Sei sulla pagina 1di 8

745

Transformer Protection
Transformer
Protection System
High-speed, draw-out transformer
Key Benefits
protection and management
Easy to use Transformer Protection System supported Simplified testing - Built in simulation features for setpoint
by industry leading suite of software tools to optimize verification including waveform playback for relay setting
transformer performance and to extend life expectancy verification
Improved security for transformer energization using Cost effective access to information - Modbus and DNP 3.0
superior Adaptive 2nd Harmonic Restraint algorithm Level 2 protocols through embedded Ethernet, standard
Accurate built-in metering functions - Eliminates auxiliary RS232, RS485 & RS422 serial ports.
metering devices and reduces cost Globally accepted - Member of the most renowned product
Advanced automation capabilities using FlexLogic to provide family in the market.
customized protection and control solutions Extended life - Optional conformal coating for chemically
Fast, flexible and reliable communications - Embedded corrosive and humid environments
10BaseT Ethernet capability provides faster data transfer for Fast and easy troubleshooting, improved maintenance
improved system performance procedures and increased device security - Security Audit
Minimize replacement time - Draw-out construction ideal in Trail provides detailed traceability for system configuration
industrial environments changes
Reduce troubleshooting time and maintenance costs - IRIG-B
time synchronization, event reports, waveform capture, data
logger

Applications
Primary and back-up protection and management of small, Stand-alone or component in automated substation control
medium and larger power transformers, autotransformers system
and reactors
Transformer asset monitoring using Hottest Spot, Loss-of-
Life and Aging Factor

Features
Protection and Control Monitoring and Metering
Variable dual-slope percent differential protection Metering - current, voltage, sequence components per
winding, power, energy, voltage
Magnetizing inrush and overexcitation blocking
THD and harmonics up to the 21st
Phase & ground overcurrent elements
Event recording - 128 time tagged events
Adaptive time overcurrent using FlexCurves elements
Tap position up to 50 tap positions
Underfrequency/Overfrequency Protection
Ambient temperature /analog transducer input
Frequency rate-of-change Detection
Analog transducer input
Overexcitation (V/Hz) Protection
Oscillography & Data Logger - 10 records up to 32 power
Restricted Ground Fault Protection
cycles
Transformer overload protection
Simulation mode and playback capability.
Communications
EnerVista Software
Networking interfaces - 10Mbps Ethernet, RS232,
RS485 and RS422 ports Sophisticated software for configuration and
commissioning
Ethernet port, 10Mbps
Graphical Logic Designer and Logic Monitor to simplify
Multiple protocols - ModBus RTU, ModBus RTU designing and testing procedures
TCP/IP, DNP 3.0 Level 2

g
Document and software archiving toolset
EnerVista Integrator providing easy integration of data in
Digital Energy the 745 into new or existing monitoring and control systems
Multilin
171
745 Transformer Protection System

Protection and Control signal for better through fault stability


under CT saturation conditions.
The 745 Transformer Protection System is 745
1 745
Transformer Protection

FlexCurve
a full featured transformer protection relay, Harmonic Inrush /Overexcitation 1
FlexCurve

suitable for application on small, medium, Inhibit

TIME
and large power transformers. The 745
The 745 offers great performance in 2
can be applied on two-winding and three- 2 3
dealing with magnetizing current inrush,
winding transformers, and can be applied 3
on transformers with breaker-and-a- by providing three programmable restraint
CURRENT
half source terminals. Multiple current methods, each of which can be enabled or
814771A2.cdr

and voltage inputs are used to provide disabled by the user.


