Sei sulla pagina 1di 15

Reading Electrical Drawings

Bakery, and Switches and


Receptacles
Part I: Reading Electrical
Drawings Bakery
OBJECTIVES
After completing the study of Part I of this unit, the student will able to
determine loading requirements
select branch-circuit conductors

PRINTS may be needed for the same connections. If


longer runs are necessary, the electrician may
The electrician should check the electrical draw
need to increase the conductor sizes and also the
ings long before the actual installation begins.
conduit sizes.
Many decisions are required even when there is a
This section of the unit will give the student
complete set of drawings. Few plans provide full
experience in determining the proper conductor size.
information on (1) the exact paths that the con
duits or cables shall take, and (2) the actual sizes
of the conductors and conduits. The circuit rout
ings are very project-dependent and the sizings THE BAKERY PRINTS
depend upon the routings. Several different applications are illustrated in the
Frequently, it is possible to install short con bakery. See Fig. 10-1. The luminaires are surface
necting conduits between wall boxes while the mounted as individual units. Raceway connections
slabs are being poured. Later, longer conduits are made to all the luminaires. Connections are
Unit 10 Reading Electrical Drawings-Bakery, and Switches and Receptacles 137

Table 10-1 Bakery Feeder Loading Schedule

Item Count VA/unit Demand Installed Demand factor Use


Load Load Feeder Service Feeder Service

MINIMUM BASIC LOAD


(Rule 8-210) 218 m2 30 W/m 2 6540 6540 6540

INSTALLED BASIC LOADS


Style C luminaires 15 87 1305 1305 1305
Style B luminaires 4 87 348 348 348
Style E luminaires 2 144 288 288 288
Style L luminaires 12 87 1044 1044 1044
Style N luminaires 2 60 120 120 120
General receptacles 20 180 3600 .a.2Q.Q 3600
Installed basic loads 6705 6705

BASIC LOAD (Use the greater of the demand or installed loads, Rule 8-106(2).) 6705 6705

SPECIAL LOADS
Show win. Its. style C 3 87 261 261 261
Show win. rec. 4 720 2880 2880 2880
Sign 1 1200 1200 1200 1200
Bake oven 1 16000 16000 16000 16000
Doughnut mach. htr 1 2000 2000 2000 2000

Motors Volts FLA Phase


Dishwasher 208 23.9 3 8600 1.25 10750 8600
Disposer 208 7.44 3 2677 2677 2677
Dough divider 208 2.2 3 792 792 792
Doughnut machine 208 2.2 3 792 792 792
Exhaust fan 120 2.9 1 348 348 348
Multimixer 208 7.48 1 2692 1 556 1556
Multimixer 208 3.96 1 1426 824 824
Total load 46785 44635

1= _P- = 46785 130A


Ex 1.73 208 x 1.73
Assuming all loads are continuous, using standard-rated equipment, and TWN75 copper conductors from Table 2, the ampere rating of the cir
cuit would be:

130
0.8
= 162.5A
The feeder would be 4 No. 2/0 AWG TWN75 copper conductors in a 2in (53-mm) raceway, supplied by a 200-ampere disconnect
c/w 175-ampere fuses.

Fig. 10-1 Electrical drawing for a bakery. Note: For complete blueprint, refer to blueprint E2 at back of text.
138 Unit 10 Reading Electrical Drawings-Bakery, and Switches and Receptacles

made from an electrical box located flush in the Overcurrent protection should be carefully
ceiling or by a raceway installed between the ends. checked if there are changes in load or load
Special attention should be paid to the branch type. Otherwise, it should not be changed.
circuits as these plans are being reviewed. The
Reassigning phase connections can be useful
branch-circuit panelboard schedule shown in Table
if there is an advantage in grouping circuits
8-2 (page 115) provides important information
to share neutrals.
about these circuits. However, project conditions
may require the electrician to make changes. Continuous and unbalanced load designa
The electrician is responsible for checking tions are usually self-evident and should not
voltage drop and conductor ampacity. Once these be revised except in conjunction with other
have been determined, the electrician must check changes.
to see if any of the items on the schedule need The wire size may need to be increased if
updating. A review of what can, what should not, voltage drop is excessive or the conductor
and what cannot be changed will be useful. ampacity is derated.
Changing the circuit load should be avoided. When the wire size is changed it may be
Changing the load could require the devel possible to increase the circuit capacity.
opment of entirely new loading and panel
board schedules.

