DESIGN MANUAL
FAN FIN COOLER FOR GAS TURBINE COOLING SYSTEM
MUARA TAWAR PROJECT
1. Purpose
This specification concerns the Lube Oil cooling by water circulation.
The purpose of the system is the cooling of the following elements :
Generator bearings lubricating oil,
2. Description
2.1 Constitution
Lube Oil are cooled in paralel.
The off-base cooling system is mainly composed of :
Fin fan cooler modules
An atmospheric expansion tank
All interconnecting piping, instrumentation and valves
c). Instrumentation
Temperature indicator 1A-1B-1C measures the water temp. at fin fan
coolers inlet.
Temperature indicator 1A-1B-1C measures the water temp. at fin fan
coolers outlet.
b). Instrumentation
Level indicator 1A-1B-1C indicates the water level in the expansion
tank
The low level switch 1A-1B-1C send an alarm expansion tank low
water level on The GT control panel if the level is under the low
level.
Setting point : 200 mm under the centre line of the expansion tank.
3. Fluid
Water Quality and control : according to Gas Turbine Manufacturer
specification
Additive : Nalco 2000 as anti-corrosion product for the first filling and the
make-up.
Supplier : NALCO COMPANY, Indonesia
4. Reference documents
Performance Data Basis Data for Water Base Generator Cooler Design