Sei sulla pagina 1di 16

SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2

DATE: 11/4/201616-3598\2_CALCULATIONS\2_4_FIRE FIGHTING\3598_FIRE_WH3.SDF


JOB TITLE: SC_1

WATER SUPPLY ANALYSIS

Static: 8.000 bar Resid: 1.000 bar Flow: 4731.0 lpm

14.0

LEGEND
12.0
1 Available pressure
2A 2
0.27 bar @ 4992.2 l/min
G
A 10.0 2 Required pressure

U 11.64 bar @ 4992.2 l/min


G
1A Avail. OnSite Demand Press.
E
8.0CA 0.27 bar @ 4614.2 l/min

P 2A Req. OnSite Demand Press.


R 11.64 bar @ 4614.2 l/min
E 6.0
A. Source Supply Curve
S
S B. System Demand Curve

U C. Available at Source
4.0
R
E

( 2.0
b
a
B
r
0.0 1A 1
)

-1.0
1000
15002000 2500 3000 3500 4000 4500 5000
FLOW (LPM)
ote: (1) Dashed Lines indicate extrapolated values from Test Results

(2) On Site pressures are based on hose stream deduction at the source
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 11/4/201616-3598\2_CALCULATIONS\2_4_FIRE FIGHTING\3598_FIRE_WH3.SDF
JOB TITLE: SC_1

NFPA WATER SUPPLY DATA

SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D


NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS.
TAG (BAR) (BAR) (LPM) (BAR) (LPM) (BAR)

SOURCE 8.00 1.00 4731.0 0.268 4992.2 11.637

AGGREGATE FLOW ANALYSIS:

TOTAL FLOW AT SOURCE 4992.2 LPM


TOTAL HOSE STREAM ALLOWANCE AT SOURCE 378.0 LPM
OTHER HOSE STREAM ALLOWANCES 0.0 LPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 4614.2 LPM

NODE ANALYSIS DATA


NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES
(M) (BAR) (L/MIN)

1 10.15 K=160.00 3.518 300.1


2 9.45 K=160.00 3.500 299.3
3 8.79 K=160.00 3.564 302.1
4 8.13 K=160.00 3.697 307.6
5 7.47 K=160.00 4.030 321.2
6 3.91 - - - - 5.623 - - -
7 10.15 K=160.00 3.539 301.0
8 9.45 K=160.00 3.519 300.2
9 8.79 K=160.00 3.583 302.9
10 8.13 K=160.00 3.716 308.4
11 7.47 K=160.00 4.048 321.9
12 3.91 - - - - 5.641 - - -
13 10.15 K=160.00 3.612 304.1
14 9.45 K=160.00 3.590 303.1
15 8.79 K=160.00 3.654 305.8
16 8.13 K=160.00 3.787 311.4
17 7.47 K=160.00 4.124 324.9
18 3.91 - - - - 5.737 - - -
19 3.91 - - - - 5.970 - - -
20 3.91 - - - - 6.194 - - -
21 3.91 - - - - 6.411 - - -
22 3.91 - - - - 6.625 - - -
23 3.91 - - - - 6.838 - - -
24 3.91 - - - - 7.052 - - -
25 3.91 - - - - 7.265 - - -
26 3.91 - - - - 7.478 - - -
27 3.91 - - - - 7.691 - - -
28 3.91 - - - - 7.904 - - -
29 3.91 - - - - 8.117 - - -
30 3.91 - - - - 8.330 - - -
31 3.91 - - - - 8.542 - - -
32 3.91 - - - - 8.753 - - -
33 3.91 - - - - 8.960 - - -
34 3.91 - - - - 9.161 - - -
35 3.91 - - - - 9.349 - - -
36 3.91 - - - - 9.522 - - -
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 11/4/201616-3598\2_CALCULATIONS\2_4_FIRE FIGHTING\3598_FIRE_WH3.SDF
JOB TITLE: SC_1

NODE ANALYSIS DATA


NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES
(M) (BAR) (L/MIN)

37 3.91 - - - - 9.631 - - -
38 3.91 - - - - 10.196 - - -
39 3.91 - - - - 10.347 - - -
40 3.91 - - - - 10.497 - - -
41 3.91 - - - - 10.606 - - -
42 3.91 - - - - 11.080 - - -
43 3.91 - - - - 10.763 - - -
44 3.91 - - - - 10.556 - - -
45 3.91 - - - - 10.271 - - -
46 3.91 - - - - 9.985 - - -
47 3.91 - - - - 9.700 - - -
48 3.91 - - - - 9.442 - - -
49 3.91 - - - - 9.204 - - -
50 3.91 - - - - 8.978 - - -
51 3.91 - - - - 8.759 - - -
52 3.91 - - - - 8.543 - - -
53 3.91 - - - - 8.330 - - -
54 3.91 - - - - 8.117 - - -
55 3.91 - - - - 7.904 - - -
56 3.91 - - - - 7.691 - - -
57 3.91 - - - - 7.478 - - -
58 3.91 - - - - 7.265 - - -
59 3.91 - - - - 7.052 - - -
60 3.91 - - - - 6.839 - - -
61 3.91 - - - - 6.626 - - -
62 3.91 - - - - 6.414 - - -
63 3.91 - - - - 6.205 - - -
64 3.91 - - - - 6.002 - - -
65 3.91 - - - - 5.808 - - -
66 3.91 - - - - 5.705 - - -
67 3.91 - - - - 5.665 - - -
68 3.91 - - - - 5.659 - - -
69 3.91 - - - - 5.654 - - -
70 10.73 - - - - 3.675 - - -
71 10.73 - - - - 3.699 - - -
72 10.73 - - - - 3.776 - - -
73 10.73 - - - - 5.318 - - -
74 10.73 - - - - 5.531 - - -
75 10.73 - - - - 5.744 - - -
76 10.73 - - - - 5.957 - - -
77 10.73 - - - - 6.171 - - -
78 10.73 - - - - 6.384 - - -
79 10.73 - - - - 6.597 - - -
80 10.73 - - - - 6.810 - - -
81 10.73 - - - - 7.023 - - -
82 10.73 - - - - 7.236 - - -
83 10.73 - - - - 7.449 - - -
84 10.73 - - - - 7.662 - - -
85 10.73 - - - - 7.875 - - -
86 10.73 - - - - 8.088 - - -
87 10.73 - - - - 8.301 - - -
88 10.73 - - - - 8.514 - - -
89 10.73 - - - - 8.727 - - -
90 10.73 - - - - 8.940 - - -
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 11/4/201616-3598\2_CALCULATIONS\2_4_FIRE FIGHTING\3598_FIRE_WH3.SDF
JOB TITLE: SC_1

