Revision A
Scenario 1
Location : Warehouse 3
1/2
K factor : 11.2 GPM/psi = 161.3 LPM/bar1/2
2
Density : 0.4 gpm/ft
Occupancy classification : Commodities class IV
2
Coverage area of sprinkler : 130 ft = 12.1 m2 radius = 2.8 m
No of sprinkler : 20 1 m H2O = 0.1 Bar
Minimum pressure : 1.7 bar
Hose allowance : 378.5 L/min = 100.7185 gpm
Friction loss HWS : 120
Sprinkler type : Control Mode Specific Area
Flow rate each sprinkler : 210.2834 L/min = 55.55704 gpm

Point Flow rate Pipe diameter Elevation

length Friction Normal


inside inside fitting & pipe Pressure
Elevation Elevation equivalen pipe Loss pressure note
Upstream - Downstream GPM diameter diameter accessories Total [bar]
L/min [m] [m] [m] [bar/m] [bar]
[inch] [mm]

FROM MCV TO PUMP ROOM


q 378.50 100.00 Lgth 53.00 Pt 3.19 Pt 3.19
MCV (NODE
- A 4.00 105.36 3.910 3.910 4L1GV1T Fit 19.26 0.076 Pe 0.00 Pv 0.41
SOURCE)
Q 4,720.60 1,247.19 Tot 72.26 Pf 5.50 Pn 2.78
q Lgth 325.00 Pt 8.69 Pt 8.69
A - B 4.00 105.36 3.910 3.910 3GVT4L Fit 20.89 0.076 Pe 0.00 Pv 0.41
Q 4,720.60 1,247.19 Tot 345.89 Pf 26.34 Pn 8.29
q Lgth 12.00 Pt 35.04 Pt 35.04
B - C 4.00 105.36 3.910 0.100 2LT Fit 12.28 0.076 Pe 0.37 Pv 0.41
Q 4,720.60 1,247.19 Tot 24.28 Pf 1.85 Pn 34.63
q Lgth 195.00 Pt 37.26 Pt 37.26
C - D 6.00 156.34 0.100 0.100 E Fit 11.70 0.01 Pe 0.00 Pv 0.08
Q 4,720.60 1,247.19 Tot 206.70 Pf 2.30 Pn 37.18
q Lgth 500.00 Pt 39.56 Pt 39.56
D - PUMP ROOM 6.00 156.34 0.100 0.100 8E Fit 46.30 0.01 Pe 0.00 Pv 0.08
Q 4,720.60 1,247.19 Tot 546.30 Pf 6.09 Pn 39.48
Pt 45.65
Fire water demand for sprinkler 4,342.10 L/min = 1,147.19 GPM
Fire demand for indoor hose 378.50 L/min = 100.00 GPM
Total fire demand 4,720.60 L/min = 1,247.19 GPM
Selected 100.00 GPM
Duration 60 minutes
3
Fire water tank capacity 283.24 m
Pressure required on pump 45.65 bar