and 5.2 in winch box.
Clear errors before
disconnecting next indicator.
Check if E6 is still active.
E6 is not active.
Error cables to (Rotzler)
connection box, connection box or
indicator.
Troubleshoot according to
Crane Info 15.
E6 is still active.
Replace winch box
Finish
30 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
Location
P2.2
2000-12-20 31
SPACE 3000, Service Manual 4.2 Troubleshooting
E6 is not active.
Column box Disconnect outer boom fixed
Disconnect wire from P2.5. platform angle indicator.
7 Clear errors. Clear errors.
Check if E6 is still active. Check if E6 is still active.
Connect wire to P2.5 Replace cable if E6 is active.
Replace indicator if E6 is not
active
E6 is not active.
Disconnect inner boom fixed
Column box platform angle indicator.
Disconnect wire from P3.2. Clear errors.
8 Clear errors. Check if E6 is still active.
Check if E6 is still active. Replace cable if E6 is active.
Connect wire to P3.2 Replace indicator if E6 is not
active
32 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
Location
7 8
P3.2
P2.5
2000-12-20 33
SPACE 3000, Service Manual 4.2 Troubleshooting
E6 is not active.
Disconnect hydraulic extension
Column box
in indicator..
Disconnect wire from P3.5.
9 Clear errors.
Clear errors.
Check if E6 is still active.
Check if E6 is still active.
Replace cable if E6 is active.
Connect wire to P3.5
Replace indicator if E6 is not
active
Finish
34 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
Location
9
P3.5
2000-12-20 35
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Voltage cable to terminal shorted to ground
- Error in terminal/handheld computer, interface or in connection cables
E7 is active.
Disconnect terminal/handheld
Check that wires connected to
computer.
P3 are properly fixed and that
Switch system off and on again
there is no dirt in terminal
Check if E7 is still active by
connector.
looking at the display in standard
Replace cable if no error is
box
found
Connect terminal/handheld
computer. E7 is active.
Switch system off and on again Error is in terminal/handheld
Check if E7 is still active by computer, interface or in
looking at the display in standard connection cables.
box
Finish
36 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
2000-12-20 37
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Contact resistance in connections
- Defective CAN-cable.
- Defective User interface, Standard box or Extended box
Standard box
Disconnect wire from P7.3 and
1 P7.4. E8 is active.
Clear errors. Replace Standard box
Check if E8 is still active.
Connect wires to P7.3 and P7.4
User interface 1
Disconnect wire from P1.3 and
2 P1.4. E8 is active.
Clear errors. Replace cable to Standard box
Check if E8 is still active.
Connect wires to P1.3 and P1.4
User interface 1
Disconnect wire from P2.3 and
3 P2.4. E8 is active.
Clear errors. Replace User interface 1
Check if E8 is still active.
Connect wires to P2.3 and P2.4
38 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
1 2
P7.4 P1.4
P1.3
P7.3
3
P2.4
P2.3
2000-12-20 39
SPACE 3000, Service Manual 4.2 Troubleshooting
User interface 2
Disconnect wire from P1.3 and
E8 is active.
4 P1.4.
Replace cable to User interface
Clear errors.
1
Check if E8 is still active.
Connect wires to P1.3 and P1.4
User interface 2
Disconnect wire from P2.3 and
5 P2.4. E8 is active.
Clear errors. Replace User interface 2
Check if E8 is still active.
Connect wires to P2.3 and P2.4
40 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
4 5
P1.4 P2.4
P1.3 P2.3
6
P1.4
P1.3
2000-12-20 41
SPACE 3000, Service Manual 4.2 Troubleshooting
Finish
42 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
7 8
P2.4 P6.3
P2.3
P6.4
2000-12-20 43
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Voltage cable to horn shorted to ground
- Vehicle battery voltage too low
- Defective horn
E9 is not active.
Replace horn.
Disconnect horn.
2 Check if E9 is active.
E9 is active.
Check if P8.2 in Standard box is
Connect horn.
shorted to ground.
Replace cable to horn if no error
is found
Finish
44 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
1 2
P10.1 P8.2
P10.2
2000-12-20 45
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Wrong channel parameter settings (channel 6, 7, 17, 18, 23 or 24 is expected from Extended box)
- Interruption in CAN, voltage or ground wires between Extended box and User interface 2
- Contact resistance in connections
- Defective Extended box
Extended box
1 Check that wires connected to P6 Wires are not fixed.
are properly fixed Connect wires
User interface 2
2 Check that wires connected to P2
Wires are not fixed.
