Sei sulla pagina 1di 4

APPLICATION NOTE

YS1700 Boiler Control Overview


users. Pressure in the header is controller. If the fuel or air controller
OVERVIEW used as an indicator of the steam is in MANUAL, the YS1700
demand. A pressure transmitter is programming logic can alert the
Automated control of industrial connected to the header and this boiler operator that the firing rate
boilers is an excellent application for signal is the process variable input to demand signal cannot be used in the
YS1700 microprocessor-based loop a YS1700 programmed as Plant combustion controllers.
controllers. These instruments can Master. This is a P+I controller that
be programmed to perform the compares the pressure with an A Flame On permissive from the
operations of plant master, boiler operator selected set point and burner management equipment
master, fuel and air control with computes a firing rate demand signal alerts the boilermaster controller that
oxygen trim and drum (output) to the combustion controls: the boiler can accept a firing rate
level/feedwater control. Each of {boilermaster(s) and the fuel/air demand signal and is not in a low
these control applications are controllers}. fire, purge or off condition.
discussed in this application note.
BOILERMASTER COMBUSTION CONTROLS
The YS1700 is a reliable and cost
effective means of upgrading boiler This controller accepts the firing rate The firing rate demand signal from
controls and increasing boiler demand signal from the Plant Master the boilermaster controller(s) is used
efficiency while lowering operating controller as the process variable. in the combustion control: fuel, air
costs by implementing advanced The output of boiler master provides and flue gas percent oxygen. The
control strategies. Although the the firing rate demand signal and YS1700 controller can be
functions of each controller operator applied bias to the fuel and programmed to perform all these
discussed here differ, the YS1700 air controllers for that specific boiler. functions. In this text, the
hardware platform is identical for This bias station allows the operator combustion control discussions will
each application. to select higher firing rates and be limited to a single fuel with a
therefore higher steam production parallel metered cross limited control
Key features of the YS1700 include: from the more efficient boilers in a
Dual PID loop capability multiple unit configuration.
Built-in Hard Manual backup
station Additionally, discrete outputs from
Two CPU design for reliability the fuel and air controllers provide
LOOP, TREND & ALARM mode status to the boilermaster
operator displays PT PLANT MASTER
Integral 24VDC transmitter
Header Pressure
power supply
Advanced self-tuning Set Point

RS485, Ethernet & peer-to-peer


communications options K
Expanded I/O option (total of 8
AI, 4 AO and 14 DI/DO A T A Firing Rate Demand

PLANT MASTER
BOILERMASTER BOILERMASTER
#1 #2
Most industrial boilers operate on a
+/- Bias Station +/- Bias Station
header system. Steam is delivered Flame ON Flame ON
Permissive Permissive
to a header pipe by one or more
boilers and is transferred from the B T A B T A
header to the various process Fuel/Air Set Points Fuel/Air Set Points

ID Number
07-07
APPLICATION NOTE
configuration. The YS1700 controller range. This minimum setting is adjusted for gain and bias (y=mx+b)
can be programmed to select required by NFPA code and insures and applied to the air flow
multiple fuels (e.g., oil or gas) or safe operation during transmitter measurement signal. High and low
control a ratio of two combustibles. outage. output limiters are used in the event
of analyzer outage.
The SAMA logic diagram below Discrete inputs and outputs are used
shows the interaction of the fuel and for tracking the auto/manual status The YS1700 can be programmed to
air controllers. The fuel and air flows of the air controller. The fuel operate as a dual loop P+I+D
are measured and compared to the controller is forced to MANUAL if the controller. Therefore, the
firing rate demand signal. Low and air controller is placed in MANUAL. combustion air and percent oxygen
high signal selectors are The fuel cannot be placed into the controls can reside in one
incorporated in the YS1700 programs automatic mode until the air instrument. The YS170 can display
to insure safe operation. The low controller is returned to AUTO. This the measured variables (air &
selector in the fuel controller action is required to insure a safe percent oxygen) on two different
compares the firing rate demand and proper air/fuel ratio. screens. Operator interface is
signal and the air flow measurement simple and easy-to-read.
and selects the lower signal as the An auto/manual station can be used
set point. Inversely, the air controller to generate a fuel/air ratio. For FEEDWATER CONTROL
compares the fuel flow measurement better combustion control and boiler
and firing rate demand signal efficiency, a flue gas percent oxygen The boiler feedwater controller is
selecting the higher as the air flow analyzer and YS1700 controller can used to maintain the water in the
set point. Therefore, the fuel flow be incorporated into the air flow steam drum at a desired set point.
will not exceed the air flow. Function control strategy. The firing rate The intent is to replace each pound
generators are applied to the outputs demand signal is modified by a of steam taken from the steam drum
for characterization to the final function generator to calculate a load with a pound of makeup water. A
control elements. A low limiter is index. An operator applied bias can high drum level may allow water
configured into the air flow controller be applied to the index and this is droplets to be carried over into the
to prevent the air flow set point from the set point to the oxygen trim steam header and damage process
being reduced less than 25% of full controller. The P+I output is equipment. A low level can cause
damage to exposed tube
From Boilermaster Firing Rate surfaces.
Demand

