Air System Design Load Summary for FF-AHU-03 with heat/humidifier

Project Name: DG Affairs- Office rev. 1 08/27/2011


Prepared by: abc 07:26AM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 49.2 C / 29.9 C HEATING OA DB / WB 12.0 C / 10.0 C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 30 m 4792 - 30 m - -
Wall Transmission 133 m 2256 - 133 m 713 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 30 m 2630 - 30 m 926 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 3 m 110 - 3 m 39 -
Floor Transmission 13 m 409 - 13 m 0 -
Partitions 406 m 10394 - 406 m 0 -
Ceiling 110 m 3470 - 110 m 0 -
Overhead Lighting 12829 W 11514 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 9200 W 8779 - 0 0 -
People 79 4983 4822 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 15% 7400 723 0% 0 0
>> Total Zone Loads - 56736 5546 - 1677 0
Zone Conditioning - 63358 5546 - -5451 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 4937 L/s 0 - 1024 L/s 0 -
Ventilation Load 968 L/s 30032 29616 201 L/s 1262 -415
Supply Fan Load 4937 L/s 2756 - 1024 L/s -944 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 1% 567 - 1% 17 -
>> Total System Loads - 96713 35162 - -5117 -415
Central Cooling Coil - 96713 35161 - -10521 -415
Central Heating Coil - 0 - - 5405 -
Humidification Load - - 0 - - 0
>> Total Conditioning - 96713 35161 - -5117 -415
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.3 Page 1 of 1