Connect wires
are properly fixed
46 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
1 2
P6
P2
2000-12-20 47
SPACE 3000, Service Manual 4.2 Troubleshooting
Finish
48 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
2000-12-20 49
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reason:
- Error in processor or programme
Finish
50 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
2000-12-20 51
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Interruption in signal, ground or voltage wire
- Signal or voltage wire shorted to ground
- Signal wire shorted to voltage
- Defective sensor
- Contact resistance in connections
Standard box
1 Check that wires connected to Wires are not fixed.
P1.1, 1.2, 1.3, 1.4, 1.5 and 1.6 are Connect wires
properly fixed
Finish
52 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
1
P1.6
P1.5
P1.4
P1.3
P1.2
P1.1
2000-12-20 53
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Interruption in signal, ground or voltage wire
- Signal or voltage wire shorted to ground
- Signal wire shorted to voltage
- Defective sensor
- Contact resistance in connections
Standard box
1 Check that wires connected to Wires are not fixed.
P2.1, 2.2, 2.3 and 2.4 are properly Connect wires
fixed
Finish
54 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
P2.4
P2.3
P2.2
P2.1
2000-12-20 55
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Interruption in signal, ground or voltage wire
- Signal or voltage wire shorted to ground
- Signal wire shorted to voltage
- Defective sensor
- Contact resistance in connections
Extended box
1 Check that wires connected to Wires are not fixed.
P5.1, 5.2, 5.3 and 5.4 are properly Connect wires
fixed
Finish
56 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
1
P5.2
P5.1 P5.4
P5.3
2000-12-20 57
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Interruption in signal or voltage wire
- Signal or voltage wire shorted to ground
- Signal wire shorted to voltage
- Defective indicator
- Contact resistance in connections
E6 is set.
Check if E6 is set Check voltage supply to Column
box according to E6
Column box
Disconnect wire from P3.2.
2 Test for min. 14,5 V between
Voltage is min. 14,5 V. Replace
cable to tilt indicator
P3.2 and P3.3.
Connect cable to P3.2
58 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
1 2
P3.3
P3.2
2000-12-20 59
SPACE 3000, Service Manual 4.2 Troubleshooting
Column box
Disconnect wire from P1.2.
3 Voltage is min. 14,5 V. Replace
Test for min. 14,5 V between
Column box
the wire and P1.8.
Connect wire to P1.2
Standard box
Disconnect wire from P5.2.
4 Test for min. 14,5 V between Voltage is min. 14,5 V. Replace
P5.2 and P5.8. cable to Column box
Connect wire to P5.2
Finish
60 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
3 4
P1.2
P5.2
P5.8
P1.8
2000-12-20 61
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Interruption in signal or voltage wire
- Signal or voltage wire shorted to ground
- Signal wire shorted to voltage
- Contact resistance in connections
E6 is set.
Check if E6 is set Check voltage supply to
Column box according to E6
Winch box
Disconnect wire from P1.2.
1 Test for min. 14,5 V between
Voltage is min. 14,5 V
V..
Replace winch box
the wire and P1.3.
Connect wire to P1.2
Column box
Disconnect wire from P2.2
2 Test for min. 14,5 V between
Voltage is min. 14,5 V.
Replace cable to winch box
P2.2 and 2.3.
Connect wire to P2.2
62 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
Location
1 2
1.2
P2.3
P2.2
P1.3
2000-12-20 63
SPACE 3000, Service Manual 4.2 Troubleshooting
Column box
Disconnect wire from P1.2.
3 Test for min. 14,5 V between Voltage is min. 14,5 V.
the wire and P1.7. Replace Column box
Connect wire to P1.2
Standard box
Disconnect wire from P5.2.
4 Test for min. 14,5 V between
Voltage is min. 14,5 V.
Replace cable to Column box
P5.2 and P5.7.
Connect wire to P5.2
Finish
64 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
Location
3 4
P5.2
1.2
P5.7
P1.7
2000-12-20 65
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Interruption in signal or voltage wire
- Signal or voltage wire shorted to ground
- Signal wire shorted to voltage
- Defective indicator
- Contact resistance in connections
E6 is set.
Check if E6 is set Check voltage supply to Column
box according to E6
Column box
Disconnect wire from P4.7.
2 Test for min. 14,5 V between
Voltage is min. 14,5 V. Replace
cable to tilt indicator
P4.7 and 4.8.
Connect wire to P4.7
66 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
1 2
P4.8
P4.7
2000-12-20 67
SPACE 3000, Service Manual 4.2 Troubleshooting
Column box
Disconnect cable from P1.2.
3 Test for min. 14,5 V between
Voltage is min. 14,5 V. Replace
Column box
the wire and P1.6.
Connect wire to P1.2
Standard box
Disconnect wire from P5.2.
4 Test for min. 14,5 V between Voltage is min. 14,5 V. Replace
P5.2 and P5.6. cable to Column box
Connect wire to P5.2
Finish
68 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
3 4
1.2
P5.2
P5.8
P1.8
2000-12-20 69
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Interruption in signal or voltage wire
- Signal or voltage wire shorted to ground
- Signal wire shorted to voltage
- Defective indicator
- Contact resistance in connections
E6 is set.
Check if E6 is set Check voltage supply to Column
box according to E6
Column box
Disconnect wire from P4.5.
2 Test for min. 14,5 V between Voltage is min. 14,5 V. Replace
P4.5 and P4.6. cable to tilt indicator
Connect wire to P4.5
70 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
1 2
P4.6
P4.5
2000-12-20 71
SPACE 3000, Service Manual 4.2 Troubleshooting
Column box
Disconnect wire from P1.2.