NODE ANALYSIS DATA


NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES
(M) (BAR) (L/MIN)

SOURCE 3.91 SOURCE 11.637 4614.2


SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
DATE: 11/4/201616-3598\2_CALCULATIONS\2_4_FIRE FIGHTING\3598_FIRE_WH3.SDF
JOB TITLE: SC_1

NFPA2 PIPE DATA

Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)


Frm Node El (M) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Notes
To Node El (M) PT Tot.(Q) Disch Act ID (M) T Pf/M (Pf)

Pipe: A 160.0 299.3 Disch 2.520 120 3.518


1 10.15 3.518 20.6 3 50.00 T: 3.0 3.050 -0.069
2 9.45 3.500 319.9 52.50 5.570 0.016 0.087

Pipe: B 160.0 302.1 Disch 2.520 120 3.500


2 9.45 3.500 -281.5 4 50.00 T: 3.0 3.050 -0.065
3 8.79 3.564 20.6 52.50 5.570 0.000 0.001

Pipe: C 160.0 302.1 Disch 2.520 120 3.697


4 8.13 3.697 -20.6 2 50.00 T: 3.0 3.050 0.064
3 8.79 3.564 281.5 52.50 5.570 0.012 0.068

Pipe: D 160.0 307.6 Disch 2.520 120 4.030


5 7.47 4.030 281.5 3 50.00 T: 3.0 3.050 0.064
4 8.13 3.697 589.1 52.50 5.570 0.048 0.268

Pipe: E 160.0 321.2 Disch 8.500 120 5.623


6 3.91 5.623 589.1 4 50.00 T: 3.0 3.050 0.349
5 7.47 4.030 910.3 52.50 11.550 0.108 1.245

Pipe: F 0.0 910.3 5 3.000 120 5.641


12 3.91 5.641 -316.4 69 100.00 T: 6.1 6.100 0.000
6 3.91 5.623 593.9 102.26 9.100 0.002 0.017

Pipe: G 160.0 300.2 Disch 2.520 120 3.539


7 10.15 3.539 23.1 9 50.00 T: 3.0 3.050 -0.069
8 9.45 3.519 323.2 52.50 5.570 0.016 0.088

Pipe: H 160.0 302.9 Disch 2.520 120 3.519


8 9.45 3.519 -279.8 10 50.00 T: 3.0 3.050 -0.065
9 8.79 3.583 23.1 52.50 5.570 0.000 0.001

Pipe: I 160.0 302.9 Disch 2.520 120 3.716


10 8.13 3.716 -23.1 8 50.00 T: 3.0 3.050 0.065
9 8.79 3.583 279.8 52.50 5.570 0.012 0.068

Pipe: J 160.0 308.4 Disch 2.520 120 4.048


11 7.47 4.048 279.8 9 50.00 T: 3.0 3.050 0.065
10 8.13 3.716 588.2 52.50 5.570 0.048 0.268

Pipe: K 160.0 321.9 Disch 8.500 120 5.641


12 3.91 5.641 588.2 10 50.00 T: 3.0 3.050 0.349
11 7.47 4.048 910.2 52.50 11.550 0.108 1.244

Pipe: L 0.0 910.2 11 3.000 120 5.737


18 3.91 5.737 593.9 6 100.00 T: 6.1 6.100 0.000
12 3.91 5.641 1504.1 102.26 9.100 0.011 0.097

Pipe: M 160.0 303.1 Disch 2.520 120 3.612


13 10.15 3.612 23.8 15 50.00 T: 3.0 3.050 -0.069
14 9.45 3.590 326.9 52.50 5.570 0.016 0.090
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7
DATE: 11/4/201616-3598\2_CALCULATIONS\2_4_FIRE FIGHTING\3598_FIRE_WH3.SDF
JOB TITLE: SC_1

Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)


Frm Node El (M) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Notes
To Node El (M) PT Tot.(Q) Disch Act ID (M) T Pf/M (Pf)