Unrestrained Differential
primary protection, control and back-up An increase in transformer voltage or
protection of transformers, including decrease in system frequency may result An unrestrained differential element
current differential, Restricted Ground in overexcitation of the transformer. It is current magnitude is provided for fast
Fault neutral, and ground overcurrent , often desirable to prevent operation of tripping on heavy internal faults to limit
over-fluxing, and on-load tap changer. The the percent differential element in these catastrophic damage to the transformer
745 also has specific features for industrial cases therefore a fifth harmonic inhibit and minimize risks to the remainder of the
environments, including a drawout case to is integrated into the percent differential power system.
limit downtime during maintenance and element to cater for overexcitation
conformal coating for harsh environments. conditions resulting from an increased
Overcurrent Elements
The 745 also includes analog inputs and V/Hz ratio. 745 can be used to provide back up
outputs, while incorporating advanced Harmonic inhibit allows the user to set protection for transformer and adjacent
features such as transformer loss of life power system equipment. Instantaneous
a harmonic restraint level of second
monitoring. overcurrent (IOC) elements can be used
or second plus fifth which, if enabled,
for fast clearing of severe internal and
remains active all the time
Percent differential protection external (through) faults. Time overcurrent
An independent fifth harmonic inhibit protection (TOC) elements per winding
The 745 features the equivalent of three
single-phase differential current relays. allows restraint for systems permitting allow to coordinate with the adjacent
Dual-slope percent differential with 2nd intentional overexcitation (overfluxing) protection zones and act as backup
or/and 5th harmonic restraints to protect during energization protection.
against maloperation due to magnetizing Energization inhibit allows the user to TOC protection functions are provided
inrush current during transformer define a temporary lower restraint level for phase, and ground currents.
energization and overexcitation. Each which will be automatically enabled A variety of standard time curves
differential element has programmable upon detection of transformer de- including IEEE, IEC, GE IAC, I2t, definite
dual-slope percentage restraint with energization or parallel transformer time are provided.
adjustable slope breakpoint. Maximum energization
winding current is used as a restraining FlexCurves to coordinate with adjacent
Each of the restraint methods features
protections (including fuses) as well
LOAD FLOW
user-defined harmonic averaging.
as transformer damage curves
V1 V3 CT 3
and thermal/damage curves for
CT 1
CT 2
Transformer Thermal
Damage Curve downstream equipment

I1 V2
I2 I3 Selected Relay Time
Overcurrent Curve
745
Percent ANSI Extremely Inverse
TIME

Differential Very Inverse


Element
Transformer Thermal Normally Inverse
Protection Margin
Differential vs. Restraint Characteristic (ld vs.lr) Moderately Inverse
Definite Time

Idifferential(x CT)
200% IEC (BS142) Curve A
Curve B
Curve C
CURRENT adap_oc.cdr Short Inverse
OPERATE SLOPE 2
REGION 100% IAC Extremely Inverse
100%
Overcurrent Pickup Setting Very Inverse
Inverse
- based on rated load capability.

SLOPE 1 RESTRAINT
50%
Short Inverse
1.00 25% Adjusted Overcurrent Pickup Setting
15% REGION
PICKUP 0.30
0.05 2.0 Irestraint(x CT)
- based on calculated load capability
due to Harmonic Factor. Custom FlexCurveTM A
KNEEPOINT FlexCurveTM B
745diff.cdr
FlexCurves to coordinate with adjacent protections FlexCurveTM C
The settings for the dual-slope, dual-breakpoint (including fuses) as well as transformer damage
curve provides higher flexibility for shaping up curves and thermal/damage curves for downstream Curve shapes - Typical application of 745 FlexCurves.
the characteristic and achieve better sensitivity equipment
and security.

172 www.GEDigitalEnergy.com
745 Transformer Protection System

Negative Sequence Overcurrent Loss-of-Life Multiple Settings Groups


For Delta/Wye impedance grounded This feature provides an estimate of how The four user defined setpoint groups

Transformer Protection
transformers, overcurrent protection is much of the transformers total insulation are available for different power system
particularly difficult to set . A negative life has elapsed (based on IEEE Standards configurations. Selection is done via
sequence based overcurrent element C57.91-1995, IEEE Guide for Loading the Logic (digital) inputs, front panel or
provides the required sensitivity phase Mineral-Oil-Immersed Transformers, communications port.
faults. Each winding is given its own and C57.96-1989, IEEE Guide for Load
element with the same programmable ing Dry-Type Distribution and Power
characteristics as the phase and neutral Trans- formers). Automation
TOC elements. The 745 incorporates advanced automation
Analog Outputs (Optional) features including powerful FlexLogic
Over / Under Frequency Protection Seven transducer output channels allow programmable logic, communication, and
The 745 calculates and maintains a running individually programm ed outputs for SCADA capabilities that far surpass what
average of the system frequency and the ranges of 0 to 1 mA, 0to5mA, 1 to 10 mA, is found in the average line relay. The 745
frequency rate-of-change (df/dt). Two 0 to 20 mA and 4to20 mA. Channels are integrates seamlessly with other relays for
underfrequency and four rate-of-change assignable to any measured parameter. complete system protection.
elements are provided to implement
traditional and advanced load shedding FlexLogic
schemes. Additionally, an overfrequency FlexLogic is the powerful programming
element can be used to trigger a generator logic engine that provides the ability of
rampdown. creating customized protection and control
schemes thereby minimizing the need,
Restricted Ground Fault and the associated costs, of auxiliary
Conventional overcurrent protection fails components and wiring. Using FlexLogic,
to provide adequate protection for star the 745 can be programmed to provide
connected windings whose neutral is required tripping logic along with custom
impedance earthed. Faults close to the scheme logic including interlocking dynamic
neutral do not generate adequate fault setting group changes.
Faults close to the neutral point of a wye-connected
current. RGF (also known as zero sequence winding does not generate adequate fault current
differential) provides sensitive ground for differential element to pick up. Restricted Ground
fault detection for low-magnitude fault Fault protection provides sensitive ground fault
detection for low-magnitude fault currents.
currents.