3 Test for min. 14,5 V between
Voltage is min. 14,5 V. Replace
Column box
the wire and P1.5.
Connect wire to P1.2
Standard box
Disconnect wire from P5.2.
4 Test for min. 14,5 V between Voltage is min. 14,5 V. Replace
P5.2 and P5.5. cable to Column box
Connect wire to P5.2
Finish
72 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
3 4
1.2
P5.2
P1.5
P5.5
2000-12-20 73
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Interruption in signal or voltage wire
- Signal or voltage wire shorted to ground
- Signal wire shorted to voltage
- Defective sensor
- Contact resistance in connections
E6 is set.
Check if E6 is set Check voltage supply to Column
box according to E6
Column box
Disconnect wire from P4.3.
2 Test for min. 14,5 V between
Voltage is min. 14,5 V. Replace
cable to pressure sensor
P4.3 and P4.4.
Connect wire to P4.3
74 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
1 2
P4.3
P4.4
2000-12-20 75
SPACE 3000, Service Manual 4.2 Troubleshooting
Column box
Disconnect wire from P1.2.
3 Test for min. 14,5 V between
Voltage is min. 14,5 V. Replace
Column box
the wire and P1.4.
Connect wire to P1.2
Standard box
Disconnect wire from P5.2.
4 Test for min. 14,5 V between Voltage is min. 14,5 V. Replace
P5.2 and P5.4. cable to Column box
Connect wire to P5.2
Finish
76 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
3 4
1.2
P5.2
P1.4
P5.4
2000-12-20 77
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Interruption in signal or voltage wire
- Signal or voltage wire shorted to ground
- Signal wire shorted to voltage
- Defective sensor
- Contact resistance in connections
E6 is set.
Check if E6 is set Check voltage supply to Column
box according to E6
Column box
Disconnect wire from P4.1.
2 Test for min. 14,5 V between
Voltage is min. 14,5 V. Replace
cable to pressure sensor
P4.1 and P4.2.
Connect wire to P4.1
78 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
1 2
P4.1
P4.2
2000-12-20 79
SPACE 3000, Service Manual 4.2 Troubleshooting
Column box
Disconnect wire from P1.2.
3 Test for min. 14,5 V between
Voltage is min. 14,5 V. Replace
Column box
the wire and P1.3.
Connect wire to P1.2
Standard box
Disconnect wire from P5.2.
4 Test for min. 14,5 V between
Voltage is min. 14,5 V. Replace
cable to Column box
P5.2 and P5.3.
Connect wire to P5.2
Finish
80 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
3 4
1.2
P5.2
P1.3
P5.3
2000-12-20 81
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Defective or loose sector plates
- Interruption in signal, ground or voltage wires to both slewing sensors
- Signal wires from slewing sensors shorted to each other
Standard box
1 Check that wires connected to Wires are not fixed.
P6.1, 6.2, 6.3 and 6.4 are properly Connect wires
fixed
Finish
82 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
P6.2 P6.4
P6.1 P6.3
2000-12-20 83
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Defective or loose sector plates
- Interruption in signal, ground or voltage wires to both slewing sensors
- Signal wires from slewing sensors shorted to each other
Standard box
1 Check that wires connected to Wires are not fixed.
P6.1, 6.2, 6.5 and 6.6 are properly Connect wires
fixed
Finish
84 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
P6.2 P6.6
P6.1 P6.5
2000-12-20 85
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Defective or loose sector plates
- Interruption in signal, ground or voltage wires to both slewing sensors
- Signal wires from slewing sensors shorted to each other
Extended box
Check that wires to slewing Wires are not fixed.
sensors are properly fixed Connect wires
Finish
86 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
2000-12-20 87
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Interruption in voltage or signal wire
- Defective indicator
- Contact resistance in connections
Winch box
2 Disconnect wire from P1.3 E34 is not active.
Check if E34 is still active Replace winch box
Connect wire to P1.3
Finish
88 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
Location
1 2
P1.3
P3.3 P4.3
2000-12-20 89
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Incorrect parameter values have been programmed
- Voltage was turned off during setting of parameters
- Parameters have not been initialised (e.g. new Standard box has been mounted)
- Defective Standard box
E35 is active.
Change current parameter if
message is Out of range.
Turn system off and on again.
E35 is active. Clear errors.
If message is Run system.
Checksum" the error may Replace Standard box if E35
appear if voltage to standard is still active
box is broken during setting of
a parameter.
