Sei sulla pagina 1di 16

Heavy Fuel Oil supply unit

Quick start guide

Heavy Fuel Oil supply units


INTRODUCTION TABLE OF CONTENTS

This instruction manual is intended for training and marketing 1. Activating pump shaft seal lubrication (Seal Guard).....................4
purposes only. 2. Inspecting fuel valve positions....................................................5
3. Venting suction filters.................................................................6
The instruction manual delivered with each unit is the only correct 4. Inspecting instrument valves......................................................7
instruction manual to be used.
5. Activating fuses and thermal relays.............................................8
6. Starting feeder/supply pumps.....................................................9
Auramarine Ltd. assumes no liability for any damages resulting from
inaccurate information found in this instruction manual. 7. Venting the deaeration tank......................................................10
8. Checking suction and feed pressure.........................................11
9. Starting the booster/circulation pump.......................................12
Warning! Note! 10. Checking booster/circulation and outlet pressure gauges...........13
11. Adjusting viscosity....................................................................14
Orange boxes contain warnings Blue boxes contain comments
and reminders. and user instructions. 12. Checking the steam/thermal oil regulator valve..........................15
13. Testing equipment and alarms..................................................16
14. Starting and running the engine on MDO..................................17
15. Switching to the use of HFO.....................................................18
16. Switching to the use of MDO.....................................................19
17. Shutting down the system.........................................................20

2 3
1. Activating pump shaft seal lubrication (Seal Guard) 2. Inspecting fuel valve positions

Ensure that Seal Guard has a functional Ensure that the heating media is not turned
gas cartridge and oil. If Seal Guard is not on. There are also inlet
activated in time, and outlet valves on
Activate the pump lubricator (Seal Guard) Open the required fuel valves according to
it may cause the the outside of the
24 hours before starting for the first time by the PI diagram.
pump shaft seals unit.
turning the switch to 9. Select MDO.
to leak. Start-up and testing
Not all pump models come with Seal Guard
are done using
if you are using one without Seal Guard,
MDO.
please go straight to Section 2.

4 5
3. Venting suction filters 4. Inspecting instrument valves

Figure 1 Figure 2

Open the venting screw (Figure 1) and Open the air valves and ensure that there is
ensure that the oil is flowing. Remember to vent adequate air pressure.
all suction filters
The suction pressure gauge (Figure 2) Check the automatic filter air pressure
and then close
should read > 0 bar (usually 01 bar). gauge to see whether the air pressure rises
them after venting.
to approximately 4 bar. (Note! Not all filter
models come with a pressure gauge.)

6 7
5. Activating fuses and thermal relays 6. Starting feeder/supply pumps

1
5
Figure 1 Figure 2

t
3

2
4

Ensure that the main switches are set to Ensure that MDO is flowing into the pump
zero otherwise, the cabinets will not open Ensure that all (see Section 3). Ensure that the
(1). drive switches are electric motor is
Test run the electric pumps. Ensure
set to zero before rotating in the right
Activate the electrical cabinet fuses (2) and that the motors are rotating in the right
switching on the direction (always
thermal relays (3). direction. If the rotation direction is wrong,
main power. clockwise).
Ensure that the drive switches are set to contact an electrician.
Never run the
zero (4). If the rotation direction is right, leave one of
pump dry.
Turn on the power with the main switch (5). After resetting, one the pumps running.
of the alarms may
Reset the alarms.
still be active this
is normal. The
lights should go off
when the unit is
started.