Part II: Switches and Receptacles

OBJECTIVES
After completing the study of Part II of this unit, the student will be able to
select switches and receptacles with the proper rating for a particular application
install various types of receptacles correctly
connect single-pole, three-way, four-way, and double-pole switches into control circuits

During the course of the work, an electrician plugs and receptacles. The differences in the
selects and installs numerous receptacles and plugs and receptacles are based on the ampacity
switches. Therefore, it is essential that the electri and voltage rating of the device. For example, the
cian know the important characteristics of these most commonly used receptacle is the CSA
devices, and how they are to be connected into the 5-15R, Fig. 10-2. The CSA 5-15R receptacle has
electrical system. a 15-ampere, 125-volt rating and has two parallel
slots and a ground-pin hole. This receptacle will
accept the CSA 5-15P plug only, Fig. 10-3. The
CSA 5-20R (Fig. 10-4) receptacle has two slots
RECEPTACLES at right angles. This receptacle is rated at 20
The National Electrical Manufacturers Associa amperes, 125 volts. The CSA 5-20R will only
tion (NEMA) and the Canadian Standards Asso accept a CSA 5-20P plug, Rule 26-700, Appen
ciation (CSA) have developed standards for the dix B, Fig. 10-5. A CSA 6-20R receptacle is
physical appearance of locking and nonlocking shown in Fig. 10-6. This receptacle has a rating
Unit 10 Reading Electrical Drawings-Bakery, and Switches and Receptacles 139

of 20 amperes at 250 volts. CSA 6-15P and


6-20P are shown in Fig. 10-7. Another receptacle
that is specified for the commercial building is the
CSA 6-30R, Fig. 10-8. This receptacle is rated at
30 amperes, 250 volts.
The CSA standards for general-purpose, non
locking and locking receptacles are shown in
Figs. 10-9 and 10-10. Following is the key to the Fig. 10-3 CSA 5-15P. A 15
catalogue numbers for these standards. ampere, 125-volt plug.
AI Single receptacle
B/ Duplex receptacle
C/ Plug
D/ Connector
E/ Flanged inlet Fig.l0-4 CSA
5-20R.A 20
F/ Flanged outlet ampere, 125-volt
+ Hospital Grade receptacle
* Available in hospital grade; add suffix HG
++ Available in isolated ground; add prefix IG
A special note should be made of the differ Fig. 10-5 CSA 5-20P. A 20
ences between the I 25/250-volt (CSA 14) devices ampere, 125-volt plug.
and the three-phase, 250-volt (CSA 15) devices.
The connection of the 1251250-volt receptacle
requires a neutral, a grounding wire, and two
phase connections. For the three-phase, 250-volt
receptacle, a grounding wire, and three-phase G
connections are required. y

Fig.l0-8 CSA 6-30R.


, A 30-ampere, 250-volt
Fig.l0-6 CSA
receptacle.
6-20R.A 20
ampere, 250-volt
receptacle.

CSA6-15P CSA 6-20P

Fig. 10-2 CSA 5-15R. A IS-ampere, 125 Fig.l0-7 CSA 6-15P, a IS-ampere, 250-volt plug;
volt receptacle. and CSA 6-20P, a 20-ampere, 250-volt plug.
140 Unit 10 Reading Electrical Drawings-Bakery, and Switches and Receptacles

Diagram 1
(See Rules 26-700,26-702,26-746, 78-052, 78-102, and 82-014 and Appendix B.)