Functional Block Diagram


VOLTS WINDING 1 WINDING 2 3
(Lowest Voltage)
3 (Highest Voltage)
ANSI Device Numbers & Functions
3
Device
T.C.
Number Function
WINDING 3 50/67 Negative Sequence IOC
(Intermediate Voltage)
50/87 Instantaneous Differential
50G Ground IOC
VOLT 59 81 HERTZ TAP POSITION 50G1 50G2 51G AMPS 250/46 350/46
81 50N Neutral (3I0) IOC
50P Phase IOC
51/67 Negative Sequence TOC
RTD 1 150/46 251/46 351/46 51G Ground TOC
AMBIENT TEMP. 187TG 51N Neutral (3I0) TOC
Extract
51P Phase TOC
151/46 51N 250P1 350P1
dcmA 2nd & 5th Harmonic 59/81 Volts-Per-Hertz
ANALOG INPUT Block 81-H5 Fifth Harmonic Level
(0-20 mA) 81O Overfrequency
150P1 50N2
87 745 250P2 350P2
81U Underfrequency
Transformer Protection 81U-R Frequency Decay Rate
INSULATION System 87 Differential (Percentage)
AGING 150P2 50N1 50/87 251P 351P
87TG Ground Differential
- Aging Factor Limit
- Hottest - Spot Limit AD Current Demand
- Loss of Life Limit AMPS Calculate 3Io AMPS AN-1 Analog Input Level 1
151P THD & SPECTRUM &
AMPS AN-2 Analog Input Level 2
HARMONIC FACTOR
Insulation Aging
THD & SPECTRUM & Aging Factor Limit
AMPS
HARMONIC FACTOR Hottest-Spot Limit
THD & SPECTRUM & Loss of Life Limit
AMPS
HARMONIC FACTOR
Tap Changer Failure
THD Total Harmonic Distortion Level
814825A5.cdr

www.GEDigitalEnergy.com 173
745 Transformer Protection System

Output Relays Differential and restraint currents for all Tap Position, Ambient Temperature,
One high-speed solid state electronic
phases Analog TransducerInput
Transformer Protection

output can be activated by any protection Ground differential currents The 745 monitors and displays tap position
element through user-defined FlexLogic All current inputs feature harmonic level and ambient temperature. An optional
equations or directly assigned from a detectors. A sampling rate of 64 times general purpose transducer input allows a
protection element. Seven of the eight the power cycle allows recovery up to the user-defined quantity to be monitored and
electro-mechanical relay outputs can 21st harmonic. Total Harmonic Distortion used as part of the protection as defined
be activated by the protection elements (IEEE.519-1986) or Harmonic Derating by FlexLogic.
according to FlexLogic equations or Factor (as per ANSI/IEEE C57.110-1986) are
directly assigned from a protection calculated for each winding and compared Simulation Mode
element. One output is factory set as an against user-adjustable setpoints. Simulation Mode allows testing the
internal self-test failure alarm relay. Asset Monitoring functionality of the relay by simply feeding
745 can monitor, calculate and log hottest- arbitrary waveform data into the relays