8 9
7. Venting the deaeration tank 8. Checking suction and feed pressure

Figure 1 Figure 2

A. Automatic venting Open all gauges by turning the yellow tip.


When manually Parallel feeder and
Low level alarm sounds venting starts. The suction side pressure should drop to
venting the booster pump pairs
If you have this type of device, venting will approx. 0 bar (Figure 1).
deaeration tank, are connected from
run automatically. the valve is opened The feed pressure should rise to 35 bar different cabinets.
only when the low (Figure 2).
B. Manual venting (pictured) One pump is in
level alarm sounds. If the connections are wrong, the feed standby mode.
Low level alarm sounds the tank is vent Otherwise, the valve pressure gauge (Figure 2) will not display Remember to test
by opening the valve. must stay closed. any values. both pumps.
When the alarm shuts off, close the valve. Never touch the
(The deaeration tank may only be checked pump relief valves! If
during the initial pump start-up.) necessary, pressure
can be adjusted
using the pressure
regulator valve
downstream from
the pumps, not with
the relief valves!

10 11
9. Starting the booster/circulation pump 10. Checking booster/circulation and outlet pressure gauges

t
Ensure that oil return circulation is allowed Vent the units external fuel system.
to the unit deaeration tank. Ensure that the Never touch the
The ships diesel engine fuel feed pressure
electric motor is pump relief valves!
Test run the electric pumps. Ensure should be the same as the units outlet
rotating in the right Outlet pressure is
that the motors are rotating in the right pressure.
direction. adjusted with the
direction. If the rotation direction is wrong, Also ensure that the fuel flow returns to pressure regulator
contact an electrician. the unit. valve located
If the rotation directions are right, leave one outside the unit,
of the pumps running. not the pump relief
valves!
Turn the switches
for feeder and
booster pumps
being shut down
to the standby
position.

12 13
11. Adjusting viscosity 12. Checking the steam/thermal oil regulator valve

3 1 2

Activate the viscometer on the control Ensure that the steam/thermal oil regulator
panel (1) and select Adjust viscosity (2). There is a 36 min valve is closed or the electric heaters are Heat tracing must
Also turn on the automatic filter (3). time delay between switched off. not be on when
manual flushings of using MDO!
Check the display to ensure that the Ensure that the heat tracing valves are
the automatic filter!
viscosity is 48 cSt. closed or electric tracing is shut off.
Note! The display can also be placed If the regulator valve is open, contact an
outside the unit (engine control room). electrician, who will switch the feed phases.
Temperature regulation is a safety function,
which is only available with HFO.

14 15
13. Testing equipment and alarms 14. Starting and running the engine on MDO

Test equipment and alarms. Ensure that heat tracing is not on for unit
outlet and inlet pipelines. Ensure that heat
Test functions according to the alarm
tracing is not on for
panel; also test remote control. Start the engine.
unit outlet and inlet
Also ensure that the alarms are being sent pipelines.
to the engine control room.

16 17
15. Switching to the use of HFO 16. Switching to the use of MDO

Open the valve for the units external heat Turn off heat tracing for the units outlet
source. Be careful of hot and inlet pipelines. A rise of more
surfaces use than 50C in MDO
Open the valves (steam/thermal oil) for the Switch the change-over valve to MDO.
protective safety temperature may
heat exchanger in use. Use only one heat
gear. damage the system.
exchanger.
Switch the change-over valve to HFO. The
switch to HFO may take around 13 hours. The viscosity
alarm monitors the
Viscosity will be automatically set to the
setpoint. It is 3
setpoint value. Check this value against
cSt of the selected
the motors technical specifications (1020
setpoint. The low
cSt). Regulation of the value may take
viscosity alarm will
several hours.
be triggered when
Open the units external fuel line heat switching to HFO.
tracing valves. This is normal. The
oil temperature
will rise to approx.
135150C.

18 19
17. Shutting down the system Notes

It is possible to shut down the ships diesel


engine when viscosity decreases. The unit If the unit must be
may also be shut down after this. shut down when
using HFO, turn
on the units heat
tracing!

The system should


always be shut
down when using
MDO never
HFO. Switching
too quickly may
damage the unit
pumps.

20 21
IMPORTANT POINTS TO REMEMBER PLEASE READ!