A phenomenon exhibited in
FT FT AT the steam drum is swelling
Fuel Flow Firing Rate Air Flow Oxygen and shrinkage. This is
Demand caused by the bubbles in the
f(x) boiler tubes and the drum
Low
Select 25% expanding and contracting.
K As the demand for steam is
< High
> A f(x) Operator
Bias increased, the header
Select pressure decreases and the
A T A
X
master pressure controller
increases the firing rate of
K + the boiler(s). The associated
K K
decrease in drum pressure
and higher firing rate causes
T A T A the water bubbles to expand
and the drum level
increases. Conversely as
f(x) f(x)
the steam demand
decreases, the header
Fuel Air pressure increases and firing
Valve Damper

ID Number
07-07
APPLICATION NOTE
rate declines, causing collapsing drum level. The YS1700 controller is single pair of twisted wires. Any
bubbles and a lowering of the steam programmed in a cascade controller parameter can be shared.
drum level. This action creates an configuration, where the output of Up to sixteen (16) controllers can be
opposite reaction in the feedwater the drum level controller is linked to linked on this data network with
controller. More feedwater is the remote set point of the feedwater custom configuration.
needed for higher steam flow, but as flow controller. The steam flow
the level swells, the feedwater measurement is applied to the SCADA/HMI
controller reduces the output to the output of the level controller to adjust
valve. Using a drum level pressure the remote set point to the feedwater Many boiler locations combine the
transmitter and compensating for the control proportional to varying steam control power and reliability of panel
change in drum pressure, the demands. The secondary control is mounted controllers by linking their
feedwater controller is not adversely the faster reacting feedwater flow YS1700 controllers with popular
affected. The drawing at the right controller. Three element control is SCADA/HMI software packages.
shows a drum pressure common on large boilers with Running such software in a personal
measurement being applied through varying load demands. This can be computer provides advanced
a function generator to the level programmed into one YS1700, as a trending, alarming, operator graphics
input. single station cascade controller with and other features while maintaining
feedforward element and pressure the boiler control functions in the
There are three types of boiler compensated drum level. YS1700s. Such a system provides
feedwater control configurations that features and functions similar to a
are commonly supplied: single PEER-TO-PEER Distributed Control System without
element (drum level only), two COMMUNICATION the high price tag!
element (level & steam flow) and
three element (level, steam & When using the RS485
YS1700 controllers can be optionally
feedwater). communication option, sixteen (16)
provided with peer-to-peer
communications. This feature YS1700s can be linked to each
Single element control is commonly permits data from one controller to communication port of the
used in small boilers that are based be sent to another digitally over a SCADA/HMI computer. The peer-to-
loaded, i.e., little variation in peer option allows sixteen
Drum Pressure Drum Level Steam Flow Feedwater Flow
steam demand. Changes (16) controllers to talk with
in load are not incorporated PT LT FT FT each other as the
into the control strategy. SCADA/HMI host computer
accesses the network. The
Two element control uses a f(x) X peer-to-peer option runs
steam flow measurement approximately eight times
as a feedforward element faster than the RS485 option
Set Point
to change position in the (78,000bps vs 9600bps).
feedwater valve. Changes Custom applications with up
in steam demand are K to 63 YS1700 controllers linked
sensed and adjustments to to a single PC
the valve are made. communications port are
Varying feedwater pressure K Feedforward
Gain possible when using the YS-
can change the flow rate Net peer-to-peer/PC network.
and drum level. Fluctuating Either YS1700 digital
pressure is common in communication card
multi-boiler feedwater discussed here can be
systems. K provided at the initial
purchase of the controllers or
The SAMA diagram below A T A easily retrofitted in the field.
shows a three element
drum level control with
pressure compensated Valve

ID Number
07-07
APPLICATION NOTE
SUMMARY industrial boiler domain.
Related Technotes
Using YS1700 loop controllers is an
answer to upgrading aging or CP-A-04 - RS485
cumbersome boiler controls. Communications/ Graphical User
Increased boiler efficiency and Interface Packages
reduced operating costs can be
realized. The programmability CP-A-08 - YS170 Peer-to-Peer
allows them to be used in a variety Communications
of applications. Discussions here
have been limited to the most CP-A-11 - Boiler Feedwater
common boiler control applications. Control
However, the YS1700 can be used for
deaerator control, steam drum b CP-A-12 - Boiler Combustion
treatment and a variety of auxiliary Control
control applications in the industrial
boiler domain.lowdown, condensate
return, water treatment and a variety
of auxiliary control applications in the
YS1700 - Boiler Control Solution

Pressure Level
Flow Temperature

High Resolution LOOP Display


Color LCD Display
TREND Display
Independent Dual
Loop Capability Pull Down
Configuration
Maximum Menus
Versatility

YS1700 Dual Loop Programmmable Controller

ID Number
07-07