Monitoring and Metering spot temperature, aging factor and lost of simulation buffer for playback as sampled
life data over a long period. These data current input signals.
The 745 features advanced metering combined with economic analysis, allows
functions including: criteria to be developed regarding the Fault Recording (Oscillography)
best time at which to replace a power System input signals are sampled at a
Currents
transformer due to load growth, i.e. to rate of 64 times the power cycle. Because
The 745 accurately measures the following minimize the cost without significantly all the signals are sampled at the same
currents: increasing the risk. instant in time the magnitude and phase
Phase A, B, C, residual (3I0) and ground relationship of each can be compared. A
currents Event Recording combination of 16 pre and post-trigger
Instantaneous and maximum current The last 128 events are captured and cycles can be saved.
demand on each phase of each stored, recording the time, date, cause,
winding The advanced disturbance (Data logger &
and system parameters of each event.
Positive, negative, and zero sequence This information is easily accessible by Waveform Capture) and event recording
currents and phase angles for all computer via communication port or the features within the 745 can significantly
windings
front panel display. reduce the time needed for postmortem
analysis of power system events and
creation of regulatory reports.

Power System Troubleshooting


The 745 contains many tools and reports that simplify and reduce the amount of time required for troubleshooting power system events.

Record the operation of the internal 745 elements and external connected devices
with 1ms time-stamped accuracy to identify the Sequence of Operation of station
devices during transformer faults and disturbances.
Analyze transformer faults using both analog and digital power system quantities
that are measured and recorded up to a rate of 12 samples per cycle.

174 www.GEDigitalEnergy.com
745 Transformer Protection System

Additional Features the relay. The front panel port allows for configuring and maintaining GE Multilin
easy local computer access. The rear products. The setup software within
The 745 offers additional features designed ports provide remote communications or Launchpad allows configuring devices in

Transformer Protection
for ease of use: connection to a DCS, SCADA, or PLC. The real-time by communicating using serial,
baud rate of all the ports is variable from Ethernet , or modem connections, or
Auto CT Configuration
300 to 19,200 bps. The optional Ethernet offline by creating setting files to be sent
All CTs are connected in a wye configuration port can be used to connect the 745 to 10 to devices at a later time.
for simplicity. All phase and magnitude Mbps Ethernet networks. The 745 supports
corrections as well as zero-sequence Included in Launchpad is a document
ModBus RTU, DNP3.0 Level 2, and ModBus
current compensation are performed archiving and management system
RTU TCP/IP protocols.
automatically based on a choice of over that ensures critical documentation is
100 transformer types. The three serial ports support ModBus up-to-date and available when needed.
RTU protocol, while either of the two Documents made available include:
Dynamic CT Ratio Mismatch rear ports can be configured to support Manuals
Correction DNP 3.0 Level 2. The optional Ethernet
Application Notes
port supports ModBus RTU via TCP/IP
Variances in on-load tap position output Guideform Specifications
protocol. The communication system of
are monitored and corrected. In addition,
the 745 is designed to allow simultaneous Brochures
external compensation CTs are not
communication via all ports. Wiring Diagrams
required.
Using Ethernet as the physical media
FAQs
Field Upgradable Option to integrate the 745 to Local or Wide
Area Networks, replaces a multidrop- Service Bulletins
An optional pass-code key may be
wired network (e.g., serial Modbus), and
purchased to allow field upgrades. Field Viewpoint Monitoring
eliminates expensive leased or dial-up
upgradable options ensure operators are
connections, reducing monthly operating Viewpoint Monitoring is a simple-to-use
able to add features and functionality
costs. and full-featured monitoring and data
when it is required.
recording software package for small
systems. Viewpoint Monitoring provides a
User Interfaces EnerVista Software complete HMI package with the following
The EnerVista Suite is an industry- Plug-&-Play Device Monitoring
Various user interfaces facilitate operation
leading set of software programs that System Single-Line Monitoring & Control
of the 745.
simplifies every aspect of using the 745
Annunciator Alarm Screens
Display relay. The EnerVista suite provides all
the tools to monitor the status of the Trending Reports
A 40 character display allows access to
transformer, maintain the relay, and Automatic Event Retrieval
setpoints, actual values, and diagnostic
integrate information measured by the 745 Automatic Waveform Retrieval
messages generated by a trip or alarm
into DCS or SCADA monitoring systems.
condition. The 745 can display 30
Convenient COMTRADE and Sequence
user-selected messages during keypad
of Events viewers are an integral part
inactivity.
of the745 Setup software included with
Indicators every 745 relay, to carry out postmortem
event analysis to ensure proper protection
Twenty LEDs indicate relay status, system
system operation.
status, and trip and alarm conditions.
EnerVista Launchpad
IRIG-B Input
EnerVista Launchpad is a powerful
This feature provides time synchronization
software package that provides users with
via standard GPS clock inputs.
all of the setup and support tools needed

