Sei sulla pagina 1di 3

ASK-170317_F+P Comment

MG9 MG10
Stone wall sub structure QQ MG11

2497 1829 1829


[8'-2 5/16"] [6'-0"] [6'-0"]
600 1838 59 1
1'-11 5/8" 6'-0 3/8" 2 5/16" 7,800 A-534 Notes:
RWP INSTALLED BY BALUSTER STONE WALL WITH All dimensions and areas subject to
LL. REFER TO F+P 1677 210 INTEGRATED HANDRAIL confirmation by a building survey.
SETTING OUT 1
5'-6" 8 1/4"
A-510 Any area indicated on this sheet are
approximate and indicative only.
STONE WALL WITH
INTEGRATED HANDRAIL Do not scale drawings. All drawings to
be printed in colour.
T 1724
5'-7 7/8" All dimensions and areas shall be
verified on site before proceeding
with the work.
01
Foster + Partners shall be notified in
writing of any discrepancies.

7'-11 11/16"
ACOUSTIC INSULATION TO 02
RAINWATER PIPES

2430
All information is to be read in
INS-3 conjunction with technical reference
03 sheet, specifications and Engineers
documentation.

04 1829 All structure elements are to be

4'-2 3/8"
[6'-0"] designed and confirmed by the

1280
Landlord Structural Engineer. All

[2'-8 1/4"]
05 information on these drawings is

819
indicative only for the sole purpose of
informing the Landlord for his Base
build works. Final structural

[8'-10 5/16"]
06
dimensions should be obtained by

2700
referring to the Landlords drawings.
MGF 07
All indicative design, elements,
finishes and materials outside the Line
08 of Demise (LOD) are indicative only
and should not be used for any other
purpose. It must not be used for
09 construction.

Retained building elements shown


indicatively to be surveyed and
10
verified by contractor.

[1'-3 3/4"]
[10'-0"]

[10'-0"]

400
3048

3048

1
A-533

[6'-2 13/16"]
1900
MGE
Apple Inc.
1 Infinite Loop
MS 52-RD
Cupertino, CA
[5'-0"]
1524

95014
[3'-3 3/8"]
1000

E 1
45'-11 5/16"

[35'-4 1/2"]

45'-11 3/8"
Architect:
[10'-0"]

14005
14004

10782

5
3048

AVENUE
WATER FEATURE
Foster + Partners
F23.01
VOID ABOVE www.fosterandpartners.com
[3'-3 3/8"]
1000

Structural Engineer (Glass):


Eckersley O'Callaghan
[5'-0"]
1524

www.eckersleyocallaghan.com

Structural Engineer:

Atkins
wwww.atkinsglobal.com
MGD
Mechanical and Electrical Engineer:

Foster + Partners
wwww.fosterandpartners.com

MEP ROOM

F+P: could you relocate


[11'-8 5/8"]
3572
[10'-0"]

[10'-0"]
3048

3048

this column in front of the


door?
1829
[6'-0"]
MGC
[1'-4 7/8"]
428

Signed: mm/dd/yyyy

Apple Store
4'-5 1/2"
1359

Sands Cotai Central


[3'-3 3/8"]

Macau, China SAR


1000

E 1
7'-11 11/16"
2430

This set originated using


ACOUSTIC INSULATION TO E 1
Apple Imperial Bulletin 6.0
RAINWATER PIPES Rev-04 - Date 12/09/2015
INS-3 Printed Full (30"x42"), Half (15"x21")
PRIMARY STRUCTURE TO BE
FIRE PROTECTED WITH
Issued/Revised Date
INTUMESCENT PAINT BY LL E 1
80%CD CONSOLIDATE 22/12/16
T 1 90% CD 18/01/17
A-509 100%CD 02/02/17
1-03 -- 100%CD Rev01 22/02/17
100%CD Rev02 30/03/17

RWP INSTALLED BY 2
LL. REFER TO F+P 2 A-510
SETTING OUT A-533
1
A-508 1897 1829 1829
6'-2 11/16" [6'-0"] [6'-0"]

3783 1771
Apple Approval Date
12'-4 15/16" 5'-9 3/4"

MG8
TECHNICAL AVENUES
SOUTH - DETAILED PLAN
SOUTH TECHNICAL AVENUE PLAN - LEVEL 1 N
L01
1 1 : 25

17/03/2017 16:26:21 D:\Revit Backup\2396-apSCC-arch-XX_rwong8118.rvt


A-506
MG8
FACADE INSET LINE 02

MG10 MG9

DUCT

TRUSS SUBFRAME TO SUPPORT


STONE CLADDING.REFER TO PCE Notes:
DRAWINGS All dimensions and areas subject to
confirmation by a building survey.