Try again to initialise the same
parameters as when the error
occured
Finish
90 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
2000-12-20 91
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reason:
- Something is acting on the control levers
- Control levers stick and do not return to neutral
- Spool sensors incorrectly calibrated
Make sure that levers are correct Levers are correct adjusted.
adjusted, run smoothly and return Calibrate spool sensors
to neutral according to section Terminal
Finish
92 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
2000-12-20 93
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reason:
- Defective sensor
Finish
94 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
2000-12-20 95
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reason:
- Defective sensor
Finish
96 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
2000-12-20 97
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Vehicle battery voltage too low
- User interface 1 is incorrectly strapped
- Contact resistance in connections
- CAN or voltage wires between Standard box and User interface 1 are broken
- Wires to emergency stop on User interface 1 are incorrectly connected
- Defective User interface 1
E0 is set
Check if E0 is set Troubleshoot according to E0
98 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
2000-12-20 99
SPACE 3000, Service Manual 4.2 Troubleshooting
User interface 1
Disconnect P2.2
1 Wait min 15 sec. Voltage is below 12,0 V.
Test for min. 12,0 V between P1.1 Replace cable to Standard box
and P1.2
User interface 1
2 Test for min. 12,0 V between Voltage is below 12,0 V.
P2.1 and P2.2. Replace User interface 1
Connect P2.2
User interface 1
Push in emergency stop.
Disconnect wire from P2.5.
3 Test for max. 1,0 V between P2.1
Voltage is above 1,0 V.
Replace User interface 1
and P2.5
Connect wire to P2.5.
Pull out emergency stop
100 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
1 2
P1.2 P2.2
P2.1
P2.5
2000-12-20 101
SPACE 3000, Service Manual 4.2 Troubleshooting
Finish
102 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
2000-12-20 103
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Vehicle battery voltage too low
- User interface 2 is incorrectly strapped
- Contact resistance in connections
- CAN- or voltage wires between Standard box and User interface 2 is broken
- Wires to emergency stop on User interface 2 are incorrectly connected
- Defective User interface 2
E0 or E39 is set
Check if E0 or E39 is set Troubleshoot according to E0 or
E39.
rface 2.
Identify User interface Jumper B2 is not strapped.
Check if jumper B2 is strapped Strap jumper B2
104 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
2000-12-20 105
SPACE 3000, Service Manual 4.2 Troubleshooting
User interface 2
Disconnect P2.2 Voltage is below 12,0 V.
1 Wait min 15 sec. Replace cable to User interface
Test for min. 12,0 V between P1.1 1
and P1.2
User interface 2
2 Test for min. 12,0 V between Voltage is not min. 12,0 V.
P2.1 and P2.2. Replace User interface 2
Connect P2.2
User interface 2
Push in emergency stop.
Disconnect wire from P2.5.
3 Test for max. 1,0 V between P2.1 Voltage is above 1,0 V.
and P2.5 Replace User interface 2
Connect wire to P2.5.
Pull out emergency stop
106 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
1 2
P1.2 P2.2
P2.1
P2.5
2000-12-20 107
SPACE 3000, Service Manual 4.2 Troubleshooting
Finish
108 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
2000-12-20 109
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Vehicle battery voltage too low
- Standard box is incorrectly strapped
- User interface 3 is incorrectly strapped
- Contact resistance in connections
- CAN- or voltage wires between Standard box and User interface 3 are broken
- Wires to emergency stop on User interface 3 are incorrectly connected
- Defective User interface 3
110 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
2000-12-20 111
SPACE 3000, Service Manual 4.2 Troubleshooting
User interface 3
Disconnect P2.2 Voltage is below 12,0 V.
1 Wait min 15 sec. Replace cable to User interface
Test for min. 12,0 V between P1.1 2
and P1.2
User interface 3
2 Test for min. 12,0 V between Voltage is below 12,0 V.
P2.1 and P2.2. Replace User interface 3
Connect P2.2
User interface 3
Push in emergency stop.
Disconnect wire from P2.5.
3 Test for max. 1,0 V between P2.1
Voltage is above 1,0 V.
Replace User interface 3
and P2.5
Connect wire to P2.5.
Pull out emergency stop
112 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
1 2
P1.2 P2.2
P2.1
P2.5
2000-12-20 113
SPACE 3000, Service Manual 4.2 Troubleshooting
Finish
114 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
2000-12-20 115
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Vehicle battery voltage too low
- Standard box is incorrectly strapped
- User interface 4 is incorrectly strapped
- Contact resistance in connections
- CAN- or voltage wires between Standard box and User interface 4 are broken
- Wires to emergency stop on User interface 3 are incorrectly connected
- Defective User interface 4
116 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
2000-12-20 117
SPACE 3000, Service Manual 4.2 Troubleshooting
User interface 4
Disconnect P2.2 Voltage is below 12,0 V.
1 Wait min 15 sec. Replace cable to User interface
Test for min. 12,0 V between P1.1 3
and P1.2
User interface 4
2 Test for min. 12,0 V between Voltage is below 12,0 V.
P2.1 and P2.2. Replace User interface 4
Connect P2.2
User interface 4
Push in emergency stop.
Disconnect wire from P2.5.
3 Test for max. 1,0 V between P2.1
Voltage is above 1,0 V.
Replace User interface 4
and P2.5
Connect wire to P2.5.