Pipe: N 160.0 305.8 Disch 2.520 120 3.590


14 9.45 3.590 -282.1 16 50.00 T: 3.0 3.050 -0.065
15 8.79 3.654 23.8 52.50 5.570 0.000 0.001

Pipe: O 160.0 305.8 Disch 2.520 120 3.787


16 8.13 3.787 -23.8 14 50.00 T: 3.0 3.050 0.065
15 8.79 3.654 282.1 52.50 5.570 0.012 0.069

Pipe: P 160.0 311.4 Disch 2.520 120 4.124


17 7.47 4.124 282.1 15 50.00 T: 3.0 3.050 0.065
16 8.13 3.787 593.5 52.50 5.570 0.049 0.272

Pipe: Q 160.0 324.9 Disch 8.500 120 5.737


18 3.91 5.737 593.5 16 50.00 T: 3.0 3.050 0.349
17 7.47 4.124 918.4 52.50 11.550 0.110 1.265

Pipe: R 0.0 918.4 17 3.000 120 5.970


19 3.91 5.970 1504.1 12 100.00 T: 6.1 6.100 0.000
18 3.91 5.737 2422.4 102.26 9.100 0.026 0.233

Pipe: S 0.0 2422.4 18 3.000 120 6.194


20 3.91 6.194 -57.4 73 100.00 T: 6.1 6.100 0.000
19 3.91 5.970 2365.0 102.26 9.100 0.025 0.223

Pipe: T 0.0 2365.0 19 3.000 120 6.411


21 3.91 6.411 -33.5 74 100.00 T: 6.1 6.100 0.000
20 3.91 6.194 2331.5 102.26 9.100 0.024 0.217

Pipe: U 0.0 2331.5 20 3.000 120 6.625


22 3.91 6.625 -16.7 75 100.00 T: 6.1 6.100 0.000
21 3.91 6.411 2314.8 102.26 9.100 0.024 0.214

Pipe: V 0.0 2314.8 21 3.000 120 6.838


23 3.91 6.838 -6.3 76 100.00 T: 6.1 6.100 0.000
22 3.91 6.625 2308.5 102.26 9.100 0.023 0.213

Pipe: W 0.0 2308.5 22 3.000 120 7.052


24 3.91 7.052 -1.4 77 100.00 T: 6.1 6.100 0.000
23 3.91 6.838 2307.1 102.26 9.100 0.023 0.213

Pipe: X 0.0 0.0 3.000 120 7.265


25 3.91 7.265 2307.0 23 100.00 T: 6.1 6.100 0.000
24 3.91 7.052 2307.0 102.26 9.100 0.023 0.213

Pipe: Y 0.0 0.0 79 3.000 120 7.478


26 3.91 7.478 2307.0 24 100.00 T: 6.1 6.100 0.000
25 3.91 7.265 2307.0 102.26 9.100 0.023 0.213

Pipe: Z 0.0 0.0 80 3.000 120 7.691


27 3.91 7.691 2307.0 25 100.00 T: 6.1 6.100 0.000
26 3.91 7.478 2307.0 102.26 9.100 0.023 0.213
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8
DATE: 11/4/201616-3598\2_CALCULATIONS\2_4_FIRE FIGHTING\3598_FIRE_WH3.SDF
JOB TITLE: SC_1

Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)


Frm Node El (M) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Notes
To Node El (M) PT Tot.(Q) Disch Act ID (M) T Pf/M (Pf)