Communications
The 745 is equipped with three standard
serial communications ports, one RS232
located in the front panel, and two RS485/
RS422 in the rear of the relay. One optional
Ethernet port is available at the rear of

www.GEDigitalEnergy.com 175
745 Transformer Protection System

Typical Wiring
Transformer Protection

g Multilin 745
Transformer Protection System

Ethernet
Option (T)

HUB

176 www.GEDigitalEnergy.com
745 Transformer Protection System

Technical Specifications
protection protection OUTPUTS
Note: [x] indicate 1 A secondary CT specifications, other Signal source: Winding 1 Phase A current/ ANALOG OUTPUTS (7)
values are for 5 A secondary. voltage Output range: 0 1, 0 5, 0 10, 0 20 or

Transformer Protection
PERCENT DIFFERENTIAL PROTECTION Level accuracy: 0.02 Hz 420mA
Operating current pu: 0.05 1.00 in steps of 0.01 x CT Operate time (delay set to 0.0 sec): Maximum load: 10 at 0 to 1 mA
Dropout level: 97% 98% of pickup Solid state output: @3% beyond pickup: 120150ms 600 at 4 to 20 mA
SLOPE-1 range: 15% 100% in steps of 1 Relay outputs 2 5: @ 3% beyond pickup: 125155ms Isolation: fully isolated
SLOPE-2 range: 50% 100% in steps of 1 OVEREXCITATION on 5th harmonic level Accuracy: 1% of full scale
KP (SLOPE-1 kneepoint): 1.0 20.0 in steps of 0.1 x CT Definite time element: OUTPUTS (1 solid state)
Harmonic restraint: 0.1% 65.0% in steps of 0.1 Max ratings: Make and carry 15 A @ 250 VDC for
Operate time: Operating current pickup: 0.03 1.00 in steps of 0.01x CT 500 ms
Solid state output: Pickup <1 x CT: 42 52 ms Pickup level: 0.1 99.9 in steps of 0.1% OUTPUT RELAYS
1 x CT < Pickup <1.1 x kneepoint: Dropout: 95% of pickup 2 5 trip: Form A (breaker TRIP rated)
34 44 ms Time delay: 0 60,000 sec in steps of 1 sec 6 8 auxiliary: Form C
Pickup >1.1 x kneepoint: 2636 ms Signal source: All phase currents 9 self-test: Form C
Relay outputs 2 5: Pickup <1 x CT: 46 56 ms Operate time (delay set to 0.0 sec): Contact material: silver alloy
1 x CT <pickup <1.1x.kneepoint: Solid state output: @ 1.10 x pickup: 20 120 ms Max ratings: 300 VAC, 250 VDC, 15 A, 1500 VA
3848ms Relay outputs 2 5: @ 1.10 x pickup: 25 125 ms
RELAYS: 2-5 TRIP
Pickup>1.1 x kneepoint: OVEREXCITATION on V/Hz (2 elements)
3040ms Voltage M/C Cont. M/C 0.2s Break Load Max
Operating voltage pickup: 0.10 0.99 in steps of 0.01x VT
INSTANTANEOUS DIFFERENTIAL OVERCURRENT Pickup level: 1.00 4.00 in steps of 0.01 V/Hz 20 A 40 A 10 A 300 W
DC 30 VDC
Pickup level: 3.00 20.00 in steps of 0.01 x CT Curve shape: Definite time (0.1 sec base curve)
Dropout level: 97% 98% of pickup IEC curve A/B/C Resistive 125 VDC
250 VDC
20 A 40 A 0.8 A 300 W
20 A 40 A 0.4 A 300 W
Level accuracy: Per current input Time delay: 0.00 600.00 sec in steps of DC 30 VDC 20 A 40 A 5A 150 W
Operate time: 0.01 sec Inductive 125 VDC 20 A 40 A 0.3 A 150 W
Solid state output: @ 1.2 x pickup: 22 30 ms Reset delay: 0.0 6000.0 sec in steps of L/R=40ms 250 VDC 20 A 40 A 0.2 A 150 W
@ 2.0 x pickup: 18 26 ms 0.1 sec AC 120 VDC 20 A 80 A 20 A 5000 VA