Pull out emergency stop
118 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
1 2
P1.2 P2.2
P2.1
P2.5
2000-12-20 119
SPACE 3000, Service Manual 4.2 Troubleshooting
Finish
120 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
2000-12-20 121
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Wrong channel parameter setting
- Interruption in CAN, voltage or ground wires between Extended box and User interface 2
- Interruption in ground cable and/or voltage cable between Extended box and ADS valve
- Contact resistance in connections
- Defective ADS valve
E10 is set.
Check if E10 is set Check error in Extended box
according to E10
122 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
2000-12-20 123
SPACE 3000, Service Manual 4.2 Troubleshooting
Extended box
Disconnect wire from P1.2
2 Measure resistance between the Resistance is incorrect.
wire and P1.1 Replace ADS valve
Should be 20-100 .
Connect wire to P1.2
Finish
124 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
1.2
P1.1
2000-12-20 125
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Wrong channel parameter setting
- Interruption in CAN, voltage or ground wires between Extended box and User interface 2
- Interruption in signal or voltage wire
- Signal or voltage wire shorted to ground
- Signal wire shorted to voltage
- Contact resistance in connections
- Defective ADS pressure sensor 1
E10 is set.
Check if E10 is set Check error in Extended box
according to E10
126 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
2000-12-20 127
SPACE 3000, Service Manual 4.2 Troubleshooting
Extended box
Disconnect wire from P2.1.
2 Test for min. 14,5 V between
Voltage is min. 14,5 V. Replace
cable to pressure sensor 1
P2.1 and P2.2.
Connect wire to P2.1
Finish
128 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
P2.2
P2.1
2000-12-20 129
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Wrong channel parameter setting
- Interruption in CAN, voltage or ground wires between Extended box and User interface 2
- Interruption in signal or voltage wire
- Signal or voltage wire shorted to ground
- Signal wire shorted to voltage
- Contact resistance in connections
- Defective ADS pressure sensor 2
E10 is set.
Check if E10 is set Check error in Extended box
according to E10
130 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
2000-12-20 131
SPACE 3000, Service Manual 4.2 Troubleshooting
Extended box
Disconnect wire from P3.1.
2 Test for min. 14,5 V between
Voltage is min. 14,5 V. Replace
cable to pressure sensor 2
P3.1 and P3.2.
Connect wire to P3.1
Finish
132 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
P3.2
P3.1
2000-12-20 133
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Wrong channel parameter setting
- Interruption in CAN, voltage or ground wires between Extended box and User interface 2
- Interruption in ground cable and/or voltage cable between Extended box and MSC valve
- Contact resistance in connections
- Defective MSC valve
E10 is set.
Check if E10 is set Check error in Extended box
according to E10
134 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
2000-12-20 135
SPACE 3000, Service Manual 4.2 Troubleshooting
Extended box
Disconnect wire from P9.2.
Measure resistance between the Resistance is incorrect.
2 wire and P9.1 Replace cable to MSC valve
Should be 20-100 .
Connect wire to P9.2.
Finish
136 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
9.2 P9.1
2000-12-20 137
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Interruption in ground cable and/or voltage cable between Extended box and dump 2 valve
- Contact resistance in connections
- Defective dump 2 valve
Extended box
Disconnect wire from P8.2.
Measure resistance between the
2 wire and P8.1
Resistance is incorrect.
Replace cable to dump 2 valve
Should be 20-100 .
Connect wire to P8.2.
Finish
138 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Location
1 2
8.2 P8.1
2000-12-20 139
SPACE 3000, Service Manual 4.2 Troubleshooting
Error reasons:
- Vehicle battery voltage too low
- Contact resistance in connections or fuse holder
- Incorrect parameter values have been programmed
- Voltage was turned off during setting of parameters
- Parameters have not been initialized (e.g. new Standard box has been mounted)
- Defective Standard box
E0 or E35 is active
Check if E0 or E35 is active Troubleshoot according to E0 or
E35
140 2000-12-20
SPACE 3000, Service Manual 4.2 Troubleshooting
Terminal is connected.
Disconnect terminal.
Turn off system and start
again.
Clear errors.
Is terminal connected to standard
Check if E48 is still active.
box when E48 is active?
Replace Standard box if E48 is
active.
Finish
2000-12-20 141
SPACE 3000, Service Manual 4.2 Troubleshooting
E49: Service
Condition:
E49 is set when the Standard box records that one of the service counters (total time, use time or number of lifts)
is full.
Error reasons:
-
Finish
142 2000-12-20
SPACE 3000, Service Manual 4.4 Repairs
4.4 Repairs
Contents
2000-12-20 1
SPACE 3000, Service Manual 4.4 Repairs
2 2000-12-20
SPACE 3000, Service Manual 4.4 Repairs
REPLACING
STANDARD BOX
STANDARD
1. Unscrew the 4-socket head screws in the front of
the User interface. It is not necessary to completely
remove these screws they are designed to be
retained in the cover, only unscrew until no further
resistance is felt.
2000-12-20 3
SPACE 3000, Service Manual 4.4 Repairs
NOTE!