Pipe: AB 0.0 0.0 81 3.000 120 7.904


28 3.91 7.904 2307.0 26 100.00 T: 6.1 6.100 0.000
27 3.91 7.691 2307.0 102.26 9.100 0.023 0.213

Pipe: AC 0.0 0.0 82 3.000 120 8.117


29 3.91 8.117 2307.0 27 100.00 T: 6.1 6.100 0.000
28 3.91 7.904 2307.0 102.26 9.100 0.023 0.213

Pipe: AD 0.0 2307.0 28 3.000 120 8.330


30 3.91 8.330 -0.3 83 100.00 T: 6.1 6.100 0.000
29 3.91 8.117 2306.7 102.26 9.100 0.023 0.213

Pipe: AE 0.0 2306.7 29 3.000 120 8.542


31 3.91 8.542 -2.7 84 100.00 T: 6.1 6.100 0.000
30 3.91 8.330 2304.0 102.26 9.100 0.023 0.213

Pipe: AF 0.0 2304.0 30 3.000 120 8.753


32 3.91 8.753 -9.6 85 100.00 T: 6.1 6.100 0.000
31 3.91 8.542 2294.5 102.26 9.100 0.023 0.211

Pipe: AG 0.0 2294.5 31 3.000 120 8.960


33 3.91 8.960 -22.2 86 100.00 T: 6.1 6.100 0.000
32 3.91 8.753 2272.2 102.26 9.100 0.023 0.207

Pipe: AH 0.0 2272.2 32 3.000 120 9.161


34 3.91 9.161 -41.6 87 100.00 T: 6.1 6.100 0.000
33 3.91 8.960 2230.6 102.26 9.100 0.022 0.200

Pipe: AI 0.0 2230.6 33 3.000 120 9.349


35 3.91 9.349 -68.5 88 100.00 T: 6.1 6.100 0.000
34 3.91 9.161 2162.1 102.26 9.100 0.021 0.189

Pipe: AJ 0.0 2162.1 34 3.000 120 9.522


36 3.91 9.522 -103.3 89 100.00 T: 6.1 6.100 0.000
35 3.91 9.349 2058.8 102.26 9.100 0.019 0.173

Pipe: AK 0.0 2058.8 35 0.500 120 9.631


37 3.91 9.631 -146.6 90 100.00 T: 6.1 6.100 0.000
36 3.91 9.522 1912.2 102.26 6.600 0.017 0.109

Pipe: AL 0.0 0.0 25.000 120 10.196


38 3.91 10.196 1912.2 36 100.00 3E: 9.1 9.150 0.000
37 3.91 9.631 1912.2 102.26 34.150 0.017 0.565

Pipe: AM 0.0 0.0 3.000 120 10.347


39 3.91 10.347 1912.2 37 100.00 T: 6.1 6.100 0.000
38 3.91 10.196 1912.2 102.26 9.100 0.017 0.151

Pipe: AN 0.0 0.0 3.000 120 10.497


40 3.91 10.497 1912.2 38 100.00 T: 6.1 6.100 0.000
39 3.91 10.347 1912.2 102.26 9.100 0.017 0.151
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 9
DATE: 11/4/201616-3598\2_CALCULATIONS\2_4_FIRE FIGHTING\3598_FIRE_WH3.SDF
JOB TITLE: SC_1

Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)


Frm Node El (M) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Notes
To Node El (M) PT Tot.(Q) Disch Act ID (M) T Pf/M (Pf)

Pipe: AO 0.0 0.0 0.500 120 10.606


41 3.91 10.606 1912.2 39 100.00 T: 6.1 6.100 0.000
40 3.91 10.497 1912.2 102.26 6.600 0.017 0.109

Pipe: AP 0.0 0.0 22.500 120 11.080


42 3.91 11.080 1912.2 40 100.00 T: 6.1 6.100 0.000
41 3.91 10.606 1912.2 102.26 28.600 0.017 0.473

Pipe: AQ Source 2701.8 43 0.500 120 11.637


SOURCE 3.91 11.637 1912.2 41 100.00 T: 6.1 6.100 0.000
42 3.91 11.080 4614.2 102.26 6.600 0.084 0.557

Pipe: AR 0.0 0.0 4.000 120 11.080


42 3.91 11.080 2701.8 44 100.00 T: 6.1 6.100 0.000
43 3.91 10.763 2701.8 102.26 10.100 0.031 0.317

Pipe: AS 0.0 0.0 0.500 120 10.763


43 3.91 10.763 2701.8 45 100.00 T: 6.1 6.100 0.000
44 3.91 10.556 2701.8 102.26 6.600 0.031 0.207

Pipe: AT 0.0 0.0 3.000 120 10.556


44 3.91 10.556 2701.8 46 100.00 T: 6.1 6.100 0.000
45 3.91 10.271 2701.8 102.26 9.100 0.031 0.285

Pipe: AU 0.0 0.0 3.000 120 10.271


45 3.91 10.271 2701.8 47 100.00 T: 6.1 6.100 0.000
46 3.91 9.985 2701.8 102.26 9.100 0.031 0.285

Pipe: AV 0.0 146.6 90 3.000 120 9.985


46 3.91 9.985 2555.2 48 100.00 T: 6.1 6.100 0.000
47 3.91 9.700 2701.8 102.26 9.100 0.031 0.285

Pipe: AW 0.0 103.3 89 3.000 120 9.700


47 3.91 9.700 2452.0 49 100.00 T: 6.1 6.100 0.000
48 3.91 9.442 2555.2 102.26 9.100 0.028 0.257

Pipe: AX 0.0 68.5 88 3.000 120 9.442


48 3.91 9.442 2383.5 50 100.00 T: 6.1 6.100 0.000
49 3.91 9.204 2452.0 102.26 9.100 0.026 0.238

Pipe: AY 0.0 41.6 87 3.000 120 9.204


49 3.91 9.204 2341.8 51 100.00 T: 6.1 6.100 0.000
50 3.91 8.978 2383.5 102.26 9.100 0.025 0.226

Pipe: AZ 0.0 22.2 86 3.000 120 8.978


50 3.91 8.978 2319.6 52 100.00 T: 6.1 6.100 0.000
51 3.91 8.759 2341.8 102.26 9.100 0.024 0.219

Pipe: A0 0.0 9.6 85 3.000 120 8.759


51 3.91 8.759 2310.0 53 100.00 T: 6.1 6.100 0.000
52 3.91 8.543 2319.6 102.26 9.100 0.024 0.215
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 10
DATE: 11/4/201616-3598\2_CALCULATIONS\2_4_FIRE FIGHTING\3598_FIRE_WH3.SDF
JOB TITLE: SC_1

Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)


Frm Node El (M) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Notes
To Node El (M) PT Tot.(Q) Disch Act ID (M) T Pf/M (Pf)