Pumps other impurities, and tends to clog the filter elements. As a result,
The pumps are equipped with mechanical shaft seals. The mechanical the automatic filter will need to be stripped and the filter elements
seals must leak to operate properly. The mechanical seals consist of cleaned, in some cases repeatedly. When the dirt has been flushed
two highly polished, very flat surfaces. The surfaces may not run dry, from the system, the automatic filter will operate normally. This is all
as they will otherwise fail very quickly. Therefore, they are designed to normal and not a guarantee issue.
allow a very thin film of liquid to exist between them. Some of the liquid
will leak out of the seal. When pumping HFO, the leaking HFO will Viscometer
visibly accumulate on the pump. This is normal and does not indicate During the initial start-up of the fuel oil unit,
a manufacturing defect. It is not a guarantee the viscometer may indicate an unexpected
issue. viscosity. Should this happen, the value will
A leakage rate of 10 drops of oil per hour tend to be too high. This is typically caused by
or less is considered normal. Please note that a dirty sensor, i.e. the pendulum. Poor quality
seals will sometimes require a run in period, oil will worsen this, thus requiring a cleaning
with leakage gradually diminishing over several of the pendulum. Flush the pendulum with
hours of operation after the initial start-up. diesel oil or a mild detergent. Be extremely
Start-ups can be particularly hard on careful when handling the pendulum, as it is
mechanical seals. Never start a pump without a sophisticated instrument.
priming. Always make sure that the Seal Guard
lubricator is activated, if the pump is equipped Guarantee
with one. Although all Auramarine fuel booster unit contracts offer a guarantee
of quality, normal wear parts are not included in the guarantee. The
following are considered wear parts:
Automatic filter Mechanical shaft seals of the pumps
During the initial start-up of the fuel system, All gaskets, rubber pistons and o-rings
the automatic filter may get clogged. This Filter candles and elements
does not indicate a defect in the automatic Couplings and coupling elements
filter. The tanks and pipes of the fuel oil Ball bearings for pumps and electric motors
system contain a lot of dirt and debris. The
automatic filter will catch the dirt, but there
may be so much of it that the filter cannot
clean itself anymore. The clogging of the filter
will also depend on the quality of the oil. Poor
quality oil contains particles, tar, paraffin and

22 23
QUICK VIEW
17
5 7
1. Activating pump shaft seal 13
lubrication (Seal Guard)
2. Inspecting fuel valve positions
3. Venting suction filters
11 10
4. Inspecting instrument valves
12
5. Activating fuses and thermal
relays
8
6. Starting feeder/supply pumps
7. Venting the deaeration tank 6
4
8. Checking suction and feed 9
pressure 1
3
9. Starting the booster/
circulation pump
10. Checking booster/circulation
and outlet pressure gauges
11. Adjusting viscosity 2
12. Checking the steam/thermal 14 16
oil regulator valve 15
13. Testing equipment and alarms
14. Starting and running the
engine on MDO
15. Switching to the use of HFO
16. Switching to the use of MDO
17. Shutting down the system

24 25
Auramarine After Sales is much more than just Auramarine Original Spare Parts available for your equipment, with
a quick spare parts supplier. Our mission is to fast delivery times and competitive prices.
bring in new cost and energy-saving solutions Stop losing money and start earning it now!
for our customers and solve challenges together The first step in improving your situation is to find out where to save.
in a competitive business situations. Fuel is a shipowners primary cost and giving a fuel system a trial is
the most effective way to achieve major savings. A trial will provide
Auramarine After Sales services include: reliable information as well as give you a rough idea as to what your
basic support for unit installation return on investment will be.
spare part sales with fast delivery times worldwide
unit commissioning and field maintenance Just send us an email and get off to a perfect start!
performance optimization For questions concerning trials, our products, Spare parts and After
component and unit design upgrades Sales services, please contact our After Sales team at after.sales@
fuel cooling systems and Marine Gas Oil -conversions auramarine.com

We help you reduce your operating costs


Besides the conventional spare part sales, we can offer
you, for example, high performance fuel consumption
monitoring systems, which will help the vessel to reduce
its actual operating costs. We can also offer you inclusive
modernization packages for measurement of the fuel booster
viscosity and control systems for improving and ensuring
more accurately-controlled combustion cycles in your
engines. All in all, Auramarine After Sales can effectively
update your auxiliary systems to the level of the newest and
most modern units, with greater reliability, higher engine
performance and lower fuel consumption.