All Standard boxes are supplied as a spare
part with the Classic program, if you are
fitting to a Duo or Pro crane refer to section
6.2 for the setting procedure.
4 2000-12-20
SPACE 3000, Service Manual 4.4 Repairs
Settings, Windows
CE terminal
1. Connect a HP Jornada terminal to
SPACE.
Cancel OK
Fig. 3
2000-12-20 5
SPACE 3000, Service Manual 4.4 Repairs
6 2000-12-20
SPACE 3000, Service Manual 5.1 Service
5.1 Service
Contents
2000-12-20 1
SPACE 3000, Service Manual 5.1 Service
2 2000-12-20
SPACE 3000, Service Manual 5.1 Service
SERVICE
REQUIREMENTS
General checks
Check all cables for wear, damage, corrosion or
tightness
2000-12-20 3
SPACE 3000, Service Manual 5.1 Service
OLP check
Check the function of OLP by moving the first and
second boom cylinders to end position.
Stickers / manuals
Check that Operators manual and Service manuals
are with truck.
Functional test
Check:
- operation of all User interface buttons and warning
LEDs
- crane movements to/from folded/unfolded position
and end positions
4 2000-12-20
SPACE 3000, Service Manual 5.1 Service
Resetting counters,
Windows CE terminal
After completing all service operations as
per the HIAB service documentation, it is
necessary to reset the counters in
SPACE 3000.
1070-366
Back
Fig. 1
2000-12-20 5
SPACE 3000, Service Manual 5.1 Service
Resetting counters,
DOS terminal
After completing all service operations as per the HIAB
service documentation, it is necessary to reset the
counters in SPACE 3000.
6. Disconnect terminal.
6 2000-12-20
SPACE 3000, Service Manual 6.1 Connecting accessories
Contents
2000-10-31 1
SPACE 3000, Service Manual 6.1 Connecting accessories
2 2000-10-31
SPACE 3000, Service Manual 6.1 Connecting accessories
CONNECTING A WINCH
General
NOTE! 2. Make the wiring connections as shown in the
connection diagram (Fig. 1).
The following instructions relate only to the
electrical connections and adjustments to NOTE!
SP ACE 3000 that are required when
SPACE Wire B (red) and E (brown) are not used and
connecting a winch. For all other must be isolated.
information you must refer to Crane Info 15
or the relevant winch manufacturers
NOTE!
installation instructions.
The diagram shows the connections to the
winch box for the Rotzler Picargo winches.
1. As with previous SPACE systems you must mount Reference must be made to the relevant
a HIAB winch box on the crane. manufacturers instructions for any other
make of winch.
Fig. 1
2000-10-31 3
SPACE 3000, Service Manual 6.1 Connecting accessories
Settings, Windows
CE terminal
1. Connect a HP Jornada terminal to Automatic Parameter Initialization
SPACE. Slew Sector 1 Slew Sector 2 Winch Ext In Indicator Manual Extension
Sector Type: Sector Type: Yes Yes Cap (%) 50 75
No No
2. Type User Name and Password, click Platf 1 Low OLP Pressure Settings (bar)
ADS Height Warn
on OK and the Main menu is Yes Yes
IB +2% 265
Cap (%) 60 Cap (%) 60
displayed. No No OB +1% 273
1070-365
Cancel OK
3. Select Init from Main menu.
1070-369
parameters and channel. Cancel OK
8. Select Levers.
Fig. 5
4 2000-10-31
SPACE 3000, Service Manual 6.1 Connecting accessories
2000-10-31 5
SPACE 3000, Service Manual 6.1 Connecting accessories
CONNECTING A FIXED
PLATFORM
NOTE!
These instructions do not include mounting
details for the mechanical components of a
fixed platform.
Description
When a crane is fitted with a fixed platform, it is
necessary to stop crane operation when there is a
possibility the operator may be struck by the boom
assembly.
To facilitate this HIAB have introduced logic into
SPACE 3000 system that will not permit the crane to
operate in the area over the platform.
6 2000-10-31
SPACE 3000, Service Manual 6.1 Connecting accessories
2000-10-31 7
SPACE 3000, Service Manual 6.1 Connecting accessories
Connection of indicators to
Column box
The inner and outer boom indicators should be con-
nected to the Column box.
Connection if no hydraulic
extension in indicator is
present
If no hydraulic extension in indicator is mounted, the
fixed platform indicators should be connected to the
Column box as shown in fig. 6, which is the most P3
common connection. 65 321
Plinth Description 1
6
P2.4-6 Outer boom fixed platform angle 5
indicator P4 4 P2
P2.4 Ground (brown)
P2.5 24 V (red)
1
P2.6 Signal (orange, 0/24 V)
NOTE!
1070-374
Fig. 6
8 2000-10-31
SPACE 3000, Service Manual 6.1 Connecting accessories
Connection if a hydraulic
extension in indicator is
present
If a hydraulic extension in indicator is mounted, the
fixed platform indicators should be connected to the
Column box as shown in fig. 7.
The hydraulic extension in indicator has to be
connected to plinth P2.4-6.