CSA Configurations for Nonlocking Receptacles

DESCRIPTION
15 AMPERE 120 AMPERE 30 AMPERE so AMPERE 60 AMPERE
RECEPTACLE RECEPTACLE RECEPTACLE RECEPTACLE RECEPTACLE

125V 5
~@ !@
!@ !@

CI
125V SA
U@

z
l5

~~I!@ !~ !
z
~
CI
250V 6

It! I

!
~ 250V SA
U@

277VAC 7
~@ ~ @
~ I@ !@ Y(J

347VAC 24
~~ ~ ~
~@ ~@
:Ii
Q Q

~~ !Y
~~ i~ iY
l5
z
:l
125/25OV 14
~
CI
~
!
g
31S250V 15
~@ ~~ !==
-~=y i ~
==~O ! ~
D~~

*For configurations 6-15R, 6-20R, 6-30R, and 6-50R, Y denotes identified terminal when
used on circuits derived from three-phase, four-wire 416-volt circuits.

Fig.I6-9 CSA Diagram 1.

Two new CSA configurations-5-20RA and HOSPITAL-GRADE RECEPTACLES


6-20RA-are designed to accept both 15- and 20
In locations where severe abuse or heavy use is
ampere plugs. The introduction of these configu
expected, hospital-grade receptacles are recom
rations will make the CSA configurations for
mended. These are high-quality products. They
nonlocking receptacles identical to those used in
meet CSA requirements as hospital-grade recep
the United States.
tacles. These receptacles are marked with a small
dot, Fig. 10-11.
Unit 10 Reading Electrical Drawings-Bakery, and Switches and Receptacles 141

Diagram 2
(See Rules 12-020,26-700, 78-052, 78-102, and 82-014 and App. B.)

CSA Configurations for Locking Receptacles

15 20 30 50 60
AMPERE AMPERE AMPERE AMPERE AMPERE
RECEPTACLE RECEPTACLE RECEPTACLE RECEPTACLE RECEPTACLE

125V L5
L5-15R
(!,
GI <P
L5-20R
C)
f)
Ii'GI
~ <P
L5-30R Q L5-50R ~ <P
~
~
L5-60R
<P

e
~

250 V L8
L6-15R ~ v<P
L6-20R v<p
LS-30R GI
({j
[i' <pv

L6-SOR U[ ~v et;)
l8-6OR
GI J

"'~~ (;)
C) (J CJ
CJ
l! mVAC L7 ~
GI <p
u GI <p
U c:> c:>
!
GI GI
L7-20R L7-3OR L7-50R L7-60R

~
N 480VAC L8
L8-20R
Q
GI
~v CGJ
.;
1r C)
~ L8-30R "'V
LB-50R
GI cd' LB-60R cd'

800VAC L9
L9-20R ~ V
,!)
~ L~50R~ L~60RCJ
v
<p
L9-3OR
"v

e
~
1251250 V L14
L14-2OR ~i L14_30~ ~ ~
1Ja
ve>
L14-SOR
(J,CIo
w J
L14-60R
(J,GIo
w J

~ ~~ ~c? ~c?
~ 30 ~ ll"
CJ 250 V L15 GI
e>Z Ti' x X

!
L15-30R
L152OR L1550R L15-6OR

~ L1S_6OR~
30
~ ll"
! 480 V L16
L16-20rJ L16-30R
e>z
L1S-SORf:)

~ W-50fl:) L17-60~
30

800 V
L17 '" llv
L1730R ~

e
~ ~IJ L21-f;1JR~GIo
~~
30
208 v 1120 V l21 (!,olJl" Iro
'2 L21_20ffi L213OR
Gle::)
L21-50R W ~
~
~ ill D~ ~ ID
30
! 480V/mv L22
L22-20@
~~
L22-30R z
L22.50R L22-6OR
J!

ffi ~ ~ =-5OR~
i. 30
~ GlO 8'
8OOV/347V l23
L23.20R "Y l23-3OR L23-50R

Fig.lO-lO CSA Diagram 2.