@ 4.0 x pickup: 11 19 ms Signal source: Voltage Resistive 240 VDC 20 A 80 A 20 A 5000 VA
Relay outputs 2 5: Range: 10 65 Hz AC 120 VAC 20 A 80 A 8 A 5000 VA
@ 1.2 x pickup: 28 36 ms Level accuracy: 0.02 V/Hz Inductive 250 VAC 20 A 80 A 7 A 5000 VA
@ 2.0 x pickup: 24 32 ms Operate time (delay set to 0.0 sec): PF=0.4
@ 4.0 x pickup: 17 25 ms Solid state output: @ 1.10 x pickup: 165 195 ms RELAYS: 6-8 AUXILIARY, 9 SELF-teST
PHASE/NEUTRAL (3I0)/GROUND/NEGATIVE SEQUENCE Relay outputs 2 5: @ 1.10 x pickup: 170 200 ms Max
TIME OVERCURRENT Voltage M/C Cont. M/C 0.2s Break Load
Insulation Aging/Hottest-Spot limit
Pickup level: 0.05 20.00 in steps of 0.01 x CT Pickup level: 50 300 in steps of 1 C 30 VDC 10 A 30 A 10 A 300 W
Dropout level: 97% 98% of pickup DC
Curve shape: (see curve shapes)
Delay: 0 60,000 in steps of 1 min Resistive 125 VDC
250 VDC
10 A 30 A 0.5 A 62.5 W
Insulation Aging/Aging factor limit 10 A 30 A 0.3 A 75 W
Curve multiplier (time dial): 0.5 30 for ANSI, IAC and DC 30 VDC 10 A 30 A 5A 150 W
FlexCurve in steps of 0.1 Pickup level: 1.1 10.0 in steps of 0.1 Inductive 125 VDC 10 A 30 A 0.25 A 31.3 W
0.05 1.00 for IEC curves in Delay: 0 60,000 in steps of 1 min L/R=40ms 250 VDC 10 A 30 A 0.15 A 37.5 W
steps of 0.01 Insulation Aging/Loss of life limit AC 120 VDC 10 A 30 A 10 A 2770 VA
Reset type: Instantaneous or linear Pickup level: 0 20,000 in steps of 1 x 10 hrs. Resistive 240 VDC 10 A 30 A 10 A 2770 VA
Level accuracy: Per current input AC 120 VAC 10 A 30 A 4A 480 VA
Timing accuracy: at 1.03 x pickup: 3% of trip Inductive 250 VAC 10 A 30 A 3A 750 VA
time or 20 ms (whichever is PF=0.4
greater) INPUTS
PHASE/GROUND/NEUTRAL (3I0)/negative sequence PHASE and GROUND CURRENT INPUT CIRCUITS METERING
INSTANTANEOUS OVERCURRENT Source CT: 1 50,000 A/1 or 5 A HARMONICS
Pickup level: 0.05 20.00 in steps of 0.01 x CT Relay input: 1 A or 5 A (specified when Individual: Range: 0.00 99.9%
Dropout level: 97% 98% of pickup ordering) Accuracy: 1% of Full Scale @ 0.5 x CT
Time delay: 0 60,000 in steps of 1 ms Burden: Less than 0.2 VA @ rated load THD: Range: 0.00 99.9%
Level accuracy: Per current input Conversion range: 0.02 46 x CT Accuracy: 1% of Full Scale @ 0.5 x CT
Operate time: Accuracy: at <4 x CT: 0.25% of 4 x CT(
Solid state output: @ 1.2 x pickup: 22 30 ms 0.01 CT)
@ 2.0 x pickup: 18 26 ms communications
at 4 x CT: 0.5% of 46 x CT
@ 4.0 x pickup: 11 19 ms ( 0.02 CT) Serial ports: Front: RS232; Rear: RS485
Relay outputs 2 5: Overload withstand: 1 sec @ 80 x rated current Baud Rate: 300 to 19200 baud,
@ 1.2 x pickup: 28 36 ms 2 sec @ 40 x rated current programmable parity
@ 2.0 x pickup: 24 32 ms continuous @ 3 x rated current
@ 4.0 x pickup: 17 25 ms Protocols: Modbus RTU, DNP 3.0 Level 2
ANALOG INPUTS (4) Ethernet Port: Optional, 10BaseT
UNDERFREQUENCY (2 elements) General purpose input:
Operating current pickup: 0.05 1.00 in steps of 0.01 x CT Type: dcmA Baud Rate: Suitable for 10 Mbs networks