If an outer boom angle indicator is used it has to be
connected to P3.4-6 instead.
Plinth Description P3
654321
P2.4-6 Hydraulic extension in indicator
boom indicator.
Fig. 7
2000-10-31 9
SPACE 3000, Service Manual 6.1 Connecting accessories
Connection of indicators to
Standard box
(Fig. 8)
The On platform indicator and slewing sector indicators
should to be connected to the Standard box.
NOTE!
Only connections for On platform indicator
and slewing sector indicators used for fixed
platform are illustrated. All other compo-
nent connections have been removed for
clarity.
NOTE!
Ensure that there is a jumper placed in the
User interface 3 between plinth P2.5 and
P2.6.
1 2 3
8 7 4
6
1070-373
1. User interface 2
2. User interface 1
3. User interface 3
4. Empty box (placed on platform)
5. Slewing sector indicators
6. On platform indicator
7. Standard box
8. Extended box or Empty box (placed on tank side)
Fig. 8
10 2000-10-31
SPACE 3000, Service Manual 6.1 Connecting accessories
Plinth Description
(Fig. 9)
P4 On platform indicator
P4.1 Ground (brown)
P4.2 24 V (red)
P4.3 Signal (orange, 0/24 V)
1070-378
positive (orange, 0/24 V)
P6.4 Signal from indicator 1,
negative (orange, 0/24 V)
Fig. 9
2000-10-31 11
SPACE 3000, Service Manual 6.1 Connecting accessories
NOTE!
Never fit just the outer boom indicator on
its own, it must be fitted together with an
inner boom indicator.
Platf 0
Platf 1
Platf 2
Platf 2S
12 2000-10-31
SPACE 3000, Service Manual 6.1 Connecting accessories
1070-365
Cancel OK
system.
Platf 2 Low:
Tilt indicators fitted to both inner and
outer booms with the inner boom
indicator connected to plinth P3 and
outer boom indicator connected to plinth
P2.
Platf 2S Low:
Tilt indicators fitted to both inner and
outer boom and both connected to plinth
P3 in the column box.
1070-369
8. Click on Back twice. Cancel OK
9. Disconnect terminal.
Fig. 11
10. Carry out function test of fixed
platform functions. Make any final
adjustments to boom angle indicator
settings that may be required.
2000-10-31 13
SPACE 3000, Service Manual 6.1 Connecting accessories
PLATF0:
No tilt indicators fitted to the boom system.
PLATF1:
One tilt Indicator fitted on the inner boom.
PLATF2S:
Tilt indicators fitted to both inner and outer boom and
both connected to plinth P3 in the Column box.
PLATF2:
Tilt indicators fitted to both inner and outer booms with
the inner boom indicator connected to plinth P3 and
outer boom indicator connected to plinth P2.
14 2000-10-31
SPACE 3000, Service Manual 6.1 Connecting accessories
9. Disconnect terminal.
2000-10-31 15
SPACE 3000, Service Manual 6.1 Connecting accessories
CONNECTING ADS
General
NOTE! NOTE!
Refer to separate instruction sheet for The illustration shows only basic
installation of hydraulic components. connection details for ADS, all other
component connections have been
To install ADS it is necessary (if not already installed) removed for clarity.
to fit an Extended box to the SPACE 3000 system.
Remove existing Empty box from User interface 2 NOTE!
position and mount Extended box. Mount all compo-
When replacing an Empty box with
nents in the ADS kit of parts using separate instruc-
Extended box, ensure that there is a jumper
tions supplied with kit. Make wiring connections as
placed in the Extended box between plinth
shown in Fig.12.
P7.5 and P7.6.
1 2
6 3
1070-376
5 4
1. User interface 2
2. User interface 1
3. Standard box
4. Pressure sensor ADS
5. Valve ADS
6. Extended box
Fig. 12
16 2000-10-31
SPACE 3000, Service Manual 6.1 Connecting accessories
Settings, Windows
CE terminal
1. Connect a suitable terminal to SPACE
and enter the main menu.
1070-365
Cancel OK
1070-369
function. Cancel OK
NOTE!
Fig. 14
If you wish to confirm that an
item is recognised by SPACE,
select System Overview from
the Parameter Initilization
menu and view the item status
in this window.
2000-10-31 17
SPACE 3000, Service Manual 6.1 Connecting accessories
8. Disconnect terminal.
18 2000-10-31
SPACE 3000, Service Manual 6.1 Connecting accessories
CONNECTING A
HYDRAULIC
EXTENSION IN
INDICATOR
Description
The hydraulic extension in indicator makes it possible
to control the lifting capacity of a crane when using
manual extensions. By using a signal from a suitable
indicator mounted approximately at the centre position
along the length of the outer boom, SPACE 3000
reduces the inner boom lifting capacity to pre-set limits
depending on the position of the hydraulic extension.
The logic for this facility is activated when the manual
extension button is pressed on the User interface.
NOTE!
HIAB do not supply any indicator kit for this
function.