ELECTRONIC EQUIPMENT ground, Fig. 10-12, they may have transient volt
RECEPTACLES age surge protection, they may be hospital grade,
Circuits with receptacle outlets that serve micro or any combination of these three. Where the iso
computers, solid-state cash registers, or other sen lated grounding is desired, an insulated grounding
sitive electronic equipment should be served by conductor is permitted to be run from the ground
receptacles that are specially designed. These terminal at the distribution panel to the isolated
receptacles may be constructed for an isolated terminal on the receptacle, Rule 10-906(9). These
142 Unit 10 Reading Electrical Drawings-Bakery, and Switches and Receptacles

. I

CJIIb
I

Fig. 10-11 BACK VIEW


FRONT VIEW
Hospital-grade
receptacle.
Fig.10-12 Isolated grounding receptacle.

receptacles are required to have an orange triangle


on their faces, except where the receptacle is
orange. In this case, the triangle is black.
Surge protection will absorb high voltage
surges on the line and further protect the equip
ment, Fig. 10--13. Surge suppressors are highly
recommended in areas of the country where light
ning strikes are common. Compared to the cost of
replacing damaged equipment and lost data, and
the cost of the receptacle, probably under $50,
seems small.

GROUND-FAULT CIRCUIT INTERRUPTER


Fig. 10-13 Surge suppressor receptacle.
RECEPTACLES (RULE 26-700(13)
Rule 26-700(13) requires ground-fault circuit
interrupters (GFCI) at certain locations in
dwellings and in the bathroom of guest rooms of
hotels and motels. The C.E.C., Part I also requires hazard exists whenever a person touches both a
the installation of GFCI protection on temporary defective appliance and a grounded conducting
wiring for construction sites and in a limited surface such as a water pipe or metal sink. To pro
number of other applications. GFCI protection is tect against this possibility of shock, the 15
required for the bathrooms of commercial build ampere branch circuits can be protected with
ings. For further information concerning GFCI GFCI receptacles or GFCI circuit breakers. The
application, the student is referred to Electrical GFCI receptacles are the most commonly used
Wiring: Residential, Second Canadian Edition form of protection.
(ITP Nelson, 1998). The CSA requires that Class A GFCIs trip on
Deaths and personal injuries have been ground-fault currents of 4 to 6 milliamperes
caused by electrical shock from appliances such (0.004 to 0.006 ampere). Figs. 10--14 and 10-15
as radios, shavers, and electric heaters. This shock illustrate the principles of how a GFCI operates.
Unit 10 Reading Electrical Drawings-Bakery, and Switches and Receptacles 143

1.0 AMPERE
COIL ..
BLACK

NO CURRENT IS INDUCED IN THE COIL


BECAUSE BOTH WIRES ARE CARRYING THE
SAME CURRENT. THE GROUNDFAULT
CIRCUIT INTERRUPTER DOES NOT TRIP
THE CIRCUIT OFF.
WHITE
GFCI
IGROUND-FAULT
CIRCUIT INTERRUPTER)

SMALL AMOUNT OF CURRENT DANGEROUS CURRENT


INDUCED IN COIL
OF OVER 0.006 AMPERE
FLOWING THROUGH
A SMALL AMOUNT OF CURRENT IS INDUCED IN
1.006 AMPERES BODY TO GROUND THE COIL BECAUSE OF THE IMBALANCE OF
... CURRENT IN THE CONDUCTORS. THIS CURRENT
DIFFERENCE IS AMPLIFIED SUFFICIENTLY BY

j
BLACK THE GROUNDFAULT INTERRUPTER TO CAUSE
IT TO TRIP THE CIRCUIT OFF BEFORE THE PERSON
TOUCHING THE FAULTY APPLIANCE IS INJURED
OR KILLED. NOTE: CURRENT VALUES ABOVE
6 MILLIAMPERES ARE CONSIDERED DANGEROUS.
GROUND-FAULT CIRCUIT INTERRUPTERS MUST
SENSE AND OPERATE WHEN THE GROUND
WHITE GFCITRIPS CURRENT EXCEEDS 6 MILLIAMPERES.
CIRCUIT OFF

Fig. 16-14 Basic principle of how a ground-fault circuit interrupter operates.