Pipe: A1 0.0 2.7 84 3.000 120 8.543


52 3.91 8.543 2307.4 54 100.00 T: 6.1 6.100 0.000
53 3.91 8.330 2310.0 102.26 9.100 0.023 0.214

Pipe: A2 0.0 0.3 83 3.000 120 8.330


53 3.91 8.330 2307.0 55 100.00 T: 6.1 6.100 0.000
54 3.91 8.117 2307.4 102.26 9.100 0.023 0.213

Pipe: A3 0.0 0.0 3.000 120 8.117


54 3.91 8.117 2307.0 56 100.00 T: 6.1 6.100 0.000
55 3.91 7.904 2307.0 102.26 9.100 0.023 0.213

Pipe: A4 0.0 0.0 3.000 120 7.904


55 3.91 7.904 2307.0 57 100.00 T: 6.1 6.100 0.000
56 3.91 7.691 2307.0 102.26 9.100 0.023 0.213

Pipe: A5 0.0 0.0 3.000 120 7.691


56 3.91 7.691 2307.0 58 100.00 T: 6.1 6.100 0.000
57 3.91 7.478 2307.0 102.26 9.100 0.023 0.213

Pipe: A6 0.0 0.0 3.000 120 7.478


57 3.91 7.478 2307.0 59 100.00 T: 6.1 6.100 0.000
58 3.91 7.265 2307.0 102.26 9.100 0.023 0.213

Pipe: A7 0.0 0.1 78 3.000 120 7.265


58 3.91 7.265 2307.0 60 100.00 T: 6.1 6.100 0.000
59 3.91 7.052 2307.0 102.26 9.100 0.023 0.213

Pipe: A8 0.0 1.4 77 3.000 120 7.052


59 3.91 7.052 2305.6 61 100.00 T: 6.1 6.100 0.000
60 3.91 6.839 2306.9 102.26 9.100 0.023 0.213

Pipe: A9 0.0 6.3 76 3.000 120 6.839


60 3.91 6.839 2299.2 62 100.00 T: 6.1 6.100 0.000
61 3.91 6.626 2305.6 102.26 9.100 0.023 0.213

Pipe: A10 0.0 16.7 75 3.000 120 6.626


61 3.91 6.626 2282.5 63 100.00 T: 6.1 6.100 0.000
62 3.91 6.414 2299.2 102.26 9.100 0.023 0.212

Pipe: A11 0.0 33.5 74 3.000 120 6.414


62 3.91 6.414 2249.1 64 100.00 T: 6.1 6.100 0.000
63 3.91 6.205 2282.5 102.26 9.100 0.023 0.209

Pipe: A12 0.0 57.4 73 3.000 120 6.205


63 3.91 6.205 2191.6 65 100.00 T: 6.1 6.100 0.000
64 3.91 6.002 2249.1 102.26 9.100 0.022 0.203

Pipe: A13 0.0 631.0 72 3.000 120 6.002


64 3.91 6.002 1560.7 66 100.00 T: 6.1 6.100 0.000
65 3.91 5.808 2191.6 102.26 9.100 0.021 0.194
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 11
DATE: 11/4/201616-3598\2_CALCULATIONS\2_4_FIRE FIGHTING\3598_FIRE_WH3.SDF
JOB TITLE: SC_1

Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)


Frm Node El (M) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Notes
To Node El (M) PT Tot.(Q) Disch Act ID (M) T Pf/M (Pf)

Pipe: A14 0.0 624.2 71 3.000 120 5.808


65 3.91 5.808 936.4 67 100.00 T: 6.1 6.100 0.000
66 3.91 5.705 1560.7 102.26 9.100 0.011 0.103

Pipe: A15 0.0 620.0 70 3.000 120 5.705


66 3.91 5.705 316.4 68 100.00 T: 6.1 6.100 0.000
67 3.91 5.665 936.4 102.26 9.100 0.004 0.040

Pipe: A16 0.0 0.0 3.000 120 5.665


67 3.91 5.665 316.4 69 100.00 T: 6.1 6.100 0.000
68 3.91 5.659 316.4 102.26 9.100 0.001 0.005

Pipe: A17 0.0 0.0 3.000 120 5.659


68 3.91 5.659 316.4 6 100.00 T: 6.1 6.100 0.000
69 3.91 5.654 316.4 102.26 9.100 0.001 0.005

Pipe: A18 0.0 910.3 5 45.000 120 5.654


69 3.91 5.654 -593.9 12 100.00 T: 6.1 6.100 0.000
6 3.91 5.623 316.4 102.26 51.100 0.001 0.030

Pipe: A19 0.0 0.0 21.901 120 5.665


67 3.91 5.665 620.0 1 50.00 T: 3.0 3.050 0.668
70 10.73 3.675 620.0 52.50 24.951 0.053 1.321

Pipe: A20 0.0 0.0 21.901 120 5.705


66 3.91 5.705 624.2 7 50.00 T: 3.0 3.050 0.668
71 10.73 3.699 624.2 52.50 24.951 0.054 1.338

Pipe: A21 0.0 0.0 21.900 120 5.808


65 3.91 5.808 631.0 13 50.00 T: 3.0 3.050 0.668
72 10.73 3.776 631.0 52.50 24.950 0.055 1.364

Pipe: A22 0.0 0.0 21.900 120 6.002


64 3.91 6.002 57.4 19 50.00 T: 3.0 3.050 0.668
73 10.73 5.318 57.4 52.50 24.950 0.001 0.016

Pipe: A23 0.0 0.0 21.900 120 6.205


63 3.91 6.205 33.5 20 50.00 T: 3.0 3.050 0.668
74 10.73 5.531 33.5 52.50 24.950 0.000 0.006

Pipe: A24 0.0 0.0 21.900 120 6.414


62 3.91 6.414 16.7 21 50.00 T: 3.0 3.050 0.668
75 10.73 5.744 16.7 52.50 24.950 0.000 0.002

Pipe: A25 0.0 0.0 21.900 120 6.626


61 3.91 6.626 6.3 22 50.00 T: 3.0 3.050 0.668
76 10.73 5.957 6.3 52.50 24.950 0.000 0.000

Pipe: A26 0.0 0.0 21.900 120 6.839


60 3.91 6.839 1.4 23 50.00 T: 3.0 3.050 0.668
77 10.73 6.171 1.4 52.50 24.950 0.000 0.000
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 12
DATE: 11/4/201616-3598\2_CALCULATIONS\2_4_FIRE FIGHTING\3598_FIRE_WH3.SDF
JOB TITLE: SC_1

Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)


Frm Node El (M) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Notes
To Node El (M) PT Tot.(Q) Disch Act ID (M) T Pf/M (Pf)

Pipe: A27 0.0 0.0 21.900 120 7.052


59 3.91 7.052 0.1 24 50.00 T: 3.0 3.050 0.668
78 10.73 6.384 0.1 52.50 24.950 0.000 0.000

Pipe: A28 0.0 0.0 21.900 120 6.597


79 10.73 6.597 0.0 50.00 T: 3.0 3.050 -0.668
58 3.91 7.265 0.0 52.50 24.950 0.000 0.000

Pipe: A29 0.0 0.0 21.900 120 6.810


80 10.73 6.810 0.0 50.00 T: 3.0 3.050 -0.668
57 3.91 7.478 0.0 52.50 24.950 0.000 0.000

Pipe: A30 0.0 0.0 21.900 120 7.023


81 10.73 7.023 0.0 50.00 T: 3.0 3.050 -0.668
56 3.91 7.691 0.0 52.50 24.950 0.000 0.000

Pipe: A31 0.0 2307.0 56 21.900 120 7.236


82 10.73 7.236 -2307.0 54 50.00 T: 3.0 3.050 -0.668
55 3.91 7.904 0.0 52.50 24.950 0.000 0.000

Pipe: A32 0.0 0.0 21.900 120 8.117


54 3.91 8.117 0.3 29 50.00 T: 3.0 3.050 0.668
83 10.73 7.449 0.3 52.50 24.950 0.000 0.000

Pipe: A33 0.0 0.0 21.900 120 8.330


53 3.91 8.330 2.7 30 50.00 T: 3.0 3.050 0.668
84 10.73 7.662 2.7 52.50 24.950 0.000 0.000

Pipe: A34 0.0 0.0 21.900 120 8.543


52 3.91 8.543 9.6 31 50.00 T: 3.0 3.050 0.668
85 10.73 7.875 9.6 52.50 24.950 0.000 0.001

Pipe: A35 0.0 0.0 21.900 120 8.759


51 3.91 8.759 22.2 32 50.00 T: 3.0 3.050 0.668
86 10.73 8.088 22.2 52.50 24.950 0.000 0.003

Pipe: A36 0.0 0.0 21.900 120 8.978


50 3.91 8.978 41.6 33 50.00 T: 3.0 3.050 0.668
87 10.73 8.301 41.6 52.50 24.950 0.000 0.009

Pipe: A37 0.0 0.0 21.900 120 9.204


49 3.91 9.204 68.5 34 50.00 T: 3.0 3.050 0.668
88 10.73 8.514 68.5 52.50 24.950 0.001 0.022

Pipe: A38 0.0 0.0 21.900 120 9.442


48 3.91 9.442 103.3 35 50.00 T: 3.0 3.050 0.668
89 10.73 8.727 103.3 52.50 24.950 0.002 0.048

Pipe: A39 0.0 0.0 21.900 120 9.700


47 3.91 9.700 146.6 36 50.00 T: 3.0 3.050 0.668
90 10.73 8.940 146.6 52.50 24.950 0.004 0.092
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 13
DATE: 11/4/201616-3598\2_CALCULATIONS\2_4_FIRE FIGHTING\3598_FIRE_WH3.SDF
JOB TITLE: SC_1

Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)


Frm Node El (M) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Notes
To Node El (M) PT Tot.(Q) Disch Act ID (M) T Pf/M (Pf)