Operating voltage pickup: 0.10 0.99 in steps of 0.01 x VT Ranges: 0 1, 0 5, 0 10, 0 20 or Protocol: Modbus RTU over TCP/IP
Pickup level: 45.0059.99 Hz in steps of 0.01 Hz 420 mA (programmable)
Dropout level: Pickup + 0.03 Hz Input impedance: 375 10% POWER SUPPLY
Time delay: 0.00600.00 sec in steps of 0.01 Conversion range:021 mA
sec Options: LO/HI (specified when ordering)
Accuracy: 1% of full scale (based on LO range: DC = 20 60 V; AC = 20 48 V @
Signal source: Winding 1 Phase A current/ input range)
voltage Tap Position Input: 48 62 Hz
Level accuracy: 0.02 Hz Type: resistance ( ) HI range: DC = 90 300 V; AC = 70 265 V @ 48 62 Hz
Operate time (delay set to 0.0 sec): Ranges: 0 500 or 0.5 5 k (programmable) Power: 30 VA nominal, 40 VA maximum
Solid state output: @ 3% beyond pickup: 120150 ms Bias current: 1 mA or 10 mA (based on input range) Fuse: (not accessible)
Relay outputs 25: @ 3% beyond pickup: Accuracy: 1% of full scale (based on Current Rating: 3.15 A
125155ms input range) Type: 5 20 mm Slow-Blow
RTD Input: Littelfuse, High Breaking
RESTRICTED GROUND FAULT Type: 3-wire: 100 Platinum (DIN.43760) Capacity; Model # 2153.15
Number of elements: 2 100 and 120 Nickel
Minimum pickup: 0.02 to 20.00CT in steps Sensing current: 5 mA production tests
of 0.01 Range: -50 to +250C
Dropout level: 97 to 98% of Pickup Accuracy: 2C Dielectric strength:
Slope range: 0 to 100% in steps of 1 IRIG-B Input: IEC 255-5 & ANSI/IEEE C37.90 (2kV @ 60Hz for 1 min)
Pickup delay: 0.00 to 600.00s in steps of 0.01 Amplitude modulated: 1.0 10 Vpp
Operating time: at 1.1 pickup: 30 to 40 ms DC shift: TTL
at 10 pickup: 20 to 30 ms environmental
LOGIC (switch) INPUT CONTACTS (16)
FREQUENCY rate of change (4 elements) Dry contacts: 1000 maximum "ON" resistance Operating temperature range: -20 C to +60 C
Operating current pickup: 0.05 1.00 in steps of 0.01 x CT 32 VDC @ 2 mA provided by 745 Ambient storage temperature: -40 C to +90 C
Operating voltage pickup: 0.10 0.99 in steps of 0.01 x V Wet contacts: Inputs 1 16: 30 300 VDC @ Humidity (non-condensing): Up to 90% (non condensing)
Pickup level: 45.00 59.99 in steps of 0.01 Hz 1.5 mA
Dropout level: Pickup + 0.03 Hz
Rate 1/2/3/4: 0.1 5.0 in steps of 0.1 Hz/sec VOLTAGE INPUT CIRCUIT
Source VT: 2 600 kV/60 120 V *Specifications subject to change without notice.
Dropout level: Pickup + 0.07 Hz/sec
Signal source: Winding 1 Phase A current/ Source VT ratio: 1 5000:1 in steps of 1
voltage Relay input: 60 120 V phase-neutral
Level accuracy: 0.02 Hz Burden: Less than 0.025 VA at 120 V
Operate time: The operate time of the frequency Max continuous: 273 V phase-neutral (F.S.)
trend element is variable and is dependent on the decay Accuracy: 1% of 2 x VT
rate setting andthe supervision frequency level.
Operating current pickup: 0.05 1.00 in steps of 0.01 x CT
Operating voltage pickup: 0.10 0.99 in steps of 0.01 x VT
Pickup level: 50.01 65.00 in steps of 0.01 Hz
Dropout level: Pickup - 0.03 Hz
Time delay: 0.00 600.00 sec in steps of
0.01 sec

