Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
12th Conference of International Building Performance Simulation Association, Sydney, 14-16 November.
- 712 -
Proceedings of Building Simulation 2011:
12th Conference of International Building Performance Simulation Association, Sydney, 14-16 November.
Province, South Korea. The building is a nine-story The target building's external walls are full-glazed
building with two underground floors, and its total curtain walls, and its frame consists of aluminium
floor area is about 23,742m2. The external walls and with a thermal break. There are two types of glazing
roofs are curved horizontally and vertically (Figure used in the curtain wall. One is 24mm clear double-
1). An atrium exists in the central part of the glazing and the other is 24mm low-e double-glazing.
building which penetrates from the first floor to the Clear double glazing is installed in the plenums on
seventh floor. The building faces almost due south each floor and low-e double glazing is installed in
(rotated 9 degrees clockwise). occupied spaces. The roof glazing located on top of
the atrium is 30mm clear double-glazing. Details of
glazing types are tabulated in Table 1.
- 713 -
Proceedings of Building Simulation 2011:
12th Conference of International Building Performance Simulation Association, Sydney, 14-16 November.
The target building's HVAC system comprises of system and decided that the drawing of the most
Constant Air Volume (CAV), Variable Air Volume detailed scale should be applied.
(VAV), and Fan Coil Unit (FCU). There are 15
AHUs that serve 12 CAV and 3 VAV systems, and Table 3
each AHU's service zone is as shown in Table 2. Marked roof insulation on each drawing
Most part of the target building are served by the Marked construction (in order of outside to
In drawing of
CAV system, but the first basement floor except the inside)
corridor and right half of the second floor are served Detailed 100 Glass Wool(48K)
by the VAV system. Also, FCU serves the perimeter Section 30mm SKY VIVA
zone of each floor. As for heat source, AHU and Roof 11.1mm O.S.B 2ply
FCU systems are dependent on two direct gas fired detail 125mm Glass Wool(24K)
absorption chillers (600 USRT in cooling,
Roof 5mm P.E. Foam
1,593,900kcal/h in heating). Two absorption chillers
panel 11.1mm O.S.B 2ply
are operated in a sequential order. In other words,
detail 63mm Glass Wool(24K) 2ply
one chiller operates first, and the other operates
when heating/cooling demand cannot be met by one.
In case of the glazing, the authors found the U-
DATA GATHERING values and shading coefficients of glazing in the
The required data include information about the drawings and specifications. In EnergyPlus, there are
building's geometry, envelopes, schedule and density two objects to define glazing material. One is
of internal heat gain (people, lights, equipment), WindowMaterial: SimpleGlazingSystem which
operation of HVAC systems (schedule, setpoint defines the glazing material with a U-value and
temperature, outdoor air rate), etc. The following is Solar Heat Gain Coefficient (SHGC), the other is
a description of the difficulties that we faced in WindowMaterial: Glazing which defines the glazing
obtaining such data. material with more detailed data (solar transmittance
at normal incidence, front/back side solar reflectance
Architectural Data at normal incidence, visible transmittance at normal
Architectural data includes geometry and spatial incidence, front/back side visible reflectance at
information and the materials used to build the normal incidence, infrared transmittance at normal
structure. Most geometric data can be obtained from incidence, front/back side infrared hemispherical
the blueprints and building document. However, emissivity, conductivity). If we used
blueprints express the actual 3D building in the form WindowMaterial: SimpleGlazingSystem with
of two dimensions with implications, and these information of the U value and shading coefficient,
implications can lead to a situation in which the there may be a significant difference in performance
building's geometry is insufficiently understood. In between the sample window system and the
other words, the architectural drawings, although simulation model (DOE, 2010). Furthermore,
provided by architects and the building manager, are because most parts of the envelopes of the target
not good enough to capture a curved complex 3D building are made of glazing, thermal and visual
geometry and inter-level rooms of the building properties of glazing are essential. In this study, the
(Figure 1) due to the nature of its two-dimensionality. detailed thermal and visual data of the glazing for
Unlike building energy simulation in design phase, the WindowMaterial: Glazing object were
the building was already completed and the authors fortunately available with kind assistance of the
could visit several times to minimize the gap manufacturer.
between the simulation model and a reality. Internal Heat Gain
The other difficulty in the architectural data Internal heat gain includes occupant, lights and
gathering is the information of materials. Even equipment. Firstly, heat gain from occupants is
though drawings and specifications were provided, strongly dependent on accurate information on the
those do not specify the detailed thermal properties schedule of occupants. Research on the
of the materials such as conductivity, density, mathematical or stochastic model of occupants
specific heat, roughness, thermal absorptance, solar behaviour has been performed, but this area is still in
absorptance and visible absorptance that EnergyPlus underdevelopment (IBPSA 2005-2009). In this study,
requires. Therefore, the authors had to make we used the stored database in the target building.
reasonable assumptions based on the literature. All entrances of the target building have an access
Additionally, drawings and specifications are not management system which records every access
coherent to each other. An example of such case is using Radio-Frequency Identification (RFID) tags.
as shown in Table 3. Three different drawings In addition, all reading rooms have a similar access
describe that a same roof panel use different layers system that records seat issues. The authors were
and materials (Table 3). This sounds unlikely but provided a backup of those databases by the building
can happen a lot in the real world. In case of the roof manager, and analysed the number of people in the
insulation, the authors could not access to the roof target building. The database was established with
- 714 -
Proceedings of Building Simulation 2011:
12th Conference of International Building Performance Simulation Association, Sydney, 14-16 November.