PUSH

TO TEST

SHUNT SOLID-STATE -L
TRIP CIRCUITRY 0

I r- -
I
I ~I-

II (SWITCHING
CONTACTS I-~
RESISTOR

I SENSOR/?~
r-".
BLACK

120-VQLT SOURCE

WHITE
1

-T \\
~
J1 .... ~ ""
(

o
120 VOLTS

Fig.I6-15 GFCI internal components and connections. Receptacle-type GFCIs switch both the black and white con
ductors. Note that when the test button is pushed, the test current passes through the sensor to the test button but
bypasses the sensor on the way back to the opposite circuit conductor. This is how an unbalance is created and then
monitored by the solid-state circuitry to signal the GFCl's contacts to open. Note that since both load currents pass
through the sensor, no unbalance is present under normal receptacle use.
144 Unit 10 Reading Electrical Drawings-Bakery, and Switches and Receptacles

THIS RECEPTACLE OUTLET SHALL NOT

BE CONNECTED TO THE HEATER CIRCUIT \

"'.. '.'.. '.".'."""'."""@

ELECTRIC BASEBOARD HEATER


1-------------1 @

Fig.lo-l6 Factory-mounted receptacle outlets on per


manently installed electric baseboard heaters may be
counted as the required outlets for the space occupied
by the baseboard unit.

RECEPTACLES IN ELECTRIC
BASEBOARD HEATERS
Electric baseboard heaters are available with or
Fig. 10-17 General-use switch.
without receptacle outlets. Fig. 10-16 shows how
a receptacle outlet can be installed in an electric
baseboard heater. Section 62 details the require Category 2 contains those ac general-use
ments for fixed electric space heating equipment. switches that are used to control
ac circuits only

SWITCHES (RULE 14-500) resistive, inductive, and tungsten-filament


lamp loads not to exceed the ampere rating
Most electricians refer to switches as toggle of the switch at 120 volts
switches or wall switches. Refer to Fig. 10-17.
These switches are divided into two categories. motor loads not to exceed 80% of the
Category 1 contains those ac/dc general-use ampere rating of the switch at rated voltage
switches that are used to control Ac general-use switches may be marked "ac
only," or they may also be marked with their cur
ac or dc circuits
rent and voltage ratings. A typical switch marking
resistive loads not to exceed the ampere is "15A, 120-277V AC" or "120-277-347V AC."
rating of the switch at rated voltage The 347-V rating is required on 347/600-volt sys
inductive loads not to exceed one-half the tems. Refer to Section 30 for the special require
ampere rating of the switch at rated voltage ments of 347-V switches for lighting circuits. See
Rule 14-512 for additional information pertain
tungsten filament lamp loads not to exceed the ing to maximum voltage limitations.
ampere rating of the switch at rated voltage if Terminals of switches rated at 20 amperes or
the switch is marked with the letter "T" (A less, when marked "CU/AL" or "CO/ALR" are
tungsten filament lamp draws a very high cur suitable for use with aluminum, copper, and
rent at the instant the circuit is closed. As a copper-clad aluminum conductors. Switches not
result, the switch is subjected to a severe cur marked "CUIAL" or "COlALR" are suitable for
rent surge.) use with copper and copper-clad conductors only.
The ac/dc general-use switch normally is not Many switches have screwless pressure termi
marked "ac/dc." However, it is always marked nals where a connection can be made by simply
with the current and voltage rating, such as inserting the bared end of the conductor. These
"lOA-125V,5A-250V-T." terminals may be used with copper and copper
Unit 10 Reading Electrical Drawings-Bakery, and Switches and Receptacles 145

clad aluminum conductors only. Push-in termi Single-Pole Switch. A single-pole switch is
nals are not suitable for use with ordinary alu used where it is desired to control a light or group
minum conductors. of lights, or other load, from one switching point.
Further information on switch ratings is given This type of switch is wired in series between the
in Rules 14-508 and 14-510. ungrounded ("hot") wire and the load. Fig. 10-18
shows typical applications with the feed to the
switch connected either at the switch or at the
light. Note that the grounded wire goes directly to
Switch Types and Connections the load and the ungrounded wire is broken at the
single-pole switch. Three diagrams are shown for
Switches for branch circuit lighting are readily each switching connection. The first diagram is a
available in four basic types: single-pole, three schematic drawing and is valuable when visualiz
way, four-way, and double-pole. ing the current path. The second diagram repre-

Grounded
conductor White
Lamp

Grounded Ungrounded
conductor conductor

Source
To source
To source

(AI Circuit with single-pole switch feed at switch

White (permitted for


"Hot" Bleck feed to switch
Source in cable only)
Source Source

j
Grounded Grounded White
conductor conductor

Lamp Lamp

Switch return - - -....