Pipe: A40 160.0 300.1 Disch 2.520 120 3.675


70 10.73 3.675 319.9 2 50.00 E: 1.5 1.520 -0.057
1 10.15 3.518 620.0 52.50 4.040 0.053 0.214

Pipe: A41 160.0 301.0 Disch 2.520 120 3.699


71 10.73 3.699 323.2 8 50.00 E: 1.5 1.520 -0.057
7 10.15 3.539 624.2 52.50 4.040 0.054 0.217

Pipe: A42 160.0 304.1 Disch 2.520 120 3.776


72 10.73 3.776 326.9 14 50.00 E: 1.5 1.520 -0.057
13 10.15 3.612 631.0 52.50 4.040 0.055 0.221

Pipe: A43 0.0 2422.4 18 21.900 120 5.318


73 10.73 5.318 -2365.0 20 50.00 E: 1.5 1.520 -0.668
19 3.91 5.970 57.4 52.50 23.420 0.001 0.015

Pipe: A44 0.0 2365.0 19 21.900 120 5.531


74 10.73 5.531 -2331.5 21 50.00 E: 1.5 1.520 -0.668
20 3.91 6.194 33.5 52.50 23.420 0.000 0.006

Pipe: A45 0.0 2331.5 20 21.900 120 5.744


75 10.73 5.744 -2314.8 22 50.00 E: 1.5 1.520 -0.668
21 3.91 6.411 16.7 52.50 23.420 0.000 0.002

Pipe: A46 0.0 2314.8 21 21.900 120 5.957


76 10.73 5.957 -2308.5 23 50.00 E: 1.5 1.520 -0.668
22 3.91 6.625 6.3 52.50 23.420 0.000 0.000

Pipe: A47 0.0 2308.5 22 21.900 120 6.171


77 10.73 6.171 -2307.1 24 50.00 E: 1.5 1.520 -0.668
23 3.91 6.838 1.4 52.50 23.420 0.000 0.000

Pipe: A48 0.0 2307.1 23 21.900 120 6.384


78 10.73 6.384 -2307.0 25 50.00 E: 1.5 1.520 -0.668
24 3.91 7.052 0.1 52.50 23.420 0.000 0.000

Pipe: A49 0.0 0.0 21.900 120 7.265


25 3.91 7.265 0.0 58 50.00 E: 1.5 1.520 0.668
79 10.73 6.597 0.0 52.50 23.420 0.000 0.000

Pipe: A50 0.0 0.0 21.900 120 7.478


26 3.91 7.478 0.0 50.00 E: 1.5 1.520 0.668
80 10.73 6.810 0.0 52.50 23.420 0.000 0.000

Pipe: A51 0.0 0.0 21.900 120 7.691


27 3.91 7.691 0.0 50.00 E: 1.5 1.520 0.668
81 10.73 7.023 0.0 52.50 23.420 0.000 0.000

Pipe: A52 0.0 0.0 21.900 120 7.904


28 3.91 7.904 0.0 50.00 E: 1.5 1.520 0.668
82 10.73 7.236 0.0 52.50 23.420 0.000 0.000
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 14
DATE: 11/4/201616-3598\2_CALCULATIONS\2_4_FIRE FIGHTING\3598_FIRE_WH3.SDF
JOB TITLE: SC_1

Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)


Frm Node El (M) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Notes
To Node El (M) PT Tot.(Q) Disch Act ID (M) T Pf/M (Pf)

Pipe: A53 0.0 2307.0 28 21.900 120 7.449


83 10.73 7.449 -2306.7 30 50.00 E: 1.5 1.520 -0.668
29 3.91 8.117 0.3 52.50 23.420 0.000 0.000

Pipe: A54 0.0 2306.7 29 21.900 120 7.662


84 10.73 7.662 -2304.0 31 50.00 E: 1.5 1.520 -0.668
30 3.91 8.330 2.7 52.50 23.420 0.000 0.000

Pipe: A55 0.0 2304.0 30 21.900 120 7.875


85 10.73 7.875 -2294.5 32 50.00 E: 1.5 1.520 -0.668
31 3.91 8.542 9.6 52.50 23.420 0.000 0.001

Pipe: A56 0.0 2294.5 31 21.900 120 8.088


86 10.73 8.088 -2272.2 33 50.00 E: 1.5 1.520 -0.668
32 3.91 8.753 22.2 52.50 23.420 0.000 0.003

Pipe: A57 0.0 2272.2 32 21.900 120 8.301


87 10.73 8.301 -2230.6 34 50.00 E: 1.5 1.520 -0.668
33 3.91 8.960 41.6 52.50 23.420 0.000 0.008

Pipe: A58 0.0 2230.6 33 21.900 120 8.514


88 10.73 8.514 -2162.1 35 50.00 E: 1.5 1.520 -0.668
34 3.91 9.161 68.5 52.50 23.420 0.001 0.021

Pipe: A59 0.0 2162.1 34 21.900 120 8.727


89 10.73 8.727 -2058.8 36 50.00 E: 1.5 1.520 -0.668
35 3.91 9.349 103.3 52.50 23.420 0.002 0.045

Pipe: A60 0.0 2058.8 35 21.900 120 8.940


90 10.73 8.940 -1912.2 37 50.00 E: 1.5 1.520 -0.668
36 3.91 9.522 146.6 52.50 23.420 0.004 0.086

NOTES (HASS):

(1) Calculations were performed by the HASS 8.6 computer program


in accordance with NFPA13 (2016)
under license no. 49031682 granted by
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760

(2) The system has been calculated to provide an average


imbalance at each node of 0.0098 lpm and a maximum
imbalance at any node of 0.5148 lpm.

(3) Total pressure at each node is used in balancing the system.


Maximum water velocity is 9.36 m/sec at pipe AQ.

(4) Items listed in bold print on the cover sheet

are automatically transferred from the calculation report.


SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 15
DATE: 11/4/201616-3598\2_CALCULATIONS\2_4_FIRE FIGHTING\3598_FIRE_WH3.SDF
JOB TITLE: SC_1

(5) Available pressure at source node SOURCE under full flow conditions is
4.71 bar with a flow of 3146.18 lpm.