4F
Monitor Corridor 8
300
200
EnergyPlus requires fraction latent, fraction sensible
and fraction radiant of electric equipment. However,
100 we dont have accurate information on the
aforementioned fraction number. The authors
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 referred to ASHRAE (2009) as shown in Table 6.
Time
Figure 3 The change of the number of occupants in
the target building on January 9th, 2010
- 715 -
Proceedings of Building Simulation 2011:
12th Conference of International Building Performance Simulation Association, Sydney, 14-16 November.
Table 6 Assumed fraction of equipment heat gain of In addition, the east and west curtain walls are
the target building (reference: ASHRAE2009 18.12, backed up with indoor automatic roll-shades. The
Table 8) central computer can control the shades, but this
Equipment
Heat Fraction Fraction Fraction Referred remote automatic control was not activated, and the
gain latent convection radiant equipment facility manager controls the shading device
0% 14inch manually when he receives a service call from
Laptop 31W 0% 100%
Laptop students or staff members due to glare or discomfort.
17inch Furthermore, the automatic control system includes
Monitor 28W 0% 60% 40% LCD
features such as night-setback, pre-cooling and CO2
monitor
2.8Ghz control, but all of those were deactivated since it
Desktop 73W 0% 90% 10% CPU with often mal-functions. This can reflect the difference
1GB RAM in building energy performance between as designed
and as operated.
HVAC system operation SIMULATION MODEL
An automatic control is applied to air handling units and
plant equipment of the target building. Start-up and stop Geometry Modeling
controls are based on predefined schedules, and the In this study, we used DesignBuilder to model the
operating schedule of each floor is shown in Table 7. complex geometry of the target building. EnergyPlus
doesn't recognize curved surfaces, and defines each
Table 7 Operation schedule of each floor surface using a straight line with 3D-based
Operation schedule
Floor coordinates. Thus, the target building's curved
Weekdays Saturday Sunday
surfaces are simplified to the combination of several
B1
(Except reading 06:00-01:00 06:00-01:00 06:00-01:00 straight lines. The more the number of segments of
rooms) the curves, the more tremendous increase in
B1 simulation efforts and running time. In this study,
08:30-17:30 09:30-17:00 Closed the number of segments of each curve is limited by
(reading rooms)
1F-3F 08:30-17:30 09:30-17:00 Closed the authors to four or six based on the length of the
4F-5F Closed Closed Closed curve. In spite of this simplification and limitation,
6F-7F 08:30-17:30 Closed Closed the total number of surfaces of the model mounts up
to 4,914. Figure 4 shows the DesignBuilder model of
After the visit survey and interview with the facility the target building.
manager, it was found that the outdoor and return air
fraction and operation of humidifiers are determined
by subjective judgment of the HVAC operator. The
humidifiers in each AHU are turned off most of the
times, and the operator controls the outdoor air
fraction manually based on indoor CO2 level and
relative humidity of outdoor air. Unfortunately, such
HVAC operation data were not stored or recorded.
In this study, the amount of outdoor air was assumed
based on the interviews with the facility managers as
shown in Table 8.
Table 8 Assumed outdoor air fraction of each AHU
Supply Air Fraction of Outdoor Air (a)
AHU No.
Volume Outdoor Air Volume
1 10.2 m3/s 10% 1.02 m3/s
2 9.5 m3/s 30% 2.86 m3/s
3 7.7 m3/s 30% 2.30 m3/s
4 4.5 m3/s 30% 1.36 m3/s
5 9.1 m3/s 10% 0.91 m3/s
6 7.8 m3/s 30% 2.34 m3/s
7 12.2 m3/s 10% 1.22 m3/s
8 7.4 m3/s 10% 0.74 m3/s
9 8.5 m3/s 10% 0.85 m3/s
10 9.0 m3/s 10% 0.90 m3/s
11 8.1 m3/s 10% 0.81 m3/s
12 15.8 m3/s 10% 1.58 m3/s (b)
13 16.3 m3/s 30% 4.89 m3/s Figure 4 Bird's eye view of the target building's
14 6.4 m3/s 10% 0.64 m3/s DesignBuilder Model (a) and 1st floor model (b)
15 8.0 m3/s 20% 1.59 m3/s
- 716 -
Proceedings of Building Simulation 2011:
12th Conference of International Building Performance Simulation Association, Sydney, 14-16 November.
- 717 -
Proceedings of Building Simulation 2011:
12th Conference of International Building Performance Simulation Association, Sydney, 14-16 November.