S1

Fig. 16-18 Single-pole switch connection.


146 Unit 10 Reading Electrical Drawings-Bakery, and Switches and Receptacles

sents the situation where a raceway will be avail is controlled from anyone of three switching
able for installing the conductors. The third dia points. Care must be used to ensure that the trav
gram illustrates the connections necessary when eller wires are connected to the proper terminals
using armoured cable (AC) or nonmetallic of the four-way switch. That is, the two traveller
sheathed cable (NMSC), Rule 4-034(2). wires from one three-way switch must be con
nected to the two terminals on one end of the
Three-Way Switch. A three-way switch has a
four-way switch. Similarly, the two traveller
common terminal to which the switch blade is
wires from the other three-way switch must be
always connected. The other two terminals are
connected to the two terminals on the other end of
called the traveller terminals, Fig. 10-19. In one the four-way switch.
position, the switch blade is connected between
the common terminal and one of the traveller ter Double-Pole Switch. A double-pole switch is
minals. In the other position, the switch blade is rarely used on lighting circuits. As shown in Fig.
connected between the common terminal and the 10-23, a double-pole switch can be used for those
second traveller terminal. The three-way switch installations where two separate circuits are to be
can be identified readily because it has no On or controlled with one switch. Both conductors of a
Off position. Note that On and Off positions are circuit may be disconnected at the same time
not marked on the switch handle in Fig. 10-19. using a two-pole switch, Rule 14-016(a).
The three-way switch is also identified by its
three terminals. The common terminal is darker in
colour than the two traveller terminals, which
have a natural brass colour. Fig. 10-20 shows the SWITCH AND RECEPTACLE COVERS
application of three-way switches to provide con A cover that is placed on a recessed box contain
trol of the light from two points. ing a receptacle or a switch is called a faceplate,
and a cover placed on a surface mounted box is
Four-Way Switch. A four-way switch is simi called a raised cover.
lar to the three-way switch in that it does not have Faceplates come in a variety of colours,
On and Off positions. However, the four-way shapes, and materials, but for our purposes they
switch has four terminals. Two of these terminals can be placed in two categories, insulating and
are connected to traveller wires from one three metal. Metal faceplates can become a hazard
way switch and the other two terminals are con because they can conduct electricity; they are
nected to traveller wires from another three-way considered to be effectively grounded through the
switch, Fig. 10-21. Notice that terminals Al and 6-32 screws that fasten the faceplate to the
A2 are connected to one three-way switch and grounded yoke of a receptacle or switch. If the
terminals B1 and B2 are connected to the other box is nonmetallic, the yoke must be grounded.
three-way switch. In position 1, the switch con Both switches and receptacles are available with a
nects Al to B2 and A2 to B1. In position 2, the grounding screw for grounding the metal yoke.
switch connects Al to B1 and A2 to B2. It is a requirement that two screws or another
The four-way switch is used when a light or a approved method be used to fasten a receptacle to
group of lights, or other load, must be controlled a raised cover. Receptacles that are installed out
from more than two switching points. The doors in damp or wet locations must be covered
switches that are connected to the source and the with weatherproof covers that maintain their
load are three-way switches. At all other control integrity when the receptacle is in use. These
points, however, four-way switches are used. Fig. covers would be deep enough to shelter the
10-22 illustrates a typical circuit in which a lamp attachment plug, Rule 26-706.
Unit 10 Reading Electrical Drawings-Bakery, and Switches and Receptacles 147

S3 Travellers S3
"Hot" ~~-l r~--,
t9k'O~+J---A
..
Switch leg
~~Jj-: - - -
To source _ Lamp y
Grounded conductor

Hot

Raceway Neutral

To source

Cable

Source

(AI Circuit with three-way switch control and feed at the switch

To source
Grounded conductor
Lamp ..-.._ .......
Lamp
Switch return Raceway Cable
Black '-'-..JV
~:II!II!fum~
( Travelers -.:=~"
,

Switch return Hot


IBI Circuit with three-way switch control and feed at the light

Fig. 10-20 Three-way switch connections.