THE AVENUE Any area indicated on this sheet are


approximate and indicative only.

Do not scale drawings. All drawings to


59 20 be printed in colour.
2 5/16"13/16"
All dimensions and areas shall be
verified on site before proceeding
with the work.

Foster + Partners shall be notified in


writing of any discrepancies.

All information is to be read in


IN-SITU COMPOSITE RESIN TERRAZZO conjunction with technical reference
SURFACE FINISH sheet, specifications and Engineers
TZ-1 documentation.
MINERAL WOOL ACOUSTIC
INSULATION TO TECHNICAL RISER All structure elements are to be
designed and confirmed by the
INS-2 Landlord Structural Engineer. All

1'-6"
457
NATURAL STONE SLAB INTERNAL
WALL LINING INCLUDING information on these drawings is
MECHANICAL FIXINGS 20 indicative only for the sole purpose of
13/16" informing the Landlord for his Base
ST-1 build works. Final structural
dimensions should be obtained by
STONE BALUSTRADE referring to the Landlords drawings.
ST-5
1
All indicative design, elements,
A-638 finishes and materials outside the Line
of Demise (LOD) are indicative only
and should not be used for any other
14620 purpose. It must not be used for
construction.

1 1/4"
FFL LEVEL 2

31
Retained building elements shown
indicatively to be surveyed and
verified by contractor.

F+P: This should be a


zone free of sub structure.
Apple Inc.
40MM CEMENTITIOUS SPRAY 1 Infinite Loop
15MM STRUCTURE TOLERANCE
MS 52-RD
Cupertino, CA
95014

PRIMARY STRUCTURE BY LL.


REFER TO ATK DRAWING SET

.00
135 Architect:

323 Foster + Partners


1'-0 3/4" www.fosterandpartners.com
13,725 [45' - 0 3/8"]

Structural Engineer (Glass):


Eckersley O'Callaghan
www.eckersleyocallaghan.com

Structural Engineer:

Atkins
wwww.atkinsglobal.com

Mechanical and Electrical Engineer:

Foster + Partners
wwww.fosterandpartners.com

LAST STONE PANEL 300MM


EXTENDED BEYOND FCL

T.L. STONE PANEL 13,095 [42' - 11 1/2"]


SADDLER AIR DIFFUSER ABUT
STONE WALL, INTEGRATED TO
THE COVER PLATE

11 13/16"
300
7 2
15 02
/1
6"

Signed: mm/dd/yyyy
12,760 [41' - 10 3/8"]
Apple Store
120 48 20 112
4 3/4" 1 7/8"
13/16" 4 3/8" Sands Cotai Central
Macau, China SAR
2
A-638 This set originated using
Apple Imperial Bulletin 6.0
Rev-04 - Date 12/09/2015
Printed Full (30"x42"), Half (15"x21")

Issued/Revised Date
80%CD CONSOLIDATE 22/12/16
90% CD 18/01/17
100%CD 02/02/17
.00

100%CD Rev01 22/02/17


135

100%CD Rev02 30/03/17


20 112
13/16" 4 3/8"

560 NO SUB-STRUCTURE PASSING THIS


1'-10 1/16" AREA, FREE FOR MECHANICAL
DUCT PASSING THROUGH, TO BE Apple Approval Date
COORDINATED WITH STONE WALL
SUB STRUCTURE ENGINEER

1532 TECHNICAL AVENUE


TECHNICAL AVENUE CROSS SECTION - TYPICAL CONNECTION DETAILS 5'-0 5/16" SECTION DETAIL
1 1:5

17/03/2017 16:06:40 D:\Revit Backup\2396-apSCC-arch-XX_rwong8118.rvt


A-613
MG10 MG9

23300
FFL LEVEL 3

1829
6'-0"
Notes:
All dimensions and areas subject to
confirmation by a building survey.
CUSTOM FABRICATED GLAZED
STRUCTURAL ROOFLIGHT SYSTEM Any area indicated on this sheet are
G-4 approximate and indicative only.