800
(a) Measured simplifications and assumptions made on geometry,
(b) Calculated
700 simulation inputs, controls, unmodeled mass and
600
heat transfer phenomena, and uncertainty in schedule
of occupants, equipment, lights, and weather. The
Solar radiation(W/)
500
trend of simulated consumption and measured
400 consumption is quite similar, but the measured
300
consumption has much greater fluctuation, because
there is intervention of human judgement in controls
200
of building systems (ventilation rate, roller shades),
100 which cannot be easily reflected in the simulation
model. For example, the control of automatic shades
0
1 6 11 16 21 26 31 36 41 46 51 56 61
Hours(start from January 6th AM 0:00)
66 71 76 81 86 91 96
(roll screen) has a great influence on gas
(a) Comparison of diffuse horizontal radiation consumption, but the facility manager performs its
800
(a) Measured
control completely in a manual manner based on his
700
(b) Calculated
subjective judgment and service calls. In addition,
many unmodeled mass and heat transfer phenomena
600
such as infiltration (exfiltration), internal air
Solar radiation(W/)
10
interview with the facility manager that the outdoor
8
and return air fraction and operation of humidifiers
6 are strongly determined by subjective judgment of
4
the HVAC operators. Moreover, the control of
automatic shades (roll screen) has a great influence
2
on building energy, but the facility manager
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
performs its control completely in a manual manner
Days(start from January 1st) based on his subjective judgment. Such operation
Figure 7 Comparison between the measured and the and control data were not stored or recorded, and
simulated gas consumption had to be reflected to the simulation model with
plausible assumptions.
The average of daily difference between the In the phase of development of simulation model,
simulated and measured gas consumption is 18%. significant simplification of the target building`s
The greatest difference is 61% on January 18th, and geometry was made. The actual efficiency curve of
least one is 0.68% on January 30th. It can be inferred the chillers hot water cycle was not provided by the
that the causes of this difference are the
manufacturer, so we assumed that its efficiency
- 718 -
Proceedings of Building Simulation 2011:
12th Conference of International Building Performance Simulation Association, Sydney, 14-16 November.
curve is same with that of a generic gas boiler. The Institute, Report SERI/TR-215-3087
diffuse horizontal radiation and direct normal Waltz, J. P., 2000, Computerized Building Energy
radiation were estimated from the global horizontal Simulation Handbook, Fairmont Press
radiation provided by KMA. The EnergyPlus
Zhu, Y., 2006, Applying Computer-based
simulation was performed after the aforementioned
Simulation to Energy Auditing: A Case Study,
procedure, and the target period was January, 2010.
Energy and Buildings, Vol.38, pp.421-428
The average of daily difference between the
simulated and measured gas consumption is 18%. It
seems that the causes of this difference are the
simplifications of geometry and assumptions of
input variables, controls, unmodeled mass and heat
transfer phenomena, and uncertainty in schedule of
occupants, equipment, lights, and weather. Solving
for the aforementioned issues and dealing with
strong uncertainty in simulation parameters will be a
future challenge of building energy simulation.
REFERENCES
Al-Homoud, M. S., 2001, Computer-aided building
energy analysis techniques, Building and
Environment, Vol.36, pp.421-433
ASHRAE, 2007, ASHRAE Handbook-HVAC
Applications, Atlanta: American Society of
Heating, Refrigerating and Air-Conditioning
Engineers, Inc.
ASHRAE, 2009, ASHRAE Handbook Fundamentals,
American Society of Heating, Refrigerating and
Air-Conditioning Engineers, Inc., Atlanta, USA
DOE, 2008, Buildings Energy Data Book,
Department Of Energy
DOE, 2010, Input Output Reference, EnergyPlus
Manual
Domnguez-Muoz, F., Anderson, B. Cejudo-
Lpeza, J.M. and Carrillo-Andrsa, A., 2010,
Uncertainty in the thermal conductivity of
insulation materials, Energy and Buildings,
Vol.42, No.11, pp.2159-2168
Erbs D. G., Klein, S. A., Duffie, J. A., 1982,
Estimation of the Diffuse Radiation Fraction for
Hourly, Daily, and Monthly-Average Global
Radiation, Solar Energy, Vol.28, pp.293-302
IBPSA, 1987-2009, Proceedings of the IBPSA
(International Building Performance Simulation
Association) conference('87, '91, '93, '95, '97,
'99, '01, '03, '05, '07, '09)
IESNA, 1993, Lighting Handbook: Reference &
Application 8th Edition, Illuminating
Engineering Society of North America, New
York, p.355
Kaplan, M., Canner, P., 1992, Guidelines for energy
simulation of commercial buildings, Portland:
Bonneville Power Administration
Korea Energy Economics Institute, 2009, Energy
Consumption Survey, Ministry of Knowledge
Economy
Maxwell, E. L., 1987, A Quasi-Physical Model for
Converting Hourly Global Horizontal to Direct
Normal Insolation, Solar Energy Research
- 719 -