www.GEDigitalEnergy.com 177
745 Transformer Protection System

Technical Specifications (continued)


TYPE TESTS CASE
Transformer Protection

Fully drawout unit (automatic CT shorts)


Dielectric voltage withstand: EN60255-5 Radiated & Conducted CISPR11 / CISPR22 / Seal provision
Impulse voltage withstand: EN60255-5 Emissions: IEC60255-25 Dust tight door
Sinusoidal Vibration: IEC60255-21-1 Weight (case and relay): 18 lbs, 6 oz
Damped Oscillatory: IEC61000-4-18/
IEC60255-22-1 Power magnetic Immunity: IEC61000-4-8
Electrostatic Discharge: EN61000-4-2 / Pulse Magnetic Immunity: IEC61000-4-9
Voltage Dip & interruption: IEC61000-4-11 APPROVALS
IEC60255-22-2
RF immunity: EN61000-4-3 / Ingress Protection: IEC60529 cULus: UL508, UL1053, C22.2.No 14
IEC60255-22-3 Relative Humidity Cyclic: IEC60068-2-30 ISO: Manufactured under the ISO90001 quality program
Fast Transient Disturbance: EN61000-4-4 / Environmental (Cold): IEC60068-2-1 : according to EN60255-5, EN50263
IEC60255-22-4 Environmental (Dry heat): IEC60068-2-2
Surge Immunity: EN61000-4-5 / Damped Oscillatrory: IEEE/ANSI C37.90.1
IEC60255-22-5 Safety: UL508 / UL C22.2-14 /
Conducted RF Immunity: EN61000-4-6 / UL1053
IEC60255-22-6

Please refer to Multilin 745 Instruction Manual for complete technical specifications

Ordering
745 * * * * * * * * * *
745 Base unit Transformer Protection System
Phase Current Input Rating W2 2 windings per phase
W3 3 windings per phase
Phase Current Input Rating P1 1 A for all windings
P5 5 A for all windings
P15 1 A for winding 1, 5 A for winding 2
P51 5 A for winding 1, 1 A for winding 2
P115 1 A for winding 1, 1 A for winding 2, 5 A for winding 3
P151 1 A for winding 1, 5 A for winding 2, 1 A for winding 3
P155 1 A for winding 1, 5 A for winding 2, 5 A for winding 3
P511 5 A for winding 1, 1 A for winding 2, 1 A for winding 3
P515 5 A for winding 1, 1 A for winding 2, 5 A for winding 3
P551 5 A for winding 1, 5 A for winding 2, 1 A for winding 3
Ground Current Input Rating G1 1 A for windings 1 and 2, 1 A for windings 2 and 3
G5 5 A for windings 1 and 2, 5 A for windings 2 and 3
G15 1 A for windings 1 and 2, 5 A for windings 2 and 3
G51 5 A for windings 1 and 2, 1 A for windings 2 and 3
Power Supply Options LO 20 60 VDC, 20 48 VAC @ 48 62 Hz
HI 90 300 VDC, 70 265 VAC @ 48 62 Hz
Enhancements A Analog input/outputs option
L Loss of Life
R Restricted ground fault option
E Enhanced display, larger LCD, improved keypad
T Enhanced display, larger LCD, improved keypad plus 10BaseT Ethernet Port
Environmental Protection H Harsh (Chemical) Environment Conformal Coating

Accessories
Dual mounting available with
the 19-2 Panel
NOTE: For dimensions see SR
Family brochure.

Accessories for the 745 Visit www.GEMultilin.com/745 to:


745 Applications Learning CD TRCD-SR745-C-S-1 View Guideform specifications
Multilink Ethernet Switch ML2400-F-HI-HI-A2-A2-A6-G1 Download the instruction manual
Viewpoint Engineer VPE-1 Review applications notes and support documents
Viewpoint Maintenance VPM-1 Buy a 745 online
Viewpoint Monitoring IEC61850 VP-1-61850 View the SR Family brochure

090821-v12
178 www.GEDigitalEnergy.com