2000-10-31 19
SPACE 3000, Service Manual 6.1 Connecting accessories
Connection of indicator to
Column box
A normally open type proximity switch must be used
as the indicator for this function.
It should be connected to plinth P2.4-6 in Column box
as shown in fig. 15.
P3
NOTE! 1
If the crane is fitted with a fixed platform
with angle indicators on the inner and outer
booms, refer to Connecting fixed platform
in this section before proceeding with 1
connection. 6
5
P4 4 P2
Plinth Description 1
Fig. 15 1070-377
20 2000-10-31
SPACE 3000, Service Manual 6.1 Connecting accessories
Settings, Windows
CE terminal
1. Connect a HP Jornada terminal to
SPACE.
Indicator and click on OK (Fig. 16). Slew Sector 1 Slew Sector 2 Winch Ext In Indicator Manual Extension
Sector Type: Sector Type: Yes Yes Cap (%) 50 75
No No
6. In Manual Extension box enter the Platf 1 Low OLP Pressure Settings (bar)
ADS Height Warn
figure that you want to reduce the Yes Yes
IB +2% 265
Cap (%) 60 Cap (%) 60
crane capacity by in percentage in No No OB +1% 273
1070-365
Cancel OK
NOTE!
The figure entered in the left- Fig. 16
hand box must always be
lower than the figure in the
right-hand box. The default
figures of 50% and 75% are
recommended.
Ready OK
7. A message window The parameters
Automatic Parameter Initialization
were successfully set! will be Slew Sector 1 ! The
Slew Sector 2 parameters
Winch were successfully set
Ext In Indicator Manual Extension
displayed (Fig 17). Sector Type: Sector Type: Yes Yes Cap (%) 50 75
No No
Click on OK and SPACE 3000 will Platf 1 Low OLP Pressure Settings (bar)
ADS Height Warn
automatically set the required Yes Yes
IB +2% 265
Cap (%) 60 Cap (%) 60
parameters and channel No No OB +1% 273
1070-369
Cancel OK
8. Click on Back twice.
2000-10-31 21
SPACE 3000, Service Manual 6.1 Connecting accessories
9. Disconnect terminal.
22 2000-10-31
SPACE 3000, Service Manual 6.2 Settings
6.2 Settings
Contents
2000-12-20 1
SPACE 3000, Service Manual 6.2 Settings
2 2000-12-20
SPACE 3000, Service Manual 6.2 Settings
SETTINGS
INTRODUCTION
We understand that not all service engineers work with
our products everyday, and this can make it difficult to
remember exactly which display to use or which
button to press when presented with a specific task,
when using one of the terminal units that are available.
With the introduction also of the new Windows CE
based programs the choices and options have
increased.
Operating systems
Desktop and laptop PC's in conjunction with the PC
interface use the DOS based program.
HP 95 and 200 handheld PC's use the DOS based
programs.
HP 680/690 and 720 handheld PC's use the Windows
CE based program.
2000-12-20 3
SPACE 3000, Service Manual 6.2 Settings
Conventions used
(Fig. 1) Throughout the instructions you
will find different types of text used, the
meanings are listed below, please take a
few minutes to read these it will help you
to understand the instructions more
clearly.
1070-372
Change Par Value
command button quickly.
Where the instructions tell you to 3 2
check an option button, simply touch Fig. 1
the screen with your pointer on the
button the centre will turn Black or
White depending on its status. Option
buttons with a black dot mean that the
function described at the side of the
button is selected.
4 2000-12-20
SPACE 3000, Service Manual 6.2 Settings
SETTING ADC
FUNCTION
When a new SPACE 3000 Standard box
is supplied as a spare part, only the
Classic crane program is present. If you
have a DUO or PRO crane, you must
enable the logic in SPACE. To carry out
this operation it is necessary for your
service responsible to obtain a special
password from product support
department at HIAB AB.
Windows CE
terminal
1. Connect a HP Jornada terminal to
SPACE.
2000-12-20 5
SPACE 3000, Service Manual 6.2 Settings
5. Disconnect terminal.
6 2000-12-20
SPACE 3000, Service Manual 6.2 Settings
DOS terminal
1. Connect a HP 95 terminal or a 200 model of
Handheld PC to SPACE.
2000-12-20 7
SPACE 3000, Service Manual 6.2 Settings
SETTING MSC
FUNCTION
When a new SPACE 3000 Standard box
is supplied as a spare part, only the
Classic crane program is present. If you
have a crane fitted with the MSC function,
you must enable the logic in SPACE. To
carry out this operation it is necessary for
your service responsible to obtain a
special password from product support at
HIAB AB.
Windows CE
terminal
1. Connect a HP Jornada terminal to
SPACE.
8 2000-12-20
SPACE 3000, Service Manual 6.2 Settings
2000-12-20 9
SPACE 3000, Service Manual 6.2 Settings
DOS terminal
1. Connect a HP 95 terminal or a 200 model of
Handheld PC to SPACE.
10 2000-12-20
SPACE 3000, Service Manual 6.3 Special applications (PLC)
Contents
2000-10-31 1