Do not scale drawings. All drawings to


be printed in colour.

All dimensions and areas shall be


verified on site before proceeding
with the work.

Foster + Partners shall be notified in


writing of any discrepancies.

All information is to be read in


22,799 [74' - 9 5/8"] conjunction with technical reference
sheet, specifications and Engineers
documentation.

All structure elements are to be


designed and confirmed by the
Landlord Structural Engineer. All
information on these drawings is
indicative only for the sole purpose of
40MM CEMENTITIOUS SPRAY informing the Landlord for his Base
15MM STRUCTURE TOLERANCE build works. Final structural
dimensions should be obtained by
referring to the Landlords drawings.
PRIMARY STRUCTURE BY LL. PRIMARY STRUCTURE BY LL. All indicative design, elements,
REFER TO ATK DRAWING SET REFER TO ATK DRAWING SET finishes and materials outside the Line
of Demise (LOD) are indicative only
and should not be used for any other
purpose. It must not be used for
construction.
.00
372 135
Retained building elements shown
51 1'-2 11/16"
2" indicatively to be surveyed and
verified by contractor.

MALL SKYLIGHT LOUVRES

NO SUB-STRUCTURE
PASSING THIS AREA, FREE
TRUSS SUBFRAME TO MINERAL WOOL ACOUSTIC FOR MECHANICAL DUCT
SUPPORT STONE INSULATION TO TECHNICAL RISER PASSING THROUGH, TO BE
4 CLADDING.REFER TO PCE COORDINATED WITH STONE
INS-2 WALL SUB STRUCTURE
A-638 DRAWING SET 1'- 5
10 60 ENGINEER
1/
16
MEP DUCTWORK " Apple Inc.
LAST STONE PANEL 300MM
EXTENDED BEYOND FCL 1 Infinite Loop
MS 52-RD
Cupertino, CA
95014
T.L. STONE PANEL 21,770 [71' - 5 1/8"]
1 35 SADDLER AIR DIFFUSER ABUT
3/
8" STONE WALL, INTEGRATED TO
THE COVER PLATE

F+P: This should be a Architect:


Foster + Partners
www.fosterandpartners.com

zone free of sub structure. Structural Engineer (Glass):


Eckersley O'Callaghan
59 20 www.eckersleyocallaghan.com
2 5/16"13/16"

Structural Engineer:
100 20 48 20 112
3 15/16" 13/16"
1 7/8"
13/16" 4 3/8" Atkins
wwww.atkinsglobal.com

NATURAL STONE SLAB INTERNAL STRETCH CEILING PANEL (CP-2)


WALL LINING INCLUDING Mechanical and Electrical Engineer:
MECHANICAL FIXINGS CP-2
Foster + Partners
ST-1
wwww.fosterandpartners.com

2
A-638

.00
135
NATURAL STONE SLAB INTERNAL
WALL LINING INCLUDING
MECHANICAL FIXINGS
ST-1

STONE SUPPORT RAILS BY GC. STONE SUPPORT RAILS BY GC


TO BE DEVELOPED IN ZONE OF Signed: mm/dd/yyyy
INTEGRATED HANDRAIL 560
1'-10 1/16" Apple Store
Sands Cotai Central
Macau, China SAR

This set originated using


Apple Imperial Bulletin 6.0
Rev-04 - Date 12/09/2015
Printed Full (30"x42"), Half (15"x21")

Issued/Revised Date
80%CD CONSOLIDATE 22/12/16
90% CD 18/01/17
100%CD 02/02/17
100%CD Rev01 22/02/17
100%CD Rev02 30/03/17

1532
5'-0 5/16" Apple Approval Date
20 1798
13/16" 5'-10 13/16"

TECHNICAL AVENUE
TECHNICAL AVENUE CROSS SECTION - TYPICAL CONNECTION DETAILS L3 SECTION DETAIL
1 1:5

17/03/2017 16:06:56 D:\Revit Backup\2396-apSCC-arch-XX_rwong8118.rvt


A-614