Worldwide presence
Auramarine spare parts, After Sales services and technical
support are globally available for all your installations
through our global Auramarine After Sales organization. Your Close to you all over the world
personnel can easily contact our technical sales engineers Auramarine has two extensive spare part facilities: one in Europe and the other
with standard spare part enquiries or any other operational in Asia. In addition to this, we have representatives in 30 countries, so customer
and technical questions. We have an excellent selection of support and service is always nearby.

26 27
gadfhsfgjhsfghsdfghnsfghn

Auramarine HFO
(Heavy Fuel Oil supply units)
HFO unit series, which offers easy
accessibility and service, meets the
increasing demand to minimize the
amount of space required for anything
other than passengers or cargo.

Auramarine MGO
(Marine Gas Oil handling unit)
Auramarine offers fast and reliable
solutions when needing to switch to low
sulphur fuel. The unit works seamlessly
with the AMB and all other HFO units.

Auramarine After Sales


Auramarines primary task is to ensure
the continuous and flawless operation of
your ships. This is why our After Sales
service is available 24/7. In addition
to this, we maintain a global dealer
and agent network. Under normal
circumstances, the required assistance
or spare part is dispatched to the ship
within 24 hours and delivered in 23
days.
THIS PUBLICATION IS DESIGNED TO PROVIDE AS ACCURATE AND AUTHORITATIVE INFORMATION
REGARDING THE SUBJECTS COVERED AS WAS AVAILABLE AT THE TIME OF WRITING. HOWEVER, THE
PUBLICATION DEALS WITH COMPLICATED TECHNICAL MATTERS AND THE DESIGN OF THE SUBJECT AND
PRODUCTS IS SUBJECT TO REGULAR IMPROVEMENTS, MODIFICATIONS AND CHANGES. CONSEQUENTLY,
THE PUBLISHER AND COPYRIGHT OWNER OF THIS PUBLICATION CANNOT TAKE ANY RESPONSIBILITY OR
LIABILITY FOR ANY ERRORS OR OMISSIONS IN THIS PUBLICATION OR FOR DISCREPANCIES ARISING FROM
THE FEATURES OF ANY ACTUAL ITEM IN THE RESPECTIVE PRODUCT BEING DIFFERENT FROM THOSE
SHOWN IN THIS PUBLICATION. THE PUBLISHER AND COPYRIGHT OWNER SHALL NOT BE LIABLE UNDER
ANY CIRCUMSTANCES, FOR ANY CONSEQUENTIAL, SPECIAL, CONTINGENT, OR INCIDENTAL DAMAGES OR
INJURY, FINANCIAL OR OTHERWISE, SUFFERED BY ANY PART ARISING OUT OF, CONNECTED WITH, OR
RESULTING FROM THE USE OF THIS PUBLICATION OR THE INFORMATION CONTAINED THEREIN.
COPYRIGHT 2013 BY AURAMARINE LTD.
ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED OR COPIED IN ANY FORM
OR BY ANY MEANS, WITHOUT PRIOR WRITTEN PERMISSION OF THE COPYRIGHT OWNER.

28 29
AuramarineNumber one expertise on the seven seas.
Auramarine has been the worlds leading manufacturer of
fuel oil supply systems for over 30 years. We have wide-
ranging experience in liquid flows and this craftsmanship
is also utilized in design and manufacture of cooling water
and lubrication oil units. With over 12,000 skid mounted
auxiliary units, Auramarine has superior experience in fuel
systems.

AURAMARINE LTD
P.O. Box 849
FI-20101 Turku, Finland
Tel. +358 204 86 5030
Fax +358 204 86 5031
sales@auramarine.com
www.auramarine.com

Potrebbero piacerti anche