A1 A2 A1 A2

Position 1
l J ! 1

,/
).
I
I
I
I Position 2
I

( '1
B1 B2
r r
B1 B2

Two positions of four-way switch

Fig.10-19 Three-way switch. Fig. 10-21 Four-way switch operation.


148 Unit 10 Reading Electrical Drawings-Bakery, and Switches and Receptacles

Grounded conductor
Source
To
Source


Hot "Hot"
Switch Jeg

NOTE: A four-way switch is always connected


between two three-way switches.

Circuit with switch control at three different locations.

Fig. 10-22 Four-way switch connections.

Black or other
Identifying colour
~I
I Separate circuits Separate loads
I connected to
Grounded one double-pole
conductor switch.

Double-pole switching may be required,


Rule 14-016(a). Grounded conductor

Fig. 10-23 Double-pole switch connections.

REVIEW

PART I: READING ELECTRICAL DRAWINGS-BAKERY

Note: Use the following questions to review the loading schedule for the bakery. Use the drug
store loading schedule, the bakery plans, and the c.. C, Part I as necessary.
1. What is the basic demand load for the drugstore?
Unit 10 Reading Electrical Drawings-Bakery, and Switches and Receptacles 149

2. The total connected load of the "special loads" (i.e., not basic load) is volt
amperes.
3. The total connected lighting load on the main floor in the bakery is volt
amperes.
4. To supply the lighting tabulated in the previous question, a total of branch cir
cuits are used.
5. The connected load on circuit number 1 is amperes.
6. The maximum allowable load on branch circuit 10 will be volt-amperes if No.
10 AWG copper conductors are installed to increase the voltage at the load.
7. The electrician might consider installing a single circuit for branch circuits 12 and 9. Is this
a good idea? Explain in detail. Do the changes required by this strategy overshadow its
advantages?

PART II: SWITCHES AND RECEPTACLES

Note: Refer to the c.E.c., Part lor the plans as necessary.


1. Indicate which of the following switches may be used to control the loads listed below.
A. Ac/dc 10 A-125 V 5 A-250 V
B. Ac only 10 A-l20 V
C. Ac only 15 A-120/277-347 V
D. Ac/dc 20 A-125 VT 10 A-250 V
a. A 120-volt incandescent lamp load (tungsten filament) consisting of ten 150-watt
lamps. _ _
b. A l20-volt fluorescent lamp load (inductive) of 1500 volt-amperes. _ _
c. A 347-volt fluorescent lamp load of 625 volt-amperes. _ _
d. A l20-volt motor drawing 10 amperes. _ _
e. A 120-volt resistive load of 1250 watts.
f. A l20-volt incandescent lamp load of 2000 watts. _ _
g. A 230-volt motor drawing 3 amperes. _ _
2. Using the information in Figs. 10-9 and 10-10, select by number the correct receptacle for
each of the following outlets.
a. l20/208-volt, single-phase, 20-ampere outlet. _ _
b. 208-volt, three-phase, 50-ampere outlet. _ _
c. 208-volt, single-phase, 30-ampere outlet. _ _
iO Unit 10 Reading Electrical Drawings-Bakery, and Switches and Receptacles

3. Show all wiring for the following circuit. The circuit consists of two three-way switches con
trolling two luminaires with the feed at one luminaire. Indicate conductor colours.
Lamp Lamp

o o

!J=======:::;, To source

~ Three-way Three-way ~
Ii!! switch switch !5!

Two three-way switches controlling two luminaires


with feed at one luminaire. Show wiring scheme.

4. Show all wiring for the following circuit. The circuit consists of two three-way switches and
one four-way switch controlling a light. One of the three switches is to be selected as the four
way switch; then complete the wiring accordingly. Indicate conductor colours.

To source

o Lamp

Two three-way switches and a four-way switch controlling


a light. Choose which switch should be the four-way and
show wiring scheme.

Potrebbero piacerti anche