Sei sulla pagina 1di 3

NALCOOL 2000

Analytical Procedure AP-62


Test Kit 420-C0145.88

SPECIFICATIONS
Method: Titration (Drop Count)
Testing Time: 5 minutes

DESCRIPTION
The NALCOOL 2000 Test Kit, 420-C0145.88, is
designed to be a quick, easy method for determin-
ing concentration of NALCOOL 2000 in diesel
cooling water. It is a very simple test requiring no
formal analytical training or experience, and can be
run by any operator.
The number of drops or milliliters of the titrant NALCOOL 2000 Test Kit
needed to reach the end point will directly indicate
the amount of NALCOOL 2000 present and the
amount to be added. Description Part No.
Drop count tube, glass, 7.72 mL 500-P0203.88*
ORDERING INFORMATION Bottle, plastic, 1 oz. (labeled as
Order as Test Kit 420-C0145.88. Order all replace- 460-S0620.73) 500-P0351.88*
Dropper bottle with (500-P2120.88)
ment parts and reagents by their part numbers.
pipet, plastic, 2 oz. (labeled as 500-P0347.88*
To be sure this product is compatible with your
460-S0621.74)
treatment program, contact your local Nalco
Carrying case 500-P0631.88*
representative. Items marked with an *
Dropper pipet assembly,
are included with the kit or set. To place your
0.51.0 mL only 500-P2120.88
order, please contact your local customer service
department.
SAFETY PRECAUTIONS
REPLACEMENT PARTS AND REAGENTS Refer to Material Safety Data Sheet (MSDS) for
specific reagent personal safety and disposal
Replacement Reagents
information.
Description Size Part No.
NALCOOL 2000-1 8 oz./237 mL 460-S0620.73* SUPPORT
NALCOOL 2000-2 16 oz./473 mL 460-S0621.74*
If you have any questions regarding this procedure,
please contact your Nalco representative. In North
America you can also contact the Nalco Equipment
Solutions Help Desk at 1-800-323-8483.
NALCOOL 2000 TEST KIT PROCEDURE

1 2 3 4
Add diesel cooling water to Add three drops of Mix gently by shaking. A Add 1 drop of NALCOOL
etched mark on the test tube. NALCOOL 2000-1 blue-green color will 2000-2 (460-S0621.74).
(460-S0620.73). develop.

5 6 7
Mix gently by shaking. If antifreeze is present, If antifreeze is not present,
continue to add NALCOOL add the NALCOOL 2000-2
2000-2 (460-S0621.74), (460-S0621.74), one drop at
0.5 mL at a time, shaking a time shaking gently after
gently after each addition, each addition, until the blue-
until the blue-green color green color disappears and
disappears and the solution the solution becomes
becomes salmon-orange. salmon-orange.
Refer to Tables 1 and 2 to
obtain the number of pints of
NALCOOL 2000 to be added
per 8 gallons of cooling
system capacity.
Table 1 NALCOOL 2000 dosage level for systems without antifreeze

Pints of NALCOOL 2000


Drops of Level of to be added per 8 gallons
460-S0621.74 treatment of system capacity
13 Danger 2
47 Danger 1
810 Borderline 1/2
1114 Good

Table 2 NALCOOL 2000 dosage level for systems with antifreeze (See Note)

Pints of NALCOOL 2000


Amount of Level of to be added per 8 gallons
460-S0621.74 (mL) treatment of system capacity
1.5 Danger 2
2.0 Borderline 1
2.5 Good

Note: Since the amount or type of antifreeze present will vary, more
accurate results may be obtained by making up a solution of the
antifreeze and water mixture being used and then adding enough
NALCOOL 2000 to make its concentration equal to 4 ounces per
gallon of solution. Then test the made-up sample using Step 6. The
reading you get will be the number you should use for a good level of
treatment reading.

NALCO COMPANY OPERATIONS


North America: 1601 West Diehl Road Naperville, Illinois 60563-1198 USA
Europe: Ir.G.Tjalmaweg 1 2342 BV Oegstgeest The Netherlands
Asia Pacific: 2 International Business Park #02-20 The Strategy Tower 2 Singapore 609930
Latin America: Av. das Naes Unidas 17.891 6 Andar 04795-100 So Paulo SP Brazil
www.nalco.com

NALCOOL, NALCO and the logo are Registered Trademarks of Nalco Company
1995, 2004 Nalco Company All Rights Reserved 7-04