(6) PIPE FITTINGS TABLE

Pipe Table Name: STANDARD.PIP

PAGE: A MATERIAL: S40 HWC: 120


Diameter Equivalent Fitting Lengths in Meters
(mm) E T L C B G A D N
Ell Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv NPTee
52.50 1.52 3.05 0.91 3.35 1.83 0.30 3.05 3.05 3.05
102.26 3.05 6.10 1.83 6.71 3.66 0.61 6.10 6.10 6.10
Client PT. BEKAERT INDONESIA
6FeQDULR

Location : Warehouse 3
1/2
K factor : 11.2 GPM/psi = 161.3 LPM/bar1/2
2
Density : 0.5 gpm/ft
Occupancy classification : Commodities class IV
2
Coverage area of sprinkle : 130 ft = 12.1 m2 radius = 2.8 m
No of sprinkler : 15 1 m H2O = 0.1 Bar
Minimum pressure : 3.5 bar
Hose allowance : 378.5 L/min = 100.7185 gpm
Friction loss HWS : 120
Sprinkler type : Control Mode Specific ASSOLFDWLRQ
Flow rate each sprinkler : 301.7273 L/min = 79.71658 gpm

Point Flow rate Pipe diameter Elevation

length Friction Normal


inside inside fitting & pipe Pressure
Down Elevation Elevation equivalen pipe Loss pressure note
Upstream - diameter diameter accessories Total [bar]
stream L/min [m] [m] [m] [bar/m] [bar]
[inch] [mm]

FROM MCV TO PUMP ROOM


q 378.50 Lgth 53.00 Pt 11.64 Pt 11.64
MCV - A 6.00 156.34 3.910 3.910 4L1GV1T Fit 29.00 0.012 Pe 0.00 Pv 0.09
Q 4,992.70 Tot 82.00 Pf 1.01 Pn 11.55
q Lgth 325.00 Pt 12.65 Pt 12.65
A - B 6.00 156.34 3.910 3.910 3GVT4L Fit 31.46 0.012 Pe 0.00 Pv 0.09
Q 4,992.70 Tot 356.46 Pf 4.41 Pn 12.56
q Lgth 12.00 Pt 17.06 Pt 17.06
B - C 6.00 156.34 3.910 0.100 2LT Fit 18.50 0.012 Pe 0.37 Pv 0.09
Q 4,992.70 Tot 30.50 Pf 0.38 Pn 16.97
q Lgth 415.00 Pt 17.81 Pt 17.81
C - D 8.00 206.30 0.100 0.100 E Fit 15.39 0.00 Pe 0.00 Pv 0.03
Q 4,992.70 Tot 430.39 Pf 1.38 Pn 17.78
q Lgth 587.00 Pt 19.19 Pt 19.19
PUMP
D - 6.00 156.34 0.100 0.100 8E Fit 46.30 0.01 Pe 0.00 Pv 0.09
ROOM
Q 4,992.70 Tot 633.30 Pf 7.83 Pn 19.10
Pt 27.02
Fire water demand for sprinkler 4,614.20 L/min = 1,219.08 GPM
Fire demand for indoor hose 378.50 L/min = 100.00 GPM
Total fire demand 4,992.70 L/min = 1,319.08 GPM
100.00 GPM
Duration 60 minutes
3
Fire water tank capacity 299.56 m
Pressure required on pump 27.02 bar
Client PT. BEKAERT INDONESIA
6FeQDULR

Location : Warehouse 3
1/2
K factor : 11.2 GPM/psi 161.3 LPM/bar1/2
2
Density : 0.5 gpm/ft
Occupancy classification : Commodities class IV
2
Coverage area of sprinkler : 130 ft = 12.1 m2 radius = 2.8 m
No of sprinkler : 15 1 m H 2O = 0.1 Bar
Minimum pressure : 3.5 bar
Hose allowance : 378.50 L/min = 100 gpm
Friction loss HWS : 120
Sprinkler type : Control Mode Specific Application
Flow rate each sprinkler : 301.7273 L/min = 79.71658 gpm

Point Flow rate Pipe diameter Elevation

length Friction Normal


inside inside fitting & pipe Pressure
Elevation Elevation equivalen pipe Loss pressure note
Upstream - Downstream GPM diameter diameter accessories Total [bar]
L/min [m] [m] [m] [bar/m] [bar]
[inch] [mm]

FROM MCV TO MAIN PIPE


q 378.50 100.00 Lgth 90.00 Pt 11.64 Pt 11.64
MCV (NODE
- A 6.00 156.34 3.910 -0.400 5LT Fit 33.63 0.012 Pe 0.42 Pv 0.09
SOURCE)
Q 4,992.70 1,319.08 Tot 123.63 Pf 1.53 Pn 11.55
q Lgth 91.00 Pt 13.59 Pt 13.59
A - B 8.00 206.30 -0.400 0.100 4EL Fit 23.88 0.003 Pe -0.05 Pv 0.03
Q 4,992.70 1,319.08 Tot 114.88 Pf 0.37 Pn 13.56
q Lgth 130.00 Pt 13.91 Pt 13.91
B - PUMP ROOM 6.00 156.34 0.100 0.100 3L Fit 23.13 0.012 Pe 0.00 Pv 0.09
Q 4,992.70 1,319.08 Tot 153.13 Pf 1.89 Pn 13.82
Pt 15.80
Fire water demand for sprinkler 4,614.20 L/min = 1,219.08 GPM
Fire demand forindoor hose 378.50 L/min = 100.00 GPM
Total fire demand 4,992.70 L/min = 1,319.08 GPM
Selected 100.00 GPM
Duration 60 minutes
3
Fire water tank capacity 299.56 m
Pressure required on pump 15.80 bar

Potrebbero piacerti anche